Transformer Temperature : oC
Make of Megger :
Recommended Test Voltage: 2.5kV or 5kV for all HV Windings & 500V or 1000V
for all LV Windings
Voltage Class of
Minimum IR Values in Mega
Winding
At 30 oC At 40 oC At 50 oC At 60 oC
66 & 132 kV 600 300 150 75
22 & 33 V 500 250 125 62.5
6.6 & 11 V 400 200 100 50
< 6.6 kV 200 100 50 25
Transformer Temperature: oC
Make of Meter/Bridge
3. RATIO TEST:
Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV
winding open circuited and measure the voltage in the secondary winding
Use good quality voltmeters for measurement; use same meter for measuring HT &
LT Volts
Check with the ratio declared in the transformer name plate/routine test certificate
Actual
Tap Applied Volts Measured Volts Ratio Calculated
Ratio
No.
1U1V 1V1W 1W1U 2u2v 2v2w 2w2u 1U1V/2u2v 1V1W/2v2w 1W1U/2w2u
1
2
Short the terminals 1U & 2u using a wire of right size (say 2.5 sq.mm Cu.)
Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV
winding open circuited and measure the voltage in the HV/LV windings
Use good quality voltmeters for measurement; use same meter for measuring HT &
LT Volts
Check if the equations for the relevant vector group are satisfied
For example, for Dyn 11 Vector Group, the following equations must satisfy:
i) 1V2w = 1V2v
Similarly, equations could be derived for any other vector group and test results can
be crosschecked.
Apply 2 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV
winding open circuited and measure the voltage in the HV windings
Use good quality voltmeters for measurement; use same meter for measuring
applied & measured Volts
Check if the balance conditions are satisfied
Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV
winding open circuited and measure the voltage, current & power in the HV winding
Check with the exciting current/no-load loss declared in the transformer routine
test certificate
Note: From the above data, we can calculate that if the exciting current is 'x'
milliamperes for the test voltage applied (say 415V), what would be the exciting
current for the rated primary volts of the transformer.
Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV
winding short circuited and measure the voltage in the HV winding and current &
power in the LV winding
Note: From the above, we can calculate that if for the test voltage (say 415V), the SC
Current is 'y' amps, then what it would be for the rated primary voltage of the
transformer.
Motorised Operations)
9. Tests on Bushing CT: All tests as per IS 2705 like Polarity, Winding Resistance,
Accuracy, Ratio Test, Mag.Characteristics, etc.
10. Tests on Protective Devices: Check all protective devices for correct operation,
settings, calibration, etc.
11. General Inspection: Check for Physical Dimensions, Clearances, Creepages, etc,
as per approved drawings; Inspect for any visual damages to any components.
12. Tests on Insulating Oil: BDV shall be 60kV across a gap of 2.5mm with 12.5mm
Dia. Spheres. Ask for test certificate.