Anda di halaman 1dari 7

7

2013 Nirma University International Conference on Engineering (NUiCONE)

T-connected Transformer Integrated Three-leg


VSC based 3P4W DSTATCOM for Power
Quality Improvement
Yogesh Rohilla, Yash Pal

high current will flow through the neutral wire and may be a
Abstract--This paper provides power factor correction, cause of insulation failure of neutral wire and hazards.
harmonics elimination, load balancing and neutral current To cope with all these problems Distribution STATic
compensation of linear and non-linear, balanced and
COMpensator (DSTATCOM) is employed [2-3]. Here
unbalanced loads using custom power device DSTATCOM for
three-phase four-wire (3P4W) system. Perfect Harmonic DSTATCOM is made with 3-leg voltage source converter
cancellation (PHC) theory has been used for reference current (VSC) with DC capacitor for three phases and T-connected
generation. A three-leg voltage source converter topology with transformer for neutral current compensation [5] [7-8]. PHC
T-connected transformer as distribution static compensator control algorithm has been used as an indirect approach for
(DSTATCOM) is used in this paper. T-connected transformer is the reference source current generation. The three-phase
introduced here for neutral current compensation. Capability of
reference supply currents are derived using sensed ac
this arrangement is demonstrated using results obtained from
MATLAB-Simulink based environment. voltages at point of common coupling (PCC) and dc bus
voltage of the DSTATCOM as feedback signals. One
Index Terms--DSTATCOM, Neutral current compensation, proportional plus integral (PI) controllers is used to estimate
Perfect Harmonic Cancellation theory, Power factor correction, the amplitudes of in-phase components of reference supply
T-connected Transformer, THD. currents. Hysteresis current controller has been used to
generate the six gating pulses to operate the 3-leg VSC.
I. INTRODUCTION Simulation results during steady state and transient operating

3 P4W systems are now widely employed in distributing


electric energy both to commercial and domestic users.
Both of these types of users use loads employing
conditions of the DSTATCOM are presented and discussed to
demonstrate power-factor correction, load balancing and
harmonic reduction capabilities of the DSTATCOM system.
semiconductors like television sets, air conditioners, ovens, Power system blockset of MATLAB (MATrix LABoratory)
refrigerators, uninterrupted power supplies, rectifiers, Simulink software is used to show the required results.
inverters, computer loads etc [1-3]. Also variation in load is
very high changing minute to minute, day n night, morning to II. SYSTEM CONFIGURATION AND DESIGN
evening. Seasonal effects also change the load requirements.
VS ZS IS IL Different
Even a half degree rise in temperature in summer results in PCC
high increase in air-conditioning loads [1]. Similarly a Varying
L s Rs IC VPCC Loads
decrement in temperature in winter increases the heating
loads. This load increment or decrement is very high in
highly cooled and hot areas. Also the lifestyle of generation is DSTATCOM
moving towards comfort zone which increases the
televisions, computer and inverter type load. Fans and
Cdc
pumping loads work on the lagging power factor and draw
reactive power from the supply. Compact fluorescent lamps Vdc
although requires very less electrical energy but works on Fig. 1. Single line diagram of DSTATCOM.
poor power factor and act a source of reactive power
consumption. 3P4W system consists of three-phase as well as Fig.1 shows the single line diagram of DSTATCOM
single phase loads. The arrangement of single-phase load on connected as shunt compensator. A three-phase, four-wire ac
spur lines is not equal and creates unbalancing in load source with line impedance (Ls, Rs) feeds power to balanced
or unbalanced, linear or non-linear load and combination of
problems. All the loads discussed above are non-linear in
all the loads. At the DC bus side of the VSC (voltage source
nature and distorts the sinusoidal nature of the supply voltage
converter) of the DSTATCOM, a DC capacitor is used to
and currents and require high amount of reactive power. maintain the constant DC bus voltage. The operation of
When this distorted supply is applied on other loads affects DSTATCOM can be accomplished in two modes, power
their performance and life also. Due to unbalanced load a factor correction (PFC) and zero voltage regulation (ZVR).
978-1-4799-0727-4/13/$31.00 2013 IEEE
7

The PFC mode is considered here. In PFC mode, among the three phases. The windings of the T-connected
DSTATCOM supplies the reactive power demanded by the transformer are designed such that the mmf is balanced
load so that the source should supply only the active power properly in the transformer.
required by the load. The PFC mode phasor diagram of
DSTATCOM is shown in Fig.2. The synchronous reference
frame control algorithm is used to extract reference source
currents and PI controller is used to regulate the DC bus
voltage. The extracted reference source currents are
compared with the respective sensed source currents and
current errors are used to generate the switching signals for
the VSC after amplification of errors. For generating the
switching signals, current errors are feed to the carrier based
PWM generator or carrier less PWM generator (hysteresis
PWM generator). Carrier less PWM generator has been used
here to simulate the DSTATCOM system in this work. The Fig.2. Phasor diagram of PFC mode of DSTATCOM.
design values of DSTATCOM system components for a load
of 20kVA, .8 power factor, 415V (L-L), 50Hz is given in A. DSTATCOM
appendix. The operation of VSC of DSTATCOM is similar to The power and control diagram of DSTATCOM is shown
the 3-leg DSTATCOM. For compensation of load neutral in Fig.3 to understand the working of it. The following steps
current, a T-connected transformer is used which allow are involved:
flowing zero sequence or loading neutral current and split it

Rr Cr

Va Ls R s CS VS isa CS iLa
Vsa Three-Phase
Foue-Wire
Vb isb Vsb iLb Linear, Non-
linear,
Vc Balanced,
isc Vsc iLc
Unbalanced
iSn iLn and Dynamic
Vsn Loads

iCn b1
b2
a2 a1
iCa iCb iCc

b3 T-connected
Transformer
Cdc

3-Leg VSC

6 Gating
isa isb isc Signals

Current Controller
Vsa
Vsb
Vsc iLa
Compute Reference iLb
Vdc Source Currents iLc

Fig.3. Power and control diagram of 3-leg VSC with T-connected transformer as DSTATCOM.

1. As shown in figure, first of all, three voltages (vSa, vSb 2. Now with the help of load currents and PCC voltages
and vSc) at point of common coupling (PCC), three load reference currents (  are generated with
currents (iLa, iLb and iLc), three supply currents (iSa, iSb the use of control algorithm. Control algorithm is needed
and iSc) and voltage across the DC capacitor (vdc) are to generate the reference source currents. Reference
sensed.
7

source currents mean the currents which the source icr(p-p) is current ripple,
should supply. fs is the switching frequency,
3. After that reference source currents and sensed supply Vdc is dc bus voltage of DSTATCOM.
currents are fed into current controller. This current
F. Computation of Controller Gains
controller produces the six switching signals on the basis
of difference in behavior of the two currents. A PI controller is required for regulating the voltage of self-
4. Feed the switching signals produced by the current supporting DC bus. It requires two controller gains,
controller in the 3-leg VSC. These switching signals are proportional gain (kp) and integral gain (ki). In this work the
used to on-off the six IGBTs (Insulated Gate Bipolar values of both the gains are found by hit and trial method.
Junction Transistor) of the VSC. As a result required G. Current controlled PWM Generator
compensator current is produced. Compensator currents
In a current controller, the sensed and reference source
are the currents which flow through the VSC. As it is
currents are compared to generate the switching signals
required that source should supply only active power of
forVSC. There is much type of current controllers in use.
load but load power requirement is of both active and
Hysteresis current controller is used here and a MATLAB
reactive types. So DSTATCOM supply the reactive
power as required by the load and source supply only model of the controller is shown in Fig.4.
active power of the load. DSTATCOM get this power
from the self-supporting dc capacitor connected at the
one end of the VSC.
B. DC Capacitor Voltage
The minimum dc bus voltage of VSC of DSTATCOM
should be greater than twice the peak of the phase voltage
of the system [6] [7]. The dc bus voltage is calculated as

Fig.4. MATLAB based model for Hysteresis Current Controller

where m is the modulation index,
VLL is the ac line output voltage of DSTATCOM. H. Design of T-connected Transformer
Fig.3 shows the connection of two single-phase
C. DC Bus Capacitor
transformers in T-conguration for interfacing with a three-
The value of dc capacitor (Cdc) of VSC of DSTATCOM phase four-wire system. The T-connected windings of the
depends on the instantaneous energy available to the transformer not only provide a path for the zero-sequence
DSTATCOM during transients [6] [7]. The principle of fundamental current and harmonic currents but also offer a
energy conservation is applied as path for the neutral current when connected in shunt at point
of common coupling (PCC). Under unbalanced load, the



zero-sequence load-neutral current divides equally into three
where Vdc is the reference dc voltage, currents and takes a path through the T-connected windings
Vdc1 is the minimum voltage level of dc bus, of the transformer. The current rating of the windings is
a is the overloading factor, decided by the required neutral current compensation. The
V is the phase voltage, phasor diagram shown in Fig.5 gives the following relations
I is the phase current and to nd the turns ratio of windings [7]. If Va1 and Vb1 are the
t is the time by which the dc bus voltage is to be voltages across each winding and Va is the resultant voltage,
recovered. then
D. Ripple Filter
A low-pass rst-order lter tuned at half the switching
frequency is used to lter the high frequency noise from the
voltage at the PCC. Ripple filter should be designed such that
its impedance as high as only a small current can pass
through. This insures the very small loss across the RC filter.
E. AC Inductor
The selection of the ac inductance (Lf) of VSC depends
on the current ripple, switching frequency, dc bus voltage. Lf
is given as



where m is the modulation index, Fig.5. Phasor diagram of T-connected transformer
a is the overload factor,
Va1 = K1Va
7


Vb1 = K2Va the DC bus voltage at a constant reference value ( ).
where K1 and K2 are the fractions of winding in the phases. is the losses of DSTATCOM and this power is required by
Considering |Va | = |Vb | = V and Va1 = Va cos 30o, Vb1 =Va the self-supporting DC bus of DSTATCOM and it is
sin 30o, then from above two equations, one gets, K1 =0.866 estimated by the PI controller over the DC bus voltage of
and K2=0.5. DSTATCOM and can be expressed as:

III. CONTROL SCHEME

Many control theories are available in the literature for the Where = error in DC bus voltage.
control of DSTATCOM by the production of reference and are reference voltage and actual voltage of DC bus of
source currents for the VSC [9-16]. Some of them are DSTATCOM respectively.  are the proportional
instantaneous reactive power theory [9], synchronous and integral gains of the PI controller over the DC bus
reference frame theory [11] [16] on single phase and three voltage of DSTATCOM.
phase basis, Icos control theory [12-14], perfect harmonic Reference supply current in a-b-c frame can be
cancellation [15] etc. In this work PHC control theory is calculated by inverse transformation as:
considered for DSTATCOM operation. The control theory is

developed for the unity power factor operation of the
 
DSTATCOM.



and are the required reference source currents.
]

2 1 1/ 2 1/ 2
v 1 .[ p DC + p DCe

3 0 3 / 2 3 / 2
These extracted reference source currents ( and ) and
is*
1 0 i sa* the respective sensed source currents  are fed
v + 1
+

0

2
2 1 1/ 2 1/ 2 i * 1 / 2 3 / 2 i sb* in hysteresis current controller to generate the switching
s 3
3 0 3 / 2 3 / 2

1 / 2 3 / 2
signals or pulses for the DSTATCOM.
( 3 )

i sc*
1
= Ax



IV. MODELING AND SIMULATION


iS 0
i S*
iS

vdc*
*
*

Fig.6. Block diagram of extracting reference source currents using PHC The DSTATCOM (3-leg VSC with T-Connected
Transformer) is modeled and simulated in MATLAB-
The block diagram representation of the PHC control Simulink with power system toolbox. This model is shown in
theory is shown in Fig.6. The perfect harmonic cancellation Fig.7. Different load arrangement is shown. The result will
(PHC) method can be regarded as a modication of the be discussed for linear as well as non-linear load with
instantaneous reactive power theory and unity power factor unbalancing using phase out. First linear but unbalanced load
theory. Its objective is to compensate all the harmonic is applied which is not shown here and then the results for
currents and the fundamental reactive power demanded by the non-linear loads are tested. After some interval of time
the load in addition to eliminating the imbalance. The source load of phase a and then phase b are out. The R-C ripple
current will therefore be in phase with the fundamental filter is connected with the DSTATCOM to filter out the
positive-sequence component of the voltage at the PCC. The ripples in the PCC voltage. PCC voltage and load current
reference source current will be given by along with the dc capacitor voltage are required to generate
the reference source current with the PHC for the hysteresis
current controller. Source current and generated reference
Where is the PCC voltage space vector with a single
fundamental positive-sequence component and K is a source current are compared in Hysteresis current controller
constant whose value depends on the PCC voltage and the to generate 6-pulse switching signals to control the 3-leg
load. The power delivered by the source will be voltage source converter IGBTs so that it supply required

reactive power by the load. Connection of T-connected
In above equation represents the DC component transformer is shown for the purpose of nearly zero neutral
which is responsible for fundamental active power whereas current.
is harmonic power component. As source is required to
supply fundamental power only and the other power V. SIMULATION RESULTS
requirement i.e. reactive power must be supplied by The performance of 3-leg VSC with T-connected
DSTSTCOM so only is required from above equation. transformer as DSTATCOM is tested with linear-unbalanced
The fundamental instantaneous active power component can and nonlinear-unbalanced load for the purpose of power
be extracted from the by using a low Pass Filter factor correction, load balancing, harmonics reduction and
(Butterworth type). neutral current compensation. All the results are shown with


the simulation environment.

A. Linear Load
Performance of DSTATCOM with linear load with

Where
 represent the reference source unbalancing is shown in Fig.8 for power factor correction,
harmonics reduction, load balancing and neutral current
current signals in --0 coordinates respectively.

compensation. Three-phase load is changed to two-phase
and is active power required to maintain load at time 0.5s and to single-phase at 0.56s. And loads are
 

reapplied from single-phase to two-phase aat 0.63s and three- i.e., whole reactive power is suppllied by DSTATCOM. It is
phase at 0.68s. Results shows PCC voltagee and load current shown neutral current by source iss nearly zero whereas load
are in same phase. Also reactive power suppplied by source is neutral current is very high at the time
t of phase out as whole
negligible small as compared to power reqquired by the load neutral current is compensated by T-connected
T arrangement.

Fig.7. Matlab-Simulink simulation based model of 3-leeg VSC with T-connected transformer as DSTATCOM

Fig.8. Performance of DSTATCOM in PFC mode for llinear load (a) supply voltage vS (V), (b) supply current iS (A), (c) load currents iL (A), (d) compensator
currents iC (A), (e) supply voltage of phase a vSA (V) annd supply current of phase a iSA (A), (f) DC bus voltage VDC (V), (g) reacctive power demand by load qL
(W) and reactive power supplied by source qS (W) for pphase a, (h) source neutral current iSn (A), (i) load neutral current iLn (A)).

B. Nonlinear load compensation. Three-phase load is changed to two-phase


load at time 0.47s and to single-phase at 0.56s. And loads are
Performance of DSTATCOM with nonnlinear load with
reapplied from single-phase to twoo-phase at 0.64s and three-
unbalancing is shown in Fig.9 for power factor correction,
harmonics reduction, load balancing andd neutral current
 

phase at 0.73s. Results shows PCC voltagee and load current shown neutral current by source iss nearly zero whereas load
are in same phase. Also reactive power suppplied by source is neutral current is very high at the time
t of phase out as whole
negligible small as compared to power reqquired by the load neutral current is compensated by T-connected
T arrangement.
i.e., whole reactive power is supplied by D
DSTATCOM. It is

Fig.9. Performance of DSTATCOM in PFC mode for nonlinear load (a) supply voltage vS (V), (b) supply current iS (A), (c) lo oad current of phase a iLA (A), (d)
load current of phase b iLB (A), (e) load current of phasse c iLC (A), (f) compensator currents iC (A), (g) DC bus voltage VDC (V),, (h) source neutral current iSn (A),
(i) load neutral current iLn (A), (j) current supplied by ttransformer iTn (A), (k) transformer current for phase a iTa (A),(l) transfformer current for phase b iTb (A),
(m) transformer current for phase c iTc (A).

Fig.10. Waveform and THD spectrum of (a) PCC voltaage of phase c, (b) source current of phase c, (c) load current of phase c.


Waveform and total harmonic distortion (THD) b) Nonlinear load: 3 Single phase diode bridge rectifier load
spectrum of PCC voltage, source current and load current is with RL=8 and CL=300 F
shown in Fig.10. We can see that the THD of load current is PI controller: Kp = .19, Ki = 6.25
45.79% and waveform is spiky in nature. This load current AC inductor: .1, 15 mH
THD is compensated by the DSTATCOM to 2.77% to make T-connected transformer: Two single-phase transformers of
supply current sinusoidal. THD in PCC voltage is 3.22%. rating 5 kVA, 240/120/120 V and 5 kVA, 208/208 V.
Both the THDs for PCC voltage and supply current is well
below the maximum THD standard i.e., 5% as given by REFERENCES
IEEE. The magnitudes of the harmonics are very less and [1] A. S. Pabla, Electric Power Distribution, TMH, 6th ed., 2011.
averaged below 0.1% of fundamental values after [2] A. Ghosh and G. Ledwich, Power Quality Enhancement using
compensation by DSTATCOM. Custom Power Device, London, U.K.: Kluwer, 2002.
[3] Narain G. Hingorani, Laszlo Gyugyi, Understanding FACTS:
Concepts and Technology of Flexible AC Transmission Systems,
VI. COMPARISON Wiley, 2000.
In this work 3-leg VSC with T-connected transformer is [4] IEEE Guide for Applications of Transformer Connections in Three-
Phase Distribution Systems, IEEE C57.105-1978 (R2008).
used as DSTATCOM because it is one of the best [8] [5] B. Singh, V. Garg, and G. Bhuvaneswari, A novel T-connected
topology for power factor correction with neutral current autotransformer-based 18-pulse ACDC converter for harmonic
compensation, harmonics elimination and load balancing. As mitigation in adjustable-speed induction-motor drives, IEEE Trans.
we find from the results transformer has performed its task of Ind. Electron., vol. 54, no. 5, pp. 25002511, Oct. 2007.
[6] B. N. Singh, P. Rastgoufard, B. Singh, A. Chandra, and K. A. Haddad,
neutral current compensation accurately. In this method the Design, simulation and implementation of three pole/four pole
rating of the transformer used is less as compared to other topologies for active filters, inInst. Electr. Eng. Proc. Electr. Power
transformer based DSTATCOM [8]. Perfect harmonics Appl., Jul. 2004, vol. 151, no. 4, pp. 467476.
cancellation control algorithm is used in this work because it [7] Bhim Singh, P. Jayaprakash and D.P.Kothari, A T-Connected
Transformer and Three-leg VSC Based DSTATCOM for Power
was found in best methods of source current generation when Quality Improvement, IEEE Transactions on Power Electronics on
the load current THD is near to or less than the 50% [15]. In Power Electronics, Vol. 23, No. 6, November 2008.
[15] it is shown that performance of this theory is better than [8] Bhim Singh, P. Jayaprakash and D.P.Kothari, Magnetics for Neutral
the some other currently running theories. This is the reason Current Compensation in Three-Phase Four-Wire Distribution
System, IEEE, 2010.
of using this theory in this paper. [9] H. Akagi, Y. Kanazawa and A. Nabae, Generalised Theory of the
Instantaneous Reactive Power in three-phase Circuits, IPEC-Tokyo
VII. CONCLUSION 1983, pp. 1375-1386.
[10] T. Furuhashi, S. Okuma and Y.Uchikawa, A study on the Theory of
Performance of DSTATCOM consisting of 3-leg VSC Instantaneous Reactive Power, IEEE Transactions on Industrial
with T-connected transformer for the 3P4W distribution Electronics, Vol.37, No.1, Feb 1990, pp. 86-90.
system is simulated and the respective results has been [11] Vinod Khadkikar, Ambrish Chandra,Three-Phase and Single-Phase p-
q Theories pplied to Three-Phase Shunt Active Power Filter under
studied for power factor correction, load balancing, neutral Different Operating Conditions: A Comparative
current compensation and harmonics reduction for various Evaluation,International Journal of Emerging Electric Power Systems
linear, nonlinear and unbalanced load. T-connected Volume 11, Issue 2, 2010 Article 1.
transformer has performed its task of mitigating source- [12] G. Bhuvaneswari and Manjula G. Nair,Design, Simulation, and
Analog Circuit Implementation of a Three-Phase Shunt Active Filter
neutral current successfully. PCC voltage and load current Using the Icos Algorithm,IEEE TRANSACTIONS ON POWER
are in phase shows that power factor correction goal are DELIVERY, VOL. 23, NO. 2, APRIL 2008, pp. 1222-1235.
achieved. Problem of load unbalancing has also solved by [13] G. Bhuvaneswari and M. G. Nair, A novel current compensation
DSTATCOM. Whole reactive power is supplied by algorithm for a three-phase system feeding non-linear and reactive
loads, in Proc. IEEE IAS Int. Conf. Petroleum Chemical Industries,
DSTATCOM. This gives reactive power compensation. New Delhi, India, Nov. 910, 2004, pp. 5054.
THD results are shown. Results obtained have the THD [14] Manjula G.Nair and G. Bhuvaneswari,Design, Simulation and Analog
below 5%. Although THD level are well below the limits but Circuit Implementation of a Three-phase Shunt Active Filter using the
it can be more corrected with perfect tuning of PI controller Icos Algorithm, IEEE PEDS 2005, pp. 553-556.
[15] Mara Isabel Milans Montero, Enrique Romero Cadaval and Fermn
and by using perfectly tuned R-C filter. It can be observed Barrero Gonzlez,Comparison of Control Strategies for Shunt Active
PHC theory is a good tool for reference current generation. Power Filters in Three-Phase Four-Wire Systems,IEEE
With the power factor correction this arrangement can also TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1,
be used for voltage regulation as well although this is not JANUARY 2007, pp. 229-236.
[16] Bhim Singh and Sabha Raj Arya, Implementation of Single-Phase
given in this paper. Enhanced Phase-Locked Loop-Based Control Algorithm for Three-
Phase DSTATCOM, IEEE TRANSACTIONS ON POWER
APPENDIX DELIVERY, VOL. 28, NO. 3, JULY 2013, pp. 1516-24.

Line voltage: 415 V, 50 Hz


Ripple filter: R = 15, C = 1 F
DC Bus voltage: 700 V
DC Bus Capacitor: 4700 F
Line impedance: Rs = 0.01, Ls = 1 mH
Loads: a) linear: 20 kVA, 415 V, 50 Hz, pf = 0.8 lag

Anda mungkin juga menyukai