Vibration Transducer Interface

Description
The Vibration Transducer Interface (VTI) is a galvanic isolation solution provided
by GEs Bently Nevada product line. With the use of galvanic isolation, an earth
ground is not required in the hazardous area. Isolating transformers used in the
galvanic isolation technique provide a physical barrier to prevent high voltages
from being transferred from the safe area to the hazardous area. The safe area
and hazardous area are isolated from each other, and can have two separate
grounding points without the possibility of ground loops occurring.

The Vibration Transducer Interface has been designed, engineered, and


manufactured by Measurement Technology Limited to our design specifications.

The Vibration Transducer Interface incorporates three-port isolation. The


transducer, monitor, and power supply circuits each have separate grounding
points, since the three circuits are isolated from each other. Therefore, +24 Vdc
plant power, with its own ground, can be used to provide power to the Vibration
Transducer Interface without creating ground loops. With the use of our1800/10
power supplies, 110 Vac or 220 Vac can also be used to power the Vibration
Transducer Interface. Two power supplies can be installed in one housing.

The following Bently Nevada transducer systems can be used with the Vibration
Transducer Interface:

3300 XL Proximity Transducer System


3300 5 mm/8 mm Proximity Transducer System

7200 5 mm/8 mm Proximity Transducer

PROXPAC
330400 Accelerometer

Accelerometer Interface Module (part number 23733-03)

Aeroderivative Interface Module (part number 86517)


3300 REBAM MicroPROX Proximity Transducer System

7200 REBAM MicroPROX Proximity Transducer System

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 1 of 8
The following Bently Nevada monitors can be used with the Vibration Transducer
Interface:

3500/25 Keyphasor Monitor


3500/40 Proximitor Monitor

3500/42 Proximitor /Seismic Monitor

3500/44 Aeroderivative Monitor


3500/45 Differential Expansion/ Thrust Position Monitor

3500/50 Tachometer Monitor

3500/53 Overspeed Protection System


3300/16 Dual Vibration Monitor

3300/20 Dual Thrust Monitor

3300/25 Dual Accelerometer Monitor

3300/26 Dual Accelerometer RMS Monitor

3300/50 Tachometer

3300/52 Reverse Rotation Monitor

3300/53 Overspeed Protection System

3300/54 Dual REBAM Monitor

3300/61 Dual Vector Monitor

3300/81 Six-channel Rod Drop Monitor

3300/95 Aeroderivative Filter Module/Vibration Monitor

2201/02 System Monitor


2201/03 Four-channel PLC Monitor

2201/06 Low Speed Machine Monitor

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 2 of 8
Signal Range
Specifications (Terminals 5
and 6, 7 and 8):
Electrical
-20 Vdc to -0.5 Vdc.
The following specifications apply
at 20 C (68 F) for one channel, Signal Input
unless otherwise noted, the Impedance
temperature coefficient is 50 (Terminals 5
ppm/C (+10 C to +65 C) and and 6):
100 ppm/C (-20 C to +10 C).
10K -1%, +2%.
Supply Voltage
Signal Output
(Vs):
Impedance
+20 Vdc to +35 Vdc.
(Terminals 7
Power and 8):
Requirements,
20 .
Vs:
DC Transfer
88 mA at +20 Vdc,
Error:
80 mA at +24 Vdc,
100 mV.
63 mA at +35 Vdc.
AC Transfer
Isolation: Error:
250 Vac between input, power, 1% from 0 to 1 kHz;
and output circuits.
-5% to +1% from 1 to 10 kHz;
Power
-10% to +1% from 10 to 20 kHz.
Dissipation
Within Unit: Voltage
Bandwidth:
1.7 W.
-3 dB at 43 kHz (typical).
Minimum
Transducer Phase Delay:
Supply Voltage
Less than 14 sec, equivalent to:
(Terminals 2
and 6) Versus -1 degree at 200 Hz;
Load Current:
-3 degrees at 600 Hz;
-22.2 Vdc at 12 mA,
-5 degrees at 1 kHz;
-21.1 Vdc at 15 mA,
-50 degrees at 10 kHz;
-18.7 Vdc at 22 mA.
-100 degrees at 20 kHz.
Max Cross-Talk
Line Fault
Noise Between
Detection:
Adjacent
Isolators: If signal input line breaks (opens),
signal output drops to
11.3mV peak-to-peak (4mv RMS).
approximately 0V.

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 3 of 8
Monitor Environmental Limits
Leadwire Operating
Length: Temperature:
30 metres (100 feet) maximum -20 C to + 65 C (-4 F to + 149
between monitor and Vibration F).
Transducer Interface.
Storage
Transducer Temperature:
Leadwire
Length: -40 C to +80 C (-40 F to +176
F).
For all applicable transducer
systems: 305 metres (1000 feet) Relative
maximum between transducer Humidity:
module and Vibration Transducer To 95%, noncondensing.
Interface. The capacitance,
inductance, and L/R parameters Enclosure
of the cable must be appropriate Base:
for the hazardous area
classification. GRP (glass-fiber-reinforced
polycarbonate).
LED Indicators:
Lid:
One green LED on top of module
indicating power to module and Transparent high-strength
two green LEDs on backplane polyester.
indicating power sources are Finish
available.
Base:
Safety
Description Light gray.

Terminals 2 to 4: Lid:

26.6 V, 94 mA, 0.66 W. Transparent.

Terminals 5 to 6: Lid fasteners:

Non-energy-storing apparatus; Captive screws

1.2 V, 0.1 A, 20 J, and 25 mW. Protection:

Hazardous Area Dust-tight and water-jet proof to


Classifications: IEC529: IP65

Approvals for hazardous areas for Permitted


all compatible transducer location:
systems are certified by BASEEFA Safe area.
/ CENELEC for Zone 0, IIC, T4-6
except the Aeroderivative Ambient
Interface Module, which is temperature
approved by SIRA /CENELEC for limits:
Zone 1, IIC, T4. -20 C to +50 C (-4 F to +122 F),
typical.

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 4 of 8
Ordering Information H: Position 7 Module
00 No module required
Note: When 3300 or 2201 monitors are ordered for 01 With module
use with the Vibration Transducer Interface, the I: Position 8 Module
monitors must be configured for no barriers. The 00 No module required
3500 monitors are configured for use with the 01 With module
Vibration Transducer Interface using the 3500/01
Rack Configuration Software. Power Supply (1800/10)
128111-AXX-BXX-CXX-DXX
Vibration Transducer Interface
A Housing Option
128112-AXX-BXX-CXX-DXX-EXX-FXX-GXX-HXX-IXX 00 No housing required
A: Housing Option 01 With housing
00 No housing required B: Input Voltage
01 With housing 01 95 to 135 Vac
B: Position 1 Module 02 210 to 255 Vac
00 No module required C: Agency Approval
01 With module 00 No Approvals
C: Position 2 Module D: Number of Power Supplies
00 No module required 01 One
01 With module 02 Two
D: Position 3 Module
00 No module required Accessories
01 With module 01700005
E: Position 4 Module
00 No module required Power supply fuse. One fuse is
01 With module installed in the backplane when it
F: Position 5 Module is shipped.
00 No module required
01 With module Spares
G: Position 6 Module
02245026
00 No module required
01 With module MTL 4031 Isolator

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 5 of 8
Field wiring diagram
Vibration Transducer Interface

Figure 1: Vibration Transducer Interface Terminals

Figure 2: Vibration Transducer Interface


Dimensions are in millimetres (inches)

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 6 of 8
Figure 3: Vibration Transducer Interface Housing (also for use with power supplies)
Dimensions are in millimetres (inches)

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 7 of 8
Figure 4: Vibration Transducer Interface Power Supply
Dimensions are in millimetres (inches)

Bently Nevada, PROXPAC, MicroPROX, Keyphasor, Proximitor and REBAM are trademarks of General Electric Company.

Copyright 2000. Bently Nevada LLC.


1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 775.782.3611 Fax: 775.215.2873
www.ge-energy.com/bently
All rights reserved.

Specifications and Ordering Information


Part Number 141499-01
Rev. C (06/07)

Page 8 of 8