2016
F
.
) (GENERATION SYSTEM -1
: .
) (TRANSMISSION SYSTEM -2
: Overhead Transmission System Underground
. Cables
Reactive Power
-3 ) (DISTRIBUTION SYSTEM
.
.
Substations
( - -).
( ) Power System Stability
( ) .
.
.
( )
.
( . V.K. Mehta
Theraja
.
.
.
Transients TL
Parameters .
.
.
.
- -
.
.
.
.
(
) .
.
:
.
:
:
.
.
K
1992
Digital Protection
Om Parakash
.MALIK
Mohindar S. Sachdev
Saskatoon IEEE
Digital Protection
Digital Protection
Dr.
( Tarlochan Sidhu ) .
IEEE Sashdev Two Tutorials
Digital Protection
.
Digital Protection is a digital Filter. Explain :
Sashdev . That is enoug Mohendar :
Sashdev
.
.
.
: :
.
-1 .
. . .
. .
-2 . ( )
. ( ) . ( ) . (
) . ( ).
-3
( ) .
-4
.
-5
( )
( ) ( )
( )
.
-6
:. ( )
.
. .
-7 : ( 14) .
Contents
...................... ................................
............................... ................................
4 .. ................................ ................................
5 ....................... ................................
Governor 29 ...................................... : 1.3.4
30 ......................................................................... : Governor 1.3.5
31 ...... ................................ 1.4
32 ........................................................ 1.4.1
32 ...................................................................: 1.4.2
34 ............................. 1.5
: 34 .................................................................. 1.5.1
: 34 ...................................................................... 1.5.2
: 35 .............................................. phase sequence 1.5.3
: 35 .................................................... phase shift 1.5.4
35 ..................................................... (Automatic method): 1.5.5
36 ........................................ 1.5.6
37 .............. LOAD SHARING 1.6
38 ............................................................... 1.6.1
40 ........................................................ 1.6.2
54 ...................................................................................................................................2
55 ............. ................................ 2.1
104 .. AUXILILARY SYSTEMS 3.5
)104 ...................... (COMMUNICATION SYSTEM 3.5.1
)104 ................................................ (CONTROL SYSTEM 3.5.2
105 ................................. (PROTECTION SYSTEM) :- 3.5.3
106 ............... ................................ : 3.6
107 .................................................... : 3.6.1
111 .................................................................................................................................4
111 ..................... ................................ 4.1
113 .............................................................................. 4.1.1
115 ........................................................................... 4.1.2
115 .............................................................................. 4.1.3
116 ................ ................................ 4.2
118 ............................................................................... 4.2.1
119 ............................................ 4.2.2
119 ............................................................................... 4.2.1
120 .............................................................................. 4.2.2
124 .................................................................................................................................
126 ................. ................................ 5.1
126 ............................................................... 5.1.1
128 ...................................................................................... 5.1.2
129 ........................................................................ 5.1.3
130 ....................................................................... 5.1.4
132 .................................................................................................................................6
134 ..... ................................ 6.1
134 ............................................... 6.1.1
135 .......................................................... 6.1.2
137 ....................... 6.2
137 ...................................................... 6.2.1
139 ........................................... 6.2.2
142 ......................... 6.3
142 .......................................................................... 6.3.1
143 ........................................................................ 6.3.2
144 .......................................................................... 6.3.3
147 ........................................................ 6.3.4
147 .............................................................................. 6.3.5
148 ......................... GEOTHERMAL 6.4
148 ......................................................................... : 6.4.1
148 ..................................................................... : 6.4.2
150 ......... TIDAL POWER STATIONS 6.5
151 ....................................................................................... 6.5.1
154 ........................... ................................ 6.6
154 ............................................................ 6.6.1
154 ................................................................. 6.6.2
155 .................................................... 6.6.3
157 ................................................................. 6.6.4
157 ....... ................................ 6.7
158 ............................................................................: 6.7.1
158 .................................................................................... : 6.7.2
159 ................................................................................... : 6.7.3
160 .............................................................................. : 6.7.4
160 ........................................................... 6.7.5
162 ............... ................................ 6.8
HVDC 187 ....................................... 7.3.3
187 ..................................................................... 7.3.4
188 .............................. 7.4
245 ............... ................................ 10.5
245 .....................................................................: 10.5.1
247 .............................................................. 10.5.2
249 ...................................................................... : 10.5.3
CAPACITANCE 252 ..... 10.6
252 ................................................................... Ferranti Effect 10.6.1
253 .......................... 10.6.2
255 ............................................ Arcing Ground 10.6.3
258 .............................................................................................................................. 11
258 ........................ ................................ 11.1
258 ..................................................... 11.1.1
259 ..................................................... Power Factor 11.1.2
260 .............................. REACTIVE POWER 11.2
263 ............................................................ 11.2.1
264 .................................................. Reactive Power 11.2.2
SURGE IMPEDANCE LOADING, SIL 265 ....... 11.3
266 ...........................................................................SIL 11.3.1
267 ................................................... 11.3.2
269 ............. ................................ 11.4
P Q 270 ...................................... 11.4.1
271 ........................................................... : 11.4.2
271 .................................................................... 11.4.3
272 .................... 11.5
272 ........................................................................... : 11.5.1
272 ................. :Over-Excited Synchronous Motor 11.5.2
273 .............................................................. : Shunt Reactors 11.5.3
273 ...................................................... : Series Capacitors 11.5.4
274 ....................................................... : Shunt Capacitors 11.5.5
275 : FACTS ...................... 11.6
276 ............... Static VAR Compensators, SVC 11.6.1
278 .................................................................: STATCOM 11.6.2
279 ................... : Static Synchronous Series Compensators 11.6.3
280 .............. Unified Power Flow Controllers 11.6.4
283 .............................................................................................................................. 12
283 . ................................ ................................ 12.1
284 .................................................Transmission S/S 12.1.1
285 ...................................................................................... 12.1.2
288 ............................................................ 12.1.3
289 ..................................................................... 12.1.4
291 ........... ................................ 12.2
: 291 .............................................. 12.2.1
: 292 ............................................................ 12.2.2
: 292 ............................................... 12.2.3
: 292 ............................................................ DC 12.2.4
: 293 .............................................................. 12.2.5
: 293 ........................................................ 12.2.6
: 293 .................................. . 12.2.7
: 293 ............................................................ 12.2.8
295 .. ................................ 12.3
317 )................. (EARTHING TRANSFORMER 13.8
: 389 ........................................ 15.4.7
: 390 ........................ 15.4.8
: 392 ...................... GPR 15.4.9
: 392 ............. 15.4.10
: 393 ............................................................... 15.4.11
401 .............................................................................................................................. 16
402 ..................................................................................................
410 .................................................................................................
411 .......................................................... SAS 16.2.9
413 ......................... 16.2.10
415 ............................................................SAS 16.2.11
417 ..............................................................
418 ..................................................... 16.2.12
419 ............................................................ 16.2.13
420 ...................................................................................
420 ................................... PLC : 16.2.14
421 ................................... Line Trap 16.2.15
422 ................................................. Pilot Cable : 16.2.16
422 .............................. Fiber Optic , FO : 16.2.17
422 ....................................................... Wireless : 16.2.18
424 .................................................................................
460 ........................ Incoming Cubicle 19.2.5
461 ............................ Cubicle Outgoing : 19.2.6
461 ............................................................: 19.2.7
462 .......................................................................... 19.2.8
463 ............................... : 19.3
463 ..................................................................................... : 19.3.1
) ( 463 ............................................................................ 19.3.2
464 ..................................................... 19.3.3
: 465 ............. 19.4
468 ...................................................... 19.4.1
468 ................................................................ Fuse 19.4.2
469 .................................................................. 19.4.3
471 ................................................................................. 19.4.4
472 ........................................................ 19.4.5
473 ........................................................ 19.4.6
480 ................................................. : 19.4.7
486 ................................................ 19.4.8
: 487 ......... 19.5
487 ............................................. : 19.5.1
489 ....................................................................... 19.5.2
491 .............................................................................................................................. 20
491 ................. ................................ 20.1
491 ...................................................................... 20.1.1
Loop 492 ................................................................... 20.1.2
Loop 494 ..................................................................... 20.1.3
494 ......................................................................... 20.1.4
495 ................................................................................ 20.1.5
499 DG .................. 20.2
500 .............................................................. 20.2.1
501 ........................................................ Coordination 20.2.2
502 ........................................................ 20.2.3
503 ................................................................ 20.2.4
503 ................................................................. Islanding 20.2.5
506 .............................................................................................................................. 21
506 .............................. 21.1
506 ........................................................... Radial 21.1.1
508 ................................................................. Ring 21.1.2
509 .......................... 21.2
543 ...... COMMUNICATIONS : 22.4
543 ....................................................... 22.4.1
544 ........................ 22.5
553 .............................................................................................................................. 23
553 ....................... 23.1
554 .................................................... 23.1.1
555 .......................... 23.2
555 ..................................................................... 23.2.1
555 ..................................................... 23.2.2
556 .................. ................................ 23.3
557 ................................ Synthetic Polymer 23.3.1
: 557 ........................................... PVC 23.3.2
558 ....................................................... Thermo-sets-: 23.3.3
558 ....................................................................... RUBBER-: 23.3.4
559 ........................................................... -: XLPE 23.3.5
559 ................... ................................ 23.4
559 ........................................................................... Losses 23.4.1
560 ........................................................... 23.4.2
560 ............................................................... : WATER TREE 23.4.3
563 .............................................................................................................................. 24
563 ........... ................................ : 24.1
564 ....................................................................... Conductor 24.1.1
( )566 .................. Semiconductor Layer 24.1.2
567 .............................................................. INSULATION 24.1.3
( ) 567 ...................................................... 24.1.4
568 ....................................................... Metallic sheath 24.1.5
569 .................................................................. 24.1.6
( ) 569 ................................ :FILLING - BEDDING 24.1.7
( ) 569 ..................................................... : ARMOUR 24.1.8
570 ............................................ Sheath Effect 24.1.9
573 ........................................... :OUTER SHEATH 24.1.10
574 ................................................................ 24.1.11
577 .............................................................................................................................. 25
577 .................... CONDUCTOR RESISTANCE 25.1
578 ................................................. Insulation resistance 25.1.1
578 ....................... INDUCTANCE OF CABLE 25.2
132. 602 ..................................... 26.13.1
DC 604 ..................... : 26.13.2
605 ............................................................... HVAC 26.13.3
606 ......................... )Very Low Frequency(VLF 26.13.4
608 .............................................................................................................................. 27
608 .... ................................ : 27.1
608 .................................................................... 27.1.1
609 .............................................................. 27.1.2
609 ................................................................................ 27.1.3
609 ................................................................................. 27.1.4
610 ........................................................... 27.1.5
610 ..................................................................... 27.1.6
611 ................ ................................ 27.2
() 673 .............................................. Voltage Sag 28.12.2
674 ...................... Short Circuit 28.12.3
674 ...................................................................................................................................
675 ......................... 28.12.4
) 676 ....................... Voltage Fluctuation (flicker 28.12.5
677 ................................................. 28.12.6
678 ................................................ 28.12.7
678 ......................................... Power Conditioners 28.12.8
682 .............................................................................................................................. 29
682 ......... ................................ STABILITY 29.1
744 ............................ 30.8
-:" 744 ..................................... "Passive Harmonic Filters 30.8.1
-: " 746 ....................................... . "Active Harmonic Filters 30.8.2
: "746 ................................. . "Compound Harmonic Filters 30.8.3
746 .................................................. Harmonic Cancellation 30.8.4
747 ............................................ Harmonic Cancellation 30.8.5
752 .... ................................ 30.9
752 ................................................................................. 30.9.1
753 ...................................................................................... 30.9.2
Energy Conversion
.
.
.
-1 : Fossil Fuel
. :
.
(
)
.
%90 .
.
( )
.
-2 : Renwable Energy
Geothermal Biomass .
( )
2
.
.
-3 : .
( )
.
.
!!
4
.
( ) Joule .
Work :
Work = Mechanical Energy (J) = Force (N) x Distance (mt) =Joules
( ) Power
:
Electrical Energy = Power (watt) time (sec) = Volt Amp Sec = Joules
kWatt-Hour
1 (kWH) = 1000 x 60 x 60 = 36x105 Joule
( Calorie ) BTU
Q .
Q
)( ) ( )( = =
:
.
(Absulute Temprature) Ko
273
( )
.
F = 32 + 1.8 times C
: .
: .
: ( -)
:
:
:
: (
) .
: .
6
8 ( )
1
1.1
1882
1863
1895 .
1964
.
DC AC ) )1-phase ( 3-
. )phase ) )40Hz ) . )50Hz
) )110 V .220V
.
1917
1928
1934
1951
( )11000 13
400 .
8
9
:
1.1.1
.
.
65506 2014
( 50
%25 18 ) .
36000
( 33 66 132 220 400 500
) ( ).
.
1.1.2
. spinning reserve
.
.
.
1952 90
. .
10 ( )
.
220. .1979 220. .
400. .
.900 MW .2009
1-1
.
400. . .
.
.
Figure 1-1
(
33.
)
2-1 .
10
11
:
Figure 1-2
1998 500 kV
18 13.3 850
400 kV (
Phase ) .
( . :
).
220 KV 28 1998
.
. 3-1
12 ( )
Figure 1-3
( Blackout )
( Restoration ) .
(
3 )
.1-1
Table 1-1
12
13
:
1.1.3
(
) . 4-1 300kV 5-1
6-1
7-1 ( 500 220 )
.
14 ( )
Figure 1-4
14
15
:
Figure 1-5
16 ( )
( )
HVDC .6-1
( : HVDC
). HVAC
16
17
:
Figure 1-6
7-1 .
18 ( )
18
19
:
8-1 .
Figure 1-8
20 ( )
( 34 )
7-1 ( 500kV
) ( 220kV ).
66kV
11kV
.
1.1.4
-1 (
) .
-2 ( ) Substation
.
-3
.
1.1.5
:
.
( 2%)
%11 %5
.9-1
Power Losses
(
) .
. % 40
20
21
:
Figure 1-9
1.1.6
No Load
Hot Spinning Reserve in operation in
service
:
-1
( )
.
-2 kWH
Base Load 24
. Base Load
.
-3 ( )
Peak Load
.
22 ( )
3 4 15 30
(
) NCC National Control Center
( )
.
Unit Commitment
Optimization
Techniques .
. Economic Load Dispatch
-4 Power Loss
-5
.
10-1 11-1
( ) ( 26 ) 2015 .
22
23
:
Figure 1-10
( ) Figure 1-11
12-1
. Peak load .
24 ( )
Figure 1-12
13-1 .
Figure 1-13
24
25
:
( )
2013 . 2014
.
100 40
30
. Hot Spinning Reserve 50-40
( Inertia
).
90 Reserve
. Load Shedding
1.2
10-1 11-1
:
:
:
Load :
26 ( )
( ) .
Electric Torque Mechanical Torque
( )Management System ( Feed
)Water Control Valve ( Forced
)Draft Fan
( )Governor Valve Mechanical
Torque Electric torque .
Frequency :
=
120
f p n
1.2.1
Table 1-2
Hz
49.2 %2
49.1 %3
49 %4
Governor
48.9 %7
48.8 %15
Load Shedding
48.7 %20
48.6 %22
.Blackout
26
27
:
. 2-1 .
Blackout 1.2.2
Blackout
.
.
:
) P (MW ) Q(MVAR
.
.
.
) (over load
Blackout . Blackout
Restoration 1.2.3
Blackout
(
....) .
-:
28 ( )
blackstart -
Auxilaries .
-
.
Synchrounization .
1.3 :
1.3.1
.
( ) E = k f Auxilaries
( ) ( Constant Power
Devices )
Rotor Automatic Voltage
AVR Regulator Rotor
. Rotor .
50 60 1.3.2
= 200 .
60
:
shaft
shaft
.
28
29
:
( )
= ,
50 60 . 60
50 .
Governor 1.3.3
. governor
governor Valve
governor
Governor Governor
.
Governor : 1.3.4
governor :
governor
governor Governor Valves
.
governor
. 14-1
Governor ( 2003
30 ( )
: Governor 1.3.5
.1 .
Flyball
.
30
31
:
Figure 1-15
.2 :
.
.3
.
1.4
:
-1
Reliability
.
-2
.
-3
.
( 400 -4
%80 ( 320 )
800 ( 320 )
%40 .
-5
.
32 ( )
1.4.1
"" Synchronization
Phase Angle
. Phase Sequence
: 1.4.2
-1
N sta rot
Eo
2
.1
.2 Nsta Stator
rot .3 Rotor
rotor
Exciter Rotor
)Automatic Voltage Regulator( AVR Exciter
( 20 ) .
7-3 .
-2
Frequency :
32
33
:
=
120
f p n
p
n rotor
Governor
.
-3 phase sequence
Phases
Phases R-Y-B R-B-Y
as magnitude and angle two phases
.
-4 phase shift
Phase
angle Phases .
Generator
( Synchronizer )16-1 CB (
) .
34 ( )
1.5
:
: 1.5.1
120
=
P . .
. Synchrouscope
: 1.5.2
N sta rot
Eo
2
34
35
:
If .
.
phase shift =0 .
Ns .
Field Poles
. Stator Phases
.
phase shift
.
( ) .
( )synchronizer
breaker
( )synchronizer ) (governor ) (AVR
36 ( )
) (synchro-check relay
.
17-1 .
Figure 1-17
18-1 .
Figure 1-18
1.5.6
36
37
:
2400 RPM 40 Hz
50 Hz turbine shaft
shaft shaft
.stator
)(Reactive power
-
-
. Circulating current
.
KW KVAR
over loading stability
.
Grid infinite Bus Bar, BB
( ) P or Q
.19-1 Q
P .
Figure 1-19
38 ( )
Q P
( )
Q
.
load sharing -:
1.6.1
Figure 1-20
38
39
:
Figure 1-21
Figure 1-22
40 ( )
Figure 1-23
1.6.2
40
41
:
field excitation . .
:
Q .P .
42 ( A- )
.
.
( - )
( ( )25-1 - - - -
- )
.
42
43
:
500kV
.220kV
66kV
500kV .220kV
.
.
Figure 1-25
.
44 ( A- )
1830kWH ( = 2014
164836 90 = . ) 1830kWH
2800 .
3-1 .
Table 1-3
44
45
:
( )
:
: 1970 1952
. %3 12
1985 :
5361 1986-1985 9850
1998-1997 %2 5
30000 .2015
...
30000 .2015
-1
%43
%27 ( -1
.)27
Figure 1-27
-2
( )
46
47
:
8
235 24 .
-3 (
)
4 kWH 40
( )2030
!!!! .
.
( )
:4-1
Table 1-4
48 ( A- )
-1 12x175 MW
.
12 .175 MW
-2 : :
: 2 627
1254 .
: 1 2 250
1 250 750
.
: 2 2 250
1 250 750
.
: 20
120 .
-3 : 2 30
60 .
-4 : 4 110
440 .
-5 : . :
(1 : )2 2 ( 4
250 2 250
) 1500 .
: 3 2 ( 1
250 2 250
) 750
48
49
:
-1
6
%40 .
( )28-1 .
12 175 MW 15.75kV
500 kV .220 kV
Figure 1-28
Figure 1-28
10000 ...
3830 520
111
40.
-2
. 1956
46 40
.
50 ( A- )
1750 ...
-3 67.5 x 4
4 67.5 .
1800 ...
-4
.
6 14.28 85.68
1993.
643 ...
-5
4 16.
470 ...
-6
.2013
5-1 .
50
51
:
Table 1-5
52 ( A- )
52
53
:
54 ( )
2
:
.1
.2
.3
.4
()
( ) ( 17 : 14 :
)17 : 22 11
.
( ) .
( ).
(
).
().
54
55
:
.
.
( 600
)
.
( 7-5) .
2.1
) ) BOILERS
( 540 160 )
.
Rotor Electric field -
) (STATOR
.
.
%50 59%
% 78 .
.
56 ( )
:
.
1 (
).
.
1 1041 .CO2
2.2
. 1-2
.
. .
Figure 2-1
56
57
:
2.2.1
.1 .
.2 .
.
.3 .
.
2.2.2
:
2-2
.
Figure 2-2
:
2
= (1 ) 100
1
T1 T2 ( )
(
58 ( )
) 550
.%64
T2 = 20+273 = 293 K
T1 = 550 + 273 = 823 K
Efficiency = ((1-293/823)*100 = 64.4 %
2.2.3
:
.1
.
.2
.
.3 () .
.
.
58
59
:
%99.5
()
.
.
distillation units
( )
: 2.2.4
( ).
Filters .
.
60 ( )
PH 2.2.5
( )NH4 PH
( (99.2 .
.
.
NH4 + O2 NO + H2O
. PH
Na3PO4
.
Na3PO4 + H2O Na2HPO4 + NaOH
NaOH + HCl NaCl + H2O
PH 2.2.6
) ) power of hydrogen or pH
.
7 ( ) 2.4
( ) 2.5 ( )2.9( . ) 6.5
.
7 . () 7.7
( . )9
7
25.
2.2.7
-1 :
60
61
:
-2 :
.
62 ( )
.
.
:
.
:
.
2.3 )(BOILER
() 3-2
.
.
540
160 .
.
( 9-2 ).
62
63
:
Figure 2-3
)(Furnace 2.3.1
.
1500 .
18
.
.
Draft Fans
.
64 ( )
.4-2
30
20 .
( ) .
Figure 2-4
)(Drum 2.3.2
5-2
.
(man-
.) hole
Figure 2-5 Drum
)(Economizer 2.3.3
. Drum and Economizer .6-2
64
65
:
Figure 2-6
( ) Heaters 2.3.4
Heaters 7-2:
Figure 2-7
Dearator 2.3.5
( Dearator 8-2
.
. 7ppm
Chimney 2.3.6
.
390
66
67
:
Air Pre-heater
Economizer Filters
.
100 .
9-2 ( .
315 )
Figure 2-9
2.3.7
/
. Feeding Pumps 225-180
. 3
.
68 ( )
2.4 )) TURBINE
. 10-2
. Governor .
150:
.
.
.
160 540
40 .
800 .
68
69
:
Figure 2-10
2.4.1
()
.
.
2.4.2
.
70 ( )
2.5 )(CONDENSER
/.
( ) 11-2
- -
.
Figure 2-11
( )
12-2
Shower
.
Figure 2-12
70
71
:
.13-2
Figure 2-13
( 2600)
.
72 ( )
2.6
.14-2
Economizer ( )Drum
Burner
(.)Air/Fuel
() Superheaters
( 542 )
( 105/)2
Governer
Shaft
( 320)
( 30/)2
72
73
:
( ) Exhaused
Reheater
.
.
Figure 2-14
3000
( 50) :
74 ( )
=
120
Rotor .
.
Diviator
270
( )Economizer
. .
2.6.1
( )
. By-pass
.
74
75
:
) (Fuel Oil
.
: ( )
:
76 ( )
1 250 ( 400
) .
( )
.
.
. ( ) 25 : 15 .
2.7 :
. 15-2
:
Figure2 -15
2.7.1
Air Compressor -
1 16
76
77
:
10.5
( .)16-2
Figure 2-16
:
.
COMPRESSOR
. %30 surge
.
Back pressure
.
2.7.3
. .
78 ( )
Ignation system Diffusion
Permix
Burners
"MAIN FLAME
Diffusion
.
50 3000 RPM
470 Difusion
premix
Premix :
Diffusion 470 500
.
1050
10.5
.
2.7.4
( )17-2
.
78
79
:
2.7.5
. shaft
.
.
2.7.6
-1
-2
-3
-4
-5 : -
80 ( )
2.7.7
Fire (
) Starting Motor
Power Electronics-based Circuit as motor 550
Fire .
:
Regasification
(
).
80
81
:
Figure 2-18
Figure 2-18
. .
3 5 .
.
.
.
(
).
82 ( )
.
. %35
82
83
:
Combined Cycle
500
.
( )19-2
HRSG Heat Recovery Steam Generator
.
.
Figure 2-19
84 ( )
( ).
HRSG
. %30
( . %52
) %61
: HRSG 2.8.1
HRSG
Catalysts Heat Recovery Steam Generator
) (HRSG
.
84
85
:
: 2.8.2
( )18% ( )31% .
%49 21-2 HRSG
140 .
Figure 2-21
: 2.8.3
Steam power plants .
.
.
.
86 ( )
: 2.8.4
.1 750 :
o 250
250.
.2 158
o 4 25 + 58.
.3 1 : 2
o 2 250 + 250.
220
.
22-2
Figure 2 -20
86
87
:
88 ( )
88
89
:
3
.
:
-1 ()Generator
-2 ()Transformers
-3 ()Excitation System
-4 Power Circuits
-5
-6 ()Switch Gear 6.3 KV
-7 ( )Switch Yard
-8 ()Power Center
-9 () MCC Motor Control Center
() Ups Un Interruptable Power Supply -10
-11
()Battery & Battery charger -12
(MEASURMENT SYSTEM) :- -13
(COMMUNICATION SYSTEM) : -14
SCADA SYSTEM -15
(CONTROL SYSTEM): -16
(PROTECTION SYSTEM) : -17
. Substations
90 ( )
3.1
. Synchronous
. Generator Synchronous Generator Rotor and Stator
Field Rotor
Stator
.
( )field ( )dc voltage Excitation
System .
1-3 .
90
91
:
- Main generator : Turbo generator 19KV 0.85 pf 440 MVA 3000 rpm
50 Hz
- Main Step-Up Transformer : 19/500 KV 480 MVA two winding Shell
Type ONAF
- Auxiliary Transformer : 19/6.6/6.6 KV 40 MVA Three winding Core
Type ONAF
- Medium voltage switchgear : 6.6KV 2500 A 40KA short circuit capacity
- Isolated Phase Bus duct (IPB): that connecting Generator Aux Transformer
and Main Transformer 19KV 16000A.
stator
.2-3 slots
92 ( )
: Stator Windings
.
Rotor
Shaft .3-3
92
93
:
3.1.2
. :
. Hydrogen Plant
Demi Water Stator Cooling
( %14 ) .
Vents
.
4-3 .
Figure 3-4
94 ( )
3.1.3
:
: DC Exciter 3-phase
: " " Exciter Field
Excitation 3.1.4
3-phase ( ) Exciter
Rectification .
Field Exciter
.
Exciter :
.
3-Phase Generator Exciter
( 100 ) Permanent Magnet
PMG PMG 3-
phase current Exciter
Field . Exciter
94
95
:
Rectifier
Permanent Unit for
Magnet exciter
Rotor
Rectifier
Output
Unit for
Stator PMG
Exciter Main
PMG
Generator
Figure 3-5
. 6-3
Figure 3-6
3.1.5
) ) (DC Excitation
.7-3 AVR
Excitation .
AVR
Firing angle
.7-3
Figure 3-7
3.1.6
20 kV (
690V) .
(High Voltage
) Generators .Powerformers
96
97
:
Powerformer ( Step-up
.)Transformer
)(a
Powerformer Powerformer
C.B.
)(b
Figure 3-8
B ()Powerformer
Figure 3-9
()Powerformer
98 ( )
( )Stator XLPE
10-3 ( )Rectangular Conductors
. ( )Rotor
.
Figure 3-10
:Powerformer
.1 Powerformer ( 1.5
) .
.2 ( )Total Fixed Cost
Powerformer .
3200
. 4 4 12
( .)Single-phaseStep-upTransformer
4 Powerformers 24
.
.3 Powerformer
.
.4 Stator
Stator
.
98
99
:
3.2
-1 step up transformer
-2 ( ) unit auxiliary
-3 ( ) start up transformer
-4 ( ) excitation transformer
(
)
step up transformer
.
15.75 23kV
15.75kV
.
220kV
( 500 kV 500 9 )
( )
. Generator-Transformer set
22 8 2 (
) off load
.tap changer
6.3 kV .
(.)C.B
-3 Start Up Transformer
220 kV
6.3 kV
( )C.B
220 kV .
-4 Excitation transformer
23 kV 900
Excitation
. (.)C.B
3.3
) : ( )
.
) ( 400 ) :
.
) (11 ) :
.
) :
.
.
100
101
:
) 6.3
( )SF6 .
:
.
3.4
250-100 MCC
Dry Transformer 400V /6.3kV
6.3 .
.
11-3
100
- Motor& Valve's
-
- ()PDP
- Battery Charger
- UPS
800
.
102 ( )
Figure 3-11
: 3.4.3
:
.
:
(110) ( 48).
:
.
DC system
Starting Blackout
. 15 MW.
.12-3
102
103
:
Figure 3-12
.
104 ( )
)(MEASURMENT SYSTEM
.
.
.
:
() V.T .1
() C.T .2
) (P.F V.T + C.T .3
( ) V.T + C.T .4
( ) V.T + C.T .5
( )Hz V.T .6
.
.
. ( )
.
104
105
:
. 13-3
. .
Figure 3-13
106 ( )
( (Simple cycle
150 66kV 220kV
common service building
Single Line Diagram .
3.6 :
o
o
o
o bus duct
o 15.75 KV (MV TR.) 6.3 KV
o ) (excitation bus bar
) (exciters
o ) (3 winding ) (static starter bus bar
o )UEL - (3-phase Motor 550KW
USG - Fire fighting pump 200KW o
o 6.3KV 400 )(LV TR.
o MV bus bar
( )excitation motors oil pumps
motor fire fighting pump
o LV bus bar Rectifiers
UPS
o UPS DC bus bar inverters
UPS
o
106
107
:
: 3.6.1
compressor turbine
shaft turbine turbine compressor
( 28MKA01 :)14-3
o C.B 2XBAC01GS001
2XBAT01
o C.B 2XBAC01GS004
2XMBJ01
o 2XBAT01 ( 2XBBT01
) 2XMBJ01
) (motor shaft turbine compressor
compassion room turbine
XBAC01GS0042 C.B turbine shaft rated
speed excitation 2XMKC10
2XMKC01GT001 & 2XBBT01GT001 C.B
synchronous speed
.
o black out Power XJ*0120
.2XBAT01
108 ( )
Figure 3-14
28MKA01
108
109
:
110 ( )
110
111
:
4
.
Reactor
.
( :
( ))6 .
.
Reactor
.
1954 5
. .
4.1
:1-4
112 ( )
Figure 4-1
4.0015 .
1.0073 .
1.0087 .
:
= 1.0073 2 = 1.0087 2
= 2.0146 = 2.0174
= 2.0174 + 2.0146
= 4.0320
-4
:2
Figure 4-2
0.0305
( )Albert Einstein 1879-1955 1907
112
113
:
( )energy
( )mass
.
E = m C2
.BINDING ENERGY
85
BTU 25
.
:
-1 235
999
.
-2 235
( ) .
( 18 30
) 3
.
4.1.1
( ) (.)
235 3-4
2 3
114 ( )
Figure 4-3
.
235
()1 MeV = 106 1.6 1019 J
114
115
:
.
( . : 1
1041 (.CO2
4.1.2
4.1.3
Uranium ( 235
)235 )Plotonium 239( 239 238
)Uranium 233( 233 )Thorium( 232
(. )nuclear fission
235
.
116 ( )
235
235 ( enrichment
.)process
:
235
.
()compact nuclear reactors
%3 %5
.
235 238 .
92
U238 238 92
U235 235
.
%5
%90 150 .
( depleted
)Uranium 235
.
% 5 .
4.2
4-4 :
116
117
:
.1
.
.2 moderator
.
.3 :
..
.4 400 450
.
.
.5
Figure 4-4
( )5-4 3
5 . 235
118 ( )
.
.235
()pellets
.
( )fuel assemblies 200 300
. 150 250 50
150 .
Figure 4-5
4.2.1
1200
.
118
119
:
2200 .
.
.
3 ) ( 3mg/kWh 700
.
4.2.2
.
.
4.2.1
()
) ) H2O ) (deuterium atoms (D2O).
.
.%10
120 ( )
- -
. .
.
4.2.2
.
. CANDU
Canada Deuterium Uranium reactor
235- .
238-
. 235- 238- 1 .
238-
.
-
235 .
.
.
120
121
:
1934
.
.
.
.
1939
( )2
1945
5:30
( )
( )150
.
.
Dwight Eisenhower
.
2:45 B-29
Tinian Island .
8:15 580
.
122
123
:
124 ( )
.
.
.
.
.
.
.
.
( ) 1-5 .3-5
124
125
:
Figure 5-1
Figure 5-2
126 ( )
Figure 5-3
5.1
(
20MW 150 MW)
.
5.1.1
.4-5
126
127
:
Figure 5-4
.1
.2
.3 :
.
.4 :Turbine
.5-5
.5 .
.
128 ( )
Figure 5-5
.6 :Pen stoke
.
.7 : .
5.1.2
.
:
( ).
%85 .
128
129
:
.
18.000 .
5.1.3
( . )Cavitation
( )
130 ( )
( )
.
5.1.4
6-5
( )
.
.
Pumping Storage
Figure 5-6
130
131
:
132
( )
6
2015 4 (
) ( 2015
EDF 250 ).
Geothermal
1-6
132
133
:
Figure 6-1
134
( )
1000 1300 .
6.1
. :
6.1.1
.
.
.
( 24 )
( 365 ) .
23 . 2-6
.
.
( ) 2-6
.
.
( )
.
134
135
:
Figure 6 -2
6.1.2
. :
90 .
( )
.
()
.3-6
136
( )
Figure 6-3
.
.
( : 15 - ) =
( : ) =
( : 15 + ) = .
4-6
Figure 6 -4
136
137
:
6.2
-1 : PV Cells
%15-10 .
-2
.
6.2.1
-1
(( )Agua Caliente Solar Project )5-6
( PV
)Photovoltaic solar cell 9.7
400 ( )First Solar
5 ( )thin film 77-75 .
138
( )
-2
(( )Charanka Solar Park )6-6
19.8 2014
300 280 .
138
139
:
-3
( Huanghe Hydropower Golmud Solar Park )7-6
( )Qinghai 5.64 .
( )PV Photovoltaic solar cell 2011 200 .
6.2.2
Figure 6-8
140
( )
Figure 6-9
(
. ) ( .
).
140
141
:
Figure 6-10
142
( )
solar
.thermal electricity
.
.
.
6.3
6.3.1
11-6
( ).
parabolic
trough solar thermal 2009 150
540 .
142
143
:
( ) ( 12-6
)
220
Figure 6-12
20 400
( )
.
1 2013
258000 2.5 100.
6.3.2
( )13-6
( ).
144
( )
Figure 6-13
( ) Molten Salt
.
( )Hybrid System .
6.3.3
.14-6
Collector
.
144
145
:
Figure 6-14
146
( )
70-30
20-10 20-15.
100
3
20 ( 100 ) 2.7 .
50
1800 - 1200 .
( . )15-6
.
Figure 6-15
146
147
:
6.3.4
.
6700
.
6.3.5
Injection Well
Production Well
( 1000)
( )16-6
Figure 6-16
148
( )
6.4 GEOTHERMAL
: 6.4.1
1904
. ( Injection Well .)17-6
Figure 6-17
: 6.4.2
( 200)
( 100)
( ) . .
. ( )18-6
148
149
:
Figure 6-18
150
( )
.
.
.
. .
.
400 .
. (
).
.
.
.
() .
. .
150
151
:
Figure 6-19
11 .
6.5.1
. ()
.
.
. 20-6
.
152
( )
Figure 6-20
. . .
.
.
.
.
.21-6
.
152
153
:
Figure 6-21
154
( )
6.6
.
.
6.6.1
6.6.2
154
155
:
3 (
) .
( ) 12
.
" "Off-Shore Wind Farms
( .)22-6
Figure 6-22
6.6.3
23-6:
-1 2 3 Rotor Blades 20
5 130.
156
( )
-2 Gear Box :
.a 30
.b 1500
-3 Nacelle Housing
/
5 . 30/.
Figure 6-23
-4 500 1500 3 5
6 7 .
-5 ( )kv 24
.
-6 Tower 40 60
140 5 .
Nacelle .
156
157
:
Induction Generator
( 50 ) ( )%0.5
( 27
/) .
" "Yawing
25/ " "Brakes
"."Nacelle
6.6.4
. :
P = 0.5 x x A x Cp V3
where:
)P = power in watts (746 watts = 1 hp
= air density (about 1.225 kg/m3 at sea level
)A = rotor area exposed to the wind (m2
V = upstream wind speed in meters/sec
v 0 v 0
2
1 1
v v
= Cp
2
)V0 (downstream wind velocity of the exit of the rotor blades
6.7
-1 :
5/
125 - 6/
216 .
1/
158
( )
" "Wake Effect .
-2 " :"Swept Area
.
-3 ":"Tip-Speed Ratio "
"Tip Blade 60
.80
: 6.7.1
Rotor
( )
.
24-6
.
Figure 6-24
: 6.7.2
.
.
158
159
:
-6
25 .
Figure 6-25
: 6.7.3
( )26-6
.
.
160
( )
: 6.7.4
.
95%
- - .
.
.
.
.
6.7.5
( )5-9 D
( )3-5 D D Diameter
.27-6
160
161
:
Figure 6-27
5D ( ) 3D
( ) . :
-1 Natural distribution
: 28-6
Figure 6-28
5D
3D .5D*3D
)2
5D :29-6
162
( )
Figure 6-29
5D
10D .3D
.
6.8
( 10 )
.
9/ 25
10.5/ .
125
.
2014 200
2003 ( )30-6
2006 .
2014 500
%12 .2020
162
163
:
Figure 6-30
164
( )
6.9
16 ( 7 ) %50
14 ( 6 )
:
(
)31-6 .
-1 :
164
165
:
-2
.
( 2.5 3.5)
.
( )
.2013
:
.
!!!.
.
:
-4 ( )
-5
( ) .
-6
-7
-8 kWh
-9
:
169
:
-1 :
.
.
.
.
-2 (
).
(
) .
. .
:
= Fuel cost 30 to 40%
= Fixed charges for the plant 50 to 60%
= Operation and maintenance cost 5 to 10%
Rate of Interst
.
1000 %3 5
150 (
1000) . ()
() .
170 - ( )
Depreciation
( ) (
)
.
.
Tariff
kWH
( )
.
:
-1
(
) . .
-2
.1-A
Figure 0 -1
170
171
:
1 1
1MVA 0.5
Apparent Poawer . 2MVA KWH
( ) 0.9 .
-3
Max Demand
. 2-A
720MWH Max Demand 1000kW
.
Figure A0 -2
Load Factor
. ( )
( Max
) Demand
172 - ( )
(.) Demand Mangment
-4
(
)
Blackout
(
) .
.
Tariff:
(1) Flat demand rate
(2) Straight line meter rate
(3) Step meter rate
(4) Block rate tariff
(5) Two part tariff
(6) Three part tariff.
1-A ( :) 2016
Table 0-1
172
173
:
450kWH
:
102
!.
2-A :
Table A-0-2
: 3-A
Table 0-3
kW kWH
.
174 - ( )
( ):
-1
(
) .
.
-2 .
-3
Load Curve
.
174
175
:
kWH
Overall Effeciency.
( ) . .
3-A ( ) $/kW
Figure A-0-3
4-A kWH ( ):
176 - ( )
Table A 0-4
5-A 2015
.
Table 0-5
176
177
:
5500
$/kW 8000$/kW 9-6 (
).
1200-1500 $/kW
. 6-A
.2008
Table 0-6
178 - ( )
178
179
:
7
.
:
DC AC
7.1
66 kV 400 kV
Table 7-1
500 kV
750 kV .
1-7
. ANSI Code
66
181
:
132 220
500 950
.
.
:
-1
.
-2
:
( ) PLoss = 3 I2 R
.
7.1.1
:
.
.
2-7 .
Table 7-2
182 - ( )
7.2
( ) DC Station )(February 11, 1847 October 18, 1931
1882
( ) .
.
(October 6,
) ) 1846 March 12, 1914 )10 July 1856 7 January 1943
(
) AC Station
.
(
) .
AC 7.2.1
-1 AC
( ( XL and XC Inductive and Capacitive Reactance
R DC
.
182
183
:
-2 Limits
Max power transmitted
V1 , V2 X
Power angle, :
1 2
= sin
DC
(
.) X
-3 AC
( .
)
AC DC Reactive Power
.
HVDC
.
HVDC HV-AC :
184 - ( )
HV-DC 7.3.1
-1
) (Rectifier ) (Inverter
1-7 .
Figure 7-1
184
185
:
-3 (
).
-4 HV DC Arc
SCRs
Gate Turn Off, GTO Commutation circuts
HV AC cycle
.
-5 . AC
HV-DC 7.3.2
HVDC :
-1 Synchronized
AC Stability
-
( ) Grids HVDC
. 6-1
. HVDC
XL . XC
-3 DC
Reactive Power ( )
DC .AC
-4 skin effect
AC ( DC )
) (I2 R DC.
-5 DC AC
skin effect .
-6 ) (I*R
) (I * (R+jX Voltage Regulation
.
-7 DC DC (
) AC
.
186
187
:
-9 Corona Losses
.
-10 S.C Current DC
AC
.
HVDC 7.3.3
HVDC Transmission
:
( 50 Hz 60Hz )
( ) ( static
) var compensators .
45 2000 HVDC .
HV-AC Capacitance
.
synchronization .
:
AC.
7.3.4
( Inverters and
Rectifiers )
( . : /
).
. DC
5-7 .
:
-1 .
188 - ( )
-2
.
-3 Break even distance
. 800
(
800) 800.
Figure 7-5
7.4
:
188
189
:
5 10 .
( )
.
.
30.000 /
.
190 - ( )
. -
.
Charactraistic Impeadance
Distance realy . Travelling Waves
7.5
.
-1 :
( ) :
Transmission towers
conductors
Damping devices
.
( ) Insulators
.
-2 TL Parameters ( )
190
191
:
Parameters
:
Inductance
Capacitance .
192
193
:
194 ( )
8
8.1
.
.
- -
30 kV/cm
.
.
:
-1
-2 .
-3 .
-4 ( . )..............
-5 .
-6 ( )
Tower Pylons
(
) .
50
( 370 ) .
( 221 )
.
194
195
:
Zhoushan
Island Tallest
2009
Overhead China Damao Island 370 m pylons in
2010
Powerline the world
Tie
Tallest
Nanjing
reinforced
Yangtze
1992 China Nanjing 257 m concrete
River
pylons in
Crossing
the world
HVDC Tallest
Yangtze electricity
River 2003 China Wuhu 229 m pylons
Crossing used
Wuhu for HVDC
Tallest
Elbe 1976 electricity
Germany Stade 227 m
Crossing 2 1978 pylons in
Europe
Tallest
Chushi
electricity
Powerline 1962 Japan Takehara 226 m
pylons in
Crossing
Japan
Overhead
line crossing 1998 Egypt 221 m
Suez Canal
Bosporus
overhead
1999 Turkey Istanbul 160 m
line crossing
III
196 ) (
One pylon
Pylons of
standing on
Ghesm 1984 Iran Strait of Ghesm 130 m
a caisson
Crossing
in the sea
World's first
Carquinez
powerline
Strait United
1901 Benicia 68 m + 20 m crossing of
Powerline States
a larger
Crossing
waterway
8.1.1
:) 1-8 (
. Tower -1
insulators -2
-3
:
Shield condctors Earthing Line
Dampers
Bundel Conductors Spacer
. Guarding Rings
196
197
:
Figure 8-1
(
).
.
.
Simulation
( ) Resistance, Inductance and Capacitance
Parameters
Ferrenti Effect Arcting Ground .
198 ( )
8.2
( ) three phases
.
.
:
-1
-2
-3 Right of Way
-4
8.2.1
55 15 ( )
.
33 KV -------------------------------------------5.100
66 KV ------------------------------------------ 5.490
132 KV----------------------------------------- 6.100
220 KV ---------------------------------------- 7.015
400 KV----------------------------------------- 8.840
Sag .
. 1-8 Formulas
:
198
199
:
Table 8-1
8.2.2
) (Span
. ) (
.
100 500
.
.
Right of Way ( -8
. )2
.
200 ( )
.3-8
Figure 8-3
( 4-8 )
500
( .
) .
200
201
:
Figure 8-4
.
10
Step Voltage .
.5-8
Figure 8-5
8.2.4
( 6-8 .) 7-8
.
202 ( )
400
8-8 15 T 1T
60 .
Figure 8-8
7kV/m .0.3kV/m
100
10 100
10 .
202
203
:
( )
.
8.3 :
.Galvanized Steel
.
% 80 .
. ( )9-8
.
. .
Figure 8-9
204 ( )
.
( )10-8
.
-
.
Figure 8-10
( )11-8
Inductance Capacitance
150
50 . Phase-R
150 .
.
204
205
:
Figure 8-11
8.4 :
.
250
". " Span
. % 99.5
.
206 ( )
:
.1 .
.2 .
.3 .
.4 .
.5 .
.6 .
.7 .
8.4.1
-1Conductivity :
.
-2 Mechanical Strength :
.
-3 Modulus of Elasticity :
.
206
207
:
-5Cost :
.
%60
.
.
8.5
( )12-8
.
skin effect
208 ( )
.
.
:
.
Electric Field
.
:
Aluminum Conductor Steel Reinforced (ACSR),
All-Aluminum Conductor (AAC),
All-Aluminum Alloy Conductor (AAAC),
Aluminum Conductor Steel Supported (ACSS),
Aluminum Aonductor Composite Core (ACCC),
Aluminum Conductor Composite Reinforced (ACCR), and
8.5.2
: 8.5.3
208
209
:
8.5.4
8.5.5
: 8.5.6
8.5.7
() 1 ( ) Moose or Zebra
2 Panther
14-8
. .
Figure 8-14
8.6 ACCESSORIES
Dampers ( )spacers
.Bundles Conductors
8.6.1
210
211
:
Spacer .16-8
.
Dampers 8.6.2
( ) Stockbridge dampers 17-8
18-8 6 11
( ) 12
. .
8.6.3
20-8
.
LEDs Flashing 60.
50
.
212
213
:
214 ( )
9
Insulators
.
. Disc Insulators
.
.
Discs .
1-9 ( ( .
Table 9-1
. .
214
215
:
9.1 :
:
-1 : ()
.
.
-2 :
.
9.2 :
9.2.1
9.2.2
216
217
:
:
Equi-Potential lines
( )5-9
.
.
Figure 9-5
9.3 :
: Porcelain: 9.3.1
.
60kV/cm Compressive Strength
5,000 Kg / cm2 Tensile Strength .500 Kg / cm2
Glasses: 9.3.2
Figure 9-6
( ) .
. & Cap
pin.
.
rubber : 9.3.3
()
.
( ( )7-9
) .
218
219
:
( )30
. .
Long rod.
Figure 9-7
9.4 :
-1 : ()
.
-2 :Breakdown :
.1
( . . . )
.2 Switching.
.3 Leakage Current .
9.4.1
Flashover
.
220 ( )
Flashover 9.4.2
(
) .
Flashover
Over-voltages 150 % .
. Flashover
Short circuit
.
Flash over
.
8-9 Flashover
D+B+C A+B+C .
Creepage distance Clearance Distance .
Figure 9-8
220
221
:
( )
Clearance Distance
arc ( 9-9
) .
Figure 9-9
2-9 .
222 ( )
Table 9-2
222
223
:
9.4.4
. .
( ) .
.
.10-9
Figure 9-10
224 ( )
9.5
Over Voltage
(
) .
Over Voltage . :
-1
-2 CB Switching
-3
-4 Open Circuit Ferro Resonance
-5 Ferranti Effect
( )
TL Parameters
.
9.5.1
Surge
Rod Gap 11-9
Gap
Gap . Gap
.
224
225
:
9.6
Partial Discharge
( ) .
electric field
disruptive potential gradient ( 30 kV/cm
)
a conductive plasma .
.
kV/cm .
.
( / / )
.
( ) Partial Discharge
CB
.
( 12-9
Partial Discharge
.Breakdown
226 ( )
Corona Losses.
Radio Interference.
: 9.6.1
:
.
: .
.
: .
:
( )
.
226
227
:
: 9.6.2
-1
(
) .
bundled
conductors Phase
short circuit
Figure 9-13 Bundle Conductors
( )13-9
.
-2
.
-3
Voltage Gradient
rounded rather than sharp edges Spacers
( ).
-4 .
-5 Corona Rings
.
. Gradient, kV/cm
.
9.7 :
Disc String
500
20 25 kV/disc
.15-9
Series Capacitors
.
Disc
Shunt
Capacitors, C1 .15-9
228
229
:
Figure 9-15
.
Disc
Flashover .
9.7.1
String Efficiency
String
.
: n
=
230 ( )
Flashover Voltage 78 5 1015
Flashover Voltage
685 490 280 ( )
4 7 9 .
.
:
:
1 75 100 48 100
2 140 93.4 90 92
230
231
:
9.7.2
Shunt Capacitors
.
16-9 Guard
Rings 17-9
Shunt Capacitors .
232 ( )
Figure 9-17
232
233
:
Capacitance
Self Capacitance
Self Capacitance
. . Insulation Coordination
234 ( )
234
235
:
236
( )
10
TL Parameters
10.1
Voltage Regulation
Transmission Efficiency Short circuit analysis .
. Parameters
R
Inductance, L
Impedance, Z Capacitance, C
Conductance . Admittance, Y
R, L and Z (Y) :
.
10.2
(I2R loss).
Sag
thermal limit of conductor
.
236
237
:
=
is the resistivity of the conductor.
ACSR
%2
.
Skin Effect
RAC RDC
( )1-10
Flux Linkage
Inductance
Figure 10-1 Flux Linkage
.
238
( )
-1 : Inductive reactance
XL
-2 : ( )
( ) XL
.
Bundle Conductors
( )
Skin Effect
. Bundle
10.3
Inductance
Inductance, L Coils
. Inductance
Inductance , L 10.3.1
Inductance, L
Inductive Reactance, XL XL = L
. R AC Current . XL
emf
XL
( R )
XL .
238
239
:
Inductance .
Self Inductance .
. L = /I1 Inductance
Mutual Inductance , M = /I2 . 2-10
.
Inductance, L ()
Phase Phases
Inductance L
.
L Self Inductance
Mutual Inductance Henery, H .
Inductance
240
( )
Indactance
.
: Indactance = 1 :
1 Ind
. Ind
Capacitance .
:
Inductance :
1
= 2
2
W Ind Henery, H
Inductance 10.3.2
P
V1 and V2 . 3-10
Figure 10-3
. V2 and V1
X 12
Power Angle Transfer Power Capacity :
240
241
:
4-10
90
90
.
Figure 10-4 Stability margin
:
-1
Power Losses
-2
Stability limit 90 .
-3 X
X Bundle conductors
.
FACTs . X
10.3.3
X
:
Lossless
.
.Thermal Stability
242
( )
( )I2 R t
Stability limit X
Thermal Limit . 5-10
( P12 ( . Surge Impeadance Load
SIL ).
Figure 10-5
Inductance 10.3.4
. Active Power, P
.
Reactive Power, Q
(
) .
( . ).
Phase Angles VSend VReciving
242
243
:
( 90 )
Phase angle
( ).
Inductance
Voltage drop
.
10.4 CAPACITANCE
Inductance
( ) Q
Q = CV
Q V
Capacitance, C
Permability o .
r 7 8 .
.
244
( )
Capacitance
0.0121
= /
log10
Self Capacitance
Two Phases Phase
Stay Capacitance
Stray Current . Capacitive Currents
Capacitance
.
(
.
244
245
:
) W (Joule
:
W = 0.5 CV2
. Admittance, Y
Admittance, Y 10.4.1
Z
Z
Admittance mho siemens
or
where
Y is the admittance, measured in siemens (1/ohm).
G is the conductance, measured in siemens. Real part of admittance Y.
B is the susceptance , , measured in siemens , Imaginary part of admittance Y.
10.5
:
: 10.5.1
Short TL 80 Lumped
Parameters R + j X 6-10 R
246
( )
X
.
( )R and L (
).
246
247
:
10.5.2
Medium TL 80 160 :
-1 Pi-Section T-Section Capacitance
T-model .7-10
-2 ( )
. 8-10
248
249
:
: 10.5.3
Figure 10-9
250
( )
Series Impedance, Z and Shunt Admittance,Y -10
.9
Integration
Differential Equation
- Sinh and Cosh Sin and Cos -
(
Supply End (VS, IS Z, Y ( Receiving End, (IR, VR
:
250
251
:
252
( )
10.6 CAPACITANCE
:
Ferranti Effect
Over Voltages
Arcing Ground
Stray Currents
. Stray Capacitance
Sir S.Z. Ferranti, in the year 1890
Ferranti Effect
252
253
:
) Leading Voltage 90
.10-10
Voltage drops
Inductance .10-10 VS VR Ferranti
. Effect
Stray Capacitance.
( Inductance
).
Capacitance .
10.6.2
Healthy Phases
Faulty Phase . 11-10
Figure 10-11
254
( )
Phase Voltage Phasor Diagram
12-10
.
Figure 10-12
Healthy Phases
11-10
( Phase Voltage -10
)13 Phase-a . .
14-10 N G Phase-A
VA- VG .
254
255
:
Figure 10-14
.Arcing Ground
( )
phase closed circuit
capacitance 11-10 .
Healthy Phases
.
system floating
CB
.
256
( )
5 .
over voltage
.
Phases.
256
257
:
258
( )
11
Reactive Power Compensators
Static VAR
Compensators
Reactive Power
Q
Powe factor
P-Q curve 9-11
. STATCOM
11.1
( ).
11.1.1
( )..
:
-1 ) (ACTIVE POWER ) (kW
) (R (
) .
258
259
:
Figure 11-1
electric load
Multi-meter
Apparent
Power VA
P Q .Power Factor
Q
. Q
260
( )
S . PF
2-11
90
.
Figure 11-2
( ( 1000kVA
) (P.F=0.8
) (P=0.8X1000=800 KW .
) (P.F=0.5
(P=500KW).
260
261
:
Figure 11-3
Active
.
Phase Shift 90 ( Lead
Lag ).
Phase Shift
.4-11
. 5-11
/
. P
.
262
( )
P
Reactive Power, Q
( )
Voltage drop
(
).
Q
Active Power, P Q
11-4 11-5
.
Coils
Q
P Q . 6-11
.
262
263
:
Figure 11-6
11.2.1
( ) P (
) Q ( . )7-11
Q (
)
.
Figure 11-7
264
( )
. 8-11
(
)
.
Figure 11-8
Q .
: Synchronous Generators
Q
.
Q Over Excited
Q ( . Under excited )9-11
/ Q Loaded
Surge Impedance Load, SIL Q SIL
. :
264
265
:
2
= )(
Reactive Power
Self Inductance . 2
) Q (used) = Q (Supplied
2
2
=
266
( )
2
= 2
= = Surge Impedance=Zo
) Q (used) = Q (Supplied Zo
C/C Impedance 600 - 400 60-40
.
Pure resistance
C/C Impedance
.
3 SIL
|V| in kVs
SIL 11.3.1
SIL
L and C .SIL
. 10-11
SIL Shunt Capacitor Q
SIL Shunt Reactor .
266
267
:
C/C Impedance 400
110 kV SIL = 30MW Operator
SIL .
11.3.2
Receiving end
.
X1 reactance of the transmission line
Reactive Power :
268
( )
Qr = Q1 (Demand) - Q2 (supplied).
3:
) Q2 (supplied) = Q1 (Demand Vs = Vr :
.
11-11 Q .
268
269
:
Figure 11-11
2014 9635 800
220 %92
. %94
11.4
Q
Q
.
Q S = P .
X Phase Angle
.
P Q 11.4.1
12-11
Figure 11-12
:
-1 ( )
-2 QR << QS
-3 Q X/R
" " Big Sink Q I2 X
.
-4
.
270
271
:
: 11.4.2
-1
.
.
-2 .
Phase Shifting .
-3
Parameters
Phase Angle
//
Facts
Flexible Ac Transmission Systems .
11.4.3
-1 :
Generator Synchronous .1
Synchronous Motors .2
Shunt Reactors .3
Series Capacitors .4
Shunt Capacitors .5
- -2 FACTs:
Static VAR Compensator, SVC .6
Static Synchronous Compensator, STATCOM .7
Static Synchronous Series Compensator, SSSC .8
Unified Power Flow Controller, UPFC .9
272
( )
- - :
-1
-2 Phase angle
-3
:
" " . Reactive Power Compensators
( 1 )5 ( 6 )9
.
11.5
: 11.5.1
Field
Field
circle diagram
Synchronous :
: P
272
273
:
VAR
Shunt Cap/Ind CBs
Contactors / .
P Q
. P and Q
Reactors
Reactive Capacitive
Shunt
Reactors
CBs
( Shunt Reactors
)13-11 .
.
( )14-11 X
.
.
274
( )
Shunt
Reactors .
Resonance .
( )15-11
. 17-11
Switching
.16-11
( )
Q
.
274
275
:
Figure 11-16
Figure 11-17
11.6 : FACTS
Capacitive/ Inductive Reactive Power
Q
SCR Control Circuits Switched Capacitors
.
FACTs .
:
276
( )
Reactance . SCR
SVC
SCR .
19-11 .
276
277
:
:SVC
-1
-2 CB
-3 Thyristor Switched Capacitor, TSC
Thyristor Controlled Reactor, TCR
-4 X ( ) Flexible
:
Inductors
Capacitive .
278
( )
: STATCOM 11.6.2
Inverter (
) Phase angle 90 Lead 90
Lag 21-11 Capacitive or Inductive
. STATCOM
( %12
SVC
) Inverter
278
279
:
SSSC STATCOM
( )22-11 X
/ .
Series Capacitors .
( )23-11
.
280
)(Substations
( )
12
12.1
.
. Substations
( )
.
Step Up S/S
( ) Step Up S/S
.
.
.
500/220 kV (
500 220 ) Transmission
Substations -
.
Distribution Substations
.
Distribution Substations
.1-12
284
( )
Figure 12-1
500 kV
220 kV
.
( )Transmission substations
.
12 Power Angle Phase Shifting
. Transformers .
284
285
:
12.1.2
66
( )2-12 66
.
286
( )
Figure 12-2
66
286
287
:
Figure 12-3
132
( )4-12
66kV
11kV 66/11kV
30 ( K1 ) K31 Distributors
.
288
( )
Figure 12-4
12.1.3
-1 .
-2 ( Losses )
.
-3
( )
.
.
288
289
:
-4
.
.
.
-2
.
.
: .
12.1.4
( ):
( ) SF6 / ()
.
.
( ) :
66/220/500. .
0.4/22. 0.4/11. .
)(outdoor type
)(intdoor type
) (control & protection Equipment ).(Control Building
) (Busbar:
1. )(Single Bus-Bar
2. )(Single Bus-Bar with Sectionalizer
3. )(Double Bus-Bar with Single Circuit Breaker
4. )(Double Bus-Bar with Double Circuit Breaker
5. )(Breaker and half with Two Main Buses
6. )(Main and Transfer Bus-Bar
7. )(Mesh or Ring Scheme
.
290
291
:
12.2
( ) :
-1 H. V. Switchgear
-2 Power Transformer
-3 M. V. Switchgear
-4 ( DC )DC
-5 Control system
-6 .
-7 .
-8
: 12.2.1
( AIS ) HV
Switchyard HV-BB
( ) Elements
HV Switchgear :
Lighting Arrestor, HVCB, VT, CT, Isolators, Earthing Switches, etc
HV-BB .
( ).
: 12.2.2
.
:
.
: 12.2.3
Incomming Cells
MV-BB .
MV-BB Single/Double BB
Outging cells MV- BB
( /).
( ) .
: DC 12.2.4
.
DC Voltage :
.1 ( )
.2
. :
.a Control circuits
220 110
.
.b 110 48.
292
293
:
: 12.2.5
( . )16
( ) 22 .
: 12.2.6
Load
Dispatch Center Inter Trip
Tele
.Protection
: . 12.2.7
Fire Fighting, FF
Compressor .
() ( )
. 5-12 220/66/11
kV
: 12.2.8
.
294
( )
294
295
:
12.3
. / / :
:
1- Primary System Characteristics
Local Utility
Nominal Voltage
296
( )
:
3- Insulation Requirements
(Basic Insulation Level) , BIL
Insulator and Bushing Creep
Minimum Clearances
Phase Spacing
Impulse voltage
// /
( )
( .
Surge Voltages
.
:
Short-Circuit Studies
Protective Device Coordination
Arc-Flash Risk Assessment
Motor Starting
296
297
:
Transient Stability
Insulation Coordination
Harmonic Analysis
Manned or Unmanned
Fault Recording
Local & Remote Control
Automation
Communication Protocol
12.4
( )13 ()
( )
. ( ) (
).
( )14
.
( )15 .
( )16 (
) DC ( ) ()
( ).
( )
299
:
13
Elements/Equipment (
) Single Line Diagram, SLD .
SLD
. SLDs .
13.1
1-13 11/66 / 66
11 /66 30
.
SLD
.SLD
Incoming/Outgoing Feeders
Incomming
Outgoing
.
300
( )
Figure 13-1
66kV
( )
( )
.
2-13 .SLD
300
301
:
66
.
Figure 13-2
302
( )
SLD :
Potential Transformers .
Earth Switches .
Wave Trap -9
3-13 Equipment
/ .
302
303
:
. . GIS
304
( )
AIS
() :
Overhead
Transmission line
. SLD
Surge Arrestor
(Lightning Arrestor, LA) .
Impulse
( Voltgaes )
.
4-13 .
Figure 13-4 LA
5-13 .
( )normal operationg region ( lightening
)surge region
5-13 .
304
305
:
:
Conventional Gapped Arrester (Valve Type Arrester) -1
Metal-Oxide (ZnO) Arrester -2
Non Linear
Resistor Element Spark Gap
.6-13
Non-linear Resistance
.
Metal-Oxide Arresters
.
Non-linear Resistance
Silicon-Carbide Metal-Oxide Non-linearity
characteristics . Series Gap
breakdown spark gaps
breakdown voltage spark gaps
.
( )Zinc Oxide
.arrestor
7-13
.LA
(
)
Figure 13-7 .
.
SS
.
LA
( ) (
) LA .8-13
306
307
:
Figure 13-8
308
( )
13.3 ISOLATORS
QLine
BB 9-13 ( ) QL1 and QL2
BB Earthing Switch
QE2 and QE3
. Earthing Switch
Figure 13-9
. CB
308
309
:
Isolators .
Isolator CB ) (Interlock
CB Isolator Isolator CB
Isolator
CB CB
CB .
(
) :
Vertical Break
Double End Break
Center Break
Double End Break Vee Type
Vertical Break
.10-13
500 .
( ).
vertical switch
.
Center Break
( .)12-13
( vertical
)break & double end break
" two
"insulator/phase
( three insulator/phase
) .
phase
Figure 13-12 Center break
.
310
311
:
2
.
Figure 13-13
13.5
( ) Feeder : 13.5.1
.1 CB .3-Phases
.2 .
.3 .
312
( )
1 ()
capacitance
.
: 13.5.2
.1 .
.2 .
.3 .
.4 .
13.5.3
.1 .
.2 .
.3 .
.4 .
.5 .
.6 .
.7 .
.8 .
.9 .
. 13.5.4
312
313
:
. CB (
) .
Relay
Autorecloser
.
. ( ) Feeder CB (
) .
.
Realy
.
(
).
1 5
. ( )Classes ( ).
CT .14-13
314
( )
Figure 13-14 CT
. CB CT
CT () CB CB BB .
. :
13.7
( 110)
.
314
315
:
)(Protection Equipment
) (Fault Recorder
.
) (Synchronizers
:
Phases and Sequences
.
( )
.
(
Figure 13-15 VT ) 15-13
(
120 )
.
.1 ( Inductive .)I.V.T
VT .15-13
.2 ()C.V.T
.Capacitive VT .16-13
CVT EHV .
CVT:
: .
: Capacitor
Coupling Capacitor Power Line Carrier
PLC
.Tele Protection
.
.
17-13 .
316
317
:
Figure 13-17
) (SOLID EARTHING
.
18-13 SLD
. .
318
( )
Figure 13-18
/
Zero Sequence Impedance
.
( .19-13
).
Ratings
Figure 13-19
.
318
319
:
Protective
Relay
Relay .
(Moving
) Contact ( )Fixed Contact
. CB .
Contacts ( )
Arc Contacts
( ) ( )
.
Contacts
:
( ) = ( ) MVA () 0.1
: 13.9.1
: :
Main Contacts
Auxilary Contacts
. 20-13 :
Figure 13-20
( ) ( )2
( .)3 2 3
( )4 ( )5
.Auxilary Contacts
2( Main Contacts )3
.
Auxilary Contacts
( )
.20-13
320
321
:
13.9.2
.1 ( :)Extinguishing Chamber .
.2 : :
()SF6
.3 ( :)Mechanism
50 ms
.100 ms
: 13.9.3
. D.C
.
Pneumatic C.B
( 66/220. )
17 ()Compressor
( )Piston
.
Hydraulic C.B
322
( )
( SF6)
. spring .
322
323
:
13.10
CBs :
13.10.1 Oil CB :
.
.
(
) . -
- ( )
) (Pump .
( )21-13 :
)Bulk Oil C.B (Dead Tank
)Minimum Oil C.B (Live Tank
324
( )
Bulk Oil
( dead tank
. )breakers
.
.22-13
Figure 13-21
Bulk Oil Bushing
21-12
Live Tank .
.
324
325
:
Air Compressor
( . )23-13
(
)
Figure 13-23 Air CB
.
.
.
.
.
:
Air Compressor
.
.
326
( )
13.10.3 : ): (Vacuum CB
( )24-13
.
.
Arc chamber
.
33
.
50
180 "
Figure 13-24 VCB
" 10000
. 75 40 60
.
13.10.4 : SF6
)( (SF6 ) :
326
327
:
2.5
5-3
.
) (SF6
) (SF6 ) (SF6 .
SF6
.
.1 SF6 6 Cable
Ducts .
.
.2
.
SF6 .
3200
.
.3 SF6 CBs SF6
Circuit Breaker .
SF6 40
.
328
( )
: SF6 13.10.5
.1 : 7
.2 6.2 :
.3 5 : Blocking
( )5 Circuit Breaker
Blocked ( )
.
.
( )
" " .
328
329
:
: . ( AIS
) Bay GIS
.
( )SF6 :
compressor .
25 .
short
circuit .
.
anti-pumping relay
.
330
( )
13.10.7 :
-1 220/66 kV SF6 66 kV
220 kV
( ) Pole Pool SF6
66 kV 3-Phases .
40 KA 220 kV
31.5 KA 66 kV
26.3 KA 11 kV
.
-3
.
Rolling .27-13
Figure 13-27
330
331
:
: -4
Restiking Voltage
( )28
.
13.11
. :
13.11.1
-1 Contacts
.
-2 .
-3 . Charging Limit Switch
-4 .
-5 .
-6
332
333
:
Operation Tests
.
Mechanical Interlock
Interlock
.
Electrical Interlock
. OFF/ON Local and
Remote. .
13.11.2
.
ON . OFF
500 (
)
Phase R-R 10 .
500
OFF-position
500 .
28-13 .
334
( )
Figure 13-28
13.11.3
- Contacts
phase 11 60-12
33kV . (25-100)
) (
.
29-13 -
100
.
334
335
:
Figure 13-29
: 13.11.4
.
.
.
:
%80 D.C 60%
D.C
: 100 %
D.C .
13.11.5
. :
O 0.3s CO 3min - CO
O Open
C Close
CO
336
( )
0.3 sec
: 0.3 sec
3 .
336
337
:
GIS
) (Circuit Breakers ) (Bus-Bars ) (Isolators ) (CT
) (VT ) (SF6 ). (Metal Housing
.
30-13 . GIS
SLD . SF6
SF6- CB .
13.12 GIS
.
Outgoing Bays -2 Switchgear
.
31-13 .
13.12.1 Bay
338
339
:
33-13 .
340
( )
Figure 13-33
CT and VT shielding
Induced currents .
3 / 12 Bays
.
340
341
:
GIS 13.12.2
( ) 35-13 Outdoor
Termination Module
( )37-13 Cable
Termination Module
342
343
:
GIS 13.12.3
SF6
.GIS GIS
GIS .
SF6-to-Air
.Bushing SF6-to-Air Bushing
GIS .SF6
344
( )
.
39-13
.
( )
).
345
:
MV Switchgear
BB CBs . 40-13
/
.
( )40-13
( )
.
.
LV BB .
Figure 13-40
.
346
( )
13.13 ( :) AIS
Phases
Phase
. 41-13 .
-1 :Outdoor .
-2 :Indoor
.
.42-13
Figure 13-42 indoor AIS
346
347
:
43-13
13.14 GIS
.
.
) (GIS
GIS %80
.
13.15
13.15.1 :
o GIS
switchgear.
348
( )
o .
o .
o .
13.15.2 :
o ) .(GIS
30 kV/cm
.
.
o
.
o AIS GIS
.
13.15.3 : GIS
o
.
o
Installers
.
o .
o AIS
AIS
AIS breaker 8-4 ( ).
o
348
349
:
.
.
o ( % 30 ).
o 400 AIS
( )GIS 2
= 199*236 =46765
43*12 = 522 2.
o :44-13
): (GIS 13.15.4
SF6
350
( )
13.15.5
GIS
. .
.
.
" " " " .
GIS
( )
GIS . GIS
. GIS AIS % 10 . %40
GIS .
. .GIS
350
351
:
14
Bus Bars
BB
. BB
() (
) .
14.1
:
-1 . Rigid bus
-2 .Strain bus
rigid
.1-14
353
:
strain
ACSR Strain type insulators
.2-14
354
( )
BB SF6 .3-14
Figure 14-3
354
355
:
:
-3 .
-4 .
-5 .
-6 .
.
Strain bus
).(strain bus
1-14
Table 14-1
14.2 BB ARRANGEMENTS
BBs :
1-Single BB
2-Double BB
3-Ring System
:
356
( )
Substation : BBs .
BB / /
/
.
BB
.
BB
.
: BB
)1 .
)2 .
)3 .
)4 .
)5
.
356
357
:
14.3.1
BB
-14
.4
BB .BB
BB
BB .
14.3.2
sectionalized Single BB
5-14
(
) Sections
.
.
.
358
359
:
Two-BBs
BB Bus Coupler, BC .
.
( )7-14 M-1
M-2 :
Bus Coupler,
BC
CB ( BC
2-BBs )
( M-2
)
M-1
Figure 14-7 Double BB with Single CB
CB BC
BC
360
( )
BB
.
CB
CB
BB
.
) (Isolators
.Bus Coupler
Bus Section BB
.
Bus Coupler BB
.
360
361
:
( )8-14 CBs .
CB
BB (
) CB
CB.
(
)
2-CBs
. Breaker Failure
Figure 14-8 Double BB with Double CB
362
( )
( )9-14 2-BB
.
.
.
3-CBs (
Bay ) 9-14 BBs
Main-BB CB
. Tie-Breaker
CBs
(
)
Feeder-8
CBs . Bay11 and Bay12
T1 10-14
CBA 1 and CBA 2
T3
Figure 14-10
S CBA 5
362
363
:
T2 S 5 6 3 .10-14
CBs
Bay
11-14
CBA 5 S
T1 4
1 T2
4 1 2 T3
4 1 2 3 6 .
.CBA 5
4
.
Figure 14-11
Two-
BBs
12-14 Bus 1
.
BB
(
)
.
Figure 14-12
364
( )
13-14 BB .
2-BBs ( )14-14
) Main ( BB CB
Bus Coupler ) bus coupler (Bus Tie
BBs
Transfer Bus CB
.
364
365
:
Transfer Bus CB
BC
Double BB with Single CB .
15-14
.
) (Circuits ) (Circuit Breakers .
(Main Bus-
).Bar
CB
Power flow
One and Half
Mesh
System
Figure 14-15 Ring System
One and Half 1.5 CBs
.
) (Circuit Breakers
).(Fault
) (Voltage Transformer
Directional OC Protection .
. One and
Half Bay .
366
367
:
14.6
.
:
-1 :
Table 14-2
-2
Table 14-3
15
( ) .
( )
.
Neutral earthed
(
)
Frames
Cable sheath 1-15
.
Figure 15-1
.
.
15.1
Return Path .
370
( )
( ) 0.5 1 .
5 ( ) . 1-15
.
Table 15-1
Ground
Potentioal Rise
.
15.1.1
.
.
d L
:
8L
R ln
2 L d
h
a a L b h
:
L
370
371
:
8L2 a 2 a b h h2
R ln 1 2
4 L ah 2a b
2
L 4L
R A
( ) IEEE-80-1986
R
2A 2A
15.2
Cable sheath
Ground
.Potentioal Rise
1
- Remote earth
- .
IF 10 kA 8
Ground Potential Rise, GPR 80 kV
( ) IF x RE . 2-15 :
.2-15
6-4
1300 .
.
15.2.1
:
.3-15
Touch
Voltage Potential
Distribution . 2-15
Figure 15 -153
372
373
:
15.2.2
IB
RB )Foot Resistace) RF
RE
.
10
. Safety Shoes
.
15.2.3
-
4-15
.
Figure 15-4
) (x1 x2
IF Step Voltage
( ) :
374
( )
I f 1 1
Vstep
IF 2 x1 x2
x1
x2
( ) X2 >> X1 .
15.2.4
. 5-15
:
-1 .
-2 Grid .
374
375
:
15.3
Grid
Meshed Electrodes .
100 100 ( )
( 6-15 11-15) .
.
376
( )
8-15
.ETAP
376
377
:
Figure 15-8
Grounf mat
Ground Grid
(
)9-15 (
)10-15
Figure 15-9 Earthing Mat .
.
Earthing
Rods .
( .)11-15
12-15
(
).
. Ground mat
Figure 15-3 :
.
Greound Grid .
378
379
:
15.4
:
Step Voltage and Touch Voltage .
.
) IEEE STD 80 (2000 "Guide for safety in AC substation :
grounding". .
15.4.1
Short circuit Study
Protective
Coordination Study
.
Soil Resistivity .
Resistivity ( )
380
( )
: 15.4.2
( Soil Resistivity
)
. Wenner four-pin method
. 2-15 (
).
Table 15-2
Four Electrode method 100-50
(
).
( )
( )
.
380
381
:
5 15
. Touch and Step Voltage
3-15
.
Table 15-3
Cs
Cs
:
382
( )
Cs
.
382
383
:
: 15.4.4
melting
( melting
) 3-15
1000
500 800 .
: .
.
IEEE-80 3
.
GPR
.
: IEEE:
384
( )
4-15
For example. commercial hard-drawn copper has material constants:
Tm = 1084 C
r = 0.00381 C - 1
r = 1.78 .cm
K0 = 234
= ) (
1973 +
+
d .
( ) = 8.832 I
IEEE-665-1995
( %60 )
.
384
385
:
.1 .
.2
( )
1000 200
.
.
.3 1202
.4 IGF
. .
386
( )
Table 15-4
.5
386
387
:
: 15.4.5
Ground Potential Rises GPR
Step Voltage
.Touch Volt
GPR
.
GPR .
(
) .
.
50kg person
70kg person:
50kg person:
70kg person:
) = ( + 2
) = ( + 2
1000 .
: 15.4.6
,
Surface Potential Distribution
. ( )
.
6-3
10 20 .
.13-15
Figure 15-4
.
388
389
:
: 15.4.7
Where )is the earthing grid resistance with respect to remote earth (
)is the soil resistivitiy (.m
-1 ( )
-2 ( )
-3
-4 ()
-5 ( )1-
.
390
( )
: 15.4.8
. Short Circuit
3-phase short circuit current
Single phase
Sf :Df
( Surface factor, Sf
)
. Sf =1
.
14-15 .
2720 :
875 ( Cable Sheath
) . GPR
.
1121 .11-15
. GPR:
GPR = IG RG
IG .
390
391
:
Figure 15-5
magnetic coupling
DC component Time Constant
. Decrement factor Df
: GPR 15.4.9
: 15.4.10
( ) Mesh Voltage
392
393
:
. .
ETAP
.
: 15.4.11
(
) . :
-1 .
-2 Current Limitter
-3
-4
394
( )
Example
:
-1 50 90
-2 3.15 kA
-3 0.5 sec
-4 0.15 sec
-5 40
-6 300 .m
-7 3000 .m 10
300 .m.
3000 .m 10
( Cs
:
394
395
:
: :
Tm = 1084 C
r = 0.00381 C - 1
r = 1.78 .cm
K0 = 242
Ta = 40 C
= ) (
1973 +
+
100 2 1202
396
( )
70kg person:
70kg person:
396
397
:
90x50 ( 6 7).
60
( 3)
22 .
120
)= 300 (.m
) = 956 (m + 22x3 + 50x7 LT = 90x6
)= 0.6 (m
A = 50 x 90 = 4500 m2
398
( )
( division
) factor is 1 X/R 15 150
Decrement Factor, Df
IG
Df= 1.25
: GPR
398
399
:
ETAP
1661 1720
.
ETAP 723
728 .
.
( )
16
Auxilary System
:
.1 AC Supply DC Supply.
.2 : .
.3 :
.
.4 .
.5 .
402
( )
: Auxilaries
16.1 : AC SYSTEM
AC Auxiliary System :
-1 Protection Panels
-2 GIS Control Panels
-3 Buildings Power Distribution Boards
-4 Building HVAC Distribution Board
-5 Building HVAC Lighting Board
MV Switchgear -6
UPS AC Loads -7
-8
402
( )
16.2 : DC SYSTEM
). (Chargers + Batteries
(
) ( 110 / 220) (48
).
. 1-16
.
Battery Charger
.
220V DC :
.a Emergency Lighting
.b Cables Protection Panels
.c Transformer Protection Panels
.d Bus Coupler Protection Panels
.e Bus bar Protection Panels
404
( )
:
.
8 .
battery charger (
)2-16:
-1
.
-2 .
( )DC Panel
. () DC Panel
.
Figure 16-2
: 16.2.2
-1 )Floating( : (
).
-2 ( )Equalizing
. ) (high rate
.
404
405
:
16.2.3
( .
).
16.2.4
:
( sulphation )
%14 .
:
cell ( ) 2.4 - 2.2 - 2
.
60
1.
.
.
406
( )
16.2.5
:
cell 1.2
.
: 16.2.6
%14 :
(
) .
406
407
:
: 16.2.7
-1
( )
-2
-3
-4
: 16.2.8
-1
. .
.
-2
.
-3 :
-
.
- .
- .
408
( )
. :
.
Distribution Control Center, DCC
. Substation Automation System, SAS .
: 3-16
SLD (
) ( 132
) BB Double
. BB
Figure 16-3
408
409
:
( )4-16
( . 11kV 2005
)
Figure 16-4
/ .
.
410
( )
SAS
).Supervisory Control and Data Acquisition System (SCADA
SAS
. 5-16 (
)
Figure 16-5
410
411
:
.SAS
SAS 16.2.9
( SAS )6-16 :
7-16 .SAS
412
413
:
16.2.10
( - - )
:
-1
-2
-3
IED
.
.
AIS GIS
( ) (
).
(Auxiliary
) contacts ( )
Contacts ) (Interlock
Contacts .
Contacts
.
414
( )
. .
:
:
.
SAS
.IEDs
.
414
415
:
16.2.11 SAS
SAS :
OFF Mode
Emergency Mode
.
.SAS
Operators Workstations
) (OWS ) .Engineering Workstations (EWS
OWS EWS ( )LAN Bay Control Intelligent
) Electronic Device (IED
.
SCADA
. OWS EWS
( )WAN and LAN Bay Control Intelligent Electronic Device
.)(IED 8-16 .SAS
416
( )
SCADA Control
Control Room
HMI Control
Local Supervisory
Conventional Control
)(PBs, Switches, etc.
Off
Local Emergency
Remote
Figure 16-8
SAS
SAS
) (IEC
SAS .IEC-61850
416
417
:
Protective Schemes
Reactors.
CT and VT .
.9-16
( )7-16
( )8-16
. .
418
) (
16.2.12
The F35 feeder protection system provides feeder protection, control, monitoring and
metering in an integrated, economical, and compact package.
418
419
:
16.2.13
The T60 transformer protection system is a comprehensive three-phase transformer
relay designed to protect medium and large power transformers.
Load Dispatch
Center, LDC .
PLC : 16.2.14
Power Amplifier
( 500. 220. )
( 50) ( 20 500) .
LDC
Wave Trap
PLC
) (HF ) (IF ) (VF
Modem Analog Digital
TCI .
420
421
:
.
.
Inductor 2000 Inductance 0.1-
2 mH
50
.Receiver .9-16
.
()
4 11
Figure 16-10 Wave Traps
.
Figure 16-11
Capacitor
422
( )
.LDC
Modem RTU
Analog Pilot Cable Modem
Analog Digital Tag Control Information, TCI
.
) (FO RTU Analog
Digital Analog TCI .
16.2.18 Wireless :
-1Towers :
.
Line of Sight
. . Repeaters
-2 Repeater .
( )
.
( )6
422
423
:
. AC DC
.
.
424
( )
.
(
)11-16 .
() .
Figure 16-12
16.3
16.3.1
-1 ) (
) ) 10 %
.
.
424
425
:
-2
.
16.4 :
.
:
.
.
( )sprinklers valves ( )deluge valves
( ) CO2/
.12-16
426
( )
.
.
Figure 16-13 :
) ) sprinklers valves ( . ) Deluge valves
) (sensors
.
16.4.1
( )
.
426
427
:
5%
.
16.5
16.5.1
Sprinklers .
.
()
.
.
428
( )
16.5.2
.
.
CO2
2 .
13-16
Figure 16-14
.
CO2
( ) .
( 24-1)
.
.
16.5.3
.
,
.
428
429
:
,
.
: 16.5.4
( )14-16
.
.
Figure 16-15 .
(
15-10 )
).
( )
431
:
)(DISTRIBUTION SYSTEM
- ()
17
17.1
" " .
3.3 kV - 6.6 kV - 11 kV - 22 kV - 33 kV :
400 220.
(PRIMARY DISTRIBUTION
66/11 ( )
. :
()
.
RMU
.
. .
.
433
:
: 17.1.1
:
:
434 ( )
Load Estimation
Load Forcasting
Load Charactraristics
:
.
. ( )
. ( ).
Demand Factor ( )
Diversity Factor
( )
.
.
load forecasting :
1. Short term load forecasting : up to 1 day
2. Medium term load forecasting : from 1 day to 1 year
3. Long term load forecasting : from 1 year to 10 years
434
435
:
Figure 17-1
: 17.1.3
.
:
Distributors
Ring Main Unit
:
436 ( )
( )
( UPS ATS
) .
( SCADA RTU).
17.1.4
.
. :
Radial / Ring
Over Head/Cables
( /)
11/22 kV
AIS/GIS
CB / Fuse
Bus Duct
BB Single/ Double/etc
Voltage regulators/Capacitors/ Tap changer
Distribted Generation //.
17.1.5
:
Short Circuit Studies
Voltage Drop
Thermal capacity
Relay Coordination
Load flow Study
436
437
:
Harmonics Studis
ETAP EasyPower
( .
.
Loss
Optimization
.Optimization
17.2.1
Objective Functions Objective Function
Stability Margin
. .Single Objective Function
Multi-Objective Functions
Stability Limit :
Optimization Techniques .
Objective Function Function
438 ( )
( ) Constrains
%3
Optimization Technique .
Optimization Technique
.
:
Particle Swarm Optimization, PSO .1
Genetic Algorithms .2
Cuckoo Search .3
.
IEEE
BBs . 2-17
.33-BBs
438
439
:
17.3
.
.
:
-1 . Distributors
-2 .
-3 RMU
Distributed Generation .
.
- ()
( )
18
.
18.1
: 18.1.1
(
) . .
.
.
1-18 .
Table 18-1
.
442 ( )
Demand Factor
Diversity Factor .
.
1-18
Demand Factor, Fdm
Diversity Factor, Fdv Max
Demand, D
( )
.
Figure 18-1
442
443
:
: 18.1.2
Distribution Substtations :
-1 11/132 11/33 11 /66 11/33
.
.
. SLD
11/66 2-18
.
-2 ) ( 11/0.4
( ) 22/0.4 (
6 ) .
Sectionlized Single BB Single BB RMU
.
1MVA
.
444 ( )
-3 Distributors
Incomming Feeders Outgoing Feeders
(
)
:
66/11 or 66/22 or 33/11
11/0.4 kV 22/0.4 kV
11/0.4 kV .
( ) KW .
22 kV
( )
( ) ( )
11kV .
:
100 kW 5MW 11 kV
15MVA 22 kV 5MVA
15MVA 30MVA 33 kV
:
30MVA 75MVA 66 kV
75MVA 200MVA 132 kV
200MVA 500 kV .220 kV
.
.
444
445
:
22 MVA 25
11 kV 1157A
33 kV .
P
L :
= 5.5 +
100
:
66 kV 33kV 400
:
33 kV 11 kV 66 kV 11 kV
11kV (400
) .
: / 18.1.3
33 kV
11 kV
.3-18
Figure 18-183
446 ( )
11/33 11/66:
o
.
o
.
o
.
.
o
: 18.1.4
.
30 .
.
15MVA
33 kV
15000
= = 262
3 33
De-ratings
400 2 . XLPE
446
447
:
.
.
Short Circuit
Capacity .
( )
Ring . 4-18
Figure 18-4
: Radial/Ring 18.1.5
11/33
11/0.4
1.5 MVA
1500
= = 78
3 11
De-rating
95 2 .
448 ( )
-1 11 kV
.
-2 50
50
.
-3 .
Ring System
Ring Main Unit, RMU
.
.6-18
.
448
449
:
18.1.6
Radial System
.
.
300 2 400
7 = 3 11000 400
1MVA % 70
7 0.7 = 10
De-rating 7 .
: 18.1.7
/
:
-1
Gas
Insulated Subststions
) (GIS
Figure 18-7 GIS building -18
(7 )
( Bays ).
-2 (Air Insulated
) .Subststions (AIS
.
( ) .
450 ( )
: 18.1.8
.
:
-1 Single BB
( SLD
)8-18
.
Figure 18-8 Single BB
.
-2
70 % Double BB
( .)9-18
.
. . BBs
.
450
451
:
.
.
-1 . Distributors
(
)
( ).
-2 kVA
10MVA ( 3.3
)kV - 6.6 kV - 11 kV - 22 kV - 33 kV 400.
(
10 MVA )MVA .
.
.
454 ( )
-3 RMU
.
.
-4
.
19.1
%50
.
()
. 20
.
).
1-19 (
) 53 2500
2800 . .
( 53 2500 ) :
3 ( ) 11/66/220 :
.
8 11/66 ( ) :
.
( )2500 ( )
361 .
454
455
:
Figure 19-1
.
456 ( )
19.2 :
Distributor 19.2.1
. 25 kVA
2-19
.
:
-1 ( ).
-2
-3 ( )
-4
( ) 19.2.2
2 -19
.
456
457
:
.
.
Figure 19-2
-1 ) )
-2 ) )
-3 Bus Riser Bus section, BS
-4 ( :)Bus Metering and Bus Earthing
VT VT
Outgoing . Voltmeter
.
-5 ( :)Auxiliary Transformer Cubical
auxiliary/lockout relays .
-6 kV11
Capacitor Bank Cubical .
458 ( )
19.2.3
3 33/11kV
Sections 11kV ( ) 2
Bus-Sections Sections
( BS ) Section
Short-circuit Level . 11kV
.A
ABTS Bus-Section
Sections 3 .
.B
ABTS Bus-Section Short-circuit Level
.kV11
:
( ) BB
.
.
458
459
:
.
Bus Coupler
Coupling CB
Bus Riser CB
3-19
( Interlock /) ( /)
.Bus Section
Figure 19-3
19.2.4
- -
:4-19
460 ( )
:
( 110 )
:
.
Figure 19-4 :
.
(: )
-1 MV-CB . 1250A
-2 .
-3 .
-4 )400*1(*3 300*3
-5 " " 3 ) )5/5/400 Phase 3-phases
.
-6 " " 3
-7 " " 3
11000 110 110
/ /
3 3 3
-8
-9 .
-10
460
461
:
: -11
Over current Relay
Earth Fault Relay
Directional Over Current Relay
Directional Earth Fault Relay
.
:
-1 630 1250
-2
-3
-4 150*3 240*32
-5 " " 3
-6 3 5/5/200
-7 .
-8
-9 :
Over current Relay
Earth Fault Relay
CT VT Directional relay
( VT ) .
: 19.2.7
:
1250
.
462 ( )
19.2.8
SLD 5-19
14 ( ) K1-K14 (
) K5,K6,K9,K10 K8, K7
. .
5 6
9 10 .
.
). (11KV / 400V
Ring
Switch
( )
.
462
463
:
19.3 :
: 19.3.1
.
:
: 5
12 .
:
. 1.2 V
: ( ) .
) ( 19.3.2
.
.6-19
Figure 19-6
( 7-19 . )
464 ( )
Figure 19-7
19.3.3
:
-1
.
-2
( ).
.
.
-3
11 kV
.
464
465
:
19.4 :
( Kiosk . )8-19
Figure 19-8
3 ( :)9-19
-1 Ring main unit
-2
-3 MLVS
RMU
RMU
RMU
11kV 400 volt
MLVS .
Figure 19-9
25 kVA, 50 kVA, 100 kVA, 250 kVA, 400 kVA, 500 kVA, 630 kVA, 800 kVA,
1000 kVA, 1250 kVA, 1600 kVA, 2000 kVA
single phase :
-1
-2 socket .
-3 ( )fan & hood
Power Factor
.
466
467
:
11-19
Figure 19-11
468 ( )
19.4.1
( ) . CB
. :
Fuse 19.4.2
.
.
:
.High Rupturing Capacity, HRC
CB ( )12-19
Energy
) let through (I2t
.
3-phase 1-phase
.
Overcurrent Protection
.
468
469
:
.
.
19.4.3
Rated value .
Fusing current
( 1.5-4 .) Fusing Factor
10A 30A .
Table 19-1
470
471
:
19.4.4
-1
( ) .
.
.
.
14-19 .
472 ( )
Figure 19-14
-2 " "
RMU
.
15-19
.
Figure 19-15
19.4.5
-7 .
( .
Type K and T %150
).
-8 .
-9 Short circuiy capacity (
)Short Circuit .
472
473
:
-10
Inrush .
-11 Coordinated
.
19.4.6
Coordination
Protective Fuse Backup Fuse
.
( %75 ).
.
16-19 .
Recloser
transient faults
( )
( ) .
474 ( )
Figure 19-16
( )
( ) .
1 ( )
( ) . 2 (
) . 3
6 ..
-3 :
ETAP.
-4 : Load Flow ETAP
.
474
475
:
ETAP
17-19 ( )
( ).
Figure 19-17
:
/ .13-19
( ).
3-19 K 6A 140A
K 8A . 200A
476 ( )
( 20K K Type )
30K
500 ( )
40K 1100 .
K
T
4-19 ( 20T 20 ) T
30T 990 . 20K 30K
500 .
476
477
:
17-19
40T ( 36)
80T 3800
1630 .
: /
/ . 18-19
( SC ) Load Flow
. :
-5 : :
-1 ANSI
:
= 0.58
3.75 sec
4 .
478 ( )
(
).
Damage Curve
.
-2 Inrush current
10
.
Log-
Log .
( Reference Voltage ) Turns Ratio
.
-6 :
.
-7 :
.
(
)
.
( )
Damage curve
.
.
478
479
:
18-19 .
: 19.4.7
( :) CB
-1
-2
:
o ( )
Inrush current /
. ( CB )
6
CBs .
o ( ) 1.2-1.5
(
) . 5-19 .
Table 19-4
480
481
:
o CB
:
( )
:
. CB 6-19
( Starting Current )
:
( 1000 MVA ) 11/0.4 .
:
= 52 A = 1443A
63
1600 CB
482
483
:
:
-1
=
3
-2 ICU ( ) :
=
-3 ICU ICM
(
. )ICU
ICM = n ICU
n 7-19 ICM
.
Table 19-6
8-19
.
Table 19-7
484 ( )
Source Impedance
Infinit bus
.
. 11kV 15 kV
500 kVA 40 .
: 9-19 ABB .
19-19 1000
.
484
485
:
Figure 19-19
486 ( )
19.4.8
Surge
Rod Gap
20-19
21-19
Figure 19-20 Rod Gap
Gap Bushing Gap .
.10-19
Table 19-9
Figure 19-21
486
487
:
19.5 :
: 19.5.1
Secondary .
:
( ) ( ) .
.
) )23-19
Figure 19-23
488 ( )
. 0.4
.
Feeder Piller
24-19
.
Figure 19-24
6-4 ( ).
25-19
3-Phase
..
488
489
:
19.5.2
26-19
( )
( .) Normally Open
.
27-19 %50.
Figure 19-27
.
491
:
20
()
.
.
20.1
20.1.1
Primary Feeder CB
1-20
. Secondary Feeders
) (FUSES
.
492 ( )
Loop 20.1.2
()
( )2-20
Radial .
( 9105 )6
. BB Sectionalized Single BB
( 7 8 ).
Loop
( )
Short Circuit Loop
:
.
( Loop CB )
()
492
493
:
.
.
Radial
. .
2-20 1 12 Open Loop
.
( ) Radial
kVA . Loop
.RMU
( 9 )10 ( 5
) 6 .
494 ( )
Loop 20.1.3
. 3-20
Loop
(Distribution S/S
)
Sub Transmission
.
Radial system
. . Synchronization
20.1.4
( )2 out of 3 : 4-20
494
495
:
(
)3 . 2 3
. .
20.1.5
Radial
Open Loop . 5-20 SLD
.
11 two Sections
( )
.
496 ( )
Figure 20-5
496
497
:
498
499
:
20.2 DG
.6-20
7-20
( )
Figure 20-6 Traditional Power Distribution
( ) .
500 ( )
( )
( ) .
Figure 20-7
20.2.1
8-20 Distrubuted
.Generation, DG
. .
500
501
:
Figure 20-8
Coordination 20.2.2
DG
DG
502 ( )
.9-20
Figure 20-9
.DG
20.2.3
DG
DG ( DG
)10-20
.
Figure 20-10
502
503
:
20.2.4
DG
DG
Short circuit Capacity
.
Islanding 20.2.5
Islanding
( Breaker A )11-20
DG
.
DG :
-1 DG
Weak Source
-2 Breaker A
DG
.
.
504 ( )
.
Islanding . DG
-3 DG Islanding
Synchronization
.
DG .
.
504
506 ( )
21
.
.
.
. .
21.1
Radial 21.1.1
1-21 Radial
66/11 ( )
506
507
:
Figure 21-1
120 ( ) )
Main Feeder
Tap-off
50 250 .
508 ( )
.RMU
Ring 21.1.2
Radial
Ring
.
2-21 RMU
1
:
-1 1
-2 2
.
-3 . 3
508
509
:
21.2
-1
-2 ( )
-3
-4
-5
-6
-7
21.3
-1 ( )3-21
.
Figure 21-3
-2 :
1000/750/500/350
11kV
510 ( )
-3 :
( )
0.25 11kV
-1 ( )
( )4-21 %80 .
80 .
.
Figure 21-4
510
511
:
-2
5-21
Figure 21-5
.6-21
512 ( )
Figure 21-6
21.4
.
() .
: .
( )7-21
.
512
513
:
suspension insulators
.8-21
11kv 22kv
.
Figure 21-8
.9-21
.
.
Figure 21-9
21.5
3 4 3 4 .
.
514 ( )
10-21
.
Figure 21-10
21.5.2
: 21.5.3
3
.
( : )11-21
-1
-2
-3 6
.
Figure 21-11
514
515
:
200
400
630
. Load Break Switch
12-21 SF6
( ).
21.6
.
. :
6/35 DIN :
352
62
1-21 (
) .
516
517
:
Table 21-1
- :
-1 6/35 12/70 2 2 5 15 .
-2 25/150 2 20 .
100 Sag . -21
.12
518 ( )
Figure 21-12
11 kV
6 8 .
21.7 RECLOSER
.
.
.
.
Recloser 13-21
)
( . 14-21
.
: . Recloser
518
519
:
( 0.3 0.5
) (
1 3 10 )
Reset . 15-21
Recloser .
21.8
.
recloser
AVR
.
(
Figure 21-16
) .
3 ( )16-21
.
520
521
:
21.9
50
1-21
.
300 400
.
( )17-21 .
Two Phases
. .
High-
. Impeadance faults
18-21 SLG
.
.
522 ( )
Figure 21-18
( -21
)19
.
Figure 21-19
522
523
:
21.10
.
.
70 2
1 .
70
2
5 .
50 2
.20-21
( )
.
21.11
-1 "Jumbers
.
-2 .
-3 .
-4 .
-5 ( )
.
-6 .
-7 ( ) .
-8
voltage drop
-9 voltage drop
-10
contact resistance voltage
drop
:
scada .
:
.
( )
.
524
525
:
.
.
.
.
22
:
-1
-2
-3
-4
22.1
.
.
Reliability
:
: 1 :
.1 10 90
.2 1000 20
.3 3 175
30000 SAIDI
( 0.714= 30000 ) 175*3 + 20*1000 + 90*10
major
events . major events
.
.
-:
circuit length
.
Circuit configuration
Ring .Radial
528
529
:
22.2.1
AUTO TRANSFORMER
.
AVR
.
. AVR
.
AVR .
AVR
Boost Buck
1000/100 1100
900
%10 . 1-22
Figure 22-1
Taps
.
/
Microprocessor
. AVR Motor 2-22
.
.
10%
32 ( 16 16 ) 10% 16
5/8% . Single and Three :
. phase Voltage regulators
15
( . :
).
530
531
:
Figure 22-2
AVR 22.2.2
KVA AVR
System 10%
Example:
Compute for the step-voltage regulator size needed by a 3-phase, 4-wire
multigrounded feeder with a system voltage of 13800Y/7970 V. The required
voltage regulation is 10% and the peak connected load is 6.0 MVA.
Solution:
Voltage regulation = 10%
Phase voltage is the line-to-neutral voltage = 7.97 kV (since it is a 4-wire
multigrounded wye feeder)
Load current = 6.0 MVA / (1.732 x 13.8 kV) = 251 A
Voltage Regulator kVA Size = 10% x 7.97 kV x 251 A = 200 kVA
Use three 32-step voltage regulators, each with a standard rating of 250
kVA, 7970 V, 10% regulation
532
( )
3-22 AVR
.
Figure 22-3
AVR
4-22 .
.5-22
532
533
:
6-22 . AVR
534
( )
Figure 22-6
534
535
:
22.3
Distribution Automation
peak
.
:
.1 .
.
.2 .
. :
IED 22.3.2
( )Microprocessors
Intelligent Electronic Devices IEDs
.7-22
. IEC
57 IEC 61850
.
SCADA 22.3.3
8-22 .SCADA
536
537
:
SCADA :
) (RTU GPS
.
( )RTU :
-1 ()Alarms
-2 ()Status
-3 ):(Measurements
-4 ): (Commands
.
RTU
.
538
539
:
:
Distribution Control System, DCS SCADA SCADA
DCS SCADA
.
22.3.4
( )
( ) D.C
( 11. )
-:
- - RTU RTU
- -
- 220 - RTU
- - RTU
- ) Local / Remot ( RTU
-
22.3.5
( )
.
( ) D.C
540
( )
( 11. )
-:
- - RTU RTU
- -
- 220 - RTU
- RTU
- . ) Local / Remote ( RTU
22.3.6
.
.
220 .RTU
.
.
.
.
: 22.3.7
() .
-1
-2
-3
-4
-5 :
()remote central location
540
541
:
-6 : Load Schedding
-7 : Voltage Regulation
. off load tap changer
.
Capacitor control -8 .
-9
-10 :
-11
.
-12
.
-13
:
o .
o .
o .
o .
o .
-14
.
Redundant System
LAN
.Reliability
542
( )
: 22.3.8
Smart Meter :
:
-1 :
-2 :
Remote switching of meter register automatically
-3 :
.
542
543
:
22.4 COMMUNICATIONS :
Load Dispatch
Center, LDC
. 10-22 .
Figure 22-10
22.4.1
. :
: :
) DLC (Distribution Line Carrier
)( Shield
) (Phase
: :
) (Radio Frequency . VHF
544
) (
22.5
ETAP
ETAP is a company specialising in electrical power system modeling,
design, analysis, optimization, and predictive real-time solutions.
Functions include arc flash analysis, load flow analysis, short circuit
analysis, motor starting, OPF, transient stability analysis, generator
start-up, parameter estimation, cable sizing, transformer tap
optimization, reliability assessment, transmission line constant
calculations, harmonic analysis, protection coordination, dc load
flow, battery discharge and sizing, earth grid design, cable pulling,
and GIS map integration.
PowerWorld
PowerWorld Corporation are a Champaign, Illinois based firm that
develop the PowerWorld Simulator suite of power systems analysis
tools for Windows. The software focuses on a visual approach to
power system simulation.
Functions include load flow, short circuit, contingency analysis,
sensitivity calculations, security constrained OPF, transient stability,
transmission line parameter calculations. Includes scripting support.
MathWorks (SimPowerSystems)
Mathworks, the makers of general purpose mathematical software
MATLAB, also develop an power systems simulation program.
SimPowerSystems is a tool that extends MATLAB's Simulink and
provides models of many components used in power systems,
including three-phase machines, electric drives, and libraries of
application-specific models such as Flexible AC Transmission
Systems (FACTS) and wind-power generation. Harmonic analysis,
calculation of Total Harmonic Distortion (THD), load flow, and other
key power system analyses are automated.
EasyPower
The flagship product, EasyPower, includes the following modules:
arc flash analysis, power flow, short circuit, OPF, protective device
544
545
:
EMTP-RV
The ElectroMagnetic Transients Program (EMTP) was first developed
by Prof. Hermann Dommel in the 60s/70s for the analysis of
electromagnetic transients. It was commercialised in 1987 and
released as DCG EMTP and later EMTP96. EMTP-RV is the latest
commercial released of the program, created by Jean
Mahseredjian and currently being developed byPOWERSYS.
ATP-EMTP
The Alternative Transients Program (ATP) is a free (closed source)
program for the digital simulation of electromagnetic (and
electromechanical) transient phenomena. ATP-EMTP was first
developed in 1984.
ASPEN
ASPEN (Advanced Systems for Power Engineering) are a California
based company that develops the following separate Windows
platform products:
546
548
548
549
:
.
.
.
.
10 20
. .
.
:
.
: ( 1 ) ) 1 33 )
( 66 ) .
( ).
PVC XLPE
.
.
550
Single Core Multi-Core
.
Multicore
.Single Core ( )
Loss
Induced currents Cupper Losses
.
Multicore
Single Core .
(
) .
:
.1 :
.a
.b
.2 :
.3 :
.4 :
.5 :
550
551
:
552
552
23
23.1
.
: ( ) .
. .
.
70% 80%
.
. 99% 1-23
.
Table 23-1
554
( )
% 10 % 27 .
Copper-Clad-Aluminum Conductors, ACAC .
Copper Clad
BB
.
Pi-metal
glands
.1-23
23.1.1
554
555
:
23.2
:
.
. PVC
23.2.1
Polarization
( )
( ) - . Polarization
23.2.2
:
-1 .
-2 .
-3 .
-4 .
-5 .
-6
.
556
( )
-7 .
-8 .
23.3
( ) : poly mer
polymer .
) (macromolecule ( 10000
10) .
) . (covalent bond
.
.
" "pitch " "resin " " gum " "rubber
.
.
.
( )
.
556
557
:
.
.
Plastics
Rubber Leather Synthetic Nylons
.Polyesters
. : Fibers
(-10
)%50 .
.
PVC
.
.
-1 thermo-plastices-:
-2 thermo-sets-:
: PVC 23.3.2
. PVC
.
558
( )
PVC ( )
.
.
) (P.V.C .
.
PVC
. PVC
.
PVC :
-1 .
-2 1000 .
-3 .
-4 " " .
-5 .
-6 .
-7 .
-8 .
Thermo-sets - : 23.3.3
" "
.cross-linking
:
RUBBER - : 23.3.4
bntyl rubber
corona
.
558
559
:
-: XLPE 23.3.5
XLPE
PVC . EXTRUSION
.
XLPE 90 .
90 250
Corona
.
23.4
.:
Losses 23.4.1
Loss
( ) .
.
Insulation Loss :
Pins V 2 C tan
( ) Loss angle
Power Factor . Load (
)
Power loss .
560
( )
23.4.2
Charging Current
. Leakage Current :
I C V C
V .Volt
( ) f (.)= 2f
C ( ) Capacitance . Farad
Capacitance
13A .220 kV
( ) Critical Length
. Power
.
132 kV 64 Km 400 KV
24 Km .
.
( - ) Water Treeing
-
.
Figure 23-2 Water tree
560
561
:
( . )2-23
.
562
( )
562
24
.
.
(
)
XLPE
.
24.1 :
( )1-24 :
.1 .
.2 ( ) .Semiconductor Layer
.3 Insulation
.4 ( ) . Semiconductor Layer
.5 ( ) Metallic Sheath
.6 ( )Filling .
.7 .Armoring
.8 ()
.9 Outer Sheath .
.
564
( )
Figure 24-1
Conductor 24.1.1
Ampacity
Flexibility .
stranded
( ).
Size
American Wire Gauge, AWG .
.
.
564
565
:
.
.
566
( )
%20
/
.2-24
.
water
tree
Figure 24-2
.
( )3-24
( (Conductor Shield
stranded effect
.
Figure 24-3
.
(
)
.
( )
.
.
566
567
:
INSULATION 24.1.3
.
. " XLPE
.
( ) 24.1.4
semi - conductor
.
( )4-24 .
( ) Phase
.
Figure 24-4
Auxiliarty Shield
semi - conductor
.5-24
Figure 24-5
( )6-24 :
( : )
- -
.
.
Figure 24-6
Metalic Sheath :
/ .
.
Extruded-
lead sheath
.
.
.
568
569
:
.
corrugted
.
() : .
24.1.6
-1 . " "
.
-2 .
-3
-4 .
-5 .
-6 .
.
PVC . :
.
.
( ) : ARMOUR 24.1.8
:
.
570
( )
( )
.
Earth Faults
.
0.5 0.8 mm .
.
.24-7
.
Figure 24-7
Induced EMF
:
-1
( )Inducted Currents )(Eddy Currents
. Loss
.
570
571
:
8-24 () ( )
( ) .
() (
Figure 24-8
).
%2
.
:
.
Single Phase .
.
-2 Cross Bonding
Cross Bonding
Cross Bonded
9-24
120
.
Cross Bonding
100 3 %3
( ).
572
( )
Trefoil
Flat
) (Transposition
Induced voltage (
10-24 ).
Figure 24-10
-3
Single phase
.
: .
.
Losses
.
Losses
Sheath Voltage Limmitter 24-
11 . -24
11 . Transpostion
572
573
:
Figure 24-11
:
.
Single Phase .
.
.
.
( P V C
)
.
()
.
.
Figure 24-12
574
( )
.12-24
24.1.11
.
Rain Shed
.13-24
11
2 22 3 33
4 . 14-24
.
574
575
:
Figure 24-14
25
:
-1
-2 ) )Inductance
-3 )) capacitance
-4 .
.
:
.1 Skin effect
.
.2 Proximity effect
.
.
578
( )
( = )R
(
)
IC
1-25 IR
Figure 25-1
. I IC
(
( R )
.
.
:
) Rms = 2 ( 0 ohm
).(ohm.m =
).(m =l
. =R
. = r0
578
579
:
Inductance .
Mutual Indctance
.
Inductance
( .)2-25
L= 0.2 ( + In ) mH/km
1
4
L1 = 0.2( + In
1 12 31
)
4 23
L2 = 0.2( + In
1 23 12
)
4 31
L3 = 0.2( + In
1 31 23
)
4 12
Figure 25-2
Inductance:
Lm = 0.2 (4 + In mH/km
1
)
= Dm .
Dm = 312 23 31
) L1 = L2 = L3 = 0.2 (4 + In mH/km
1
(L) Reactance
Inductance
Inductance
.
Inductance 0.08-0.24 /.
580
( )
C
:
=C F/m
20
) (/0
= 0 )(8.83 x 10-12 F/m
= .
= r0 .
= R .
) (Cc ) ( Cs
.3-25
Figure 25-3
:
0.111
=C 2 (32 2 )
F/m
2
) 0 (276 6
580
581
:
= r0 ).(mm
= R ).(mm
= a ).(mm
25.4 :
"
" .
.
.
.
Single Phase .
4-25 .
Figure 25-4
582
( )
25.5
.
. :
: .
: (
Figure 25-5
) .
" " .
(
. 6-25
.
.
Figure 25-6
.
:
:
E /
V
x .
582
583
:
= v/ m
.
7-25
.
Figure 25-7
:
=
ln
: 25.5.2
.
.
Gland
.
584
( )
Stress Control Tube
8-25 Stress Control
Tube
.
Stress Control
. Tube
(
.)9-25
Figure 25-9
( - ) Water Treeing
-
.
.
.
584
26
.
:
Routine Tests. .
Special Tests. .
Type Tests. .
Electrical Tests after Installation. .
IEC
60228 : IEC: 55-1, 141, 229, 230, 502, 840, 885
.
: 26.1.1
.
30 150 :IEC-840
).(Partial Discharge
.
.
587
:
275 :IEC-141
.
.
. Tan
.
( ): 26.1.2
IEC .
30
150 ICE 840:
).(Conductor Examination
.
.
.
.
Hot St Test XLPE
.EPR
.
.HDPE
275 IEC-141:
( )Tan .
.
: 26.1.3
.
.
30
150 ):(IEC 840
.
) .(tan
.
10 .
.
26.2
.
.
( ) :
.1
.2
.3
.4 Cable Capacitance
.5 (
) Tan
.6 Sheath Test
.7 Cross Bonding
.8 Earth resistance measurement of link
boxes
.9 zero & positive impedance
588
589
:
1-26
phase ) (Megger
Phases
.
Figure 26-1
.
26.4
Joints .
590
( )
R R Shield
R Shield
2-26
0 20
10
Figure 26-2
.
26.5
DC Conductor Resistance
( IEC ) Losses
) (Current Carrying Capacity
.
L A :
L
R
A
) (Resistivity m
Micro ohmmeter DC Current
:
V
R
I )(
Km 20 C
o
:
) R (measured
R 20
))L (1 20 (T 20
:
590
591
:
)(Km :L
( / Km ) 20 C
o
: R20
)( :R
20 C
o
:
20
= 0.00393
: T
AC Supply Z
. Reactance
26.5.1
) (Short
Figure 26-3 :3-26
R & Y
) (R&B Y&B :
) (R Y ) (Y B ) ( R B
R
2
Y (R Y ) R
B (R B ) R
(
) .
592
( )
\
) (C :
C measured
C\
L
:
: C measured F
( .)capacitance meter
.4-26 ()F
Figure 26-4
( )Charging Current ( )VAR
( (Critical Length
of Cable .
26.7
) (R
) (Metallic Sheath )(Leakage
) (Radial
.
592
593
:
:
.
11 11 .
( 5000)
(100 )
. (1 ).
.
Charging Capacitive Current 60
Capacitive Current
.
( ).
.
.
20
. ( )
.
-1
.
-2
-3
-4
-5
594
( )
.IEC 60840
( )5-26
5000 .
:
. 500 1000
1 2500
6.6 5000
Figure 26-5
Table 26-1
594
595
:
Hipot 26.7.1
HiPot .
:
Phase
6-26
.
Figure 26-6 . two phases
.
(
) DC
.
:
Hipot Open
Circuit ( )
.
.
:
( ) .
.
596
597
:
.
.
: 26.7.6
2-26
598
( )
Table 26-2
( )Armor
()PVC
()HDPF
10 kV ( metallic
)Sheath PVC PVC
Semi Conductor Material
SHEATH .
) (Leakage Current
) (No Breakdown 9-26 :
598
599
:
Figure 26-9
26.9
Contact Resistance Test of Link Boxes
Micro-ohmmeter
) (Cross Bonding
Links .SLV . 20
26.10
Cross Bonding Verification Test of Metallic Sheath
( )AC Current ( )
%3
.
600
( )
( )%3
Live .
) (Non Linear Resistance
Sheath Voltage Limiter, SVL
1G .1000V
26.11
Earth resistance measurement of link boxes
A
S
E P 5- 10 m C
5- 10 m
Figure 26-10
600
601
:
.
.
.
.
.
( .)Average Value .10
.
IEC
50 ( )PD
. PD
.
PD tests :
Online PD test
offline test
.
:Offline PD test
fault
.
602
( )
26.13
( )11-26
.
Figure 26-11
.
132. 26.13.1
( )
15
11 44
.
.
-
.
602
603
:
) (Variable Frequency
L
) (Reactor ) (Resonance :
1
f res
2 LC
:
.F :C
).(H) (Inductance :L
I test CV
Figure 26-12
Figure 26-13
DC : 26.13.2
DC Supply
DC
Water Tree Break Down .
-1 ( ) Bubbles ()Scratching
HVDC
( ) Partial Discharge
.
-2 ( )
( ) ( )AC
.
604
605
:
DC E1 / E2 = 1 / 2
AC E1 / E2 = 2 / 1
-3 ) ( Space Charge
( ) Accessories
( )AC ( )Stress
.
-5 ( )DC
8 ( )U0
( )U0 . .
HVAC 26.13.3
Supply AC
HVDC
. AC Supply
.
DC AC
606
( )
DC supply AC supply
( . ) VLF( )Very Low Frequency AC
DC
I = C V
VLF
( )conductor
( )grounding shield .14-26
Figure 26-14
( IEEE 400.2
( )3Vo( )Normal line to ground voltage 30
60.
606
607
:
Table 26-3
.%95 0.1 HZ 0.05& 0.02
.
Table 26-4
27
- -
.
.
.
27.1 :
)
) .
27.1.1
.
.
608
609
:
27.1.2
.
58 . :
.1
. Lightening and Switching
.2
.
.3
.
.4 .
27.1.3
.
.
27.1.4
.
.
( ) corrosion
.
610
( )
27.1.5
.
.
27.1.6
610
611
:
27.2
:
VLF
. 3
11kV ( 35kV
) .
( ) 15
150
.
.
:
()Megger
( )
:
< Pulse Echo
< < 2
2 < <50
> ( )
500 10000
.1-27
612
( )
Figure 27-1
:
( )
.
:
Pulse Echo Bridge
( . ).
:
( .
).
27.3
.
612
613
:
( )2-27
Discountinutty
.
:
Figure 27-2 TDR
.
transition point
. .
:
614
( )
2 1
=
2 + 1
:Z1
:Z2
Rf 3-27
1
= 2
+ 1
Figure 27-3
1
=
2 + 1
short Z2 =Rf =0 :
= 1
Open Circuit = Z2
= +1
614
615
:
) (short circuit
( (open circuit
Open ( : )4-27
Figure 27-4
( :)5-27
Figure 27-5
616
( )
( )6-27
.
Figure 27-6
7-27
Figure 27-7
T section .8-27
Figure 27-8
616
617
:
T section .9-27
Figure 27-9
TDR Short
.
10-27
.
Figure 27-10
618
( )
( .11-27 ).
Figure 27-11
27.3.4
TDR
1
=
2
:x
:v
:t
2 .
:
.
.
.
.
.
.
618
619
:
: TDR 27.3.5
200
.
:
TDR
200 .
) (megger
) (spark-over .
( ) Bridge 27.3.6
.
: 12-27
Figure 27-12
= =
2
100
:
= L
620
( )
= Lf
Reading .
%80 %100
620
621
:
Wheatstone bridge .
.
( )1%
.
Figure 27-13
14-27
RB1 , RB2
Rx Lx
L Rg
.
622
( )
27.4
. :
( )14-27 1940
.
.
.
E = V2 C/2
E V C .
622
623
:
Pulses 15 25
80 .
:
.
:
.
.Pulses
(
).
624
( )
Surge Generator
750 2
5.
E = (1/2) CV2
E = (1/2) (750x10-6) (2000)2 = 1500 Joules
27.4.2
Surge Generator
( .)15-27
Figure 27-15
200
.
624
625
:
TDR
Surge Gen
Surge Gen fault
200
TDR
Figure 27-16 Arc Reflector
TDR
.
faults .
27.4.4
.
-27
Figure 27-17 17
626
( )
) )simple magnetic loop antenna
loop antenna
fault
antenna Loop.
27.5
. .
.
( )
:
-1 :
-2 +:
Figure 27-18
626
627
:
.
-3 :
( +)
(
)
-4 : ( ) (
)
Figure 27-19
Figure 27-20
Figure 27-21
628
629
:
Figure 27-22
RMU
( )
27.6
-1 phases .
-2 .
-3 conductor
.
-4 .
-5 ( 100) trial
and error
630
( )
-6 ( 3 ) TDR
(
) .
-7
.
-8 Pilot Cable
.
630
631
:
632
( )
632
633
:
.
:
( )Transients
.
:
Transients.
Power System Stability
.
(
. )Harmonics
634
634
28
Transients in Power System
28.1 :
DC or AC Supply
:
-1 R,L, and C .
-2 DC or AC
. Steady State, SS
Superposition, Norton, Thevenen, etc
.
Transient .
Transient
2ms 0.1 Hz 20kHz 50MHz
GIS substations Frequency response
.
Transient Analysis
Transients
. Transient Analysis
(
RMS ) . Steady State Analysis
: transient .SS
28.1.2
636
637
:
Ferroresonance--------------------------------------0.1 Hz to 1 kHz
Transient 28.1.3
Transient
Transients :
-1
-2
-3
-4 reactors
-5 :
Impulse wave .a uni-direction wave
Transient waves .b
-6 ferro resonance
: .
Transients
.
638
( )
Transient
. CB
max. Impulse voltage .
( )Drives
.
Transients 28.1.4
638
639
:
Figure 28-1
transient
Transient . SS
640
( )
28.1.5
DC Supply AC Supply
. AC analysis and DC analysis
DC analysis
voltage source Switch
2 2-28
.
AC analysis Frequency
response
Figure 28-2
:
Magnitude
.
: DC AC
DC
AC Supply DC Signals :
640
641
:
28.1.6
Transient
( ) SS
Transient
Transient
.Condition L and C
Transient
.Transient
Transient L, R and C
Time Constant .
28.1.7
: AC or DC
.SS :
DC Supply
AC Supply
:
Voltage surges :
642
( )
: Over Voltages
Voltage Swell . Impulse surges
: Voltage
( drop ) . :
.i
.ii
.iii
.iv
.v Voltage Sags
Voltage Instability
Stability.
.
1-28 :IEEE 1159
Table 28-1
642
643
:
.
644
( )
28.2 DC SUPPLY
( )3-28
V
V/R
Exponentially
Figure 28-3 .
(
)
RC=
4-28 :
SS
Exponentially . Transient
644
645
:
Figure 28-4
TC
.
-28
.5
28.3 DC SUPPLY
( )6-28 (
)
L/R=
Time Constant
X/R ratio
Time Constant
. SS
Figure 28-7 Transient
Time Constant
TC R and L .
2 8-28 source
SS Transient
.
Transient Source
Transient .
646
647
:
Figure 28-8
28.4 AC SUPPLY
AC Source ) v = Vm sin (t +
R+L SS + Transient :
I = Is + It
SS Circuits
648
( )
Transient R-L
Exponentially . Io
Io AC t=0
t = 0 I = 0 Io :
Io Transient
90 .
Sinwave Transient .
648
649
:
t=0 = = Io
Transient
9-28
Transient . - = /2
Transients .
( )Voltage Surges
.
" " .
28.5
-1 .
-2 Surges
kHz :
/ ( ) -
-
-
-
Voltage Surges .
-3 Surges
( 15 kV )
Discharge
650
651
:
Anti static.
-4
Ferroresonance
.
. Surge
V 200 kA 40 kA
.
Surges :
.1 Rise
Time
1-2s
( 1.2 -28
.)10
Surge
. Basic Insulation Level, BIL
.
652
( )
Table 28-2
BIL
Surge
.
Surge Voltage
.
.
.
Surge
( )NEC article 280 Surge arrestor
Switching.
3-28
( ):
652
653
:
Table 28-3
.1 .
.2 / ( )
.3
.4
.5 Ferroresonance
654
( )
28.6 : LIGHTNING
28.6.1
.
( )11-28
Figure 28-11
""
( ) 3x106 V/m = 30 kV/cm .
Leader
Streamer 12-28
Figure 28-12
Leader Streamer
.
654
655
:
V
200 kA 40 kA
1-2s 50-100 s
50% 10-28 Voltage
surge/ Impulse Wave (. 1.2x50
. )s
28.6.2
. " "impulse transient
.
Travelling Wave
Figure 28-13 Traveling Wave (
)13-28
.
Direct Strokes
/ 200
.
Electric Arc
Arc Gaps ( ).
656
( )
Turns Ratio
XL = 2 f L
.
.
coupling
capacitor, C1 14-28
" turns
Figure 28-15
.
.
656
657
:
: 28.6.3
Lighting arrestor
.
Short
( ).
Over voltage
66 325 . IEC
658
659
:
28.7 ( )
Power System
.
CB
Oscillatory Surges
Travelling Waves
( .)TOV Temporary Overvoltage,
16-28
Figure 28-16
Arcing Voltage .
Restrike
Voltage 17-28 Transient
Voltage
.
Figure 28-17
.
Oscillation
.
660
( )
Oscillation
Losses Overshoot
CB
.
CB
Capacitance
( ) Inductance
.
Pure Inductive
90
Figure 28-18 18-28
( ) Ind Cap
Restrike Voltage CB
Oscillation .
Restriking Voltage , :
660
661
:
CB 28.7.1
Capacitive switching
.19-28
Arc
Figure 28-19 .
arc
.
Restrike Voltage
662
663
:
Recover Voltage
20-28 Critically
Damped
.
Figure 28-20
664
( )
Power Quality . Power Conditioning
" "Reactive Power
" . "Power Factor Correction
Filters ( )
FACTs ( )
Converters.
Fixed Bank
Time Constant ( . TC ).
Reactive
Power Overvoltage
Switching .
28.8.1
Capacitor Switching
Oscillatory Transient :
664
665
:
%170 .21-28
-2
.
-3
.
overvoltage switching
lightning lightning
switching
power factor
.
Overvoltages Switching
Overvoltages EHV & UHV System Voltages
300
.
Shunt Reactors .
666
( )
28.8.2
22-28 CB
Stray
Capacitance Unloaded
. .
CB
( 90
)
Figure 28-22
CB 1 ( B CB
Vgm (max of
) Vg
.
A
CB
.23-28
R
CB
2Vgm
Figure 28-23
))(Vgm-(- Vgm
CB Re-Strike
High Frequency Transient
L and C .
Re-strike Voltage
2Vgm Re-
666
667
:
:Capacitor switching
over-compensation
fixed reactor . pre-insertion resistor
Surge arrestors
28.9
Transient
Inrush currents .
Resonance
. . 10-15 cycle
24-28
cycles 2pu
.
668
( )
Figure 28-28-24
25-28 50
. BB
50 Figure 28-25
Transients Transient Voltages
.
668
669
:
Non linear Resonnance ) Non Linear Inductance (Iron core inductor
Disturbance ( Open circuit
) condition
Ferroresonance
.
Ferroresonnace
.
Open circuit
Inductance
.
: RLC 26-28
:
XL = Xc
Figure 28-26
670
( )
Faraday cage
.
( )
Filters
Voltage limiters Low Voltage
. Surge Arrestprs
Voltage Suges
:
Zener diode
.
670
671
:
Figure 28-28-27
Varistor Zener
. (
).
Power Conditioners
672
( )
28.12
:
%10 %90
( . ) Sag
%10 Interruption .
Figure 28-28
Voltage Drop
%4 %8 (
.)%6-3 .
672
673
:
Voltage drop
. VD = I.R :
-1
voltage drop .
-2 .voltage drop
-3 contact
resistance voltage drop
%10 %90
.
.
Figure 28-29
-1 Voltage Drop
-2 Short Circuit
-3
674
( )
SLG or 2LG, Phase to phase
.
Figure 28-28-30
N VG
Va Va Vg Phase
Two phases Vb- VG Two
. Different Phases
31-28
674
675
:
Figure 28-31
28.12.4
6-5
voltage drop ) (R + j X Point of
( Comon Coupling, PCC )32-28 .
.
Power Factor
0,3
. (
)Soft Starting Delta/Star switch or
.
676
( )
Figure 28-32
-1
.
-2
( )33-28
% 10
.
Figure 28-33
:
-3 .
-4 ( ) .
.
()
.
.
-5 .
676
677
:
-6 resistance welding
voltage fluctuation
28.12.6
Induction Motors :
-1
.
-2 Voltage Sag
-3
( Constant Power
incandescent lamp
( %90
%70 . )%80
(
) Constant Power
fluorescent lamp
Chock Coil
. ( )70%
Electronic Ballast
.
678
( )
Reactive Power . %90
Q ( %81 )
.
(P
) = V x I cos
. 10%
CB
.
.
28.12.7
.
:
.1 ()Power Conditioners
.2 ()voltage regulator
.3 ( )emergency power generators
.4 ( ) battery backup .UPS
678
679
:
Power Conditioners:
-1 ( :)Isolation Transformer
Power Conditioners
. ( .)magnetic shielding
.
-2 ( )voltage regulator
. Power Conditioners .
:
-1 / Manual/Auto Tap switches regulator
-2 Ferroresonance Regulator
-3 Magnetic synthesizers
) (tap- switchers
80 145 110 125 .
.
-3
) Uninterruptible power supply (UPS
UPS
. UPS :
On-line UPS
( )35-28 UPS
inverter .
680
681
:
Stability
Synchronization
Blackout .
29.1 STABILITY
Figure 29-1
P and Q
. Stable
Power System :
Frequency
Rotor Angle/ Power Angle
Voltage
Islanding
.
Rotor angle
90 90
Stability margin .
684
( )
29.2
Interconnected
Networks
:
-1 = Loss +
-2 Synchronized
-3 Frequency ( ) 50/60 Hz
-4 BBs
-5
.
. Disturbance
. Short and long term disturbance
29.3
IEEE Stability
:
-1
-2
-3 Rotor angle
684
685
:
. 2-29
.
Stability.
Power Deficit
.
Disturbance .
Q (
Field .) Q
686
687
:
Stability 29.3.4
.
688
( )
- - Synchronous speed, N
P F
N = 120 F/P
Rotor ) T (Mechanical
Rotor magnetic field Stator
Stator magnetic Field
.
) T(Electric) = T (Mechanical :
Rotor magnetic field Stator magnetic Field Synchronous
speed, N Rotor field Stator field Rotor angle
Phase shift.
688
689
:
Rotor Angle
Power Angle
Transfer Power Capacity
V2 and Vt
Transmission Line .X
12 Power
Angle
Rotor angle
.
Figure 299-29-3
690
( )
90 ( )
.3-29
Rotor angles
Load shedding
. Transient Stability
Transient Stability .
Transient stability
.
( )
( )Steady State Stability Linear
.Equations
690
691
:
Pe = Pm 4-29
Rotor angle, 90
.
Initial Output, P0
a 0 .
Changed Output, Ps
.
Figure 29-4
a b
( ) de-acceleration ( E
) ( )I = V-E/X
692
( )
Pe 0 s
b .Pe = Pm
Oscillation b
b Spinning Energy of
heavy Rotor m .c
A1 and A2
. A1
A2 .
b . b c Pe
Pm , E ( ( )I = V-E/X
b b
Damping .
692
693
:
Figure 299-29-4
Stability 29.5.2
:6-29
Figure 29-6
Power angle 0
s 90
. stability margin
694
( )
6-29 0 25
60
Oscillations
.
( Disturbance )
s Inertia
Oscillations
m 0 7-29
A1 and A2 .Oscillations
( )
A1>A2 7-29
.
Figure 29-7
(
).
694
695
:
29.5.3
8-29
. 0 Pre-fault
During Fault
c Clearing . A1=A2
.
Figure 29-8
( c ) o
A1>>A2 .Out of step
696
( )
49.2 HZ
.50.3 HZ .10-29
Figure 29-10
29.7 INERTIA
696
697
:
29.7.1
Bands 12-29 :
Figure 29-12
.
.
Hz
%2 49.2
%3 49.1
%4 49
%7 48.9
%20 48.8
%20 48.7
%22 48.6
Governor
698
699
:
Load Shedding
.Blackout
: 29.8.1
primary control
primary control
secondary control
: Tertiary control
secondary control
secondary control
.
:Time control
.
700
( )
Stability
.
Stability Voltage Stability
:
Voltage Fluctuations
Voltage Flickers
Voltage Collapse
Voltage Stability
Stability .
cascaded outage . Blackout
700
701
:
Tap Changing Transformers
Long term phenomenon
BB .
Short Circuit
BB
Voltage Instability Voltage
Collapse .
29.11
.12-29
Figure 299-29-5 :
702
( )
= sin
2
= + cos
VR :
2 4
= 2 2 2
2 4
P-V 13-29
Nose curve . ( Load1
)or Load2
:
Figure 29-13
-1 ( )
Stability Margin Load1. Load2
702
703
:
Stability
Margin
-1 ( ) Unstable
- -
Voltage Collapse
.
(
) Voltage drop
= .
-2 Short Circuit
Short Circuit
SC SC.
29.12
2 4
= 2 2 2
2 4
VR Q 14-29
704
( )
Q
Voltage collapse..
15-29 Q
Q
P Q
Supply Q
. Voltage Collapse Active Power
. P
Q
P
Q .
704
705
:
Figure 29-16
Qr = QS QL
Vs = Vr Qr = 0 QL = QS -1
Vs > Vr Qr = + QL > QS -2
706
( )
-3 QL < QS Qr = - Vs < Vr
Voltage Dip
Ferranti Effect .
Q
29.13 ( )
.
:
-1 Xline
Source
Load
X
P-V
( -29
) 17
Figure 29-17
Stability Limit
.
-2 Starting
. Voltage drop Constant Power Devices
706
707
:
( ) P= V . I
.
-3 .
Stability Margin PF
. .
29.13.1
Figure 29-18
-3
.
-4
Noze Curve
.
708
( )
29.14
: 29.14.1
.1 Exciter
.
.2 Reactors 500. (
165 / ) :
).
.3 ( 500. 3
65 / )
.4 66/220 220 /500.
.5 Tap Changer
11/66.
.6 Series Capacitive Compensation -29
.19
P-Q Curve Q P
.
708
709
:
Figure 29-20
: 29.14.2
-1 :
.
-2 :
.
: 15% QC
Sn
710
( )
: : 15% QC
Sn
( ) : QC
(..) : Sn
( 6 12)
:
()
""
( )HRC .
( )Regulator ..
.
( )CT
.
-3 DG
Distributed
Generation, DG (
)
. DG
( )
.
21-29
Nose Curve DG Stability Margin
.
710
711
:
Figure 299-29-6
-4 .
Nose Curve Load Shedding
-5
Network Reconstruction Network
.Reconfiguration
-6
DG
.
712
( )
-1
-2 Stability Limit
Optimization Techniques
-3 VAR Compensators
( )
Dynamic
.Stability
712
714
()
30
HARMONICS
voltage signals sin wave .
.
.
sin wave Phase
. angle
Linear Load
.
non-linear loads
Power Electronocs, PE Speed Drives
switching power DC supply
. supplies
. Harmonocs
714
715
:
30.1 HARMONICS
sin
wave Non-
linear . %50
non linear loads .
Figure 300-30-1
.PE
30.1.1
Spectrum Analyzer
( Fourier Transform )3-30
50Hz
50Hz
- ( ) -
. Harmonics
( )H5 H7 H3
( .)H6H4H2
50
5 50 . 250Hz
Figure 300-30-3
Even harmonics
half symmetrical wave Sin
Full symmetrical waveforms .
4-30
Fundamental
Figure 300-30-4
Resultant
.
716
717
:
Spectrum -30
.5
Figure 300-30-5
.6-30
Figure 300-6
Harmonics 30.1.2
Harmonics PE
( ) 50Hz
718
()
50Hz
.7-30
L3 Linear Load
BBs
. Voltage drop
L2
Non Linear
V2= I2 x Z2
Figure 300-7 . V1= I1 x Z1
BBs
Impedances, Z1, Z2 Z
.
-1 .
( )
.
-2 Short circuit Capacity ( Strong Grid
Xgrid) Harmonics ) ) Z times I
. 8-30
Figure 300-8
.
30.2 : HARMONICS
:
.1 PE LED
718
719
:
.2
.3
.4
Figure 300-9
. 6-Pulse 6k1
5 711 ( 13 ).
12-Pulse 11 12k113 23 25 .
49 .
12-Pulse .6-Pulse
18-pulse ( ) 37 35 19 17
.
: 30.2.2
.
%30 .
. Compact Florescent Lamp CFL
.
720
721
:
Table 30-1
Table 30-2
722
()
Table 30-3
.1 High Performance, HP
THD
. IEC 61000 -3-2
. THD
. %18
.2 ( )Low Performance, LP
THD %100 .
10-30 .
722
723
:
Figure 30-10
( )power 22
( 0.158 )current
( )( 0.66 (lead) )total power factor
( 0.92 (lead) )displacement power factor
:
724
()
724
725
:
:
726
()
. ""Short Circuit
" "Harmonics
.
:
( )B-H curve 11-30
non-linearity c/c
.
726
727
:
Figure 300-11
Saturation .
.
4-30 .
Table 30-4
728
()
30.3 .
150
250
. Phase Sequence
three phases
Phase Sequence Zero Sequence
.Currents
three phases :
three phases
Negative
.Sequence Currents
Positive Sequence
Currents
728
729
:
12-30
Figure 30-12
Table 30-5
730
()
Phase Sequence .
Harmonic Cancellation
.
30.4
:
-1 Individual Harmonic Distortion
( )
-2 Total Harmonic Distortion
( )
() .
() .
THD .
. IHD
Fundamental = V1 = 114 V
3rd harmonic = V3 = 4 V
730
731
:
5th harmonic = V5 = 2 V
7th harmonic = V7 = 1.5 V
9th harmonic = V9 = 1 V
30.5 .
. .
: 30.5.1
Losses .
732
()
Hysteresis loss
- -
K-Factor
.
K-Factor 30.5.2
Hi Speed-
Electronic Switches Discharge Lamp
Non-Linear loads
Harmonics .
. K-4 Transformers
%50
. 6-30 K-Factor
.
732
733
:
Table 30-6
K-Factor 30.5.3
.
Fundamental
= 12 + 32 + 52 +. .
1 3
= 1 = 3
= 12 12 + 32 32 + 52 52 + .
k-Factor
734
()
K-Factor :
222 K-Factor .9
30.5.4
:
.
Skin
effect
) variable frequency drives (VFDs
Rotor
.
734
735
:
Crawling and cogging are related to space harmonics. The above question is about
time harmonics.The speed of an IM with respect to nth harmonic is nNs where
Ns is the synchronous speed of the motor with respect to fundamental voltage
harmonic. Morover 3rd harmonic is destroyed in 3 phase windings of IM.5th
harmonic is negative sequence harmonic .hence it rotates at -5Ns with respect to
the rotor speed.7th is a positive sequence harmonic and rotates at 7Ns ,11th
negative and so on... For negative sequence harmonics ,slip is >1 where as for
positive sequence harmonics s<1
In this way the rotor gets the tendency to reverse its direction of rotation back
and forth .Also additional losses are attatched with these harmonics which all
together result in a pulsating nature of torque under non sinusoidal voltage
)supply(combination of harmonics
.
negative sequnce Reverse Torque
Breaking Torque
3-phase currents Rotating
Field Air gap
.neqative sequence torgues
Skin Effect
.
Skin Effect
Dielectric losses :
.
736
()
"."Neutral Cables
Neutral (
) " " Balanced " "Unbalanced
.
Neutral Earth
( . )IEEE1100-92
:
choke coils .
( ) )P.F = P/(V.I
50Hz True PF
:
736
737
:
13-30
THD-i
Figure 300-30-13
7-30 .
Table 30-7
.
738
()
:
.Aveage
THD
%100 (
.) 50Hz
Power factor
. True PF :
true PF
7-30.
= 2
1
30.6
. Resonance
SVC
) ( Inductive reactance
) ( Capacitive reactance
.
738
739
:
30.6.1
fn L = 1/c
- - =
) Short circuit (Z= 0 Short .
:
limitation
.
: .
30.6.2
Self
capacitance XCS XL Self capacitance
Equivalent reactance, XLS Short Circuit capacity, SCC
.14-30
Figure 300-14
740
()
Network
inductance . 15-30
Figure 300-15
30.6.3
16-30
. BB .
Short
. .
Figure 300-3016
740
741
:
30.7 :
.Point of Common Coupling PCC
1- 2 3
. SCC/ILoad
) SCC (
BB
.
742
()
742
743
:
4 :
IEC 61000-3-2 16
. THD .individual harmonic distortion
.
30.8
-1
BBs .
-2 non linearity
. magnitaization
-3 .
-4 %30
%15 .
-5
:
hr = resonant frequency as a multiple of the fundamental frequency
kVAsc = short circuit current as the point of study
kVARc = capacitor rating at the system voltage
Filters .
Filters :
" "filters : .
744
745
:
17-30 L
C
" . "Harmonics
" . " 5th , 7th
Figure 300-17
harmonic current
%30 electric drives
.
series
18-30 L
C
Figure 300-3018
Filters
Neutral .
Filters Filters
.
746
()
( -30
)19 Filters
(
)
.
Figure 300-19
" "Harmonic Wave + Pure
"" sinusoidal wave = " "distorted current wave
( ) .
.
. Harmonic Cancellation
Magnitude and Angle (
746
747
:
-1 ( ) D/Y + Y.Y .
-2 Phase Shifting Transformer
Magnitude Turns Ratio
Magnitude Angle (
) .
-3
( )cancellation ()mitigation
.
.
.
.1
.2 CFL
.3
.4
:
748
()
748
749
:
:
750
()
cancellation
LED
. light dimmer
750
751
:
.
752
()
30.9
30.9.1
750
kVA BB B2
5 MVA
.20-30
Figure 30-20
Six Pulses Inverters
5 711
.
BB-B2
. 21-30
Power
Analyzer
Figure 300-21 .
5 7 11
%3 .
752
753
:
30.9.2
Y/Y
/Y
phase shift 30
.22-30
phase shift
Cancellation .
Figure 300-22
754
()
Power
Analyzer
.
11
.
.
BB B2
.
23-30
. 11
Figure 300-23
754
755
:
1 (Low Pressure
2 Absulute Temprature
3 Admittance
4 Arcing Ground
5 Arrestor
7 Base Load
8 Blackout
9 blackstart
10 Boiler
11 Bruches
12 Bundle Conductors
13 Capacitance
14 Capacitive Reactance
15 Chimney
16 Circulating current
17 Combined cycle
18 common service building
19 COMMUNICATION
20 compressor
21 Condenser
22 Dampers
23 Demand Mangment
24 Digital Protection
25 Disc
26 Distance realy
27 Dry Transformer
756
28 Economizer
29 Electric Field
30 Excitation
31 Exciter
32 Field Current
34 Flashover
35 Flux Linkage
36 Frequency
37 Generator
38 Governor
39 Governor Valve
40 Guard Rings
41 Healthy Phases
Heat Recovery Steam
42 Generator, HRSG
43 Impedance
44 in operation
45 in service
46 Inductance
47 Inductive reactance
49 inverters
50 Load Curve
51 Load Demand
52 Load Factor
53 Load sharing
54 Load Shedding
55 Max Demand
56 Mechanical Torque
58 Open Circuit
756
757
:
59 Parameters
60 Partial Discharge
61 Peak Load
62 phase sequence
63 phase shift
64 Phases
65 Power
66 Power Angle
67 power factors
68 Power Loss
69 Reactive Power
70 Reactor
71 Receiving End
72 Rectifiers
73 Reheater
74 Resistive Loads
76 Rotor
77 Series Capacitors
78 Shunt Capacitors
79 Shunt reactors
80 Single Line Diagram
81 skin effect
82 Spacer
83 spark gap
84 spinning reserve
85 stability
86 Stability limit
87 Starting Motor
88 Stator
89 steam valve
90 String
758
91 Synchronized
92 synchronous speed
93 Tariff
94 thermal limit
95 Tidal
96 Transients
97 Travelling Waves
98 turbine shaft
99 Vents
758
759
:
U
-1
-2
-3
-4 1998
-5 2005
-6
-7
-8
-9
-10
-11 ( )2016
-12 .
-13 .
1- Electric Power Substation Engineering, 2nd Eddition, Edited by John D.
McDonald, CRC press, 2007.
2- IEEE Recommended Practice for Electric Power Distribution for
Industrial Plants, 1993
3- Power Plant Engineering, A.K.Raja, New Age International (P) Ltd., Publishers,
2006.
4- Principles of Power Systems, V.K. Mehta
5- Elements of Power System Analysis, William Stevenson, McGrow-Hill
Publishing, 4th edition
6- Electrical Technology, B. L. Theraja, 2005
7- SUBSTATION GROUNDING, Inna Baleva, MASTER OF SCIENCE,
2012
8- IEEE Definition and Classification of Power System Stability, IEEE
TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 2, MAY 2004
760
760
761
: