Learning objectives u
W
Understand the codes and standards that govern fire and life safety systems. S
Know that active and passive fire protection systems can be combined to provide life safety. o
Learn to integrate fire and life safety systems with HVAC systems.
V
T
H
The fire and life safety systems within high-rise buildings, as defined by the 2012
Z
International Building Code (IBC) Section 403, serve to notify occupants of an
emergency, suppress or control an active fire, evacuate or manage smoke in a W
fire area, and pressurize exit stairs for safe exit. The life safety systems often use a
HVAC fans and dampers to configure the required systems for a specific zone in u
alarm. Systems and components must be listed and approved for the purpose for
which they are installed as indicated in 2012 IBC Section 907.1.3. T
S
There are many active and passive systems that provide life safety to occupants A
in high-rise buildings. Often they are integrated or work in unison to provide the 2
safety intended. It is important to understand how they relate to each other in C
order to provide a proper approach to the design and installation of these G
systems. e
f
Below are some important items to
be considered when integrating fire and life safety systems with HVAC systems W
for both active smoke control and the recently introduced post-fire salvage, or a
smoke removal. u
1. Prioritize control of any HVAC equipment used for smoke control so that the G
fire alarm control is the highest level of priority. This will override any other n
control signals to allow for the required airflow quantity for exhaust/makeup air, b
life safety damper closure and opening, and required unit shutdown. This may s
require bypassing hands-off automatic (HOA) or variable frequency drive (VFD) V
controls when life safety functions occur.
a
2. Each HVAC item that is required for smoke control or life safety systems (air H
handling unit smoke detectors, fire/smoke or smoke dampers, stair pressurization E
fans, smoke exhaust fans) may require a dedicated wiring connection to the fire T
alarm system. This is a parallel path from the HVAC control system if the fire S
alarm system is used for life safety control of the building management system
A
(BMS). The BMS can monitor these connections, but no control can be given through the BMS unless the BMS is listed for
smoke control. If the BMS is used for smoke control, and is listed, then the manner in which the fire alarm and BMS share I
signals needs to be incorporated into the design. A
P
3. Carefully review which type of activation is required for smoke control systems. Is it activated by the fire sprinkler system or s
the smoke detection system? For areas such as high-rise hotel tower corridors, a common method of activation is by smoke C
detection in the corridor. For low-rise podium smoke control zoning, a common method of activation is through fire sprinkler G
waterflow.
S
If it is activated by fire sprinkler, then the sprinkler system zoning must match the smoke control zoning. Modifications to s
zone boundaries during construction will require modifications to sprinkler systems in the field. d
If it is activated by smoke detector, then the detectors must be zoned to identify which units will activate the smoke control
system and which will not.
Some properties use both fire sprinkler and smoke detection to activate the same smoke control system. In these cases,
both systems need to be coordinated with zone boundaries.
4. Coordinate zoning of HVAC equipment with the smoke control zoning. This will reduce the number of life safety dampers
(smoke and combination fire/smoke) required in the system and allow proper unit shutdown and activation for a specific area
without affecting other zones. Only a single zone in alarm will be affected for the active smoke control systems, but the fire
alarm zone typically notifies both the area under emergency and adjacent spaces for evacuation and instruction. This is also
important with fire/smoke dampers. Rather than splitting the branch ductwork within the adjacent zone, split the ductwork inside
the zone to reduce the amount of fire/smoke dampers needed.
https://www.csemag.com/single-article/top-tips-for-integrating-fire-protection-hvac-systems/44bc49994b8113008940e5e5a639af4f.html 1/3
11/5/2017 | Consulting-Specifying Engineer
7. The design should consider the benefits of using either dedicated equipment or
nondedicated equipment (HVAC fans). Dedicated fans are those used only for
smoke control purposes and do not operate under normal HVAC conditions. They
are typically used for stairwell pressurization and smoke exhaust systems.
Because they are not used frequently they do not require as much maintenance,
but they do require more frequent testing. Nondedicated fans (HVAC dual-
purpose fans) are allowed by code and can provide benefit to smoke control
systems to reduce costs. They are used for normal HVAC and smoke control and can be beneficial because they are
maintained more frequently. However, maintenance needs to be performed such that it does not impact the smoke control
operation. This includes any changes to VFD controls. The expected temperature of smoke must also be taken into account
when selecting the temperature rating for active smoke control equipment (through either UL 705 Power Ventilator listed smoke
exhaust fans or by providing calculations to clarify a reduced temperature rating, which may be 200 to 250 F for air handling
unit fans).
8. The International Building Code requires ductwork that penetrates fire-resistance rated walls to be protected with fire
dampers, smoke dampers, or combination fire/smoke dampers. Fire dampers are less expensive to install and maintain
because they do not require power and smoke detection for control. Often fire/smoke dampers are the default because it is
sometimes difficult to determine what type of wall is being penetrated. The design of the system needs to take into account the
type of wall and the required damper to minimize costs, both upfront and ongoing, as well as reduce the complexity of the
system. The layout of the ductwork also needs to be considered to minimize the amount of dampers. It is better to make one
penetration into a corridor and feed the corridor with one duct than to penetrate with several lateral branch ducts, which require
more dampers.
9. VFDs are a great way to control the amount of air required under both HVAC
and smoke control functions. Most VFDs are programmable to allow setpoints to
be used for smoke control functions. The VFDs need to be designed and installed
such that the setpoints established during smoke control testing are not changed
in the field due to HVAC controls or other functions. It is important to recognize
the relationship that the VFD plays in both smoke control and normal HVAC use.
In addition, VFDs should be located in areas that provide a level of protection to
the panel so that during a fire condition, they are not impacted by the fire.
Matt Dolan is a senior project engineer with JBA Consulting Engineers. His
expertise is in designing complex HVAC and plumbing systems for various
building types, such as commercial offices, health care facilities, and hospitality
complexes including high-rise guestroom towers and numerous restaurants.
Related News:
Piping arrangements for fire pumps - 16.03.2015 05:13
Use NFPA 3 for new, existing buildings - 17.12.2014 06:13
2014 HVAC and Building Automation Systems Study: Seven key findings - 15.12.2014 06:43
Designing smoke control systems - 12.12.2014 06:19
Fire risk from solid fuel commercial cooking - 08.12.2014 21:45
Specifying passive firestop systems - 24.10.2014 05:55
Additional info about integrating BAS and fire/life safety systems - 14.10.2014 20:14
Balancing active and passive fire protection - 13.10.2014 05:33
Post a comment
https://www.csemag.com/single-article/top-tips-for-integrating-fire-protection-hvac-systems/44bc49994b8113008940e5e5a639af4f.html 2/3
11/5/2017 | Consulting-Specifying Engineer
Events & Awards Magazine Archives Pure Power Blogs Survey Prize Winners CFE Edu
Product of the Year 40 Under Forty: Get Recognized MEP Giants Program
Consulting-Specifying Engineer's Product of the Consulting-Specifying Engineer magazine is The MEP Giants program lists the top mechanical,
Year (POY) contest is the premier award for new dedicated to encouraging and recognizing the most electrical, plumbing, and fire protection engineering
products in the HVAC, fire, electrical, and... talented young individuals... firms in the United States.
Articles New Products Topics Training, Tools Events and Awards News, Views, Blogs Newsletters Advertising Abo
Career Smart New Products Automation, Controls Apps for Engineers 40 Under 40 Career Smart Codes & Standards Case Study Database Term
Case Studies and White Innovations from the Codes & Standards Career Smart MEP Giants Collaborating against Electrical Solutions Listing App
Papers Industry Electrical Systems Case Study Database Product of the Year counterfeit electrical Fire & Life Safety Contact Us Con
Codes & Standards CSE Product & Media Fire & Life Safety Videos Upcoming Events products HVAC Innovations from the Abo
Magazine Showcase HVAC/R Cut the Copper NewsWatch: Data Industry Adv
Industry Roundup Product of the Year Lighting Engineering Change Centers Internet Profiles How
Magazine Archives Plumbing, Piping IEEE Power Perspectives NewsWatch: Educational Magazine Con
Projects in Progress Industry News Facilities CSE Product & Media Mag
Insights on Power NewsWatch: Hospitals Showcase Con
Research Analyst Blogs Pure Power Mag
RSS Feeds eNewsletter Archive EGS
Social Media Per
Understanding Plan
Specifications, Codes, Priv
and Standards Pur
Sub
https://www.csemag.com/single-article/top-tips-for-integrating-fire-protection-hvac-systems/44bc49994b8113008940e5e5a639af4f.html 3/3