Anda di halaman 1dari 3

GTP-13

(to be filled in and signed by the tenderer)


GUARANTEED TECHNICAL PARTICULARS AND DETAILS FOR
11 KV XLPE CABLE 3C X 185 Sqmm.

SR Particulars/Details AS SPECIFIED BY GED PROVIDED BY BIDDER


NO required to be given by
the tenderer
1 Voltage Grade 11kv( E )
2 Type of cable. Stranded Aluminium
Conductor,Screened XLPE
Insulated Extruded
Semiconducting
compound,water sweallable
tape,copper tape,Pressure
extruded PVC Inner
Sheathed,GIWire armoured
bound by rubberized cotton
tape and PVC Outer
sheathed

3 Conductor
a Material. H2/H4 grade aluminium
conductoras per IS:8130-
1984
b No.of cores & size 3cx185SQ.MM
c Minimum No. of wires 30
d Shape of conductor Stranded Compacted Circular
4 Conductor screen: Extruded Semi Conducting
Compound(min thickness
0.3mm)

5 Insulation

a Material. XLPE Insulation as per


IS:7098(Part-II)-1985
b Nom.Thickness 3.6mm
6 Insulation screen.
a Non-metallic part Extruded Semi Conducting
Compound Layer(min
thickness 0.3mm)

b Water Swellable tape wrapped semi conducting


compound
c Metallic Part Copper Tape(min thickness
0.045mm) with standard
overlap

d Identification of cores By using coloured strips as


per Cl.13 of IS:7098(II)-1985
7 Inner Sheath
a Material. Extruded PVC Compound ST-
2 as per IS 5381-1984

b Minimum Thickness 0.7mm


c Process of applying Pressure extrusion
8 Armouring
a Material Galvanised steel wire
(round) as per IS-3975:1979

b Nom.Dia 3.15mm

c Armouring Area Coverage 90%(min) The gap between


any tow armoure wire shall
not be more than the
diameter of armour wire

c Rubberized Cotton Tape RC tape to be provided to


bind armour wires.Min
thickness 0.2mm

9 Outer Sheath

a Material Extruded PVC Compound ST-


2 as per IS 5381-1984

b Minimum Thickness/Nom 2.52mm


thickness
10 Approximate Overall Dia 71mm
of Cable
11 Tolerenc on Dia 3 mm (+or-)

12 Standard Length with 500 meters + or -5%


Tolerence
13 Dimensions & Drawing to be furnished by bidder
of the cable Drum
14 Equivalent Effective to be furnished by bidder
Impedeance of the
cable(Ohms/Km)
15 Equivalent Effective to be furnished by bidder
Capacitance of the
cable(mF/Km)
16 Short Circuit Capacity 17.5KA
for one sec
17 Max.Dc Resistance at 20 0.164ohm/km
degree centigrade
18 Short time O/L capacity to be furnished by bidder
For 1hr, 24hrs & 72hrs in
Amperes
19 Continuous Current
Rating of the cable when
laid
a Direct in ground at 30 275 Amp
deg.C
b In Air at 40 deg.C 335 Amp

c in ducts to be furnished by bidder

d in two circuits to be furnished by bidder

e in three circuits to be furnished by bidder

Date Signature

Place Name

Status

Whether authorized attorney


of the tendering company.

Name of tendering company