voltage induced in the pipe by the current flowing in the con- and suggests that these errors could be caused by a slight dis-
ductor is cancelled by a voltage induced in the pipe in an opposite placement in the position of the two potential leads. As the
direction by the return current flowing in the pipe. As any in- same cables with fixed potential leads were used in magnetic and
duced voltage must be the result of a mutual effect, it is my nonmagnetic pipes, I doubt that this is the explanation. It is
feeling that it must be assigned to the central conductors. This true that these measurements were made at the center of a 45-
agrees with comments already made and results in a net voltage foot test length. The measured values, especially at low cur-
drop along the pipe which is equal to the difference between the rents, were in the millivolt range, and it is conceivable that slight
IR drop and the induced voltage. errors resulting from stray fields may have been included in the
Mr. Mildner suggests that the measurement of voltage drops measurement. These errors may then have been enlarged by
measured along the pipe and the return conductors were in error converting the measurements to a 1000-foot basis.
Abstract: Because of the progressively greater distances from The succeeding years witnessed longer and higher voltage
sources of hydroelectric power to large load centers, there is a lines. Two of the notable ones are the Los Angeles Depart-
constant search for more efficient and less costly means of long-
distance transmission. This paper proposes a half-wavelength ment of Water and Power 265mile 287-kV Boulder lines,
transmission system for point-to-point transmission of power feeding Los Angeles, completed in 1936, and Sweden's 593-
to eliminate many of the operational and design problems asso- mile 380/420-kV line, completed in 1952. At present, Hydro-
ciated with conventional long transmission lines. Quebec of Canada is building a 700/735-kV 400-mile system
to draw on the abundant hydro potential of northern Canada.
Large load centers are often located at great distances from The design of economical ELD transmission lines is becom-
abundant sources of hydroelectric power. Because the long ing increasingly difficult due to the high cost of compensat-
electric power transmission line thus far is the only economical ing equipment. Instability precludes the transmission of
means of transporting this energy, utilities are developing power from a remote generator if the angle between the gen-
more interest in EHV and extra-long-distance (ELD) point- erator terminal voltage and the receiving end bus voltage is be-
to-point transmission lines. tween 90 and 180 electrical degrees. To provide a sufficiently
Historically, the first long high-voltage transmission line stable margin of safety, a criterion for preliminary studies of
appeared in 1914, when the Southern California Edison Com- approximately 30 electrical degrees has been suggested as the
pany placed in service the 150-kV 243-mile line from the maximum phase shift to be allowed over the line. At 60 c/s,
Sierra Mountains to Los Angeles; in 1924, it was changed a 250-mile line at surge impedance loading (SIL) has an angle
to 220 kV. of approximately 30. To maintain an angle of 300 for ELD
lines longer than 250 miles at SIL, 100-percent compensation
reommnde andappove bythe ranmision
Pape 31TP 5-12 is required of all lengths in excess of 250 miles. Therefore, as
and Distribution Committee of the IEEE Power Group for presenta- the line length increases, the cost per-unit length (including
tion at the IEEE Winter Power Meeting, New York, N. Y., January compensation) increases. Aside from the high capital
31-February 5, 1965. 1964;-
Manuscript submitted August 21, netet L ie rdc prtn rbes uha
made available for printing November 13, 1964. -lvsmn,EDle rdc prtn rbes uha
F. J HUERT nd. R GEN ar wih th Deartent f Wter surplus volt-amperes reactive (vars) during light load condi-
and Power, City of Los Angeles, Los Angeles, Calif. tions, Ferranti effect, and generator self-excitation.
IEEE TRANSACTIONS ON POWER APPARATUS AND 5Y5TEM5 VTOL. PAS-84, NO. 10 OCTOBER, 1965
Instead of shortening, if the line is electrically lengthened The following are computed per-unit (pu) values on a 1000-
so that its effective electrical length is between 1800 and 2700, MVA base:
an interesting phenomenon occurs. The system is as stable z=0.0123+jO.249 &/100 mi.
as one operating in the first quadrant (O to 900). For y=O+jO.167 mho/100 mi.
example, if the generator terminal voltage is 1900 with re-
spect to the load, the stability limit of the system is the same Zo -=1.22-jO.00303 ohm
as if the generator were operating at 100 from the load. In -o
addition, there are none of the usual long line operating where Zo is the surge impedance or characteristic impedance
polems
problems.
The most attractive feature of the half-wavelength system
ofwherlieZO isthe seriesimpedance oftharce lne, anpd te y s
Table 1. Percent Voltage at Sending and Receiving End Transformer High-Voltage Sides During 1-, 2-, and 3-Phase-to-
Ground Short Circuits
Percent Voltage at Sending End Percent Voltage at Receiving End
Transformer High-VoltageSide Transformer High-Voltage Side
Type Fault Fault Location Phase A Phase B Phase C Phase A Phase B Phase C
Thre-has
fe-paulse
I Sending end transformer, high-voltage side 0 0 0 166 166
Receiving end transformer, high-voltage side
222000
166
222 222
Load 190 190 190 232 232 232
Two-phase-to I Sending end transformer, high-voltage side 69 0 0 170 136 194
groPund faults -( Receiving end transformer, high-voltage side 265 242225 0 41
Load 68 178 167 163 0 219 226
Single-phase-to- I Sending end transformer, high-voltage side 099 74 171 49 165
ground faults -( Receiving end transformer, high-voltage side 235 180
99 0 89 79
Load 142 31 162 204 141 131
L TRANSORMER 5\-4
40
TRANSFORM ER
S00
EIVING END
HIGH VOLTAGE// / SIDE
\
GENERATOR
'\_l 4e
HIDE _ o
/G ;
HIGH VOLTAGE TERMAL
-
SIDE LOADNA
IN'TERNALLA
270"
GENERATOR
/ O 10 25 50
/_O_10_25_50 % VOLTAGE SCALE
INTERNAL % VOLTAGE SCALE Fig. 6. Voltage phasor diagram of half-wavelength 500-kV
Fig. 4. Voltage phasor diagram of half-wavelength 500-kV 900-mile system at 28 cycles (11 cycles after clearing)
900-mile system at SIL under normal operating conditions
400
GENERATOR 90g T-18 CYCLES
w 360
~~~~TEs~~~~~~~~~~~~4 S~~~~~~~ _-
_ 0
o /NSENDING END
WINAL LOAD Z 300 _
180 0 FAULT
/~~~~~~~~~~~~0
aX
41// w~~
0 - o ~ 't' 4
0 10 25 50 0 RECEIVING END
N. 4r 4
%VOLTAGE SCALE 270 j 100 /
0 40 50 60 70
0 10 20 30
TIME IN CYCLES
load. While in the second quadrant, the sending end genera- Fig. 7. Swing curve of generator internal voltage angles for
tor is motoring, the power flow in the line is reversed, and fault of 17-cycle duration applied in region of receiving end
simultaneously the voltage along the line is oriented in the equivalent of half-wavelength 500-kV 900-mile system
opposite quadrant; therefore, the motoring generator is still
over 1800 from the other end. Using the phasor diagram for
reference, it can be said that the power flow is always in the
clockwise direction, taking the longest path measured in not only increases the SIL but lengthens the line electrically.
in terms of electrical degrees. For example, assume that the SIL of the line in the first design
To arrive at the conditions shown in Fig. 6 (T = 28 cycles), (900 miles of single-circuit twin Chukar at 500 kV) is to be
the motoring action of the generator and the turbine drive increased from 820 MW to 1400 MW.
combine to force the generator back into normal operation. For SIL of 1400 MW, the admittance necessary for this
Here, at 28 cycles, the power flow has again reversed and co- line would be
incidentally the voltage has flipped back towards its original
position. In tests at lower clearing times, the motoring gen- y =zIP =jO.249(1.4)' =jO.489-pu mho/100 mi. (7)
erator situation did not occur. on 1000-MVA base.
In summary, the remarkable transient stability of the half-
wavelength transmission system to a 'fault 1. . 1.
of extraordinary The
Teeoe h admittance
natural ifrneo ofO32hst emdpu/100
the line is i0.167 pwt mi.
duration iS self-evident In Fig. 7, the swing curve for the 17- shunt capacitors. A total of 9(0.322) (1,000) or 2900 Mvar,
cycle fault. distributed at 100-mile intervals along the line, is required to
Alternate Designs increase the SIL from 820 MW to 1400 MW.
DESIGN NUMBER
Two ~~~~~~~~Since the admittance of the line has been increased, the
phase shift over the line has also been increased. The new
If greater line-carrying capacity is desired without going to phase shift, 6, over the 900-mile line is:
higher voltages, the SIL of the line can be increased by adding______
shunt capacitors along the line. This additional admittance 0 =57.3LX/zy =57.3(9) X/(0.249)(0.489) =1800. (8)
Abstract: Systems of sheath bonding which eliminate sheath fact that appreciable voltages may arise at various points
losses in single-core cables cause sheath overvoltages as a result of the sheath circuit because of transients or faults, will be
of transients and faults. Equations for transient sheath voltages
are derived for the first incident wave, through the use of equiva- discussed i this paper which iS a sequel to [1], which dealt
lent circuits to represent bonding points. The method is ex- with earlier phases of the work presented here. Some of the
tended to subsequent reflections with a digital computer; cal- material in the earlier paper is repeated here if it seems vital
culated results are given for several values of the relevant param- to provide a complete picture. Hence, the present paper
eters, and the effect of these parameters is discussed. Transient
sheath voltages can be limited by the surge diverter described in supersedes rather than supplements the prevous one.
this paper; and the necessary sheath insulation levels, with and
without surge diverters, are discussed. Equations for sheath Types of Sheath Bonding Considered
overvoltages caused by external steady-state faults are given.
Calculated and measured sheath voltages when compared, show The following section describes the principal methods, used
reasonable agreement for both transient and steady-state cases. in Great Britain, of bonding the sheaths of single-core cables
to eliminate sheath losses.
The rapid growth of loads to be transmitted bv power cables
in recent years has directed the attention of cable engineers in SINGLE-POINT BONDING
Great Britain to the advantages of special sheath-bonding Short cable circuits, mostly interconnections within a sub-
connections. These special methods of connection are station or terminations of an overhead line into a substation,
applicable to single-core cables and replace the traditional have frequently been dealt with by bonding and earthing
method of bonding and earthing the sheaths at both ends of the three sheaths at only one point along the cable route.
the cable route. They have the object of eliminating or This point is normally at one end or at the center.
greatly reducing the circulating currents in the sheaths and, The British Electricity Boards have imposed limitations on
hence, the sheath losses. As a result, thev considerably sheath voltages resulting from full-load current in the cable
increase the current rating of the cables. conductors which, until recently, have been 10 volts at an
While those bonding methods are not new and some have exposed termination and 50 volts for an underground sheath.
been widely used in the United States, they were not intro- The first limitation was recently raised to 25 volts; the second
duced in Great Britain until six or seven years ago, but are now is under review for possible revision.
firmly established. Some of the load transmission require- The difference between these two limitations has initiated
ments of the Central Electricity Generating Board at 275 kV the use of a further type of single-point bonding in which
or 400 kV could not be met by a single circuit without some sheaths are earthed at the terminations and interrupted at
method of eliminating sheath losses. some point along the lengths, usually the center. This per-
It has been recognized that the introduction of special mits employment of longer cable lengths inasmuch as the
sheath-bonding methods brings disadvantages as well as limitation of sheath voltage is not so severe.
advantages. The disadvantages, mainly associated with the These bonding methods are variations of single-point bond-
ing in that each length of sheath is earthed at only one point
- by- the Insulated
Paper 31 TP 65-128, recommended and approved ~~~~~andthere are no connections between sheaths except at the
Conductors Committee of the IEEE Power Group for presentation earth point.
at the IEEE Winter Power Meeting, New York, N. Y., January 31-
February 5, 1965. Manuscript submitted November 6, 1964; CROSS BONDING
made available for printing January 4, 1965.
E. H. BALL is with the Pirelli General Cable Works, Ltd., South- Longer cable circuits have been dealt with by the Kirke-
amptonl, England; and E. OCCHINI and G. LUTONI are with Pirelli, Searing type of cross bonding [2], [3] adapted to cables laid
S.p.A., Milan, Italy. in flat formation by combining transposition and sheath bond-
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS VOL. PAS-84a NO. 10 OCTOBER, 1965