AA-0019E
Fundamentals of Automatic Control for Building Systems
i
07. CHARACTERISTICS AND CONTROLS OF AHUS 7-1
07.1 FANS .........................................................................................................................................7-1
07.2 COOLING AND HEATING COILS .........................................................................................7-5
07.3 HUMIDIFIERS .........................................................................................................................7-6
07.4 TOTAL HEAT EXCHANGERS (ECONOMIZERS) ..................................................................7-7
ii
13.2 DEHUMIDIFICATION CONTROL ....................................................................................... 13-2
19. VARIABLE AIR VOLUME AIR HANDLING UNIT CONTROL SYSTEMS 19-1
19.1 SYTEM SCHEMATIC ........................................................................................................... 19-1
19.2 HOW TEMPERATURE CONTROLLER WORKS ............................................................... 19-1
iii
20.4 DISCHARGE AIR TEMPERATURE OPTIMUM RESET (LOAD RESET) .........................20-2
iv
28. SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL 28-1
28.1 PURPOSE OF SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL ...... 28-1
28.2 TYPES OF SECONDARY PUMP DISCHARGE PRESSURE CONTROL .......................... 28-1
28.3 CAUTIONS FOR PARALLEL OPERATION OF CONSTANT SPEED PUMPS
AND VARIABLE SPEED PUMPS ......................................................................................... 28-5
v
35. AN OVERVIES OF BUILDING MANAGEMENT SYSTEMS 35-1
vi
01. CHARACTERISTICS OF AIR
GENERAL
This chapter describes the properties of air, and how HVAC (heating ventilating and air-conditioning)
systems maintain these properties at desired levels.
The purpose of HVAC system is to provide occupants with a comfortable environment through
conditioning the four properties of air; temperature, humidity, air velocity, and cleanliness, and distributing
air to rooms evenly. For example, according to a Japanese code related to indoor air quality, the
recommended conditions for properties of air for buildings with many occupants (e.g., office buildings
with 30,000 square meters or larger) are as listed in Table 01.1.
Indicator Requirement
1. Air bourn particles Below 0.15 mg per 1 m3 of air
2. Carbon monoxide Below 10 ppm
3. Carbon dioxide Below 1000 ppm
4. Temperature 17 to 28
5. Relative humidity 40% to 70%
6. Air velocity Below 0.5 m per second
7. Formaldehyde Below 0.1 mg per 1 m3 of air
1) Temperature
Indicates occupants feeling of hotness and coldness, and is usually represented by dry-bulb temperature.
2) Humidity
Indicates the amount of moisture in the air and is usually represented by relative humidity. Relative
humidity is the ratio of the amount of moisture in the air to the maximum amount of moisture the air can
hold at the same temperature and pressure.
3) Air velocity
Occupants may feel uncomfortable when air velocity is higher than 0.3 m per second. High air velocity
may cause problems of difficulty to adjust body-temperature, or thermal discomfort, while low air
velocity may cause remaining harmful contaminants or respiratory discomfort. For example, a Japanese
IAQ code regulates air velocity to be below 0.5 m per second.
4) Cleanliness
Indoor air is polluted due to inhalation, smoking, combustion, or substance emitted from building
materials, therefore, it must be diluted by ventilation.
For example, the Building Management Law of Japan defines contaminants to be limited: airborne
particles, carbon monooxide, carbon dioxide, and formaldehyde.
AA-0019E 1-1
01. CHARACTERISTICS OF AIR
COOLING TOWER
ROOM
RETURN AIR
(RA)
CONDENSER
WATER PIPING RETURN
EXHAUST AIR
(EA) FAN
SUPPLY AIR
(SA)
HOT WATER
PIPING
SUPPLY WATER
OUTDOOR AIR
(OA) CHILLED
WATER
PUMP HUMIDIFIER
HOT WATER
HOT WATER PUMP
1) Flow of Air
Figure 01.1 illustrates airflow from an air handling unit (AHU) to a room. Air conditioned by the AHU
is delivered to the room through the duct (SA: supplied Air). The supplied air circulates within the room,
then the part of it is exhausted to outdoor (EA: Exhaust Air), while the rest of the air returns to the AHU
for reuse of heat. (RA: Return Air). Outdoor air is brought in as fresh air to replenish oxygen supply to
the room and maintain cleanliness (OA: Outdoor Air). Thus the air circulating around the AHU system
provides a comfortable environment.
2) Flow of Water
The AHU is equipped with a cooling-coil, a heating coil, and a humidifier to condition temperature and
humidity of the air. Heat source equipment that produces and then distributes chilled or hot water to the
AHU coils includes: a chiller producing chilled water, and a hot water boiler producing hot water.
Chilled or hot water produced by heat source equipment is distributed through the chilled or hot water
piping, then removes heat from or adds heat to the air at the chilled or hot water coil to produce cold or
warm air respectively. The absorbed heat is returned to the chiller, then distributed to the cooling tower
to be dissipated to outdoor air. Thus, a HVAC system consists of AHUs; heat sources; cooling towers;
pipes and pumps to distribute water; fans and ducts to distribute air.
1-2 AA-0019E
02. PID CONTROL
1) The temperature sensor (TE) measures the room temperature and then transmits an input signal
to the temperature controller (TIC).
2) The temperature controller (TIC) compares the input signal to the setpoint and then determines
an output to the chilled water valve (MV) to regulate chilled water flow.
3) Air cooled by the chilled water coil is distributed to the room, and is mixed with the room air to
change the room temperature.
If the chilled water valve opens too wide, the room temperature falls below the setpoint. If too narrow the
heat generated in the room or transmitted through the walls is not adequately removed resulting in the
room temperature above the setpoint. To keep the room temperature at the setpoint, it is required to
modulate the chilled water valve properly in response to varying room conditions. As this example, an
operation to maintain a controlled object in the desired condition is called a control, and when it is done
by devices, not manually, is called an automatic control.
.
TIC
COMPARISON
/DECISION
RA
MV
MANIPULATION
OA FAN SA TE
RESPONSE DETECTION
HEAT ENTER
ROOM INDOOR LOAD /LEAVE
AA-0019E 2-1
02. PID CONTROL
control or a closed-loop control. Feedback controls have various configurations and methods of
calculating the value of the manipulated variable, and the PID control is one type of feedback control.
Figure 02.2 shows a signal flow diagram for the room temperature control in Figure 02.1. This diagram,
called a block diagram, represents configurations and characteristics of control systems using
signal-processing elements and signal flows and is used for designing automatic control systems. Table
02.1 lists terms and abbreviations of these variables. Using these terms, a feedback control can be defined
as a control that changes the value of the manipulated variable to eliminate the deviation. Disturbances in a
room temperature systems include; indoor loads generated by office machinery, lighting, or occupants; heat
entering/leaving the room, and changes in outdoor air temperature or chiller water temperature.
DISTURBANCE d
CONTROLLER CONTROLLED OBJECT
Abbreviation Term
SP Set point (desired value)
PV Process variable (controlled variable)
MV Manipulated variable: a controller signal sent to an actuator
e Error (deviation): setpoint minus the value of a process variable
d Disturbance: External elements that disturb the control system
2-2 AA-0019E
02. PID CONTROL
1
K= is called a gain. T is called a time constant.
k
When t = 0: x(0) = 0
1
When t = : x =K=
MODEL SYSTEM HEAT CAPACITANCE C
k
ROOM TEMPERATURE x
OUTDOOR AIR
SUPPLED HEAT u TEMPERATURE x0
STEAM
AA-0019E 2-3
02. PID CONTROL
1 1
X (s ) = K( )( )
Ts 1 s
1 1
= K( )
s 1
s
T
By Inverse Laplace transformation:
t
x(t ) = K (1 e T
)
-------------------------------------------------------------------------------------------------------------------------
As in the example, a first-order lag system is a system where the relationship between an input and an
output is expressed in a first-order-linear derivative equation.
Although actual controlled systems are expressed in non-linear high order derivative equations they can be
expressed approximately by a gain, a time-constant, and a lag, and can be handled as first-order-lag
systems when applying PID control.
STEP INPUT
STEP RESPONSE
MAXIMUM SLOPE
INPUT BAND
OUTPUT
63.2% OF
INPUT
OUTPUT BAND
OUTPUT BAND
GAIN
TIME
DEAD TIME TIME CONSTANT
Figure 02.4 First order lag + dead time system step open loop step response
2-4 AA-0019E
02. PID CONTROL
STEP INPUT
THREE TIMES
OF GAIN
TIME OF REACH
63.2% UNCHANGED
OUTPUT
INPUT
TWICE OF GAIN
INITIAL GAIN
TIME
Figure 02.5 First order lag + dead time system step open loop step response with different gains
2. Time Constant:
Figure 02.6 illustrates responses of a first-order-lag system with different time constants. When the time
constant doubles or triples, the time between startup of the output and the time the output reaches 63.2%
of a total response doubles or triples respectively, but the total response remains constant. For example,
in the temperature control, the time constant relates to heat capacitance.
STEP INPUT
INITIAL
TIME CONSTANT
FINAL VALUE
OUTPUT
UNCHANGED
INPUT
THREE TIMES OF
TIME CONSTANT
TWICE OF
TIME CONSTANT
TIME
Figure 02.6 First order lag + dead time system step open loop step response with different time
constants
AA-0019E 2-5
02. PID CONTROL
3 Dead Time:
Figure 02.7 illustrates responses of a first-order-lag system for different dead time. When the dead time
doubles or triples, while the shape of the response is unchanged, the time between the time of input and the
time the response begins doubles or triples respectively. For example, in a temperature control system, the
dead time depends on duct length.
STEP INPUT
PATTEN
UNCHANGED
OUTPUT
INITIAL
INPUT
DEAD TIME
THREE TIMES
OF DEAD TIME
TWICE OF
DEAD TIME
TIME
Figure 02.7 First order lag + dead time system step open loop step response with different dead
time
Where: m0 is a base value, or a manual reset value, of the manipulated variable (m).
2-6 AA-0019E
02. PID CONTROL
CONTROL CHARACTERISTICS
LINE (2)
CONTROL CHARACTERISTICS
LINE (1) LOAD CHARCTERISITCS
LINE
OFFSET
AA-0019E 2-7
02. PID CONTROL
CONTROLLED
VARIABLE
ERROR
PROPORTIONAL DERIVATIVE
P-ACTION
m m
INTEGRAL PROPORTIONAL
I-ACTION
D-ACTION
2-8 AA-0019E
02. PID CONTROL
SETPOINT/CONTROLLED VARIABLE
COPNTROLLED VARIABLE OVERSHOOT=a1/A
DAMPING RATIO=a2/a1
STABILIZED VALUE
SETPOINT ALLOWABLE RANGE
OFFSET
OVERSHOOT TIME
STABILIZED TIME
AA-0019E 2-9
02. PID CONTROL
P-CONTROL
PI-CONTROL
PID-CONTROL
ZIEGLER-NICHOLS METHOD
2-10 AA-0019E
03. PSYCHROMETRIC CHART
AA-0019E 3-1
03. PSYCHROMETRIC CHART
Specific heat at constant pressure Cp kJ/kg(DA) C Heat of moist air per 1 kg dry air under constant pressure.
3-2 AA-0019E
03. PSYCHROMETRIC CHART
AA-0019E 3-3
03. PSYCHROMETRIC CHART
HE
A
RA T/MO
TIO ISUT
UR
ON
E
I
RV RAT
PY
E
CU TU
Y
AL
IT
SA
TH
ID
HEAT RATIO
M
EN
SENSIBLE
HU
ABSOLUTE HUMIDITY
IC
VE
IF
EC
TI
LA
SP
RE
DRY-BULB
HE
A
RA T/MO
TIO IS UT
UR
E
DI E
MI IV
TY
HU LAT
HEAT RATIO
PY
RE
AL
SENSIBLE
ABSOLUTE HUMIDITY
TH
EN
IC
IF
WE
EC
T-B
SP
U LB
SP
EC
IFIC
VO
LU
ME
DEW-POINT DRY-BULB
3-4 AA-0019E
03. PSYCHROMETRIC CHART
When volumetric flow (V) is used instead of mass flow (G), substitute V/v in G.
V : volumetric flow (m3/h)
v : specific volume of air m3/kg (DA)
However, as the specific volume (v) depends on the dry-bulb temperature, volumetric flow varies before
and after a heating processes. Therefore, usually standard air, or dry air at 20, (1.2 kg of density),
which is constant in the air distribution system is used to handle the volumetric flow. As the specific heat
of the standard air is 0.83 [m3/kg(DA)], the volumetric flow converted to the standard air is:
V0=0.83G, then
V0
q= (h 2 -h 1 )/3600 (03.4)
0.83
Also, the constant pressure specific heat of moist air can approximately be handled as cp=1.006:
q = 1.21 V0 (t 2 - t 1 )/3600 (03.5)
-----------------------------------------------------------------------------------------------------------------------
(Example)
when
t 1 = 12 (C), h 1 = 22.9 kg/kg(DA)
t 2 = 32 (C), h 2 = 43.2 kJ/kg(DA)
V 0 = 500 (m3/h)
From (03.5):
q= 3.36 (kW)
----------------------------------------------------------------------------------------------------------------------
q = G (h 1 - h 2 )/3600 (03.6)
AA-0019E 3-5
03. PSYCHROMETRIC CHART
V0
= (h 1 - h 2 )/3600 (03.7)
0.83
Where,
G: airflow in mass kg (DA)/h
The amount of water [kg/h] removed by the cooling coil is:
L = G(x 1 -x 2 )
V0
= (x 1 - x 2 ) (03.8)
0.83
---------------------------------------------------------------------------------------------------------------------
(Example)
When:
h 1 =71.6 kJ/kg(DA)x 1 =0.0162 kJ/kg(DA)
h 2 =37.3kJ/kg(DA) , x 2 =0.0092 kJ/kg(DA)
V 0 =10000 (m3/h)
From (03.7):
q=114.8 (kW)
From (03.8):
L=84.3 (kg/h)
----------------------------------------------------------------------------------------------------------------
When moist air is cooled by a cooling coil, if the surface temperature of the cooling coil is above the
dew point temperature of the air, water vapor in the air does not condense, then the condition of the air
moves to the left on a line with constant absolute humidity (Line 1-2) as shown in Figure 03.5. The
amount of heat required for cooling [q(kW)]is the same as in heating:
q = G (h 1 h 2 )/3600 (03.9)
V0
= (h 1 h 2 )/3600 (03.10)
0.83
or,
q = CPG (t 1 t 2 )/3600 (03.11)
3-6 AA-0019E
03. PSYCHROMETRIC CHART
Where:
G: airflow in masskg (DA)/h
AA-0019E 3-7
03. PSYCHROMETRIC CHART
This line can approximately be handled as a constant wet-bulb temperature line. Enthalpy-water ratio (u)
is expressed by the following equation;
h
u=
x
Where:
h= difference of enthalpy
x= difference of absolute humidity
The required water for humidification is:
L=G (x 2 - x 1 ) (03.16)
V0
= (x 2 - x 1 ) (03.17)
0.83
Where:
L= amount of water for humidification (kg/h)
G= airflow in mass [kg(DA)/h]
(Example)
x1 =0.0067 kg/kg(DA)
x2=0.0088 kg/kg(DA)
V0 =10000 (m3/h)
From formula (03.17):
L=25.3 (kg/h)
-------------------------------------------------------------------------------------------------------------------------
HE
E
RA T/MO
TUR
TIO ISU
TU
RE
SU
RAT T/MOI
IO
HEA
3-8 AA-0019E
03. PSYCHROMETRIC CHART
AA-0019E 3-9
03. PSYCHROMETRIC CHART
FAN
HEAT RATIO
SENSIBLE
OUTDOOR RETURN ROOM
AIR AIR
FAN
HEAT RATIO
SENSIBLE
HUMIDIFIER
OUTDOOR ROOM
AIR RETURN
AIR
3-10 AA-0019E
03. PSYCHROMETRIC CHART
AA-0019E 3-11
03. PSYCHROMETRIC CHART
3-12 AA-0019E
04. SENSORS
04. SENSORS
GENERAL
This chapter provides information on commonly used sensing elements for variables in HVAC systems
such as temperature, or humidity, and how to use these sensors.
04.1 ROOM TEMPERATURE/HUMIDITY SENSORS
Room temperature/humidity sensors are wall-mounted in rooms (Fig. 04.1, 04.2). There are two types: a
sensor incorporating either temperature or humidity sensor, or both in a single case. Platinum resistance
temperature devices (RTDs) are commonly used to measure temperature. Polymer thin-film are used to
measure relative humidity.
[Locations for installation]
At 1.5 m above the floor where representative temperature or humidity can be measured.
At the location where air circulation is not disturbed by furniture or doors, and heat from office
machinery, etc., does not remain.
Note: Appropriate ambient air velocity at the installed location is 0.1 to 0.2 m/s.
Avoid locations affected by infiltration, down airflow, heat radiation from cold/hot water piping
or duct, and solar radiation.
Without oscillation
Without water spray.
Without condensation.
WALL-DIRECT
MOUNTING KIT
MOUNTING
UNIT SURFACE
AA-0019E 4-1
04. SENSORS
RESISTANCE
TEMPERATURE
(a)n (b)
4-2 AA-0019E
04. SENSORS
Where:
Rx: resistance temperature element
Since the current does not flow through Point c-Point d, current I1 flows through Point a - Point c, and
Point c - Point b, and current I2 flows through Point d - Point b, and between Point a - Point d.
Comparing to Equation 04.2, 2Rl is added to the balancing condition of the bridge, consequently a
voltage drop (I12Rl) occurs and causes an error, and does not allow longer wiring length. With a
three-wire system, as shown in Figure 04.5 (b), assuming wiring length Rl1, Rl2, Rl3 are equal, the
balancing condition of the bridge becomes as follows:
R 1 (R 4 + R l 2 ) = R 3 (R l1 + R x ) (04.4)
Where:
Rx = resistance temperature element
R l1 , R l 2 , R l 3 = resistance of wire
When the bridge is balanced, current I1 flows through Rl1, and current I2 flows through Rl2. Since the
voltage drop IRl3 due to Rl3 is included in the power supply circuit, it does not affect the balancing
condition, and allows longer wiring length. From this reason, when high accuracy for indicating and
recording of temperature is required, three-wires circuit is usually used.
racy for indicating and recording of temperature is required, three-wire circuit is usually used.
(a) (b)
HIGH POLYMER
LEAD WIRE
LOWER ELECTRODE
GLASS PLATE
AA-0019E 4-3
04. SENSORS
(2) Characteristics
[Strength]
. Quick response
. Relatively less expensive
. Easy to handle
. Reliable over time
. Small changes in characteristic over time
[Weaknesses]
. Limitations in ambient air (Table 04.1)
[Sensing range]
Relative humidity 0-100 %RH (at 15-35 C)
Accuracy 3 %RH (at 15-30 C, 30-70 %RH)
5 %RH (at 15-30 C, 20-80 %RH)
Cigarette particles B
Ultraviolet irradiation B
Ozone D
Organized solvent D
Acrylic paint B
Epoxy paint B
Ulethan paint B
Chloride solution D
Flammable gas D
Condensable environment D
Legend: A: Applicable B: Applicable with a certain error C: Applicable depending on the case
D: Not applicable
4-4 AA-0019E
04. SENSORS
UNIT
Figure 04.7 Insertion type
temperature/humidity sensor (HTY7803)
[How to select]
1) Length of Sensing Elements
Select a sensing element that reaches the center of the pipe.
Note: The minimum length of insertion is 100mm, and about 50mm for mounting socket must be
considered.
2) Locations for Installation
Install the sensor at locations that meet the following conditions.
. Where water flow does not stagnate.
. Locations that meet the purpose of measurement (e.g., water flow is well mixed).
. If there are elbows, tees, valves upstream from the sensor, install the sensor a distance of 10 D
(diameter) away.
3) How to Install
In water pipes, install the sensor from above the horizontal line (to prevent water condensation on the
pipe from entering the head cover of the sensor). Figure 03.11 illustrates the installation condition of a
pipe-insertion type sensor.
AA-0019E 4-5
04. SENSORS
INSERTION LENGTH
SCREW CONNECTION
WELDERING WELDERING
PIPE
PROTECT TUBE
FLOW DIRECTION PROTECT TUBE
STRAIN GAUGE
WIRING
DIAPHRAM
Photo
AA-0019E 4-7
04. SENSORS
Photo
4-8 AA-0019E
04. SENSORS
l 1 1
v = ( )
2 cos t1 t 2
Where:
v : fluid velocity
l : distance between probes
:: angle of ultra sonic wave to the pipe center
t1 : travel time in forward direction
t 2 : travel time in backward direction
AA-0019E 4-9
04. SENSORS
Photograph
Figure 04.13 Electromagnetic flow meter principle Figure 04.14 Vortex flow meter principle
4-10 AA-0019E
05. CONTROL VALVES AND DAMPERS
PLUG STEM
BONNET
BODY
SEAT
VALVE SIZE
PORT SIZE
AA-0019E 5-1
05. CONTROL VALVES AND DAMPERS
Material
Name Applications
symbols
FCD450 Nodular graphite cast iron Body with pressure rating JIS20K
SCPH2 High temperature, high pressure cast steel Body of cage valve
SCS14
5-2 AA-0019E
05. CONTROL VALVES AND DAMPERS
FLOW
AA-0019E 5-3
05. CONTROL VALVES AND DAMPERS
FLOW FLOW
Figure 05.4 Single-seated valve (V5063) Figure 05.5 Double-seated valve (V5064)
FLOW
(5) Butterfly valves (Figure 05.8) Figure 05.7 Rotary type electric valve (ACTIVAL)
Structure: Rotates a disc around a valve-stem.
Characteristics: This type of valve is usually used as a switching valve. Butterfly valves are typically
with large valve sizes, a small pressure loss and allows large fluid flow, but the rangeability is not large.
5-4 AA-0019E
05. CONTROL VALVES AND DAMPERS
FLOW
STROKE STROKE
A valve authority affects the flow characteristics of the valve. Figures 05.12 and 05.13 show flow
characteristics for different valve authorities. Valve authorities greater than 0.5 are recommended for
good controllability.
AA-0019E 5-5
05. CONTROL VALVES AND DAMPERS
FLOW
FLOW
STROKE STROKE
5-6 AA-0019E
05. CONTROL VALVES AND DAMPERS
further even if the differential pressure across the valve increase. Therefore the Cv is calculated
separately depending on whether or not the differential pressure (P) is larger than 50% of the primary
pressure. Usually the valve is sized so that the pressure loss is below 50% of the primary pressure.
Note: Absolute pressure: Pressure from a complete vacuum (zero), usually is denoted abs.
Gage pressure: Pressure from an atmospheric pressure.
0 kPa gauge pressure (G) = absolute pressure 101 kPa (abs)
P1
When P <
2
W W
CV = =
0.1391 P1 P2
2 2
0.1391 P ( P1 P2 )
P1
When P
2
W
CV =
0.1205P1
Where:
P1: primary absolute pressure (kPa)
P2: secondary absolute pressure (kPa)
W: mass flow (kg/h):
-------------------------------------------------------------------------------------------------------------------------
(Example)
P 1 = 201 kPa, P 2 =141 kPa, W = 60 kg/h
P1
P = P 1 -P 2 = 60kPa <
2
60
CV = = 3.01
0.1391 60(201+141)
-------------------------------------------------------------------------------------------------------------------------
Table 05.3 lists typical values forP of air handler control values.
Name of control P
AA-0019E 5-7
05. CONTROL VALVES AND DAMPERS
Selected
P Calculated CV Controllability Pump running power
valve size
High Small Small Good effective flow characteristics, Increase in control valve
effective range ability, and resistance, pump head, and
controllability of a control valve. pump power.
Low Large Large Low effective flow characteristics, Decrease in control valve
effective range ability, and resistance, pump head, and
controllability of a control valve. pump power.
1. Controllability
An effective rangeability is a range ability for actual flow. Selecting a control valve with a larger Cv
than required results in a smaller effective rangeability. For example, a control valve with 50 : 1
reangeability has a 30 : 1 of effective ranageability.
2. Pump power
In direct return systems that are applied to most of the todays buildings, the pressure drop across an air
handling unit coil plus a control valve in every floor is higher than 100 kPa, therefore, the P of the
control valve can be specified to be higher than 30 to 50 kPa. While in reverse-return systems (Fig.
05.14 (b)), since the pressure drop across the control valve in ever floor is equal, the P of the control
valve must not be specified to be higher than 30 to 50 kPa.
(1) 3. Piping Systems and P
In direct return systems that are applied to most of the todays buildings, the pressure drop across an air
handling unit coil plus a control valve in every floor is higher than 100 kPa, therefore, the P of the
control valve can be specified to be higher than 30 to 50 kPa. While in reverse-return systems (Fig.
05.14 (b)), since the pressure drop across the control valve in ever floor is equal, the P of the control
valve must not be specified to be higher than 30 to 50 kPa.
5-8 AA-0019E
05. CONTROL VALVES AND DAMPERS
05.2.4 Close-Off-Rating
A close-off-rating is the maximum permissive pressure drop across the valve in the full-closed position.
The pressure difference (P) of the valve multiplied by the port area is the force exerted on the valve
stem, and when this force is less than the actuator force needed to close the valve, the valve can keep full
closed.
Note: For the close-off-rating of a three-way mixing valve, select the greater pressure drop between
either of the two inlets ports and the outlet port for a mixing valve, and the inlet port and the greater
pressure drop between either of the two outlet ports for a three-way diverting valve.
1. How to Check Close-Off Ratings
To select a control valve, check if the close-off-rating is greater than the maximum pressure drop across
a valve (Pmax) which is determined by a pressure chart. Refer to 26 Pressure Charts of a Piping
Systems, and 31 Selecting Control Valves for Heat Sources.
2. Valve Size and Close-Off Ratings
A close-off-rating of a valve depends on the actuator as well as the port size. The larger the valve size,
the smaller the close-off-rating for the same actuator.
05.2.5 Rangeability
A rangeability is a ratio of maximum flow (qmax) to minimum flow (qmin) that are controllable, and
usually is expressed as R1:1. Rangeabilities of 30:1 to 50:1 are usually used. From the definition, a valve
with a larger rangeability can control the fluid flow of a wider range.
For example, assuming the maximum controllable flow is 100l/min with a constant pressure drop, an
Actival (VY5100, rangeability 50:1) can control as low as 2l/min flow.
K C : cavitation coefficient
P1 inlet pressurekPaabs
P2 outlet pressurekPaabs
Pv saturated vapor pressure at the fluid temperature (kPaabs)
AA-0019E 5-9
05. CONTROL VALVES AND DAMPERS
From the equation, the larger as the differential pressure across the control valve, or the lower the
downstream pressure with the same inlet pressure, the lager kc resulting in more possible occurrence of
cavitation. To use a control valve under the conditions in which cavitation can occur, the following
measures must be considered to avoid damages by cavitation-erosion,
Select materials, usually stainless steel, for the valve body and pipes that withstand bumping
pressure.
Select larger sized valve body and pipe, usually 1 to 2 size up, so that bubbles do not bump into the
valve body.
Connect two valves in series so that the pressure drop for each valve becomes lower. This is
effective especially when the pressure drop is 1 Mpa or higher.
In addition to pump-bypass valves, or pressure holding valves in the return piping of the thermal storage
systems, care must be taken when the heat source equipment is located on the roof, because pressure at
downstream from the pump-bypass valve is low and it may cause cavitation.
SECONDARY
PUMP
DIFFERENTIAL
PRESSURE
OUTLET PRESSURE
SATURATED STEAM PRESSURE
AT THE FLUID TEMPERATURE
CAVITY GENRATES CAVITY DIMINISHES
PRESSURE DISTRIBUTION
5-10 AA-0019E
05. CONTROL VALVES AND DAMPERS
Item Considerations
Fluid flow Flow rate through coils in air handling units or heat exchangers is necessary for Cv
calculation. But it is often revised during the process from design through completion in
building projects, so acquire the latest data.
Differential pressure A P for Cv calculation should be properly determined and the valve authority should
(P) be greater than 0.5.
For water flow, determine an appropriateP based on pump heads and pressure losses in
the piping system.
For steam flow, determine an appropriateP based on the pressure upstream from the
control valve (primary-side) and the pressure required by equipment located downstream
from the valve (secondary-side).
Valve type Globe valves, motorized valves, or cage valves are usually used for proportional control of
variables, such as temperature, humidity, pressure or differential pressure. Ball valves or
butterfly valves are used for two-position control or as switching valves.
Valve seat leakage Valve seat leakage is below 0.5 % Cv for double-seated valves and below 0.01% Cv for
single-seated valves, or motorized rotary valves. For complete shut-off applications such
as steam flow, use valves for shut-off features. For steam flow, select control valves with
valve seat leakage below 0.01 % Cv.
Fluid temperature Fluid temperature must be within the allowable temperature range of the control valve. For
cold fluid below -0.5 such as brine, the body material must be SUS or SCS as means to
avoid low temperature fragility.
For saturated steam at 0.8 Mpa, and about 170, it is recommended to select stainless
steel for body material to improve reliability. (The allowable temperature is 175 for a
motorized rotary valve or globe valve with JIS10K pressure rating and FC200 body
material).
Differential pressure and When the differential pressure across the operating valve is high and the downstream
downstream pressure pressure is low (below 100 kPa), cavitation or erosion may occur. Care must be taken to
select the body size, body material, and valve type.
AA-0019E 5-11
05. CONTROL VALVES AND DAMPERS
2. Damper Actuators
Electric direct-coupled damper actuators (Fig, 05.18) are used to actuate dampers. There are types of
damper actuators; two-position, proportional, spring-return, and high-torque. Select types that meet the
given control specification. Also, select actuators with a margin for increased torque over time. Figure
05.19 illustrates damper actuators.
5-12 AA-0019E
06. STRUCTURE OF AIR HANDLING UNITS
EXHAUST DAMPER
RETURN FAN
EXHAUST AIR (EA) RETURN AIR (RA)
AA-0019E 6-1
06. STRUCTURE OF AIR HANDLING UNITS
FILTER
DAMPER
DAMPER
AUTOMATIC
ACTUATOR
REWIDER
HOT WATER
COIL MOTOR
DUCT
HUMIDIFIER
FAN
Figure 06.4 Hot water coil and humidifier Figure 06.5 Supply fan
6-2 AA-0019E
07. CHARACTERISTICS AND CONTROLS OF AHUS
07.1 FANS
(1) Types and Characteristics of Fans
Fans used in AHUs are classified into multi-blade fans (scirocco fans), limit-load fans, or turbo-fans.
Multi-blade (scirocco) fans are commonly used in AHUs with static pressure up to 1000 Pa. Turbo-fans
and limit-load fans are used for static pressure above 1000 Pa. Table 07.1 shows characteristics of the
multi-blade and limit-load fans.
Turbo-fans have characteristics similar to limit-load fans, but are used when higher static pressure is
required.
Table 07.1 Characteristics of multiple bade fan and limit load fans
Blade structure
Efficiency 45 60 % 55 65 %
Shaft power As air flow increases, the shaft power When airflow increases, the shaft power
characteristics (power consumption) increases. increases, but after a peak, decreases.
Applications Low speed duct High speed duct
OPERATING OPERATING
POINT POINT
POWER
POWER
FLOW FLOW
AA-0019E 7-1
07. CHARACTERISTICS AND CONTROLS OF AHUS
120 f
N=
p
Where:
N= motor speed (rpm: return per minute)
f:= power frequency (Hz)
p:= number of poles of motor
Four-pole motors are commonly used for AHU fans. The motor speed is about 1500 RPM at 50 Hz and
900 RPM at 30 Hz. Actually, the speed is below a theoretical value due to slippage of the motor and the
pulley ration of a V-belt.
.
[Fan characteristics by speed control]
Fan curves (Q-Ps curves) corresponding to the speed n1 through n3 are shown in Figure 07.1. Assuming
the duct resistance curve is unchanged, as a fan speed decreases, airflow varies from Q1 to Q2, then to Q3,
fan power decreases from W1 to W2 then to W3 based on the following equations:
1. Airflow varies with fan speed. Q = f (n)
2. Static pressure varies as the square of fan speed. Ps = f (n2)
3. Fan power varies as the cube of fan speed. W = f (n3)
Where:
W= fan power
Q= air flow
Ps= static pressure
n= fan speed
Also, fan power varies with the air flow multiplied by the static pressure:
W = f ( Q Ps )
This means that fan speed control by a variable frequency drive (VFD) can reduce airflow, however if
the static pressure remains constant the fan power is not reduced sufficiently. It is necessary to reduce
the static pressure as low as possible. Since duct system resistance is proportional to the square of
airflow, fan power is reduced effectively by reducing the static pressure proportionally to the square of
airflow. (Fig. 07.3).
In constant static pressure (Ps) control, when the damper is closed, the duct resistance becomes from R2
to R3, the fan speed becomes from n2 to n3, the airflow becomes from Q2 to Q3 respectively. In the
control method that varies the static pressure setpoint, when airflow becomes from Q2 to Q3, the speed
becomes from n3 to n4 respectively. The variable static pressure control can reduce more speed at the
same airflow rate, and then provides a large reduction of the fan power. (Fig. 07.3)
7-2 AA-0019E
07. CHARACTERISTICS AND CONTROLS OF AHUS
CHARACTERISTICS (n1)
DUCT RESISTANCE CURVE
CHARACTERISTICS (n2)
STATIC PRESSURE
AXITIAL POWER
SPEED
CHARACTERISTICS (n3)
FLOW
FLOW
Figure 07.1 Fan characteristic change Figure 07.2 Power characteristic change
by speed control by speed control
CHARACTERISTICS
FLOW
AA-0019E 7-3
07. CHARACTERISTICS AND CONTROLS OF AHUS
Control based Receives data from each Reduces fan speed until at least one VAV Most VAV air
on VAV VAV controller including unit damper is full open resulting in reduced handling units.
airflow (Fig. demand airflow and current fan power.
07.5) damper positions. Since the fan speed varies in response to the
Summarizes these data to load changes in a single zone, static pressure
determine the load of the at one zone can be affected by load changes
air handling unit group and in other zones.
modulates the fan speed.
FLOW DEMAND
POSITION DATA
7-4 AA-0019E
07. CHARACTERISTICS AND CONTROLS OF AHUS
AA-0019E 7-5
07. CHARACTERISTICS AND CONTROLS OF AHUS
(3) Temperature Difference between Inlet and Outlet of a Chilled Water Coil.
Figure 07.6 illustrates a heat transfer characteristic of a chilled water coil in an AHU with a constant
amount of discharge air. As shown in the graph, the less water flow, the larger the temperature difference
of water between entering and leaving the coil, conversely the more water flow, the less the
temperature difference. Selecting too large-sized control valve results in too high chilled water flow in
the full-open position and too a small temperature difference of water. Therefore control valves must be
properly sized. Also in room or return air temperature control, if the deviation from the setpoint remains,
the control valve tends to be full-open due to an integral windup, resulting in the less temperature
difference of water. In these cases, a discharge air temperature cascade control using a discharge air
temperature sensor is effective to maintain water flow through the control valve within the capacity of
the coil.
INLET/OUTLET
TEMPERATURE
DIFFERENCE
TEMPERATURE
DIFFERENCE
COOLING
CAPACITY
AIR FLOW
CHILLED WATER
INLET TEMPERATURE
INLET AIR TEMPERATURE
INLET AIR ABSOLUTE
HUMIDITY
NUMBER OF COILS
07.3 HUMIDIFIERS
Typical humidifiers used in AHUs can be classified into; vaporization, direct steam-jet, and electrode
steam-jet humidifiers. To determine the control system for humidification, the type of humidifier must be
checked. Table 07.4 shows examples of control operations of typical humidifiers used in HVAC systems.
Vaporizing humidifiers are commonly used in office buildings. Direct steam-jet, or electrode steam-jet
humidifiers are commonly used for constant temperature and humidity rooms. Since control of vaporizing
humidifiers generally is two-position, vaporizing humidifiers cannot to be applied to discharge air
humidity (dew point) control where a fast response is required, but applied to room or return air humidity
control.
SUPPLY WATER
STEAM
7-6 AA-0019E
07. CHARACTERISTICS AND CONTROLS OF AHUS
SPECIFIC ENTHALPY
ABSOLUTE HUMIDITY
INLET
EXHAUST AIR
SUMMER
SEPARATER OUTLET
OUTDOOR AIR
SEPARATER OUTLET
ELEMENT
MOTOR ROTOR
DRY-BULB
Figure 07.7 Rotary type total heat exchanger Figure 07.8 Heat exchange of air in total heat
exchanger during summer season
AA-0019E 7-7
07. CHARACTERISTICS AND CONTROLS OF AHUS
7-8 AA-0019E
08. ROOM TEMPERATURE CONTROL SYSTEMS
q s = q i +q w +q l +q p +q e (08.1)
Where:
q s = heat supplied by the AHU
q i = heat of infiltration
q w = heat from the wall
q l = heat from lightings
The amount of sensible heat supplied by the AHU is determined from Equation 08.2. To change the
amount of sensible heat (qs) supplied to the room, there are two methods; changing either supply air
dry-bulb temperature (ts), or the volume of the supply air (Gs).
q s c p G s (t s t i ) (08.2)
Where:
AA-0019E 8-1
08. ROOM TEMPERATURE CONTROL SYSTEMS
08.2 CONSTANT AIR VOLUME SYSTEMS AND VARIABLE AIR VOLUME SYSTEMS
CAV systems vary the supply air dry-bulb temperature (ts) with a constant air volume, while VAV system
vary the volume of supply air (Gs) with constant supply air dry-bulb temperature (ts). A CAV system
modulates a chilled or a hot water valve and varies the discharge air dry-bulb temperature to maintain the
room temperature. In a VAV system a VAV unit modulates its damper to regulate the volume of supply air
to rooms to maintain the room temperature. When the VAV system cannot respond to changes in the indoor
loads due to the minimum setting of VAV airflow rate, the controller resets the discharge air dry-bulb
temperature setpoint.
8-2 AA-0019E
09. TYPES OF AIR HANDLING SYSTEMS
[Characteristics]
When a single room is served by an AHU, this system provides proper temperature, or humidity
control responding to the load.
When an AHU serves multiple rooms with different load characteristics, proper temperature control is
not provided except the room with a temperature sensor installed.
AA-0019E 9-1
09. TYPES OF AIR HANDLING SYSTEMS
Since the AHU supplies constant airflow, the system does not provide fan power savings during light
load conditions.
[Applications]
Standard floors, entrance halls, cafeterias, large meeting rooms, or halls in office buildings.
Constant temperature/humidity control in factories with an AHU serving a single room.
ROOM ROOM
[Characteristics]
Even with load variance between zones, the system provides proper temperature control.
Airflow rate is reduced as loads decrease, resulting in fan power savings.
Without means to bring in outdoor air, the amount of fresh outdoor air becomes insufficient, which
results in lower air quality.
[Applications]
These system are commonly applied in interior zones of mid to large-sized office buildings, sometimes
in perimeter zones.
9-2 AA-0019E
09. TYPES OF AIR HANDLING SYSTEMS
ROOM ROOM
DAMPER MOTOR
AIR VELOCITY
SENSOR
CONTROL PART
[Characteristics]
Even with a load variance among rooms, the room temperature is properly controlled.
Without proper control of cold or warm air discharge temperature, a mixing loss occurs.
[Applications]
Rooms requiring high-level comfort such as executive rooms in owner-buildings.
HOT AIR
MIXING BOX
COLD AIR
ROOM ROOM
AA-0019E 9-3
09. TYPES OF AIR HANDLING SYSTEMS
[Characteristics]
Since the CAV-AHU supplies a fixed amount of outdoor air, this system maintains an indoor air
quality during light load conditions.
High first cost due to large duct spaces.
To apply outdoor air cooling, the design airflow of CAV-AHU must cover airflow required for
outdoor air cooling.
[Applications]
Standard floors in office buildings.
MIXING BOX
ROOM
9-4 AA-0019E
09. TYPES OF AIR HANDLING SYSTEMS
[Characteristics]
The direction of the discharge airflow matches the room airflow. (Warm air flows upward in the
room.)
Diffuser can be relocated and the airflow rate is adjustable, therefore this type of system is flexible
to the load changes (e.g., addition of office machines). However, usually airflow rate is not
controlled automatically, so precise temperature control in not available.
Cold drafts may occur in the cooling periods. In that case, temperature difference between the room
and discharge air must be reduced.
When the thermal insulation of the floor is not sufficient, it may cause occupants complaint due to
longer cool-down/warm-up time, especially when distances between the AHU and the diffuser is
large.
[Applications]
Standard floors in office buildings.
CEILING PLENUM
ROOM
CEILING PLENUM
EQUAL PRESSURE
PLENUM SA
EQUAL PRESSURE PLENUM METHOD
ROOM
CEILING PLENUM
ROOM
FREE ACCESS
PRESSURED
PLENUM SA
PRESSURED PLENUM METHOD
AA-0019E 9-5
09. TYPES OF AIR HANDLING SYSTEMS
[Applications]
Standard floors in office buildings or broadcast buildings.
ROOM ROOM
OUTDOOR AIR PROCESSING AIR HANDLER
[Characteristics]
Since the heat medium is water, a small-sized unit can handle large loads. (it is particularly effective
for warming up north-side perimeter zones in winter.)
Water piping may damage the room due to water leakage.
9-6 AA-0019E
09. TYPES OF AIR HANDLING SYSTEMS
[Applications]
Perimeter zones of standard floors in office buildings.
Individual rooms in hotels and hospitals.
START/STOP SIGNAL
INDIVIDUAL CONTROL
ZONE CONTROL
DISPLAY
A
COMMUNICATION SETTING
TO BMA
POWER
DISTRIBUTION
PANEL
START/STOP SIGNAL
ZONE CONTROL
INDIVIDUAL CONTROL
Application
Characteristics
Individual control Zone control
Ether cooling or heating is available Individual rooms in office Standard floors in office
depending on that water delivered to buildings. buildings.
Two-pipe
the fan coil is whether chilled or hot Hotel guest rooms. Perimeter zones.
water.
When both chilled and hot water are Guest rooms in quality Standard floors in office
supplied, both cooling and heating are hotels. buildings.
available to meet any desired Perimeter zones.
Four-pipe temperature.
Compared to two-pipe systems, initial
and operating costs are large.
AA-0019E 9-7
09. TYPES OF AIR HANDLING SYSTEMS
[Characteristics]
Heat source equipment is not required.
Individual operation is available.
Fans to introduce outdoor air must be installed separately.
[Applications]
Small to mid-sized office buildings.
COMPRESSOR
INDOOR UNIT INDOOR UNIT INDOOR INDOOR INDOOR
UNIT UNIT UNIT
OUTDOOR UNIT
9-8 AA-0019E
09. TYPES OF AIR HANDLING SYSTEMS
[Characteristics]
Heat source equipment is not necessary.
Individual operation is available
[Applications]
Fire command centers in office buildings. Restaurants..
SUMMER WINTER
SUPPLY
FAN
EVAPORATOR (CONDENSER)
CONDENSER
(EVAPORATOR)
COMPRESSOR REFRIGERANT PIPING
COOLING
AA-0019E 9-9
09. TYPES OF AIR HANDLING SYSTEMS
9-10 AA-0019E
10. ONE-COIL AND TWO-COIL OF AIR HANDING UNITS
Figure 10.2 Chilled water coil and hot water coil air handling unit
AA-0019E 10-1
10. ONE-COIL AND TWO-COIL OF AIR HANDING UNITS
Table 10.1 Structures and characteristics of a chilled/hot water air handler, chilled or hot water
(steam) coil air handler
Heat source Heat source provides chilled water during Heat source system must supply both
the cooling season, hot water during chilled and hot water at the same time.
heating season.
Characteristics
Low cost due to a simple structure.
High cost
Either cooling or heating is available.
Cooling and heating are always available
Duct structure and control system must
Dehumidification control is available.
enable outdoor air cooling for the cooling (Over-cooling dehumidification and
load during the hot water period. reheat is available.)
Cautions
Direct/reverse action of a controller is When a dehumidification control program
required for switching chilled/hot water. is implemented and heating source is not
Since the control valve is sized for chilled operated, the room temperature will drop
water flow, it may result in too large size without reheat, therefore, prohibition of
for hot water flow and unstable temperature dehumidification must be implemented.
control in the heating season.
10-2 AA-0019E
11. SYSTEM SCHEMATICS
COMMUNICATION TO BMS
Sequence of operation:
FREE COOLING
MINIMUM OPENING
TEMPERATURE
HEATING FREE COOLING
SETPOINT COOLING SETPOINT
SETPOINT
AA-0019E 11-1
11. SYSTEM SCHEMATICS
humidifier valve is shut off when the discharge air temperature is below the low limit.
(Dehumidification)
A chilled water valve is proportionally controlled based on the room relative humidity and reheat is
applied based on the room temperature.
CHILLED WATER
OPENING
VALVE
CONDITION
HUMIDIFIER
HUMIDITY
HUMIDIFICATION DEHUMIDIFICATION
SETPOINT SETPOINT
4. Cool-down/warm-up control
During the startup period, outdoor and exhaust air dampers are closed and the return damper are opened
for cool-down/warm-up, and the humidifier is shut off.
5. Interlock with AHU off (Controlled objects: dampers, two-way valves, humidifier)
MD Motor damper
11-2 AA-0019E
11. SYSTEM SCHEMATICS
DIRECT DIGITAL
COMMUNICATION TO BMS CONTROLLER HUTCHED SYMBOLS REPRESENT
DEVICES INSTALLED IN THE CONTROL PANEL
AC100/AC200
RETURN DUCT
AC100/AC200
AA-0019E 11-3
11. SYSTEM SCHEMATICS
11-4 AA-0019E
12. TEMPERATURE CONTROL
OUTDOOR
AIR DAMPER
MINIMUM OPENING
(FREE COOLING NOT AVAILABLE)
ROOM TEMPERATURE
STEAM JET
HUMIDIFIER
CHILLED HOT
WATER COIL WATER COIL
ROOM
AA-0019E 12-1
12. TEMPERATURE CONTROL
varying the amount of reheat to maintain the room temperature. The temperature rise from Point 5 to
Point 7 in the supply duct can be ignored.
SPECIFIC ENTHALPY
ABSOLUTE HUMIDITY
REFERENCE POINT
SENSIBLE
HEAT FACTOR LINE
REHEAT
DRY-BULB
HEAT/MOISTURE RATIO
ABSOLUTE HUMIDITY
SATURATION CURVE
DRY-BULB
12-2 AA-0019E
12. TEMPERATURE CONTROL
VALVE OPENING
VALVE OPENING
ROOM TEMPERATURE
HEATING SETPOINT COOLING SETPOINT HEATING SETPOINT COOLING SETPOINT
AA-0019E 12-3
12. TEMPERATURE CONTROL
Control name Room temperature control Return air temperature control Discharge air temperature control
Schematics
Operates based on the signal Control is based on the signal Control is based on the signal
from the temperature sensor. from the return air from the discharge air
Action
temperature sensor. temperature sensor.
A commonly used method to Assumes the return air Applied to the primary
maintain constant room temperature represents the temperature control in
temperature. room temperature. primary/secondary temperature
Characteristics The zone in which the sensor is Installation cost is lower than control system. (The secondary
installed is controlled at a room temperature control. system is room temperature
constant temperature. control)
In a large space, a large In a large space, a large A method to reset the discharge
response time causes large response time causes a large air temperature setpoint in
overshoot at startup. overshoot at startup. response to the varying loads
The measured temperature is must be incorporated to save
Considerations
higher than the room energy.
temperature and needs
adjustment.
12-4 AA-0019E
12. TEMPERATURE CONTROL
Control name Discharge air temperature cascade control Discharge air temperature compensation control
Prevents disturbances in chilled, hot water Prevents overshoot due to response delay in air
temperature, or pressure from affecting the room handling systems for a stable control.
Objective
temperature.
ROOM
TEMPERATURE
PREDICTION
Schematic
The room temperature controller resets the Modulates the control valve based on the assumed
discharge air temperature setpoint to maintain the room temperature calculated by the discharge air
Action
room temperature. temperature and time constant of the room.
Constant temperature/humidity air handling
Large spaces
unit.
Air handling systems with possible overshoot
Air handling unit where temperature difference due to a large response delay.
Application of chilled water must be maintained.
Air handling units with high/low limits of the
discharge air temperature.
AA-0019E 12-5
12. TEMPERATURE CONTROL
12-6 AA-0019E
13. HUMIDITY CONTROL
HUMIDIFIER
HUMIDIFICATION VALVE
AA-0019E 13-1
13. HUMIDITY CONTROL
Control name Room relative humidity control Return air relative humidity control Discharge dew point control
Schematics
A common method to maintain the Assume the return air humidity represents Fast response prevents
constant room humidity. room humidity. over-humidification.
Characteristics
Installation cost is relatively low Two-position control is not
compared to room humidity control. allowed.
Commonly applied in a constant Applied to roughly control room Applied to systems that varies the
airflow system. humidity. supply airflow such as a variable
Application Applied when no place is available in the air volume air handling unit or an
room to install a sensor. outdoor air handling unit.
HUMIDIFICATION VALVE
COOLING VALVE
(DEHUMIDIFICATION)
SCHEMATIC DIAGRAM
ROOM TEMPERATURE
HEATING SETPOINT COOLING SETPOINT
Control name Outdoor air cooling Minimum outdoor air (CO2) control
When outdoor air is effective as a cooling source, When outdoor air is cooling/heating load, regulates
Purpose positively brings in outdoor air to reduce the outdoor airflow as less as possible to reduce the loads,
cooling loads. while keeping the room CO2 below the high limit.
The outdoor air duct must be sized for the design Outdoor air, exhaust air ducts are sized for the design
supply airflow. outdoor airflow.
Ducting system
When outdoor air satisfies the condition where MDs (OA, RA, EA) are controlled based on either
outdoor air can be used as cooling source (Fig. room or return air CO2.
Control strategy 14.2), MDs (OA, RA, EA) are modulated based
on either room temperature or discharge air
temperature.
HEATING VALVE
COOLING VALVE
ROOM TEMPERATURE
Figure 14.1 Outdoor damper, heating valve, cooling valve during free cooling, CO2 control
AA-0019E 14-1
14. OUTDOOR AIR CONTROL
SATURATION CURVE
ENTHALPY
ROOM RELATIVE HUMIDITY
ROOM CONDITION
ROOM ENTHALPY
CO2 (ppm)
14-2 AA-0019E
15. CONTROLS RELATED TO START/STOP OF AIR HANDLING UNITS
ROOM TEMPERATURE
CONTROL SETPOINT
OPTIMUM START
CONTROL SETPOINT
ROOM
ROOM TEMPERATURE OCCUPANCY
AA-0019E 15-1
15. CONTROLS RELATED TO START/STOP OF AIR HANDLING UNITS
COMMUNICATION LINE
TEMPERATUER HUMIDITY
CONTROL CONTROL
START/STOP
HUMIDIFICATION CHILLED
OUTPUT
OUTPUT
TEMPERATURE HUMIDITY
HOT WATER CHILLED WATER HUMIDIFCATION CHILLED WATER
VALVE OUPUT VALVE OUPUT VALVE OUTPUT VALVE OUPUT
OUTDOOR MD
OUTPUT
POWER PANEL
CHILLED WATER HOT WATER STEAM INTERLOCKED
MOTOR
MOTOR
HIMIDITY TEMPERATURE
ROOM SENSOR SENSOR
RETURN FAN
15-2 AA-0019E
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
AA-0019E 16-1
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
TO OTHER DDC
LEGEND
BUILDING MANAGEMENT
SYSTEM MEASURED SIGNAL INPUT
CONTROL SIGNAL OUPUT
CONTACT SIGNAL INPUT
CONTACT SGNAL OUTPUT
COMMUNICATION FILE
COMMUNICATION LINE
SUPPLY FAN
CONTROL CALCULATION
RETURN FAN HUMIDIFIER
AIR HANDLING UNIT
INVERTER
TEMPERATURE/HUMIDITY
MODULE
SENSOR
DAMPER
TEMPERATURE/HUMIDITY
SENSOR
CONTROL VALVE
OPERATOR TERMINAL
ENGENEER DATA TERMINAL
16-2 AA-0019E
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
Digital input/output
Analog input Analog output Latch ( Totalizer pulse
Digital input Momentary
a or b contact) input
AI SOP COPm Start/stop COPl TOT
Analog input Status point point Start/stop point Totalizer input
AOP CCPm CCPl
Alarm point Start/stop+ status Start/stop+ status
AO3 CAPm CAPl
SAP
Analog output Start/stop+ Start/stop+
Status+ alarm
Input / output M/M status+alarm status+alarm
type AO4
OOA
Analog output
On/off/auto
4-20 mA
AO5
HOL
Analog output
Hi/off/low
1-5 V, 2-10 V
[Symbols]
AI Analog Input COP Command Only Point
AO Analog Output HOL High/Off/Low
AOP Alarm Only Point OOA ON/OFF/AUTO
CAP Command with status and Alarm Point SAP Status and Alarm Point
CCP Command with status and COS Point SOP Status Only Point
COS Change Of State TOT Totalizer Input
m Momentary M/M Motor
l Latch
Re Remote
AA-0019E 16-3
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
Product
Functions Point examples
number
RY5008S 8 Contact input Motor state, alarm contact
RY5008D 8 Contact output Start/stop command output to motor
RY5004P 4 Temperature input Pt resistance input (e.g, room/discharge temperature)
RY5004A 4 Voltage/current input Humidity, pressure input
RY5003F 3 Motor output Output to Control valve, MD actuator
RY5002M 2 Voltage/current output Output to fan inverter panel
16-4 AA-0019E
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
External wiring
Field device
RESISTANCE TEMPERATURE DEVICE
OPEN
CLOSE
CONVERTER
CONTROL MOTOR
TRANSMITTER
1. Input signal: Pt 100 ohm 1. Input signal: DC 4-20 mA 1. Control output:
2. Circuit voltage, current: DC1 2. Input impedance: 300 ohm SPST+SPST
Note V, 1 mA 2. Feedback resistance:
3. Measuring range: -20-80 C, nominal 135 ohm
0-50 C
AA-0019E 16-5
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
Remote unit
(RS or DDC)
External wiring
OPERATIONAL CUICUIT
OPERATIONAL CUICUIT
panel)
1. Input contact for status acknowledge, use a contact of auxiliary relay (52X).
Note
2. For remote auxiliary relay (CX, TX) mount spark killer (e.g., diode)
16-6 AA-0019E
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
Point Display
Input/
type IPD Input/output allocation
output
range
Point name Central Signal
type output
Input1 Input2
Low/
Symbol ID Symbol ID
high Slot I/O Slot I/O Slot I/O
No. No. No. No. No. No.
1 1-1 Air handler supply
CAPm 33 Off/on 106 1 9 1 10 1 1
fan
2 Normal/a
1-1 Filter alarm AOP 22 76 1 11
larm
3 1-1 Room temperature AI 1 C 24 0.050.0 Pt100 2 1
AA-0019E 16-7
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
16-8 AA-0019E
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
DATA
ROOM TEMPERATURE X-AXIS-1 INPUT2
HOT WATER VALVE OUTPUT
DATA X-AXIS-2
ROOM TEMPERATURE SETPOINT
Y-AXIS-1
STATUS
PROPORTIONAL BAND
AIR HANDLING UNIT SUPPLY FAN Y-AXIS-2
RESET TIME (MIN)
DIRECT
RATE TIME (MIN)
OUTPUT SIGNAL MODULE
RESET VALUE (%)
HOT WATER
DEVIATION GAP VALVE
DIRECT/REVERSE SELECT
ROOM TEMPERATURE
MODULE
X-AXIS-1 INPUT2
OUTPUT SIGNAL
Y-AXIS-1
Y-AXIS-2
ROOM TEMPERATURE
MODULE
OUTPUT SIGNAL
CHILLED WATER
VALVE
ROOM TEMPERATURE
AA-0019E 16-9
16. CONFIGURATION AND CONTROL PROGRAMS OF DIRECT DIGITAL CONTROLLERS
16-10 AA-0019E
17. ELECTRIC CONTROL SYSTEMS
Figure 17.1 Electric controller schematic of constant air flow air handler
SETTING SCREW
BALANCING LEVER POTENTIOMETER
POINT
TEMPERATURE
TEMPERATURE
MICRO-SWITCH
BELLOWS
AA-0019E 17-1
17. ELECTRIC CONTROL SYSTEMS
PROPORTINAL TEMPERATURE
CONTROLLER
TEMPERATURE
RISE
BALANCING RELAY
TRANSFORMER
LIMIT LIMIT
BLUE WHITE
CONDENSER
DRIVING MOTOR
ELECTRIC ACTUATOR
(CONTROL MOTOR)
YELLOW WHITE
CLOSE OPEN
COIL COIL
RED
OPEN CLOSE
FEEDBACK POTENTIOMETER
17-2 AA-0019E
17. ELECTRIC CONTROL SYSTEMS
(thermostat) (T). The thermostat is switched between cooling and heating modes by the contact of
cooling/heating switching signal relay (X4) in the circuit . When the AHU fan is off, the interlock
contact X1 breaks and positions the control valve MV full-closed.
Circuit Humidifier Control Circuit
The humidifier is turned on or off by the room humidity controller (H). The humidifier turns on when the
contact of the relay X5 makes. (when the system shuts off outdoor air, the humidifier must be off
because humidification is not needed.)
Since the contact of the room humidity controller cannot directly turn on or off the humidifier, the signal
is amplified by the relay X2.
Circuit Cooling/Heating Changeover Circuit from the Central
The cooling/heating mode changeover command is sent from the central as momentary contacts
(CCP-mo) to relay CX and TX. When the system is switched to cooling, the contact of CX makes, then
X3 and X4 makes and self-hold. The contact of relay X4 is used to switch between cooling and heating
of the temperature controller in the circuit . When the system is switched to heating, the relay TX is
energized, the contact TX of the self-holding circuit breaks, and then X3 and X4 are de-energized.
Circuit Interlock OA Damper and Humidifier Control during the Cool-down/Warm-up Periods.
During cool-down/warm-up period after the AHU is turned on, the switch SW is switched to the timer
TLR1 to shut off the OA damper and the humidifier. When the system open the OA damper and turns on
humidifier during the cool-down/warm-up periods the switch (SW) is reversed.
Circuit Filter Clogging Alarm Circuit
A filter clogging alarm is detected based on the differential pressure across the filter. Since it may
generate false alarms, when the air handling fan is turned on or off, the alarm is generated when the
alarm remains for 30 seconds-timer.
Circuit Outdoor Air Open/Close Circuit
Opens/closes the motorized damper (MD) by the contact of the relay X5 in the circuit .
HEATING COOLING
FAN INTERLOCK
EARTH
HUMIDIFIER
COOLING/HEATING SWITCH FROM BMS
AA-0019E 17-3
17. ELECTRIC CONTROL SYSTEMS
17-4 AA-0019E
18. ELECTRONIC CONTROL SYSTEMS
Figure 18.1 Electronic controller schematic of constant air volume air handling unit
AA-0019E 18-1
18. ELECTRONIC CONTROL SYSTEMS
COMMUNICAITON I/O
REMOTE SP (RSP) INPUT EVENT (EV) OUTPUT
CONTACT
RUN READY
PID control Executea PID control PID operation is suspended. Outputs preset value for READY MODE.
Event output Enabled Enabled/disabled selectable
In a RUN mode, the controller performs PID control of control valves, etc. In a READY mode the
controller does not perform PID control, but outputs a fixed value. Usually, switching between RUN
and READY is done by an external contact input e.g., the status of fans or pumps. When PID control
operates with fans or pumps on, the integral action accumulates the manipulated signal (integral
windup), and this results in a large signal output and an unstable control when the control is
energized. Therefore, a fan or pump status signal should be input to switch RUN/READY.
18-2 AA-0019E
18. ELECTRONIC CONTROL SYSTEMS
AUTO MANUAL
RUN Outputs PID operation result. Output manually entered value via keys.
READY Outputs preset value for READY MODE.
AUTO mode outputs the results of PID calculation in the RUN mode, and a preset manipulation
value in a READY mode. In the MANUAL mode, a manual output is performed through operator
keys on the surface of the controller regardless of RUN/READY mode.
Manipulated Variables (MV)
For manipulated variable, relay contacts, current (mA), motor-drive relay contacts are available, and
they are selectable depending on input signals to actuators. Figure 18.3 illustrates the wiring of a
relay contact output to drive the control motor. This type of control motor is called an electronic
type motor (or F-motor) and its operations are as follows: When the bridge circuit of the controller
becomes unbalanced, the controller sends a contact signal to the actuator motor toward either open
or closed. The control motor feedbacks the potentiometer signal that indicates the motor rotation to
the controller. When the bridge circuit is balanced, both open and closed contact signals become
open, then the control motor stops in that position.
CONDENSER
CLOSE OPEN
COIL COIL
OPEN CLOSE
POTENTIOMETER
AA-0019E 18-3
18. ELECTRONIC CONTROL SYSTEMS
position the control valve full-closed. The cooling/heating relay X3 switches the control operations of
the temperature controller (TIC); on a rise in temperature, the controller opens the control valve in the
cooling mode, closes the control valve in the heating mode.
FAN INTERLOCK
HUMIDIFIER
COOLING/HEATING SWITCH FROM BMS
18-4 AA-0019E
19. VARIABLE AIR VOLUME AIR HANDLING UNIT CONTROL SYSTEMS
10 SETS
COMMUNICATION
TO BMS
AA-0019E 19-1
19. VARIABLE AIR VOLUME AIR HANDLING UNIT CONTROL SYSTEMS
VELOCITY
SENSOR ROOM
VAV CONTROLLER
BMS
DEW POINT
SENSOR
TEMPERATURE
SENSOR
AIR HANDLER
TEMPERATURE SENSOR
19-2 AA-0019E
20. TEMPERATURE/HUMIDITY CONTROL FOR VAV-AHUS
HEATING COOLING
ROOM
HEATING SP COOLING SP TEMPERATURE
ROOM TEMPERATURE SP
MINIMUM POSITION
(FREE COOLING NOT AVAILABLE)
DISCHAGE TEMPERATURE
AA-0019E 20-1
20. TEMPERATURE/HUMIDITY CONTROL FOR VAV-AHUS
ROOM TEMPERATURE
20-2 AA-0019E
20. TEMPERATURE/HUMIDITY CONTROL FOR VAV-AHUS
AIR VOLUME
HEATING COOLING
HEATING SP COOLING SP
ROOM TEMPERATURE
BMS
DEW POINT
SENSOR
TEMPERATURE
SENSOR
AIR HANDLER
TEMPERATURE SENSOR
AA-0019E 20-3
20. TEMPERATURE/HUMIDITY CONTROL FOR VAV-AHUS
20-4 AA-0019E
21.FAN SPEED CONTROL OF VAV AHUS
If there are no dampers full-open (100%), the controller determines that duct pressure can be reduced, then
reduces the fan speed as low as possible while satisfying the load and thus provides a large fan power
reduction. The execution interval is one minute.
BMS
DEW POINT
SENSOR
TEMPERATURE
SENSOR
AIR HANDLER
TEMPERATURE SENSOR
AA-0019E 21-1
21. FAN SPEED CONTROL OF VAV AHUS
POWER POWER
AHU
CONTROL COMMUNICAITON LINE
COMMUNICAITON LINE
PANEL (DDC)
POWER POWER
VELOSITY SENSOR
VAV UNIT
TEMPERATURE TEMPERATURE
SENSOR SP
21-2 AA-0019E
22. CONFIGURATION OF HEAT SOURCE SYSTEMS
COOLING TOWER
AIR HANDLER
CONDENSER WATER
TEMPERATURE CONTROL
SUPPLY WATER
PRESSURE CONTROL
SECONDARY TEMPERATURE
PUMP SENSOR
(CHILLED/HOT
FLOW METER
WATER PUMP)
BYPASS PIPING
SUPPLY RETUREN
HEADER HEADER
CHILLED/HOT WATER
GENERATOR
PRIMARY PUMP
(CHILLED/HOT WATER PUMP)
CONDENSER WATER PUMP
AA-0019E 22-1
22. CONFIGURATION OF HEAT SOURCE SYSTEMS
3 CHILLERS
FLOW
HEAT
2 CHILLERS
HEAT
FLOW
1 CHILLER 1 CHILLER
TIME
Figure 22.6 Air handling load pattern in a day and the number of operating chillers
22-2 AA-0019E
23. TYPES AND CHARACTERISTICS OF SOURCE EQUIPMENT
Fuel or power
Heat medium Heat source Principle/type Type
source
Combustion Oil, gas Once-through, fire-tube,
Steam Steam boiler
water-tube boilers
Hot water Hot water boiler Combustion Oil, gas, electric Vacuum, no-pressure
Reciprocating Chiller
Compression chiller Centrifugal Electric Turbo chiller
Chilled water
Rotary Screw chiller
Absorption chiller Absorption Oil, gas, steam
Reciprocating Air sourced heat pump
Compression heat pump Centrifugal Electric Double-bundle turbo chiller
Chilled/hot water Rotary Screw heat pump
Absorption
Hot/chilled water generator Oil, gas
Combustion
1. Steam Boilers
Steam boilers are classified into once-through, fire tube (flue and smoke tube) and water tube boilers.
Table 23.2 shows the types and characteristics of steam boilers. In office buildings, chilled/hot water
generators or hot water boilers are commonly used and steam boilers are rare. In hospitals or hotels
where large heating loads such as hot water supply exist, once-through or fire tube boilers are commonly
used. Today, modular once-through boilers with 1 to 2 ton/hour of steam capacity (with a maximum
operation pressure of less than 1.0 Mpa, and a heat transfer area of below 10 m2) are increasing.
Advantages of modular once-through boilers are good performance at partial loads and a quick response
to varying load. Small modular once-through boiler usually are equipped with built-in control
mechanism for steam pressure control and staging control. Steam generated by a boiler is de-pressured
to about 0.2 Mpa, and distributed to AHU steam coils in AHU or fan coil units for heating or
steam-to-hot water converters for hot water supply.
AA-0019E 23-1
23. TYPES AND CHARACTERISTICS OF SOURCE EQUIPMENT
MAIN COMBUSTION
Principle SUPPLY WATER
CHAMBER
PUMP
WATER
HEATING FIRE TUBE FLUE
WATER DRUM
Water within a water pipe in the Cylindrical fire tubes and smoke tubes are Consists of a brackish drum at the
boiler is heated and evaporated. within the boiler vessel. Burns the fuel top and a water drum at the
Does not have a boiler vessel or within the fire tube to heat and evaporate bottom and water tubes
Structure drum. the water within the vessel. connecting them.
Burn the fuel around the water
tubes and evaporate water in the
brackish drum.
Small amount of holding water With a large amount of holding water, this A small amount of held water
provides fast startup. type of boiler covers a wide range of load provides fast startup. High-level
Suites for small capacity. changes. control such as water-level
Performance Pressure is below 1 Mpa. Suites for middle to large capacity. control is required.
Pressure is below 1 Mpa. Suites for high pressure, large
capacity applications.
Used in small to mid-sized Used to steam supply in mid-sized to large Used for steam supply or steam
buildings. buildings and DHCs. turbine turbo chillers in large
Application
DHCs.
3. Compression Chillers
Figure 23.1 shows the principle of compression chillers. The refrigerant gas is cooled by the condenser
water at the condenser and condenses to be mid-temperature, high-pressure refrigerant liquid. The
refrigerant liquid expands when it flows through the expansion valve and the evaporator produces chilled
water by vaporization heat. Compression chillers are classified by the type of compressor into centrifugal
(turbo), reciprocating, or screw chillers. Also, they are classified by the cooling method at the condenser
into water-cooled, or air-cooled. Table 23.2 illustrates the principle and characteristics of each type of
23-2 AA-0019E
23. TYPES AND CHARACTERISTICS OF SOURCE EQUIPMENT
chiller. Centrifugal and screw type chillers have almost similar capacity characteristics. In reciprocating
chillers with multiple step compressor control, which is commonly used, the chilled water temperature
varies drastically, therefore, care must be taken when precise temperature control is required for
applications such as constant temperature/humidity rooms or clean rooms. Also, when a system includes
multiple types of chiller, the startup curve depends on the type, therefore, care must be taken for control
parameters such as start/stop intervals.
COMPRESS
REFRIGERANT
COMPRESSOR GAS
CONDENSER
WATER OUTLET CHILLED WATER
INLET
REFRIGERANT
CONDENSER EVAPORATES AND
RAPIDLY EXPAND DEPRIVES HEAT
REFRIGERANT FROM WATER
CONDENSES AND GAS
COOLS EVAPORATOR
REFRIGERANT GAS EXPANSION VALVE
LOW TEMPERATURE
/LOW PRESSURE LIQUID
Capacity
Capacity Capacity control Start-up
Type Name Principle control range COP
(kW)) (URT) method time
(%)
The refrigerant is compressed, 352 7040 Suction vane 30-100 3-18 5 min
condensed, and evaporated. Chilled (100-2000) control by the
Turbo chiller
water is produced by evaporating centrifugal
refrigerant. compressor
Vapor-compr Uses a reciprocating compressor. 17- 352 Based on Depends on 3-4 5 min
ession Reciprocating (2-100) compressor step the steps of
chiller control, or compressor,
un-loader control. or unloader
Uses screw type compressor. 106- 1760 By sliding vane. 20-100 3-6 5 min
Screw chiller
(30-50)
Lithium-bromide solution absorbs the 176- 7040 Controls heat 20-100 1-1.6 30 min
Absorption chiller water vapor within the vacuum (50-2000) source (gas,
Absorption Chilled/hot water vessel. steam, oil) by a
generator Chilled water is produced by control valve
evaporating water.
AA-0019E 23-3
23. TYPES AND CHARACTERISTICS OF SOURCE EQUIPMENT
4. Absorption Chillers
Figure 23.2 illustrates the principle of an absorption chiller. Absorption chillers use water as refrigerant,
and lithium bromide (LiBr) as absorbent, and consists of an evaporator, an absorber, a generator, and a
condenser. Functions of each component are as follows:
In the evaporator, the refrigerant water evaporates in the vessel that is kept vacuum, and the chilled
water is cooled by vaporization heat.
In the absorber, the dense lithium bromide solution absorbs water vapor that evaporated in the
evaporator and becomes the week absorbent solution.
The generator applies heat to the week absorbent solution pumped by the solution pump with heat of
either steam, gas, or oil combustion to evaporate water in the solution and make dense solution, then the
dense solution is sent to the absorber through the heat converter. Water vapor is sent to the condenser.
Condenser cools the water vapor then the condensed water is distributed to the evaporator.
Thus, the absorption chiller produces chilled water by changing the phase of the refrigerant (water). It
takes about 30 minutes after startup of the chiller for the chilled water to reach the design temperature.
WATER VAPOR
GENERATOR CONDENSER
LITHIUM BROMIDE
SOLUTION CONDENSER WATER
OUTLET
WEAK
ABSOBENT
CONDENSER WATER
WATER VAPOR
(HEAT SOURCE)
REFRIGERANT
HEAT WATER VAPOR (WATER)
STRONG ABSORBENT
EXCHANGER
REFRIGERANT
ABSORBER (WATER) EVAPORATOR
STRONG
ABSORBENT
WEAK CHILLED WATER
ABSOBENT OUTLET
23-4 AA-0019E
23. TYPES AND CHARACTERISTICS OF SOURCE EQUIPMENT
produces only chilled water as a turbo chiller, and the condensed heat is dissipated at the cooling tower.
When hot water is needed in winter, it produces hot water in the condenser.
AA-0019E 23-5
23. TYPES AND CHARACTERISTICS OF SOURCE EQUIPMENT
verified by the chiller manufacture when operating the chiller at the condenser water temperature below
the design temperature.
FAN
FAN SPRAY WATER TANK
CONDENSER
ELIMINATOR WATER INLET
WATER SPRAY ELIMINATOR
CONDENSER
WATER INLET OUTDOOR WATER WATER OUTDOOR
AIR AIR
WATER REPLENISH FILLING
FILLING WATER
CONDENSER
TANK WATER OUTLET
OUTDOOR AIR OUTDOOR AIR
OUTDOOR AIR
REPLENISH WATER
CONDENSER PARALELL FLOW COOLING TOWER
WATER OUTLET
TANK
FAN
ELIMINATOR
SPRAY WATER
CONDENSER
WATER INLET
CONDENSER
WATER OUTLET
OUTDOOR HEAT EXCHANGER
OUTDOOR AIR
AIR REPLENISH
SPRAY WATER WATER
PUMP
TANK
23-6 AA-0019E
24. CHILLED/HOT WATER PIPING AND HEAT SOURCE SYSTEMS
EXPANSION EXPANSION
TANK TANK
AIR HANDLER
AIR HANDLER
SECONDARY
SYSTEM
PRIMARY PUMP
CHILLER CHILLER PRIMARY PUMP
AA-0019E 24-1
24. CHILLED/HOT WATER PIPING AND HEAT SOURCE SYSTEMS
HEAT EXCHANGER
HEAT PUMP PRIMARY PUMP
SECONDARY
PUMP BRINE PUMP CHILLER
CHILLED WATER
PUMP
Figure 24.2 Water storage tank system Figure 24.3 Static ice storage tank system
Table 24.3 Characteristics of open piping system, water storage, ice storage systems
24-2 AA-0019E
25. PUMPS AND PIPING SYSTEMS
RESISTANCE CURVE
(SQUARE VURVE)
RESISTANCE
PUMP
FLOW
Figure 25.1 Relationship between flow and resistance in water distribution system
RESISTANCE INCREASES
AS VALVE IS REGULATED
RESISTANCE
FLOW
AA-0019E Figure 25.2 Resistance curve change when control valve is regulated 25-1
25. PUMPS AND PIPING SYSTEMS
CONTROL VALVE
PRESSURE METER FLOW METER POSITION SETTER
FLOW
POWER CURVE
POWER
POWER PANEL
POWER METER
FLOW
Figure 25.3 Example of pump head/power curve Figure 25.4 How to obtain head curve and power curve
CONTROL VALVE
CURVE
AIR HANDLER COIL
PUMP
25-2 AA-0019E
25. PUMPS AND PIPING SYSTEMS
PUMP
From above relationships, the pump power varies with the flow multiplied by the head. Therefore, in
flow control by the pump speed, a method that reduces both flow (Q) and head (H) provides a large
pump power savings. The Q-H curve for reduced pump speed can be determined by measuring flow and
pressure at pump speeds of 60% and 80% the same way as determining the Q-H curve of a constant
speed pump in Section 25.3.
CONTROL VALVE
RESISTANCE
FLOW DECREASES
CURVE
PUMP
FLOW
AA-0019E 25-3
25. PUMPS AND PIPING SYSTEMS
25-4 AA-0019E
26. PRESSURE CHARTS FOR PIPING SYSTEMS
(1) Determine the pressure losses of pipes and components, the pump head, the heights of air handling
units and a expansion tank from the central plant room. If the piping losses are unknown, estimate 3
to 5 mH per 100 m for piping losses.
(2) The height from the central plant (base point) is on the Y-axis and pressure (kPa) on the X-axis. The
Y-axis also represents a head, therefore if the both axis are the same scale (1m = 10 Mpa), it is
helpful to read the pressure chart.
(3) Find a point (base point) where the pressure is constant regardless of varying flow in the piping
system. In Figure 26.1, the point where the expansion tanks is piped to the return header is the base
point. The water surface of the expansion tank is 40 m above the header (), therefore, the pressure
at Point is 400 kPa. Draw a dotted line from the location at 40 m to 400 kPa ().
(4) Draw the line starting from the base point, add piping heads to or subtract piping losses from the
existing pressure. When the line returns to the base point, a pressure chart has completed.
(5) The drawn pressure chart is for the design flow. Draw dotted lines for no flow (when control valves
in all of the AHUs are full closed). Figure 26.2 shows the pressure chart of the primary-only system
in Figure 26.1.
PIPING RESISTANCE
CHILLER RESISTANCE
AA-0019E 26-1
26. PRESSURE CHARTS FOR PIPING SYSTEMS
26-2 AA-0019E
27. CONTROLS FOR CLOSED HEAT SOURCE SYSTEMS
AIR HANDLER
COMMUNICATION TO BMS
CONTROL MENU
CHILLER GROUP
CAPACITY CONTROL
HEADER DIFFERENTIAL
PRESSURE CONTROL
COMMUNICATION TO BMS
MEASUREMENT (START/STOP, MONITORING,
SETTING, MEASUREMENT)
CHILLER
Figure 27.1 System schematic and control menus of closed primary-only pumping system
AA-0019E 27-1
27. CONTROLS FOR CLOSED HEAT SOURCE SYSTEMS
AIR HANDLER
CONTROL MENU
CHILLER CONTROL
SECONDARY PUMP GROUP
CAPACITY CONTROL
SECONDARY PUMP SUPPLY WATER
PRESSURE CONTROL
COMMUNICATION TO BMS
(START/STOP, MONITORING,
SETTING, MEASUREMENT)
MEASUREMENT SYMBOL NAME
CHILLER CHILLER CONTROLLER
PUMP CONTROLLER
MEASUREMENT
PIPE INSERTION TYPE TEMPERATURE SENSOR
CHILLER FLOW METER
Figure 27.2 System schematic and control menus of closed primary-secondary pumping
t
27-2 AA-0019E
27. CONTROLS FOR CLOSED HEAT SOURCE SYSTEMS
Table 27.1 Heating/cooling source types and group capacity control criteria
Heat source type Heat source equipment Process variable for sequence control
Chiller, chilled/hot water Performs sequence control based on load flow.
generator Add a chiller based on supply temperature high
Primary-only systems limit.(*1)
Drops a chiller based on return temperature (chiller
entering temperature) low limit.(*2)
Chiller, chilled/hot water Performs sequence control based on load heat.(*3)
generator Add a chiller based on the supply temperature high
Primary-secondary system limit.
Drops a chiller based on the return temperature (chiller
entering temperature).(*2)
Secondary pump Performs sequence control based on load flow.
*1: The control based on load heat causes insufficient number of operating chillers when the temperature
difference in the secondary system is small, and it causes the primary pumps operating with chillers
to be over-loaded.
*2: Chiller capacity varies due to changes in condenser water temperature or degradation of capacity
over time. Also, the temperature difference in an air handling unit coils is small with large water
flow and it is large with small water flow. From this reason, control based on either load flow or load
heat causes insufficient or excessive operation of chillers. Therefore, when the supply water
temperature is above the setpoint, the controller adds a chiller, and when return water temperature
(chiller entering water temperature) is below the setpoint, drop a chiller before the built-in controller
stops the chiller.
*3: Since the primary role of chillers is to provide heat corresponding to the load, the number of
operating chillers is determined by load heat (the amount of water flow to satisfy the load flow is
supplied by secondary pumps).
OPERATING CHILLERS
AA-0019E 27-3
27. CONTROLS FOR CLOSED HEAT SOURCE SYSTEMS
3. Chillers Group-Stop
The building management system issues a group-stop command to the chiller controller, then the
chiller controller routes the stop-command to the chiller operation panel based on the
predetermined chiller operation priority. The chiller operation panel stops the chiller then after a
preset time period, stops chilled water pumps and condenser water pumps.
4. Interlock Circuit
The chiller operation panel usually contains built-in circuits for an interlock with chilled water
pumps and condenser pumps, and off-timer circuits. If they are not contained, it is required to
determine these circuits are included in either electrical or in automation scope in the project.
POWER LINE
CHILLED/HOT WATER GENERATOR
SIGNAL LINE
CHILLED/HOT WATER GENERATOR PANEL
START/STOP SIGNAL
TO BMS
CHILLER CONROLLER
RUN/TROUBLE SIGNAL
CHILLED WATER PUMP
START/STOP COMMAND
CHILLED WATER PUMP
STATE SIGNAL CHILLED WATER PUMP
CONDENSER WATER PUMP
START/STOP COMAND
POWER PANEL
27-4 AA-0019E
28. SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL
AA-0019E 28-1
28. SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL
Pressure detecting
Control method Supply water pressure setting Control name
point
Bypass valve Constant pressure Constant pressure control by bypass valve.
control
Constant pressure Constant pressure control by speed control.
Variable pressure based on the Variable discharge pressure control based on load
Pump discharge load flow flow (Assumed-end-pressure control).
Pump speed
pressure Variable pressure based on the Variable discharge pressure control based on end
control (+ bypass
end pressure differential pressure (End-differential pressure
valve control)
control).
Variable pressure by Variable discharge water pressure control by
coordination with DDC coordinated DDCs (DDC-Coordinated-control).
OPERATING POINT
BYPASS FLOW
HEAD
POWER
PRESSURE
FLOW
28-2 AA-0019E
28. SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL
control measures the pressure at the immediate outlet of the pump (header pressure) to maintain
discharge pressure, but does not reduce the pump head at light loads, and does not save pump power
significantly.
OPERATING POINT
OPERATING POINT
HEAD
( LOW SPEED LIMIT )
(SPEED)
POWER
INVERTER
OUTPUT
BYPASS VALVE
FLOW
PRESSURE
PUMP OUTPUT
PRESSURE SP (SPPED)
PRESSURE TRANSMITTER
HEAD
FLOW
FLOW METER
(SPPED)
INVERTER
OUTPUT
BYPASS VALVE
PRESSURE FLOW
AA-0019E 28-3
28. SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL
HEAD (SPPED)
COMM.LINE
PRESSURE TRANSMITTER
SETPOINT FLOW
CHANGE
(SPPED)
POWER
INVERTER
OUTPUT
BYPASS VALVE
FLOW
PRESSURE
Figure 28.4 Discharge water pressure variable control by end differential pressure (End
differential pressure control)
28-4 AA-0019E
28. SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL
BMS
PROGRAM
AHU
COMMUNICATION LINE
NOMINAL OPERATING POINT
HEAD
AHU
(SPEED)
PRESSURE
TRANSMITTER
FLOW
SETPOINT
CHANGE (SPEED)
POWER
INVERTER BYPASS
OUTPUT
VALVE
FLOW
PRESSURE
Figure 28.5 Discharge water pressure variable control by DDC (DDC coordinated control)
PIPING RESISTANCE
FLEXIBLE JOINT
1 CHILLER 2 CHILLERS
FLOW DISTRIBUTION SYSTEM
CONSTANT/VARIABLE PUMPS
IN PARALLEL OPERATION
Figure 28.6 Parallel operation of constant speed pump and variable speed pump
AA-0019E 28-5
28. SECONDARY PUMP DISCHARGE WATER PRESSURE CONTROL
28-6 AA-0019E
29. CONTROL OF COOLING TOWERS
CONDENSATION
EXPANSION
N
IO
SS
RE
MP
CO
EVAPORATION WORK BY
COMPRESSOR
RIGREGERATION AMOUNT
ENTHALPY
AA-0019E 29-1
29. CONTROL OF COOLING TOWERS
CONTROL MENUS
SYMBOL NAME
TEMP/HUMI CONTROLLER/INDICATOR
PYPE INSERTION TYPE TEMP.SENSOR
PYPE INSERTION TYPE THERMOSTAT
ELECTRIC THREE-WAY VALVE
MEASURE MEASURE LEVEL SWITCH
ELECTRIC TWO-WAY BALL VALVE
CONDENSER WATER BLOW CONTROLLER
ELECTRIC HEATER
THREE-WAY VALVE
FAN
3. Anti-Freeze Control
An electric heater is turned on or off based on the water temperature in the cooling tower to
prevent water from freezing-up in winter. (If the cooling tower does not operate in winter,
freeze-up prevention and heating with no-flow prevention controls are not required.)
4. Heating with No-Water Prevention Control
When the anti-freeze control turns on an electric heater, the control must be interlocked by a
level switch to avoid heating with no water.
29-2 AA-0019E
29. CONTROL OF COOLING TOWERS
CONDUCTANCE
AA-0019E 29-3
29. CONTROL OF COOLING TOWERS
29-4 AA-0019E
30. HEAT EXCHANGER CONTROL
[Controls]:
1. The electric two-way valve is controlled to maintain the supply water temperature.
2. The electric two-way valve is shut off when the chilled water pump is off.
[Notes]
The primary chilled water must return with a design temperature difference, therefore when the
secondary return temperature is low resulting low primary return temperature, a cascade control is
applied to raise the heat converter leaving temperature.
CASCADE CONTROL
MEASURE
PRIMARY CHILLED
SYMBOL NAME
SECONDARY CHILLED
WATER SUPPLY WATER SUPPLY
TEMP CONTROLLER/INDICATOR
AA-0019E 30-1
30. HEAT EXCHANGER CONTROL
[Controls]
1. The electric two-way valve is controlled to maintain the hot water temperature.
2. The electric two-way valve is shut off when the hot water pump is off.
[Notes]
1. Use single-seated valves or rotary valves with low leakage.
2. As a measure for overheat protection on loss of power, use an electric two-way valve with spring
return or shut-off capability. (Ordinary control valves maintain the existing position on loss of
power, and do not become full closed, resulting overheating of hot water.)
MEASURE
SYMBOL NAME
TEMPERATURE INDICATION
TIC CONTROLLER
OVERHEAT PROTECTION TEW PIPE INSERTION
SHUT OFF VALVE TEMPERATURE SENSOR
R RELAY
30-2 AA-0019E
31. SELECTING CONTROL VALVES FOR HEAT SOURCE SYSTEMS
CHILLER
CHILLER
CHILLER
CHILLER
[Notes]
1. The differential pressure (P) is the primary-pump head minus the pressure loss of chillers and
piping related to chillers. An accurate P is obtained by drawing a pressure chart, but a half of
the primary-pump head can be used as an approximate value.
AA-0019E 31-1
31. SELECTING CONTROL VALVES FOR HEAT SOURCE SYSTEMS
[Notes]
1. TheP must be equal to the secondary-pump head.
2. The Cv calculation equation is the same as in Section 32.1.
3. Other control valve specification is as follows;
31-2 AA-0019E
31. SELECTING CONTROL VALVES FOR HEAT SOURCE SYSTEMS
[Notes]
1. The P is equal to the secondary-pump head.
2. For Cv calculation the same equation as Section 31.1 is used.
3. Bypass valve flow is about 10% of the pump nominal flow.
4. Other control valves specification is as follows:
Control valve
Item Selection
specification
If height from heating/cooling source plant to expansion tank
The highest operating pressure 2.0 MPa + secondary pump head (water head) is less than 200 m, it is
usable.
Operating differential pressure, Since secondary pump head is 300 kPa, 1Mpa is enough.
permitted differential pressure at 0-1.0 MPa
close-off.
Minimum flow bypass valve is modulated by two-position
Control signal Two-positioned
control.
AA-0019E
31-3
31. SELECTING CONTROL VALVES FOR HEAT SOURCE SYSTEMS
CHILLER
CONDENSER
WATER PUMP
[Notes]
1. 20kPa of P is used for Cv calculation. (a too high P results in too small control valve
size, and decreased condenser water.)
2. For Cv calculation, the same equation as in Section 31.1, is used.
3. Other control valve specification is as follows;
31-4
AA-0019E
32. SELECTING PRESSURE TRANSMITTERS AND FLOW METERS
PRESSURE TRANSMITTER
RANGE SELECTION
CHILLER
CHILLER
AA-0019E 32-1
32. SELECTING PRESSURE TRANSMITTERS AND FLOW METERS
PRESSURE
q (m3/s) = A x V
3 D 2
Q (m /h) = x V x 3600
4
Since V = 3 (m/s), Q = 450 (m3/h),
32-2 AA-0019E
32. SELECTING PRESSURE TRANSMITTERS AND FLOW METERS
D = 0.230 m
4. Two sizes are obtained; 200 A and 250 A in the neighborhood of 230mm size. Select 200A.
Note that with 200A size, the flow velocity is faster than 3 m/s at the maximum flow.
5. Select the flow meter with a flow velocity of 3 to 5 m/s at the design flow. Too fast flow velocity
may result in selecting an electromagnetic flow meter with a considerably smaller diameter compared
to the mounting pipe size, and it may cause the following troubles.
A) Too high flow velocity through the electromagnetic flow meter accelerates erosion of linings.
B) Increased pressure loss.
C) Smaller flow meter causes less mechanical strength for the given pipe size.
D) Reducers with considerably different sizes at both ends are required up- and downstream from the
flow meter.
AA-0019E 32-3
32. SELECTING PRESSURE TRANSMITTERS AND FLOW METERS
32-4 AA-0019E
33. CHILLER CONTROLLERS
Name/product
Primary application Equipment and application Optional functions
number
Primary-only pumping system Header differential pressure
Chiller controller Chiller group capacity
control
(WY2001Q) control
Primary-secondary pumping system
OPERATOR INTERFACE
AA-0019E 33-1
33. CHILLER CONTROLLERS
NUMBER OF
OPERATING CHILLERS
CHILLER
2
CHILLER
1
CHILLER
LOAD FLOW
CHILLER
PRIMARY-ONLY PUMPING SYSTEM STAGING CONTROL CHILLER GROUP CAPACITY CONTROL (FLOW BASED)
NUMBER OF
OPERATING CHILLERS
3
CHILLER
2
CHILLER
1
CHILLER
LOAD HEAT
CHILLER
33-2 AA-0019E
33. CHILLER CONTROLLERS
(3) Adjusting the number of operating chillers based on the supply water temperature
If the supply water temperature of the chiller is above the setpoint for a set time period, the controller
adds one chiller.
(4) Adjusting the number of operating chillers based on the return temperature (forced stop)
If the return water temperature is below the setpoint (in the cooling mode), and for a set time period the
chiller is stopped by a built-in thermostat and the controller judges it as a trouble. The controller drops a
chiller before the built-in thermostat is activated.
No.2 CHILLER
AA-0019E 33-3
33. CHILLER CONTROLLERS
STOP CHILLER
No.2 CHILLER
(6) Restart-Prevention
1. Restart prevention when a chiller starts
The controller excludes the chiller started by the staging control from chillers to be restarted for a
set time period to protect the chiller. During the restart-prevention periods, the chiller cannot be
restarted, therefore, when addition of the chiller is requested, the controller starts an alternative
chiller with the next higher priority. The purpose of restart-prevention is to prevent overheat due to
the startup current in drive motor of compression chiller.
No.2 CHILLER
RESTART PROHIBIT
No.2 CHILLER
33-4 AA-0019E
33. CHILLER CONTROLLERS
No.1 CHILLER
START-UP RESTART PROHIBIT
START-UP
No.2 CHILLER
No.3 CHILLER
LOAD PATTERN
TIME
( SEQUENTIAL) ( ROTATE)
START ORDER START ORDER
STOP ODER STOP ORDER
AA-0019E 33-5
33. CHILLER CONTROLLERS
CAPACITY
Level (352kW) (704kW) (1408kW)
Level 1
Level 2
Level 3
Level 4
Level 5
Level 6 LOAD
Level 7
PROGRAMMABLE START/STOP ORDER
33-6 AA-0019E
33. CHILLER CONTROLLERS
VALVE POSITION
DEFF PRESSURE
SP
ADD REQUEST
ADD PREDICTION
No.2 START
No.1 CHILLLER
ADD PREDICT
No.2 CHILLLER
BYPASS VALVE
BYPASS VALVE
POSITION
Figure 33.8 Bypass valve open FULL OPEN
at addition
AA-0019E 33-7
33. CHILLER CONTROLLERS
33-8 AA-0019E
34. PUMP CONTROLLERS
Name/product
Primary application Equipment and application Optional functions
number
Constant speed pump + bypass Discharge water pressure control (bypass
Pump valve valve control)
controller Pump staging control Variable speed control + bypass Discharge water pressure control
(WY2001P) valve (Variable water control + bypass valve
control)
NUMBER OF
PUMPS
4 CHILLERS
3 CHILLERS
2 CHILLERS
1 CHILLER
FLOW
PUMP SYSTEM
AA-0019E 34-1
34. PUMP CONTROLLERS
START PUMP
STARTUP PERIOD
No.2 PUMP
No.3 PUMP
ALTERNATIVE PUMP
34-2 AA-0019E
34. PUMP CONTROLLERS
3. VFD (PI) control-plus-bypass-valve (on/off)-control (When all pumps are equipped with VFDs.)
The pump speed is controlled to maintain the pump discharge pressure. The bypass valve opens to
maintain the minimum flow when the load flow is below the low limit. (Fig. 34.5)
OUTPUT
VALVE POSITION
BYPASS VALVE
INVERTER
INVERTER OUTPUT
LOW LIMIT
SP OUTPUT PRESSURE
OUTPUT PRESSURE
PRESSURE SP
Figure 34.3 Bypass valve control (PI)
Figure 34.4 VFD control (PI)+ bypass valve control (PI)
OUTPUT
LOAD FLOW
FLOW SP
OUTPUT PRESSURE
PRESSURE SP
LOAD FLOW
AA-0019E 34-3
34. PUMP CONTROLLERS
34-4 AA-0019E
35. AN OVERVIEW OF BUILDING MANAGEMENT SYSTEMS
By positively adopting IT technologies (e.g., personal computers, the Internet), the BMS has
increased the point capacity and furnished more advanced functionality with an improved
cost/performance ratio.
Today it is common knowledge that BMS functions to collect, store, analyze building data are
essential to solve energy saving issues. Therefore. the BMS is used as an energy management
system as well as a monitoring system. A BMS with energy management features is referred to as
a building and energy management system (BEMS).
To manage the building from a single window for efficient operation, individual systems (e.g.,
HVAC, electric, lighting, fire alarm) have become integrated through a communication network.
The standardization of building management system is accelerated in areas such as hardware
configuration, functionality, or communication protocols.
AA-0019E 35-1
35. AN OVERVIEW OF BUILDING MANAGEMENT SYSTEMS
35-2 AA-0019E
36. SYSTEM CONFIGURATION
AA-0019E 36-1
36. SYSTEM CONFIGURATION
36.3 BACnet
36.3.1 History of BACnet
In the past, building owners strongly desired to manage, monitor, and control various building equipment
(e.g., HVAC, electric, fire alarm, lighting, elevator) from a single monitoring terminal. The system
integration was achieved through a interfaces that venders agreed and developed, however, it did not
satisfy building owners need in both costs and functionality. Therefore, it was proposed to develop a
single communication protocol. The American Society of Heating and Refrigerating and
Air-conditioning Engineers, Inc. (ASHRAE) established a standard committee participated by end users,
manufacturers, universities, governmental organizations to develop a common protocol. BACnet, A Data
Communication Protocol for Building Automation and Control Network was developed as a
ANSI/ASHRAE standard 135 in 1995, and was standardized as ISO 16484-5 in 2003, and was revised as
ANSI/ASHRAE Standard in 2004. For IP network, it was standardized as BACnet/IP.
SERVICE
TCP/IP BACnet
OBJECT
PROPERTY
IF ROOM TEMP
(1) Device
B-OWS (BACnet Operator Workstation)
A B_OWS allows the building operator to monitor, issue start/stop commands, and reset
parameters of building equipment. Also it monitors operating statuses of devices in the network
and controls the device status of entry to and detachment from the system.
B-BC (BACnet Building Controller)
A B_BC individually monitors, and transmits operating status of building equipment to the
network.
36-2 A-0019E
36. SYSTEM CONFIGURATION
(3) Service
Services are operations to objects. Examples of services are as follow;
1. Alarm monitoring
When an alarm occurs, a B-BC transmits an Unconfirmed Event Notification service to a Binary
Input Object.
2. Start/stop
To transmit a start/stop command, the B-OWS transmits a Write Property Service to a Binary
Output Object in a B-BC. To confirm a status changes caused by a start/stop command, the B-BC
transmits an Unconfirmed COV Notification service.
3. Reading a measured value.
The B-OWS sends a Read Property Multiple Service to the Analog Input Object in the B-BC.
Table 36.2 and 36.3 list standard BACnet objects defined by ANSI/ASHRAE 135-2004.
AA-0019E 36-3
36. SYSTEM CONFIGURATION
8 Read Range
9 Write Property
36-4 A-0019E
36. SYSTEM CONFIGURATION
GRAPHIC PANEL
MONITORING PC
ANNUCIATOR
AHU/GENERAL I/O
CHILLER/
POWER
PUMP
DISTRIBUTION
AHU/
GENERAL I/O
LIGHTING
MONITORING PC
SYSTEM DATA
TOTAL
MANAGEMENT MANAGEMENT
MANAGEMENT
SERVER SERVER
VETICAL DISTRIBUTION
INDIVIDUAL
MANAGEMENT
HORIZONTAL DISTRIBUTION
AA-0019E 36-5
36. SYSTEM CONFIGURATION
(2) Networks
The system uses Ethernet the same way as a LAN in offices. LAN cables (100 BASE-TX) or optical
fiber cables (100BASE-FX) are used for wiring. The protocol is TCP/IP. Upon a request from the
monitoring PC, each device transmits data using web services. Therefore, the monitoring PC needs
just a web browser for operation. Also the system supports BACnet/IP to interface with other
systems on the Internet.
Reference:
ANSI/ASHRAE Standard 135-2004 BACnet A Data Communication Protocol for Building
Automation and Control Networks.
Windows, Internet Explorer are trademarks of Microsoft Corporation.
BACnet is a trademarks of ASHRAE.
savic-net, Infilex are trademark of Yamatake Corporation.
36-6 A-0019E
37. SYSTEM FUNCTIONS
AA-0019E 37-1
37. SYSTEM FUNCTIONS
Start/stop and status monitoring Starts/stops building equipment and monitors status of building equipment from the
monitoring terminal.
Integrated Control parameter reset Reset control parameters from the monitoring terminal.
management level Energy data management Collects, stores, edits energy data and generates related reports.
Alarm/status change data Collects, stores, edits alarm/status data and makes reports.
management
Power demand control Anticipates power consumption during the demand interval, compares it to a limit
and then adds or sheds registered loads. Thus reduces the contract power and
prevents penalty charges or increased contract power.
Time schedule Automatically turns equipment on or off based on predetermined date, day of the
week, or time of the day.
Power failure control Upon detecting power-failure, suppresses alarms that indicate start/stop commands
System
and actual status do not match due to power-failure.
management control
When the generator starts, the system moves to the generator power supply mode.
level
Starts equipment registered in the generator load table, while suspends ordinary
controls. Manual commands are effective during the generator power supply mode.
When power recovers, issues restart commands to start/stop points. The command
is determined so as to restore equipment to the state which should be at the time of
power recovery.
Temperature/humidity control Performs PID controls of temperature and humidity.
Outdoor air cooling Compares outdoor air and return air enthalpy. If outdoor air is effective for cooling,
modulates the damper to positively bring in outdoor air to reduce the cooling load.
Duty cycling Calculates the stop time of building equipment such as AHUs in a control interval,
while maintaining indoor comfort to reduce heat source energy and electric power.
Start/stop command output Issues start/stop commands to building equipment. Manage command priorities
processing depending on commanders including; manual command, time schedule,
Individual control power-failure, other control programs. Compares start/stop command and status
level input, and if they dont match after a predetermined period, generates an alarm as a
start/stop command failure.
Alarm/status change detection Detects alarm/status changes and send them to the central.
High/low limit of When a measured value exceeds the predetermined high/low limits, generate an
measurements. alarm. The types of high/low limits include: absolute limit specified by an
absolute value, and deviation limit specified by the deviation from the setpoint.
Runtime/cycle count Accumulate runtime/cycle count of the building equipment and utilize them for
maintenance purpose.
37-2 AA-0019E
37. SYSTEM FUNCTIONS
TOP SCREEN
MENU MENU
SELECTION SELECTION
LIST LIST
AA-0019E 37-3
37. SYSTEM FUNCTIONS
37-4 AA-0019E
37. SYSTEM FUNCTIONS
SCHEDULE SCREEN
ENTER START/STOP
SELECT AHU FAN
PROPERTY [ON] TIME
FAN ON GRAPHIC
MONDAY IS DISPLAYED
AA-0019E 37-5
37. SYSTEM FUNCTIONS
37-6 AA-0019E
37. SYSTEM FUNCTIONS
ELECTRIC
HEATING/
COOLING SOURCE TRANSFER ROOM
KICHEN
HOT WATER/
BOILER
AA-0019E 37-7
37. SYSTEM FUNCTIONS
37-8 AA-0019E
37. SYSTEM FUNCTIONS
(2) Do (D)
Take actions for one year.
CHILLED WATER
TOTALIZED HEAT (PREV YEAR)
CHILLED WATER
TOTALIZED HEAT (THIS YEAR)
OUTDOOR AIR TEMP (PREV YEAR)
MONTH
[Example 1] Optimizing the set point for chilled water secondary-pump staging control (Fig.37.7).
In this example, a bypass valve differential pressure control and staging control based on the load flow
were applied to a chilled water secondary-pump system. By comparing the thresholds to add/drop
chillers and to the load flow, the graph shows that during night time two pumps ran, also the header
differential pressure exceeded the threshold to add the second chiller. It can be assumed that the actual
flow of the secondary-pump was more than the design flow that was used to determine the threshold to
AA-0019E 37-9
37. SYSTEM FUNCTIONS
add a chiller and the maximum flow of the bypass valve. Summarized, it can be said that resetting the set
point to add a chiller upward would satisfy the load flow and one pump would be enough during
nighttime.
SO FOR 3 PUMPS
HEADER DIFF PRESSURE
BYPASS VALVE
CHILLED WATER FLOW (l/min)
DIFF PRESSURE
HEADER DIFF PRESSURE
Figure 37.7 Chilled water secondary pump staging control addition setpoint
In this graph, the chilled water valve of the interior AHU and the hot water valve of the perimeter AHU
were always open. This indicates that a mixing loss may have occured in which the cooling energy
becomes heating load, and the heating energy becomes cooling load. To prevent the mixing loss, it is
effective to lower the heating set point in perimeter than the cooling set point in interior.
HEATING COOLING
ROOM TEMP
HEATING SP COOLING SP
TIME
An occupant complaint for too high room temperature arouse in the system that contains an air handling
unit (AC1) with discharge temperature control and the heat exchanger in the secondary system of the heat
storage. A graph of related data to investigate the cause is shown in Figure 37.9. The discharge air
temperature of AC1 was always above the 15 set point. Chilled water entering temperature was always
37-10 AA-0019E
37. SYSTEM FUNCTIONS
above 0 rated temperature. The temperature leaving the heat exchanger was always above the 9 rated
temperature. Temperature difference of the AC1 cooling coil and the temperature leaving the heat
exchanger were appropriate, therefore it can be assumed the high temperature at the heat converter primary
system was the primary cause of the occupants complaint. Capacity of the heat storage and chillers must
be investigated.
ROOM TEMPERATURE
ROOM TEMPERATURE SP
AHU
HEAT EXCHANGER
AC1DISCHAGE TEMPERATURE SP
TEMPERATURE
CHILLER
AC1CHILLED WATER INLET TEMPERATURE SP
TIME
AA-0019E
37-11
37. SYSTEM FUNCTIONS
37-12 AA-0019E
38. DESIGNING BUILDING MANAGEMENT SYSTEMS
MONITRING PC
AA-0019E 38-1
38. DESIGNING BUILDING MANAGEMENT SYSTEMS
REMOTE CONTROL
PANEL
SYSTEM CONTROL MONITORING PC
PANEL
SWITCHING HUB
MONITORING
PC
38-2 AA-0019E
38. DESIGNING BUILDING MANAGEMENT SYSTEMS
AA-0019E 38-3
38. DESIGNING BUILDING MANAGEMENT SYSTEMS
Graphic number
Display symbol
Remote panel
Point name
Optimum start/stop
Deviation alarm
High/low alarm
Status unmatch
No.
Power demand
Power failuyre
Time schedule
Free cooling
Measurment
Switch over
Totalization
Alarm level
Star/stop
Alarm
Status
Reset
OFF/
1 AC1 AHU 1 1 1 1 CP-1 10.001 5.001 100 2
ON
NML/
2 AC1 Filter 1 CP-1 10.002 5.002 11 2
ALM
AC1 Room
3 1 CP-1 10.003 C 0.0- 50.0 5.003 4
temperature
AC1 Room
point
AC1 Room 0-
5 1 CP-1 10.005 %RH 5.005 4
humidity 100
AC1 Discharge
6 1 CP-1 10.006 C 0.0- 50.0 5.006 10 4
dew point
AC1 Discharge
7 1 CP-1 10.007 C 0.0- 50.0 5.007
dew point setpoint
OFF/
8 AC1 Free cooling 1 CP-1 10.008 5.008
ON
OPEN/
9 4F East locked 1 1 CP-2 30.001 5.009 1
CLOSE
OPEN/
10 4F West locked 1 1 CP-2 30.002 5.010 1
CLOSE
OPEN/
11 4F East lighting 1 1 CP-2 40.001 5.011
CLOSE
OFF/
12 4F West lighting 1 1 CP-2 40.002 5.012
ON
0-
15 4F Power CP-1 10.011 kWh 5.015
999999
38-4 AA-0019E
38. DESIGNING BUILDING MANAGEMENT SYSTEMS
1. Dynamic symbols
A dynamic symbol changes its color or shape according to start/stop or alarm status. Color or
shapes of dynamic symbols must be standardized.
2. Example of color: Chilled water is blue, hot water is purple red, and steam is dark red.
1. System schematics
Graphics that focus on system schematics (e.g., air handling units, heat sources, electric
distribution) and usually are displayed for the building operation personnel to monitor the
building equipment. In graphics for the heat source, important components such as headers,
must be included as well as heat source equipment such as chillers or pumps.
2. Floor plans
Expresses floors to identify the physical locations of equipment or sensors.
3. Vertical layouts
Expresses a building vertically to allow the building operation personnel to know the status of
important equipment such as AHUs in all floors at a glance. This graphic is convenient to see
running status of AHUs during after-work hours.
AA-0019E 38-5
38. DESIGNING BUILDING MANAGEMENT SYSTEMS
HVAC SYSTEM
AHU
(1) FLOOR PLAN SELECT
LOWER
FLOORS HVAC LIGHTING
38-6 AA-0019E
38. DESIGNING BUILDING MANAGEMENT SYSTEMS
AA-0019E 38-7
Specifications are subject to change without notice.
http://www.azbil.com/