Anda di halaman 1dari 1

NOTES

THIS DOCUMENT IS THE PROPERTY OF LARSEN & TOUBRO LIMITED ECC DIVISION AND MUST NOT BE PASSED
ON TO ANY PERSON OR BODY NOT AUTHORIZED BY US TO RECEIVE IT NOR BE COPIED OR OTHERWISE MADE
USE EITHER IN FULL OR IN PART BY SUCH PERSON OR BODY WITHOUT OUR PRIOR PERMISSION IN WRITING.
Checked By Sign Date Checked By Sign Date
Architecture Electrical
Civil FDP
Structural Airside Infrastructure
PHE Landside Infrastructure
ACMV
IT PASSIVE
1. All dimensions and co-ordinates are in mm and elevations are in meters unless otherwise specified.
2. Minimum height of the dyke wall is 2.0m from grade level. The free board is 0.2m.
3. This drawing is valid for hazardous area classification only.
4. This hazardous area classification is based on IP model code of safe practice part 15-
area classification code for petroleum installation july 2005 3rd edition.
5. Open pit, trenches, pits or sump below grade level and within Zone 2 area are classified as Zone 1.
6. Where pipe track crosses the roadway the piping system to be designed avoiding flange joints such that
hazardous area does not impinge on roads.
7. Selection of electrical for hazardous shall be conforming to IEC EN 60079-14.
8. Inside tank is classified as Zone 0, r2 of Zone 2 shall be extended upto bund height as per
fig.3.1 of IP15. All notes therein shall also be considered.
LEGEND 9. Zone 2, hazardous area shall extend down to ground level for the vent as per fig.5.3(a) of IP15 and
vent height shall be deteremined upon dispersion study.
Zone 0 10. Apparatus sub-group and temperature class.
OFF-LOADING LANDSIDE Zone 2
FLAMMABLE APPARATUS TEMPERATURE (T) CLASS
Zone 1 LIQUID SUB-GROUP OF SUITABLE EQUIPMENT
Safe area
Jet A1 II A T3

11. As per IP15 table A2 typical commonly encountered petroleum materials.


PETROLEUM TYPICAL TYPICAL FLASH POINT TYPICAL BOILING RANGE
CLASS AND EXAMPLES (C) (C)
FLASH POINT
RANGE
PANEL
31 - 7LT - 07 BOARD

II Avtur jet A fuel 38 minimum 150-240


21-55C
12. Table-2, Hazard radii (R1) for drains and liquid sample points is 5m. Category A liquids to be cooled before draining
or sampling to avoid release of vapour.

FUEL FARM
ELECTRICAL BUILDING REFERENCES
SA-LTG-CVCF-P-750GOXX-00208 Fuel Farm Overall Plot plan
32 - 7LT - 07

LNL-987-17-FCG-7XS-07

17-5PA-25
2.2kW

FUEL OPERATOR FACILITY


33 - 7LT - 07

FUEL HYDRANT PUMP STATION 70-5MV-01


70-7FT-05

LNL-986-00-FLN-6QS-14
SULTANATE OF OMAN
70-7FT-04
LNL-986-00-FLN-6QS-17
70-7FT-03
29-5PJ-02
22-5PA-02

21-5PA-02
02-5PA-01

70-5MV-03
178kW

178kW

37kW
37kW

70-5MV-04
LNL-986-00-FLN-6QS-16
LNL-986-00-FLN-6QS-15

OFF-LOADING AIRSIDE

FUEL FILLING STATION

P.O. Box 3148, P.C. 111, CPO. Sultanate of Oman Tel: +968 2451 8230
Fax : +968 2452 1053

P.O. Box : 27, P.C. 102, Qurum. Sultanate of Oman Tel: +968 2456 2570
Hill International Fax : +968 2456 2138

P.O.Box 598, P.C 112, Ruwi. Sultanate of Oman Tel: +968 24551941
Fax : +968 24551946

P.O.Box 587,
C P.C 112, Ruwi,
Sultanate of Oman
Tel: +968 24852000
Fax : +968 24815850

1
SCALE 1:500

SALALAH AIRPORT
FUEL FARM
GROUND LEVEL (TERRAIN)
HAZARDOUS AREA
CLASSIFICATION
DRAWING REFERENCE