February 2005
PROTECTION MEASURES FOR RADIO BASE STATIONS
SITED ON POWER LINE TOWERS
Copyright 2005
Ownership of a CIGRE publication, whether in paper form or on electronic support only infers right of use for
personal purposes. Are prohibited, except if explicitly agreed by CIGRE, total or partial reproduction of the
publication for use other than personal and transfer to a third party; hence circulation on any intranet or other
company network is forbidden.
Disclaimer notice
CIGRE gives no warranty or assurance about the contents of this publication, nor does it accept any
responsibility, as to the accuracy or exhaustiveness of the information. All implied warranties and conditions
excluded to the maximum extent permitted by law.
TABLE OF CONTENTS
Abstract ................................................................................................................... 1
Abbreviations ....................................................................................................................................1
1. Particularities of RBS on power line towers ............................................................ 1
2. Tower earthing potential rise ...............................................................................................2
3. Zone of the earth potential rise .............................................................................................3
3.1. Estimation of the minimum length of junction cable ......................................................3
3.2. Control of the touch- and step voltage by PGE .............................................................4
4. Power supply and protection ...............................................................................................6
4.1. Feeding from LV network .............................................................................................6
4.2. Feeding from MV network . ............................................................................................8
4.3. Feeding from HV line .....................................................................................................8
5. Additional requirements on the antenna system ..................................................................9
6. Telecommunication links .....................................................................................................9
7. Installation and maintenance ................................................................................................9
References .................................................................................................................................9
Abstract parameter for the required power fre- depth around the equipment
quency isolation level cabinet(s).
Locating radio base station antennas Characterization of the EPR and the
in power line towers is mainly of interest control of the touch and step voltages by
in rural areas, where there are no tall potential grading earth electrodes (PGE)
buildings for the antennas to be installed. Guide on the design of the protection
1. Particularities of
In order to get a comprehensive view for schemes against the simultaneous
the use of power line towers for RBS in stresses due to EPR and lightning surges. RBS on power line
different countries a common question- The Recommendation K.57 (October tower
naire has been made up commonly by 2003, Geneva) can be ordered from the
CIGR and ITU. The Study Group 5 of Electronic Bookshop of ITU, on CD- At every power line tower with a
ITU-T has developed the Recommenda- ROM, on paper or on-line through the radio base antenna, there is a cabinet
tion K.57 in close co-operation with the following website: http://www.itu.int/ located near the tower or between the
CIGRE WG C4.2.02 (formerly WG publications/main_publ/itut.html. legs sometimes elevated, if possible (see
36.02) on the bases of the replies re- Keywords: LV supply protection, Figure 1).
ceived and the considerations of the par- RBS feeding, RBS protection, Tower
ticular electromagnetic environment EPR
affecting an RBS mounted on power line
tower.
The Recommendation K.57 specifies Abbreviations
measures to be taken with respect to
safety and risk of damage to equipment EPR Earth Potential Rise
through earth potential rise, when power T-EPR Tower earthing potential rise
line towers are used for locating radio Z-EPR Zone of the earth potential rise
base stations. It also considers the special RBS Radio Base Station
lightning protection scheme, which is HV (High Voltage), Voltage levels
needed for this type of installation. This exceeding 100 kV a.c.
is of special concern, when power is fed MV (Medium Voltage), Voltage
from the low voltage network, which is levels lying between LV and
the most common situation. Different HV
feeding options are described. LV (Low Voltage), Voltage levels
The design of the protection of the not exceeding 1 kV a.c.
supply circuit is covering the following MOV Metal Oxide Varistor Figure 1: RBS antenna (upper part of
the figure) and the elevated cabinet
areas: SPD Surge Protective Device
Identification of the tower potential PGE Potential Grading Earth is an The location of the equipment cabinet is
rise due to earth fault, which is the key electrode system laid at small not a safety issue, but rather a question of
ELECTRA 1
accessibility to the tower and/or the own- The last factor has of secondary impor- 2. These are given for different parame-
ership of the land occupied by the cabi- tance. ters assuming an average span of 333 m.
net. This cabinet is hosting equipment for When the power line is equipped The so-called base tower earth potential
transmitting and receiving and has cable with aerial or underground earth wires, rise (T-EPR) values are plotted in Table
connections for power feeding and occa- the significant portion of the fault current 1 as per 10 kA, which is the total earth
sionally for signal transmission as well. returns through these wires and only a fault current (3I0). The correction factors
There is a transformer cabinet for power fraction of the earth fault current flow for the EPR due to span smaller or lower
supply in close proximity to the equip- through the tower footing. The T-EPR that 333 m are plotted in Table 2. The T-
ment cabinet or in a dedicated part of the can be characterized by the product of EPR is practically not affected by the
cabinet. The antenna may be mounted that fraction (3I0E) of the zero sequence span in case of power line equipped with
below or above the phase conductors or component of the earth fault current (3I0) counterpoise.
even above the overhead earth wire(s), if that is passing through the tower footing, By the use of Ub base T-EPR values
any. and the earthing resistance (R) of the the following two kinds of design values
There are two phenomena that have tower, i.e. 3I0 E R. The T-EPR values cal- can be determined:
to be considered simultaneously: culated by the multiconductor line simu- 1. The required isolation voltage Uis for
When a single earth fault on a power lation technique [1] are shown in Figure a given earth fault current can be de-
line of a network with directly earthed
neutral or a double earth fault on power
line(s) of a network with non-directly kV 1*10 kA, L=60 km, 0.1/0.1
earthed neutral occurs, a large EPR will
12
appear at the tower, maybe tens of kVs.
Potential Rise [kV]
ELECTRA 2
Table 2: Correction factors for the tower potential rise of lines with different span magnitude of the T-EPR causing the
(Base: the tower voltage for span of 333 m) Z-EPR
geometry (size and structure) of the
Span Tower earthing resistance
earthing system
[m] 8 ohm 25 ohm 50 ohm soil characteristic (geological nature,
stratification etc.).
200 0.77 0.77 0.77
The potential funnel is investigated
333 1.00 1.00 1.00 by the powerful CDEGS software, which
500 1.22 1.22 1.22 solves the electromagnetic field problem
of the modelled electrode system embed-
Line configuration: 400 kV, 2 shield wires ded in homogeneous earth with a given
Line length: L = 60 km specific soil resistivity. (The CDEGS
Fault location: L/2 = 30 km
software can model stratified earth struc-
Substation earthing resistances: 0.1 ohm / 0.1 ohm
ture as well.) The results of the investiga-
tion have been used according to the
Power line
tower
following sections.
MV
Public LV
3.1 Estimation of the minimum
length of junction cable
network
Feeding LV l i n e
Coupling Junction
point point
(box)
ELECTRA 3
1 Ve Table 3: Minimum required lengths of the junction section corresponding to the
x min = ------ --- ----- isolation voltage levels and admissible Z-EPR at the junction point
2 R V x
where the following values are assumed Minimum length, [m]
to be known: Isolation
to conversion cabinet for
the specific resistivity of the sur- voltage of the junction section
copper telecom cable 1)
face soil at the location of the level
tower holding the RBS Admissible EPR at the junction point, Vx
R earthing resistance of the tower
[kV] 650 V 1 kV 1.5 kV 2 kV
holding the RBS (the value consid-
ered in Appendix I of K.57) 10 44 29 19 14
Ve potential rise of the tower holding 15 67 43 29 22
the RBS (the value obtained
20 28 58 39 29
according to Appendix I of K.57)
Vx admissible no load earth potential 50 221 144 96 72
at the remote end of the junction 1) Note: See Figure 14
section, i.e. at the junction point.
When the junction cable is laid along a
straight route, then xmin is equal to the EPR [p.u.]
=1500 m
required minimum length of the junction 0,45
=50 m
section. 0,40
The / R ratios have been deter-
0,35
mined by the CDEGS program for a
0,30
series of actual tower footing arrange-
ments (they are actually 21 different 0,25
Cabinet Cabinet
0,9 m
0,6 m
Both the field measurements [2] and a) Application of single PGE frame b) Application of double PGE frame
ELECTRA 4
tem of a power line tower (Figure 4) is
Y Y
significantly lower than the T-EPR. On tower earth
0,3 m
Cabinet Cabinet
0,6 m
0,9 m
tower earth double grading
earth frame
bonded with the tower, and the step volt- 0,3 m
0,6 m
age around the cabinet can be very sig- 0,9 m
800
Figure 7: Application of the PGE system when the cabinet is located
30 between the tower legs
6212
0.8
6212
occurs in a narrow zone just above the Single frame Double frame
PGE electrode. The reduction rate can be 0.1
even below 0.25, when the cabinet is Grading frame Tower earthing
beside the tower. 0.0
The application of a second grading 5 4 3 2 1 0 1 2 3 4 5
frame provides an additional reduction Distance [m]
ELECTRA 5
The effectiveness of the use of PGE caused by the lightning strokes to the 10 ohm = 500 kV peak).
is demonstrated also for those two cases tower hosting the RBS. Apart from what is described in the
when cabinet is located beside the tower different options below, the following
Protection against power frequency
or between the tower legs in Figure 8 and shall be observed:
EPR
Figure 9, respectively. The cable shall not be stapled
The step voltage is given by the gra- The principle of the protection is the towards earthed parts in the transformer
dient (steepness) of the earth potential isolation of the LV feeding system, cabinet.
profiles. The following statements can entering the Z-EPR against the potential The cable shall approach the cabinet
characterize the effect of the PGE elec- rise. The potential of the conductors of perpendicular to the power line in order
trode system on the step voltage: the feeding line is fixed to remote earth. to avoid induced voltages.
the application of the grading frames (The phase conductors are earthed If the ground does not allow buried
practically does not affect the step volt- through the neutral earthing [assuming cable, aerial cable may be used.
age outside the outer grading frame TN system] while the neutral and the In order to protect the LV network,
the step voltage is significantly cable screen, if applied, are directly other measures have to be fulfilled, that
reduced in the zone above the double earthed.) The primary winding of the iso- may be required by the LV network oper-
PGE electrode frames lating transformer is also on the potential ator.
the step voltage is practically identi- of the remote earth due to its metallic As an alternative to a LV cable in
cal for the single and double PGE frame connection to the feeding line. On the plastic pipe a MV cable, which has the
systems outside the outer grading frame. other hand, the neutral of the secondary required insulation level, may be used for
winding is bonded to the tower earthing. power supply. This shall be installed at
Under the above conditions, the pro- least 50 m nearest to the tower. The MV
tection can be provided by the appropri- cable shall not contain screen, i.e. MV
ate:
4. Power supply and isolation of the primary (delta) wind-
cable manufactured without screen for
this purpose is required.
protection ing of the isolating transformer with
The applicable protection practice,
respect to the secondary winding, the
The RBS equipment may be powered such as the way of connection and selec-
iron core and any other metallic part of
in the following ways: tion of SPDs, is significantly affected by
the cabinet
From the LV network through an iso- the feeding arrangement, especially the
isolation of the phase conductors and
lating transformer in order to separate the structure of the junction cable that
any metallic part (neutral screen) of the
EPR area from the surrounding. This is together with the isolating transformer
LV junction cable with respect to any
most commonly used. are commonly protected with the SPDs
earthed part of the cabinet and tower, and
From a MV power network. In this applied at the feeding cabinet of the RBS.
to the earth in the Z-EPR zone
case you can use the MV/LV transformer K.57 describes the following three
power frequency withstand of the
as isolation between the EPR area and options for the scheme and protection of
SPD (MOV or similar device), i.e. appro-
the surrounding. the LV feeding system.
priate selection of its rated voltage Ur.
From the HV power line itself for In the case of option 1 the junction
example through capacitive voltage Protection against lightning-generated cable has no metallic screen and neutral,
divider, capacitive coupled conductor or surges the metallic parts of the cable are only the
inductively coupled loop. No technically When lightning strikes a tower host- three phase conductors. The voltage
finished and economical method is avail- ing an RBS, the majority of the lightning stresses (lightning impulse and 50 Hz
able for this feeding method and used in current is flowing to the earth through the potential rise) occur between the phase
hardly any. earthing of the tower. Thus a similar, but conductors and the earth.
impulse type EPR occurs as the EPR due Regarding the ways of providing the
to earth fault currents as described above. appropriate insulation with respect to the
4.1 Feeding from LV network
The magnitude of the impulse type tower earth the options are the following:
Typical arrangement of LV feeding T-EPR is essentially determined by the LV three-core cable with additional
system is shown in Figure 3, when the product of the magnitude of the lightning increase of isolation to earth. The addi-
equipment cabinet is powered from the current and earthing impedance of the tional isolation shall be provided by insu-
LV network. tower. Their ranges are for the lightning lating jacket on the cable or placing the
The protection of LV feeding system current 10 to 100 kA peak and for the junction cable in watertight insulating
involves the protection against power earthing impedance 5 to 20 ohm. There- tube.
frequency (50 Hz) overvoltages due to fore, the tower potential rise ranges from MV cable without metallic screen
earth faults and the impulse stresses 50 to 2000 kV (Typical value: 50 kA (may be manufactured by special order).
ELECTRA 6
In this case the required isolation to earth
Junction point
is provided by essentially the core insula- (box)
Junction cable
Feeding cabinet Isolating transformer Equipment cabinet
without screen
tion itself, which is further increased by
Ant. feeding
L3
an option, the cable may be three single- N
N
core cables. Isolating tube
or use of MV cable MV
The protection scheme for junction arrester
PE
Ant. feeding
L3
N
N
cable with concentric copper wire screen Isolating tube
L1
L2
cially in the vicinity of the tower. The
Ant. feeding
L3
N
required isolation to earth shall be pro- N
Isolating tube
Connections to
LV arresters
The screen carries the surge current earthing of tower
ELECTRA 7
4.2 Feeding from a MV network
ELECTRA 8
5. Additional have an adequate isolation level the frequency domain, Part 1:
be laid in an insulating, water-tight, Numerical solution, Part 2:
requirements on the plastic tube Case studies. COST 261
antenna system be terminated via a transformer Workshop, Cagliari, 2000
be provided with feasible over-volt- [2] Favez B. and Gougeuil J. C.:
General requirements on RBS
age arrestors. Contribution of studies on
located on antenna towers are given in
the technical specifications [6] and [9].
The transition point should not be problems resulting from the
The requirements on the installation
closer than the point, where the EPR is proximity of overhead lines
of the RBS sited on power line towers are
expected to be 650 V. This voltage level with underground metal pipe
the following:
is the limit for short-term overvoltage lines. CIGR 36.04, 1970.
with a duration of 0.5 s. Other levels may
Coaxial cables between equipment [3] ITU-T Recommendation K.8:
be chosen with reference to ITU-T Rec.
cabinet and antenna(s) shall be placed in Separation in the soil between
K.33 [4].
a suitable way in dedicated cable ducts or telecommunication cables and
clamped to the tower structure, in order Further information is given for the
earthing system of power facil-
to get unhindered maintenance and fault separation in the soil between telecom-
ities, Nov. 1988
repair of the equipment and the tower. munication cables and earthing system of
power facilities in the ITU-T Rec. K.8 [4] ITU-T Recommendation K.33:
Underground cables between equip-
[3]. L im i t s f o r p e o p l e s af e ty
ment cabinet and tower shall be laid in
When radio communication link is related to coupling into tele-
isolated pipes.
applied, which is a preferred technique communications system from
Communication equipment, antenna
for RBS sited on power line tower, the a.c. electric power and a.c.
and accessories shall be type approved
installation arrangement is shown as an electrified railway installations
according to national regulations and
example in Figure 15. in fault conditions, Oct. 1996
requirements.
The antennas will be placed in strong [5] ITU-T Recommendation K.52:
electric fields, where they may be Guidance on complying with
exposed to corona and sparks. The owner limits for human exposure to
of the antennas must be aware of this in 7. Installation and electromagnetic fields, Febr.
order to avoid degraded function of the 2000
antennas.
maintenance
[6] ITU-T Recommendation K.56:
Depending type of tower and loca-
Installation and maintenance of the Protection of radio base sta-
tion of the antenna(s), the levels of elec-
equipment located in the tower such as tions against lightning dis-
tric and magnetic field strengths from the
antennas and cables, is restricted to peo- charges, Aug. 2003
power line may be achieved from the
ple specially trained with knowledge
power company. [7] IEC 61643-1: Surge protective
about electric and magnetic fields from
If antennas are placed above the devices connected to low-volt-
power lines, normally linesmen of the
overhead earth wires, they shall be pro- age power distribution systems
power company. However, special cau-
vided with lightning protection [6]. - Part 1: Performance require-
tion has to be observed concerning the
ments and testing methods;
risk of exposure to electromagnetic fields
Edition 1.1, January 2002
from the RBS antenna(s). For guidance
6. Telecommunica- see ITU-T Recommendation K.52 [5]. [8] IEC 61643-12 Low-voltage
The installations on ground are nor- surge protective devices - Part
tion links mally done by specially instructed RBS 12: Surge protective devices
people. National regulations may require connected to low-voltage
When wire communication link is
further restrictions on this type of work. power distribution systems -
applied, in order to avoid problems of
Selection and application prin-
induction and EPR at earth faults, the tel-
ciples; First edition, Febr. 2002
ecommunication should use metal-free
fibre optic cables (see Figure 14). [9] ETSI Guide, Electromagnetic
If metallic cables are used for the tel- References compatibility and Radio spec-
ecommunication, they shall be con- trum Matters (ERM); Radio
structed and connected under the same [1] Sollerkvist F. J., Varju Gy. and site engineering for radio
conditions as the LV power supply. It Karolyi K.: Sophisticated equipment and systems, ETSI
means that they shall: multiconductor modelling in EG 200 053 V1.4.1, June 2002
ELECTRA 9
APPENDIX
Introduction The benefit of feeding from a MV net- antennas must be below the phases. Oth-
work is, that the normal MV/LV trans- ers use safe distances to live conductors
This Appendix contains a compila- former may serve as isolating trans- of 2 m.
tion of the comments received from the former. In densely populated urban All maintenance in the tower are
questionnaire, that was circulated areas, earth potential rise, EPR, is so low made by special power company person-
among the member countries of ITU-T
and the potential equalizing so effective, nel.
and CIGR SC 36, now SC C4, in the
autumn of 2001. Many responders also that there is no need for an isolating The installation of the transmitting
attached figures and photos of solutions transformer. equipment in a cabinet as well as its
and installations. earthing grid may be done by the wire-
It is acknowledge, that the answers to less company. Special attention is taken
the questionnaire constitute a worldwide to the bonding of the copper earthings to
experience of radio base stations sited in
power line towers - an experience, which Safety & distur- the galvanized steel tower in order to
avoid corrosion. Cathodic protection
is incorporated in ITU-T recommenda- bances may be needed.
tion K.57.
A summary of the answers as well as Concerning safety, there are different In answering the questionnaire some
the questionnaire itself is attached. have attached photos and articles, which
restrictions and legal instructions from
authorities, which have to be followed. have been published earlier, see the Bib-
Some countries allow working in a liography and Photos below.
General power line tower, when in operation.
There is also special attention taken to
Among the countries that have the risk of being exposed to RF radiation.
answered the European countries, Aus- There are general restrictions of Bibliography
tralia, Canada and USA use high voltage, working in towers during thunderstorms.
HV (> 100 kV) towers for locating Radio There is very little experience con- [1] van WAES, van Riet, van Deursen,
Base Station antennas and transmitting cerning disturbances from the HV and Provoost and Cobben: Experimen-
equipment. Some also use medium volt- tal study on safety aspects of cellu-
MV systems into the radio antennas. See
lar phone systems in HV towers
age, MV (1 - 100 kV) towers, which also table below. CIRED 2001
is the case in Japan and Thailand.
[2] G. Lessard and Y. Rajotte: Safety
Many countries avoid placing the
issues related to the connection of
antennas above top earth wires to mini- MV and HV grounding systems out-
mize the risk of lightning striking them. Special comments side substations, Transmission
Some locate the antennas below the and Distribution Construction,
phase conductors in order to make main- Many electricity companies use Operation and Live-Line Mainte-
tenance possible during operation of the overhead earth wires all through their nance Proceedings. 2000 IEEE
ESMO - 2000 IEEE 9th Interna-
HV line. HV network. This is of benefit to the
tional Conference on Safety, Main-
The equipment cabinet is normally EPR at earth faults. However, in areas tenance and Operations, 8-12 Oct.
placed between the tower legs, on ele- with low earth resistivity, some compa- 2000, pp. 375 - 381
vated platform or very close to the tower, nies only have earth wires a few kilome- [3] Y. Rajotte, J. Fortin and G. Les-
because they need a common earthing tres close to the substations. sard: Safety issues related to the
system. Feeding cables from the cabinet to connection of MV and HV ground-
The power feeding of the equipment the antenna are installed in a metallic ing systems outside substations,
16th CIRED Conference, 2001,
is the crucial point. The used options are pipe or on cable ladders bonded to the
Paper 2.14
feeding from the LV public network, tower structure.
which is most common, or feeding from Many have regulations that forbid [4] H. Zeuschel und P. Hoi: Nieder-
Spannungsversorgung von Mobil-
the MV network, the use of which working in a tower above the phase con-
funkstationen an Hochspannungs-
depends normally on the accessibility to ductors during HV operation. In order to masten,
a LV network in the proximity of the site. avoid power outages, the location of any EVU-Betriebspraxis 12/1998
ELECTRA 10
Questionnaire
Use of Power Line Poles for Radio Base Stations.
Information
Name:
Company :
Country :
General
Comment:
Comment:
Location of antenna(s)?
Comment:
Comment:
Location and way of installation of the cables between the cabinet and the antenna(s)?
(Connections of the screen to the pole and the cabinet, installation in metallic pipes etc)
How is the voltage drop in the tower during earth fault managed?
Others?
Power feeding?
How is the earth potential rise during earth fault (or double earth faults) managed?
Safety of people?
During installation?
During operation?
Mitigation techniques: