FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
Contents
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
1.0 GENERAL
1.1 Introduction
CNPCI is responsible for development operations of the South Azadegan oil field located in
the southwest of the Islamic Republic of Iran, close to the border of Iran and Iraq and 80km
west of Ahwaz city in Khuzestan province.
This document covers the Architectural design for the Surface Facilities development
of the South Azadegan Oilfield Project. Specific Project Specifications have been prepared
based on Iranian National Building Codes and Iranian Petroleum Standards,International
Standards and Codes of Practice.
1.2 Definitions
Vendor/Supplier/Subcontractor The party to the contract and/or purchase order which has
undertaken the obligation to supply the goods and/or
services which are ordered and specified herein
1.3 Abbreviations
QA : Quality Assurance
QC : Quality Control
The South Azadegan Field facilities are to be designed and constructed in accordance with
applicable Iranian Petroleum Standard (IPS) and international code/standards.
Iranian National Building Codes (INBC)
o Part 3: Fire Protection
o Part 4: General Notes for Buildings
o Part 5: Construction Materials
o Part 12: Safety for Construction
o Part 13: Electrical Equipment and Wiring
o Part 14: HVAC and Plumbing in Construction
Iranian criteria for design and administrative
o Part 16: Sanitary Equipment
building, Publication No. 178 shall be added
o Part 17: Piping of NG (Natural Gas) in Buildings
o Part 18: Sound Insulation in Buildings
o Part 19: Energy Conservation in Buildings
o Part 20: Signs and Tableaus
Iranian Petroleum Standards (IPS)
o IPS-E-CE-200 Engineering Standard for Concrete Structure
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
The Interior Finish should satisfy Chapter 10 of the Building Construction and Safety
Code (NFPA 5000).
The fire resistance rating of decoration materials should be considered in decoration
design.
Fire-resistance rating of steel fire door and fire window is 1.5 hour rating. All fire doors
should fix door closer, Double-leaf fire doors need door closer and gravity arm door
selector, hold-open fire doors need signal control close and feedback device.
The fire door satisfies the Standard Methods of Fire Tests of Door Assemblies
(NFPA252). The fire window satisfies the Standard on Fire Tests for window and Glass
Block Assemblies (NFPA257).
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
The sound pressure level anywhere in the site area shall not exceed 115 dBA in any
situation, including emergency.
The maximum allowable sound pressure level for site buildings is specified in the following
table.
5.1.1 Roofing
The roof use colour steel sandwich panel which chip with polyurethane that is not less than
100mm thick and the bulk density is not less than 40kg/m3 2, the colour profiled steel
sheet is more than 0.6mm in thickness and the weight of double plated Al-Zn is 180g/.
Fasteners should adapt to the fixed components.
5.1.2 Wall
200 mm thickness clay hollow block, 110 mm thickness face clay brick and 50mm thickness
thermal insulation are used for the outside walls.200 mm thickness clay hollow blocks are
used for the inside walls.
5.1.3 Interior finish
The toilet wall is affixed with tiles and the rest room wall is painted with white emulsion
paint.
5.1.4 Ceiling
Toilet adopt aluminium alloy gusset plate ceiling.Office,control room,equipment room
adopt light steel keel mineral wool slab.
5.1.4 Outside finish
Outside wall is covered with face brick.
5.1.5 Ground
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
5.3.1 Roofing:
Reinforced concrete roof shall be according to structural section.
5.3.2 Wall:
200 mm thickness clay hollow block, 110 mm thickness face clay brick and 50mm
thickness thermal insulation are used for the outside walls. 200 mm thickness clay hollow
blocks are used for the inside walls.
5.3.3 Ceiling:
Toilet and shower room adopt aluminium alloy gusset plate ceiling and the other rooms
adopt light steel keel mineral wool slab.
5.3.4 Interior finish:
The toilet wall is affixed tiles and the rest room wall is painted with white emulsion
paint.
5.3.5 Outside finish:
Outside wall is covered with face brick.
5.3.6 Floor:
Laboratory adopts acid and alkali resistant tiles.Toilet adopts anti-skid tiles. The rest rooms
adopt ceramic floor tiles and concrete ground.
5.3.7 Windows:
Unless specified, all windows are single frame hollow glass aluminium-alloy windows
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
Exterior Wall1: Face Brick Wall Floor1: White Anti-skid Ceramic Tile
Standard commercial Iranian manufactured, 18mm-10mm thick ceramic tile, grout (or
white color sand-lime brick shall be used. color
The maximum absorption (by weight) shall grout) troweled joints.
be 16% by 24 hours submersion in cold 2220mm thick 1:3 hard cement mortar
water or 19% by 5 hour boiling and the coating, scatting cement dust on the
minimum compressive strength shall be 176 surface.
kg/sq.cm.(2500 psi), tested according to 3Humid insulation
ASTM C67. 41:3 cement mortar or 30mm thick for the
1Brick sizes shall be such that the thickness thinnest fine aggregate concrete slope
of grout or mortar between masonry units making screeding .
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
1100mm thick fc= 25 MPa concrete placing 120(30)mm thick Anti-Acid tile, push joints
and troweling, dregged 1:1 cement sand with epoxy mortar(2-3mm gap).
over the floor finish the floor. 25mm thick epoxy mortar bonding layer.
2Cement slurry (mixes the construction 3Epoxy glass copper(2 layer epoxy
adhesive). primer)
3100mm thick fc= 15 MPa Lean concrete 2 layer glass fiber cloth) isolation layer.
layer. 420mm thick dry-mixed mortar leveling
4300mm thick hardcore (50mm gravel on layer.
250mm hardcore). 5120mm thick fc= 15 MPa Lean concrete
5Soil to be Compacted up to 95% aashto layer.
modified. 6300mm thick hardcore(50mm gravel on
250mm hardcore).
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
Ceiling1 Light steel keel mineral wool slab Ceiling2 Aluminum alloy square plate
112 thick mineral wool sound-absorbing 1 Aluminum alloy square plate 600 X600
panel surface,standard 600x600 fixed with special supporting keel.
2T-cladding light weight steel secondary 2A square plate connected with special
keel TB24x28,distance 600,spliced with lower keel ,the distance <600mm.
major keel. 3Special upper keel (<1200mm) ,make
3T-cladding light weight steel secondary leveling.
keel TB24x38(or TB24x28) ,distance 410 galvanized low carbon steel wire
600,fixed with main keel by pendant. boom, the boom fixed with reserve rings.
4U-cladding light weight steel main 5.110 steel ring should be Cast-in-place
keelCB38x12,distance1200,jointed with reinforced concrete board reserved
the steel boom by hanger then leveling. reinforced exchange, distance < 1200mm
56 steel boom two-way midordinate
1200,the top of boom is fixed with future
expanding steel hanger
6Cast in-site reinforced concrete beam
reserves 10 steel hanger (hook) ,two-way
midordinate1200
Skirting1:Ceramic tile skirting(100mm high) Skirting2: PVC skirting(100mm high)
Building
Building area shall be specified during List
detail of CTEP
design
stage based on updated architectural plan by EPCC
contractor.
Fire water
B03 house(BD-20016) - - - - 1 -
Foam house (BD-20017) - - - - 1 -
Building area and other specifications Building List of SOUTH-GOSP
shall be specified
during detail design stage based on updated
architectural plan by EPCC contractor. Height Structure Building Storey Quantity Fire
No. Construction Name m Type Area Resistance
7.8 Rating
1 Control room Reinforced 1464 One 1 2-HR
(BD-70001) 6.3 concrete
frame
2 Substation Steel frame 863 One 1 2-HR
9.85
(BD -70002) Structure 2
3 Guard room 19 One 1 2-HR
3.45
(BD -70003)
for N-GOSP and S-Gosp unit , pump house (quantity=4) shall be added
FEED SERVICE FOR SURFACE FACILITIES
DEVELOPMENT OF SOUTH AZADEGAN PROJECT
(EARLY PRODUCTION)
4.8
7.0 Protection B03
Provide final protection and maintain conditions, in a suitable manner which ensures
material selection & manufacturing, storage ,construction being without damage or
deterioration at time of substantial completion.