The loads allocated to a line segment or a distribution transformer using diversity factors are a function of the total number
of customers downstream from the line segment or distribution transformer. With the allocated loads flowing in the line
segments and through the transformers and the impedances, the voltage drops can be computed. The assumption is that
the allocated loads will be constant real power and reactive power. The voltage drop is calculated from the source to the
last transformer.
Example :
For the given system above, assume that the voltage at N1 is 2400 volts and compute the secondary voltages on the three
transformers using the diversity factors.
Assume that the power factor of the loads is 0.9 lagging.
Using (ACSR Linnet : R=0.3 ohm/mi, GMR =0.0243 ft, 3.4 spacing)
GMD=3.4
L=0.7411 log(GMD/GMR) mH/mi = 1.59 mH
XL=(2)(pi)(f)(L)=0.6 ohm/mile
Determine the noncoincident maximum kw demand and maximum diversified kw demand for each line segments.
Segment N1 to N2
The maximum noncoincident kw demand is the sum of the maximum demands of all 18 customers.
265.8
Max. div. demand = --------- = 92.8 kw
2.86
Segment N2 to N3
The maximum noncoincident kw demand is the sum of the maximum demands of all customers 6 to 18.
The maximum diversified kw demand is then computed by using the diversity factor for 13 customers.
199.1
Max. div. demand = --------- = 72.6 kw
2.74
Segment N3 to N4
This line segment sees the same noncoincident kw demand and diversified kw demand as that of transformer T3.
The maximum diversified kw demand is then computed by using the diversity factor for 7 customers.
117.5
Max. div. demand = --------- = 48.9 kw
2.4
Segment N1-N2: P12 = 92.8 KW S12 = 92.8 + j 45 KVA
Segment N2-N3: P23 = 72.6 KW S23 = 72.6 + j 35.2 KVA
Segment N3-N4: P34 = 48.9 KW S34 = 48.9 + j 23.7 KVA
Convert the transformer impedances to ohms referred to the high voltage side:
V2 = V1 Z12 * I12
V2 = 2400/0 (0.2841 + j0.5682) * 43 /-25.84 = 2378.4 /-0.4 V
V3 = V2 Z23 * I23
V2 = 2378.4/-0.4 (0.0284 + j0.0568) * 33.9 /-26.24 = 2376.7 /-0.4 V
V4 = V3 Z34 * I34
V4 = 2376.7/-0.4 (0.0426 + j0.0852) * 22.9 /-26.27 = 2375 /-0.5 V
Calculate the percent voltage drop to the secondary transformer T3. Use the secondary voltage referred to the high side.
= 3.0789%
V2=2378V V3=2376.7V V4=2375V
2400V