INSTRUCTION MANUAL

TR-210 - IM-L541(2)-0E
Analog transmitter for float tank gauges Aug.,1999

1. Sceope of descriotion and


relevant manuals
This Instruction Manual covers TR-210 - type ANA-
LOG TRANSMITTER FOR FLOAT TANK GAUGES.
TR-210 - type ANALOG TRANSMITTER FOR
FLOAT TANK GAUGES are installed onto FT-1
Float Tape type Tank Gauges or onto FP-1 Pipe
guided Float Tank Gauges and outputs liquid level data
in the form of DC4-20mA.
Refer to the following separate Instruction Manuals for
such mechanical portion of tank gauges;
Model Applicable Instruction Manual 3. Operational notes
FT-1 IM-L541
General notes
FP-1 IM-L542

This product is delivered after


2. Notation rules manufacturing and adjustment. Inspections have been
Safety symbols conducted based on the optimum quality control method
This manual classifies safety notes using the following for industrial instruments. If any attempt is made to
symbols: modify or change this instrument,it may fail to perform
as intended , or incompatibility or accidents may result.
Do not modify or change this instrument in any way. If it
If this indication is disregarded and this instrument is is necessary to modify or change it,contact Tokyo Keiso
operated incorrectly,serious injury or fatal accident may Co.
result.
Be sure to operate the instrument
If this indication is disregarded and this instrument is within the ranges of the specifications for fluid pressure
operated incorrectly, injury or property damage may re- and temperature listed in the Approval drawing. If the
sult. instrument is operated out of these ranges, it may be-
come defective or be damaged.

General information symbols


During transportation and storage,
This operation manual classifies general information
ensure to prevent moisture, dirt or sand from entering
notes using the following symbols:
the instrument as such will cause damage or render the
instrument defective.
Indicates procedures or information required to operate
this product. When connecting the instrument to
your process, center the pipes appropriately,set the flanges
correctly, and match the sizes of the joints.If there is an
Indicates information that should be understood to en- error in size stress may occur in this product,causing de-
able this product to be operated safely and comfortably. fects, malfunction or damage.
(-p. )
The indicated page contains information other than notes Use this product only as an indus-
that should be referenced. trial instrument.
Material 4. Product outline, operation
principle and product
The material of this product is de-
scribed in the Approval drawing.Although we make ev- construction
ery effort to select the optimal material for the customer's 4.1 Product outline
specifications, it may not be perfect due to the presence TR-210 - type ANALOG TRANSMITTER FOR
of foreign matter.Thus you are responsible for checking FLOAT TANK GAUGE converts the mechanical rota-
for anticorrosivity and compatibility. tion angle of tank gauges into current signal. The liquid
level in tanks is output in DC4-20mA form against 0 ~
Maintenance and inspections 100% of span and transmitted through 2 wire signal loop
for remote level monitoring.
When removing this product from
your process for maintenance or inspection, make sure 4.2 Operation principle
there is no object to be measured remaining in the instru- The movement of float of tank gauge drives its measur-
ment. If the object is corrosive or toxic,the operator may ing tape and rotates sprocket pulley in indicator housing.
be adversely affected. The rotation angle (number of rotation) of the sprocket
pulley corresponds to the length of tape movement which
The frequency and contents of the is finally corresponds to liquid level movement.
maintenance and inspection of this product vary depend- TR-210 - type ANALOG TRANSMITTER FOR
ing on the operational conditions.See the relevant selec- FLOAT TANK GAUGE is mechanically connected to
tion of this manual or check the actual operational con- this sprocket pulley and converts the mechanical rota-
ditions. tion of sprocket pulley into electric current signal.

Control Safety

Although this product is delivered


after manufacturing, adjustment and inspections have
been conducted based on the optimum quality control
method for industrial instruments, an unexpected defect
may occur. If this product is used for process control
that may result in a critical safety problem, take all nec-
essary actions to maintain safety.

TR-210 - type ANALOG TRANSMITTER FOR FLOAT TANK GAUGES Operation principle

-2-
4.3 Product construction 4.3.2 Intrinsically safe version TR-210S-
4.3.1 Weather Proof version TR-210W- and * Angle convertor
Pressure tight explosion proof version * Link Motion
TR-210E- * Gear down mechanism
* Gear down mechanism Block diabram TR-210S-
* Conversion Potentio-meter Angel convertor
* Current output circuit
* Terminal Terminal box
* Power circuit (Only for AC version)

Power unit
(Option)
Link motion
Potentio meter

Gear down mechanism

Current output circuit

Details of specification is as follows;


Gear down mechanism AC Power
(Option)
Level change for one rotation of sprocket pulley
Coupling plate Output
300mm
Terminal box Used angle convertor
YEW EBS Rotation angle 40
Block diagram of TR-210W- and TR-210E- Max. load resistance 350
Combination safety barrier BARD400
Details of specification is as follows; Ex-Proof cerrtificate
Level change for one rotation of sprocket pulley EBS angle convertror RIIS 34322
300mm BARD400 Safety barrier RIIS30772
Used Potentio-meter
Type CP-6 by Midori Instruments Co. 5. Model code
Rotation angle 240~270 TR-210 - type ANALOG TRANSMITTER is iden-
Resistance change 0~2k tified by the following model codes;
Type of R/I convertor and max. load TR-210 -
Type of R/I convertor and max load indicates the housing enclosure construction.
TR-210 W- W Weather proof (Non-Ex)
DC 24V PM2W(M System) 400 E Pressure tight explosion proof (Ex-d)
AC 100V PM(M System) 750 S Intrinsically safe (Ex-i)
TR-210 E- (Specified safety barrier to be used together)
DC 24V PB30B(Tokyo Keiso) 600
AC 100V PM(M System) 750
TR-210 -
Ex-Proof cerrtificate Cable glands with flame proof pressure tight gasket are
optionally provided. indicates this supply.
Type Power supply Classification Cert. No.
C Thread connection only
TR-210 E- DC 24V d2G4 37865
B Cable glands with flame proof gasket is provided.
TR-210 E- AC 100V d2G4 37865
F Others

-3-
6. Installation 7. Wiring and adjustment
6.1 Installation of total tank gauge with 7.1 Wiring
transmitter (new installation) 7.1.1 TR-210W, TR-210E 2 wire transmission
TR-210 - type ANALOG TRANSMITTER is type
mounted and delivered onto FT-1 or onto FP- 1) The standard cable entry is G1/2 thread. Other screws
1 tank gauges. are also available on request. Confirm in Approval
Refer to Instruction Manual of applicable tank gauge and Drawing.
conduct Wiring and Adjustment mentioned in 7. 2) Conduct wiring as per following figure.
3) The terminal screws is M 3.5 for TR-210W and M4
for TR-210E. Use compression terminal chips for firm
6.2 Additional installation of guage
connection.
In case of installation onto existing tank gauge, the rear
cover of subject tank gauge is to be the type of Trans-
mitter Attachable.
4) Follow the local ex-proof regulations for Ex-d version.
These Transmitter Attachable tank gauges are indicated
5) Conduct suitable water tight sealing after completion
and identified by the following model codes;
of wiring to avoid introduction of rain water.
FT-1 2, FP-1 2
6) The power supply voltage and load resistance are to be
For the additional installation of transmitters onto stan- within the specification mentioned in Approval drawing.
dard tank gauges, replacement of the rear cover of sub-
Load/Indicator
ject tank gauge is required. Contact Tokyo Keiso for de-

tails of such availability. +
+
The procedure of Additional Installation of transmitter is
as follows;
1) Remove the cover of transmitter connection unit. DC24V
2) Insert the coupling plate of transmitter into the mount-
ing hole of rear cover of transmitter. Do not forget Standard Wiring diagram
the gasket.
3) The slit of the coupling plate is to match the position 7.1.2 AC Power supply TR-210W, TR-210E
of the pin of the sprocket pulley in tank gauge. 1) The standard cable entry is G1/2 thread. Other screws
4) The cable entry of terminal box is to be located down- are also available on request. Confirm in Approval
ward. Drawing. Two cable entries are provided for AC
5) Mount and fix by using bolts. These bolts are cus- power supply and signal transmission. Use separate
tomers' scope of supply. cable entrires.
6) Tighten the bolts equally by using a spanner with 2) Conduct wiring as per following figure.
17mm width. (M10 bolts ) 3) The terminal screws is M 3.5 for TR-210W and M4
7) Mount the cover of transmitter connection unit. for TR-210E. Use compression terminal chips for
8) In case of Intrinsically safe version (TS-210S-), the firm connection.
housing of transmitter has different shape than other
version. However, the installation procedure is iden-
tical. Pin 4) Follow the local ex-proof regulations for Ex-d version.
5) Conduct suitable water tight sealing after completion
of wiring to avoid introduction of rain water.
6) The power supply voltage and load resistance are to
Sprocket pulley
be within the specification mentioned in Approval
Gasket Coupling plate
drawing.
Local/Indicator
+
+

U
AC Power supply
Rear cover of tank gauge
V

Standard Wiring diagram

-4-
7.1.3 Intrinsically Safe ,TR-210S FINE ADJUSTMENT
1) The standard cable entry is G1/2 thread. Other screws 1) Zero and Span adjustment Potentio-meters are located
are also available on request. Confirm in Approval on the surface of R/I convertor unit PM2W.
Drawing. 2) By using float hoisting mechanism of tank gauge, lo-
2) Conduct wiring as per following figure. cate the float at0% position and 100% position. Then
3) The terminal screws is M4. Use compression termi- adjust the output by rotating potentio-meters.
nal chips for firm connection.
Zero Adjustment Potentio-meter

4) In case of IS version, follow the local ex-proof regu-


lations for wiring. Specified safety barrier is to be
installed in safe area. In case that the safety barrier is
Tokyo Keiso's scope of supply, details of wiring dia-
Span Adjustment Potentio-meter
gram is shown in Approval drawing. Refer and con-
firm it.
5) After completion of wiring, conduct proper water tight
sealing to avoid introduction of rain water into termi- 7.2.1.2 TR-210E
nal box. COURSE ADJUSTMENT
1) Loosen the screw which fix the shaft of potentio-meter
to gear down mechanism to make the movement of
6) The supply voltage and load resistance are to be within potentio-meter shaft free. Rotate the potentio-meter
the description in Approval Drawing. shaft to obtain reasonable output current correspond-
ing to local indication.
2) Confirm that the resistance of potentio-meter changes
+ A continuously for full span of tank gauge.
3) After completion of course adjustment, tighten the
B screw of coupling.

BARD-400
Safety barrier Gear Screw

Standard terminal arrangement

7.2 Adjustment and confirmation of output


7.2.1 Adjustment of output
Potentio-meter
7.2.1.1 TR-210W
COURSE ADJUSTMENT FINE ADJUSTMENT
1) Loosen the screw which fix the shaft of potentio-meter 1) Zero and Span adjustment Potentio-meters are located
to gear down mechanism to make the movement of on the surface of circuit board PF-030B.
potentio-meter shaft free. Rotate the potentio-meter 2) By using float hoisting mechanism of tank gauge, lo-
shaft to obtain reasonable output current correspond- cate the float at 0% position and 100% position. Then
ing to local indication. adjust the output by rotating potentio-meters.
2) Confirm that the resistance of potentio-meter changes
continuously for full span of tank gauge This adjustment is conducted by
3) After completion of course adjustment, tighten the opening of housing with power supply. During opening
screw of coupling. the housing cover, the explosion proof function is lost.
Take necessary and proper actions to meet the local ex-
proof regulation requirement.
Gear Screw Zero Adujustment Potentio-meter

Span Adjustment Potentio-meter

PF-303B

Potentio-meter
-5-
7.2.1.3 TR-210S 7.2.2 Confirmation of output
1) Loosen the screw which fix the shaft of angle con- 1) By using float hoisting mechanism of tank gauge,
vertor to link motion move the float from 0% position to 100% position
2) Rotate the shaft of angle convertor to obtain reason- and confirm that the output changes from 4mA to
able output current corresponding to local indication.. 20mA properly.
3) After completion of course adjustment, tighten the
screw of angle convertor shaft.

Gear down Angle convertor


mechanism

Shaft screw

Link mechanism

0% Level

Hoisting handle

100% Lavel

Hoisting handle

2) When any discrepancy/error is found, check the ad-


justment of output according to 7.2.1.

-6-
8. Maintenance 9. Service net work
8.1 General maintenance items and their Contacts following for service and spare parts supply,
intervals etc.
Recommended maintenance items and their intervals are
TOKYO KEISO CO., LTD.
shown below;
Overseas Department
MAINTENANCE PROCEDURE RECOMMENDED Shiba Toho Build.
ITEMS INTERVALS
1-7-24, Shibakoen, Minatoku, Tokyo, 105-8558
Water and rust in
Visual check 12 months T E L : 3431-1625
terminal box
Loosening of F A X : 3433-4922
Visual check 12 months
terminal connection T L X : 02425378TICJ
Confirmation of Comparison E-mail address : overseas.sales@tokyokeiso.co.jp
12 months
output signal against local indication

Or

8.2 Trouble shooting


Your agent in your locality
Typical problems, suspected cause and their countermea-
sures are shown below;
10. Product guarantee
We offer the following guarantee unless otherwise speci-
Phenomena Suspected cause Countermeasures
fied.
Reconnection
No output Terminal loosening
Replacement Duration:
(0mA) Cable breakage
/repair of cable
18 months after our delivery or 12 months after start-up
No output
Problem of electric circuit
Replacement whichever comes earlier.
(4mA) of electronics

Output
Mechanical error
Check and readjust Scope of guarantee:
discrepancy Readjustment
against local
Electric adjustment
Replacement Problems caused by our design, manufacturing and/or
Internal electronics failure
indication /re-adjustment material.

Guarantee:
8.3 Spare parts Guarantee will be completed by replacement of equiva-
In case of requirement of spare parts, identify the parts lent instrument or repair of subject instrument. Tokyo
name and the manufacturing number of subject product. Keiso is not responsible for secondary losses even if any.
The manufacturing number of subject product is shown
on Tag plate.
Example of Manufacturing No. L99-12345-6