01 Specification of 220 kV Feeder Protection and Automation
www.siemens.com/poweracademy Copyright Siemens AG 2013. All rights reserved.
Specification of 220 kV Feeder-Protection and Automation

= D 01
3~50Hz 220 kV
100 km

Copyright Siemens AG 2012. All rights reserved.


220 kV:

220 kV:

-BA 11
01 Specification of 220 kV SG
Version: D_10_Page 2 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Specification of 220 kV Feeder-Protection and Automation

220 kV:

3~50Hz 220 kV
-BA 11

Copyright Siemens AG 2012. All rights reserved.


-QB 11
-QA1

-QC 11

= D 02
-QC 2

-QC 1
3

-QB 21

-QC 21
220
220kV:
kV:

-BA 21
01 Specification of 220 kV SG
Version: D_10_Page 3 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Specification of 220 kV Feeder-Protection and Automation

This specification covers the design of a HV substation protection system.


A combined distance and Two end differential protection relay (3 pol.) shall be provided to protect and control the OHL feeder =D01
and the Busbar Coupler =D02.
The devices should have 19 binary inputs, 12 Standard and 3 Fast binary outputs.
The protection device has to have 2 Voltage- and 2 Current-systems interfaces for Line 800/1 5P30 48 VA (Error 1%/ 5%)
and for BC 2500/1 5P30 40 VA (Error 1%/ 5%) (CT neutr. point not to objects). The 220 kV Network is insulated.

Copyright Siemens AG 2012. All rights reserved.


The device should be flexible enough to activate maximal additional protection functions at any time without changing the device and
without additional costs.
The interface for GOOSE communication should be separated from the differential protection interface.
The protection device should have a changeable FO-interface with dual ports, one channel for two end line differential protection
and one channel for existing Substation Automation System with IEC 60870-5-103.

For the communication to the new Substation Automation System and for Inter-device-GOOSE-communication should be use IEC
61 850 protocol. For IEC 61850 should be use a separate changeable electrical module with two canals and integrated Ethernet-
switch.
The protection devise should communicate over a separate Ethernet-interface for DIGSI 5.
The device should be flush mounting and provide local control functionality with a large display and key switches and should have
32 LEDs, 16 LEDs of those should be color changeable.
The power supply in the substation is 48 V DC.

01 Specification of 220 kV SG
Version: D_10_Page 4 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course