Anda di halaman 1dari 12

Corros Rev 29 (2011): 179190 2011 by Walter de Gruyter Berlin Boston. DOI 10.1515/CORRREV.2011.

008

Electrochemical techniques for the repair of reinforced concrete


suffering carbonation-induced corrosion

Elena Redaelli*, Maddalena Carsana, Matteo corrosion propagates, the formation of corrosion products at
Gastaldi, Federica Lollini and Luca Bertolini the steel-concrete interface generates mechanical stresses that
cause cracking of concrete cover, delamination and, eventu-
Politecnico di Milano, Department of Chemistry,
ally, spalling, as it is depicted in Figure 1 (Bertolini, 2008;
Materials, and Chemical Engineering Giulio Natta
Tuutti, 1982). Each of these phenomena represents a limit state
Piazza Leonardo da Vinci 32, 20133 Milano, Italy,
in the life of the structure, since it is an undesired event that
e-mail: elena.redaelli@polimi.it
limits the serviceability and functionality of the structure and
* Corresponding author makes an intervention necessary.
The repair of structures suffering carbonation-induced cor-
rosion is traditionally carried out by removing carbonated con-
Abstract crete and replacing it with a new alkaline material, typically
a repair mortar that passivates the steel thanks to its cementi-
The use of electrochemical techniques in the repair of rein- tious nature. This is referred to as conventional repair. If the
forced concrete suffering carbonation-induced corrosion is intervention is carried out removing all carbonated concrete
increasing thanks to advantages connected with the possibility and with care to mortar placement and curing and to the proper
of preserving carbonated concrete and minimising the altera- embedment of reinforcement (i.e., proper concrete cover), the
tion of the surface, which make these techniques attractive for expected service life may be relatively long, also thanks to
facades or monuments that have a high cultural, historical or the imperviousness of repair mortars, that hinder further car-
architectural value. Electrochemical techniques allow repas- bonation (ACI 546R-96, 1996; BRE Digest 444-3, 2000; EN
sivation of the steel through the application of a temporary 1504-9, 2009; Schiessl, 1994). However, according to the
or permanent cathodic current. These techniques have been depth of carbonation and the thickness of the concrete cover,
used for several decades, although some aspects connected it may be required to remove large amounts of concrete. This
with their application have not been clarified yet. This paper operation is usually undesirable due to the massive production
presents a state-of-the-art on the techniques of electrochemi- of waste, noise and dust that may affect the serviceability of
cal realkalisation and cathodic protection used in carbonated the structure, in particular in the presence of large amounts of
concrete, and describes the recent developments in this field, carbonated, but structurally sound concrete.
with particular reference to experimental investigations and An alternative to conventional repair is provided by electro-
on-site applications carried out in Italy in recent years. chemical techniques that aim to stop reinforcement corrosion
by applying a cathodic current (Bertolini, Elsener, Pedeferri,
Keywords: carbonation; cathodic protection; electrochemi- & Polder, 2004; COST 521, 2003; Liu & Shi, 2009). The
cal realkalisation; reinforced concrete; repair. application may be temporary, as in the case of electrochemi-
cal realkalisation, or permanent, as in the case of cathodic
protection, and is obtained with an anode usually placed on
1. Introduction the concrete surface and generally connected with a power
supply (Figure 2). Electrochemical techniques do not require
The repair of reinforced concrete suffering carbonation- the removal of all carbonated concrete, since the protection
induced corrosion is a problem of great concern due to the large of steel from corrosion is guaranteed by the effects of the
number of structures, buildings and other artefacts exposed to applied current: only already damaged concrete (e.g., cracked
the atmospheric environment experiencing this phenomenon. or delaminated) has to be repaired locally. This allows reduc-
Steel reinforcement, which is initially passive as a result of the ing the consequences connected with concrete removal and
contact with alkaline hydrated cement paste, starts to corrode to preserve as much as possible the original concrete. To this
when the carbonation front reaches the rebar depth due to the regard, it should be mentioned that in Italy, as well as in many
reaction with atmospheric carbon dioxide. After corrosion ini- other European countries, many modern buildings made with
tiation, the corrosion rate mainly depends on moisture content reinforced concrete, even of recent construction, are protected
in the concrete, being negligible (i.e., lower than 1 mA/m2, from demolition or excessive alteration due to their histori-
which means roughly 1 m/year) in dry environments (i.e., cal or architectural value, and this aspect may be of primary
relative humidity lower than 7080%, as in the case of internal importance in the selection of the repair technique. As a con-
exposure) and higher than 10 m/year in wet environments sequence, increasing attention is dedicated to the conservation
(i.e., relative humidity higher than 90% or in the presence of reinforced concrete, thanks to the awareness of its peculiar-
of occasional wetting) (Glass, Page, & Short, 1991). When ities with respect to more traditional historical materials, such

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
180 E. Redaelli et al.: Electrochemical techniques in carbonated concrete

realkalisation occurs on two fronts: from the rebar towards


the concrete surface and from the concrete surface towards
the reinforcement; when the two fronts overlap, the entire
concrete cover is realkalised (Figure 3).
Compared to conventional repair, ER allows preserving
carbonated concrete, provided it has not been damaged by
steel corrosion, and being a temporary treatment it reduces
the alteration of the concrete surface since the anodic system
is needed only during the application of the current. Typically,
the anodic system is distributed on the concrete surface and
being flexible it can be adapted even on elements of complex
shape, and it is removed at the end of the treatment. The use of
small localised and sacrificial anodes has also been proposed
Figure 1 Evolution of steel corrosion in time during initiation and (Pollet, Guerin, Tourneur, Mahouche, & Raharinaivo, 1997;
propagation phases and consequences of the formation of corrosion Tong, Bouteiller, Marie-Victoire, & Joiret, 2009). For these
products (Bertolini, 2008). reasons, ER is becoming more and more attractive when it
is required to preserve the original aspect of concrete surface
and it can be advantageous compared to conventional repair
as stone and brick (De Jonge, 1997; Heinemann, Van Hees, & in the presence of large amounts of carbonated but sound
Nijland, 2008). concrete and small amounts of cracked concrete to be locally
In this paper, included in the special issue dedicated to repaired with mortar.
Corrosion in Italy, a state-of-the-art on the techniques of ER was introduced in Norway in the 1980s (Noteby, 1987;
electrochemical realkalisation and cathodic protection in Vennesland & Miller, 1992) and since then it has mainly
carbonated concrete will be presented. The main recent find- been used in Northern Europe and North America (Elsener,
ings in this field will be reviewed, with particular reference to Zimmermann, Brchler, & Bhni, 1997; Mietz, 1998;
experimental investigations and on-site applications carried Odden, 1994; Polder & Van den Hondel, 1992; Velivasakis,
out by the authors in Italy. Henriksen, & Whitmore, 1998). In Italy only few cases of
application of ER have been reported (Bertolini, Carsana,
& Redaelli, 2006; Bertolini, Carsana, & Redaelli, 2008;
2. Electrochemical realkalisation Bertolini, Redaelli, Lattanzi, & Mapelli, 2010), but the inter-
est in its potentialities is increasing, mainly in the field of
Electrochemical realkalisation (ER) is a temporary treat- cultural heritage. The aim of ER (as of any other repair tech-
ment that aims at restoring concrete alkalinity through the nique) is to stop steel corrosion and to avoid the occurrence of
application of a cathodic current and, therefore, at recreating carbonation-induced corrosion for the expected residual life,
an environment which is favourable to steel repassivation. typically 1020 years. However, experiences on the long-term
Concrete realkalisation is obtained through the application of effects of ER treatment are lacking in the scientific literature.
currents of 12 A/m2 with respect to steel surface for a period To discuss the effectiveness of ER, data on the effects of the
ranging from few days to few weeks (Bertolini et al., 2004). treatment on concrete alkalinity and on the corrosion condi-
During the treatment, hydroxyl ions are produced at the rebar tions of steel will be considered in the following sections and
surface and, at the same time, an alkaline solution applied examples of on-site application of ER carried out in Italy will
on the surface penetrates the concrete. As a consequence, be presented.

Figure 2 General schematisation of electrochemical techniques applied to reinforced concrete (Bertolini et al., 2004).

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
E. Redaelli et al.: Electrochemical techniques in carbonated concrete 181

Figure 3 Evolution of concrete realkalisation following application of ER treatment (Bertolini et al., 2004).

2.1. Effects of ER on concrete of realkalisation detected through phenolphthalein test (pink


toning at pH around 9) on a cylindrical specimen subject to
The main effect of ER is the restoration of concrete alkalin- a cathodic current density of 1 A/m2 for different periods of
ity, due partly to the cathodic reaction at steel surface and time: the radial thickness of realkalised concrete increases
partly to the ingress of an alkaline solution from outside. To with time, reflecting the increase in the amount of alkalinity
this regard, the circulated charge density, i.e., the product produced at the steel surface (Redaelli & Bertolini, 2011a).
between the applied current density and the duration of the Figure 4 also shows the contribution to concrete realkali-
treatment is usually considered as the main influencing factor. sation of the alkaline solution penetrating from outside, that
For instance, the European Standard on realkalisation indi- results in an external ring coloured by the indicator: also in
cates a circulated charge of 200 Ah/m2 that should be reached this case, the thickness of the realkalised ring increases with
before terminating the treatment (CEN/TS 14038-1, 2004). time, however it is not clear whether the applied current plays
This stems from a basic electrochemistry principle, i.e., the a role on the ingress of the alkaline solution, whose mecha-
fact that the amount of hydroxyl ions produced at the steel/ nism is not completely clear. Although in-depth studies on
concrete interface is proportional to the applied cathodic cur- the possible mechanisms involved are not available, many
rent, and that, after their production, hydroxyl ions contrib- experimental tests indicate that in the presence of an applied
ute to the current flow, moving towards the anode. This can current the penetration of the alkaline solution is higher com-
be seen, as an example, in Figure 4 that shows the evolution pared to that expected with mechanisms of diffusion and/or

Figure 4 Evolution of realkalisation fronts detected with phenolphthalein test during the application of 1 A/m2 on the rebar of a specimen
made with a concrete with w/c ratio of 0.55 and slag cement (Redaelli & Bertolini, 2011a).

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
182 E. Redaelli et al.: Electrochemical techniques in carbonated concrete

absorption, and, as a consequence, support the hypothesis To this regard, it should also be mentioned that the use of
that the applied current forces the solution into the concrete phenolphthalein, which is very common in practice, as also
pores, mainly due to electro-osmotic phenomena (Andrade, suggested by the European Standard on realkalisation (CEN/
Castellote, Sarra, & Alonso, 1999; Polder & Van den Hondel, TS 14038-1, 2004), only discriminates regions with pH higher
1992). However, other authors have also reported that the or lower than about 9 and does not allow small variations of
penetration is the same as in natural conditions, i.e., without pH values above the threshold of 9 to be detected. Concrete
applied current (Mietz, 1995). The conditions of humidity with pH around 13 is obviously very different (in terms of
content in the concrete prior to the treatment, to which little protection to steel from corrosion) from concrete with pH
attention is dedicated in the literature, may have an effect on around 10, but after phenolphthalein test their colour is the
the ingress mechanism in the initial stages, when concrete sur- same; only a qualitative difference might be evidenced by
face gets in touch with the solution and, being hygroscopic, it a different intensity of the colour. It should always be con-
will suck the solution if its pores are empty, while, if pores are sidered that a positive phenolphthalein test on concrete does
already soaked with water, a mechanism of pure diffusion is not necessarily mean that concrete is protected from corro-
expected (before the application of the current). However, it sion, since this can only be achieved for pH values of at least
seems unlikely that the initial humidity conditions of concrete 11.5. So, although values of pH higher than 13 are likely to
may affect the ingress mechanism in the long term, after the be reached at the steel surface, the use of phenolphthalein test
initial transitory period of wetting. to detect realkalised concrete can only give an indication on
Recent laboratory tests carried out comparing the penetra- the evolution of the treatment; a higher extent of coloured
tion of alkaline solution in specimens of mortar with and concrete may be due to a higher porosity of concrete, that pro-
without applied current suggest that the current promotes the moted the distribution of alkalinity away from its source, and
ingress of alkaline solution (Bertolini, Lupica Spagnolo, & not necessarily to a higher effectiveness of the treatment. As
Redaelli, 2012). Tests were performed with two different pH a matter of fact, it is expected that the durability of concrete
indicators, phenolphthalein and a commercial indicator which realkalisation, i.e., its permanence in time, may be reduced
turns blue for pH values higher than 12, enabling the realkali- due to possible mechanisms such as, e.g., a new reaction of
sation due to cathodic reaction to be distinguished from real- carbonation or leaching of alkaline constituents, all of which
kalisation due to electrolyte penetration. It was observed that are enhanced by an increase of porosity; however, no informa-
the extent of realkalised area due to electrolyte penetration tion on this is available in the literature. For instance, it is not
was higher when a current was applied, indicating a higher clear if carbonation can further propagate after the treatment,
amount of penetrated solution. and what would be the nature of such a reaction in realka-
A proper circulated charge density, obtained with an ade- lised concrete, since portlandite crystals are no longer present
quate combination between applied current and duration of due to the first carbonation process. Experimental tests are
treatment, allows obtaining the realkalisation of concrete over presently carried out to investigate this issue.
thicknesses of the order of several tens of millimetres, which The type of cement may also have an effect on the extent of
are the typical values of concrete cover. However, also param- realkalised concrete: i.e., tests carried out on concrete speci-
eters connected with concrete properties contribute to deter- mens with the same mix proportions (i.e., the same dosage of
mine the realkalisation thickness on both fronts. Concrete cement, water and aggregate) but two different cement types,
porosity plays an important role, as for all other transport phe- i.e., limestone portland cement and ground granulated blast
nomena. For instance, for a given applied current density and
duration, the thickness of realkalised concrete due to cathodic
reaction is higher for concretes with higher water/cement ratio
(Bertolini et al., 2012). For instance, Figure 5 compares the
evolution of realkalisation on concrete with different types of
cement (Redaelli & Bertolini, 2011a), water/cement ratio of
0.55 (shown in Figure 4) and 0.70. The realkalised thickness
around the steel bar (dark grey lines in the lower part of the
Figure) is higher for concrete with w/c of 0.70, which has a
higher porosity compared to concrete with w/c of 0.55. Since
the amount of alkalinity produced by the cathodic reaction
is expected to be the same, being the applied current density
the same, the higher realkalised thickness indicates an easier
transport of hydroxyl ions away from steel surface. Although
phenolphthalein does not allow small pH differences to be
detected, it can be assumed that the local values of pH of real-
kalised areas are slightly lower in the case of w/c of 0.70, due
to a higher dilution of the produced alkalinity. Also realkali-
sation thickness due to the ingress of alkaline solution from Figure 5 Position of internal and external realkalisation fronts
outside is affected by concrete porosity: this is also shown by in specimens made with different concrete mixes, after different
the light grey lines in the upper part of Figure 5. durations.

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
E. Redaelli et al.: Electrochemical techniques in carbonated concrete 183

furnace slag cement, showed different realkalised areas. In and such value can be achieved in the vicinity of steel surface
particular, concrete with slag cement showed lower internal due to the applied cathodic current. Hence, it has often been a
realkalised thickness compared to that with limestone port- priori assumed that after ER treatment, steel is repassivated.
land cement. This is usually considered to be related to the However, a number of experimental tests that investigated
lower initial alkalinity and lower porosity of slag cement the corrosion behaviour of steel after the application of ER
concrete compared to limestone portland cement concrete. showed a different behaviour of steel in realkalised concrete
However, the external realkalised thickness was higher for compared to steel in an originally alkaline concrete. In this
slag cement concrete. If concrete contains chlorides, even in regard, the corrosion conditions of steel before the applica-
small amount, the thickness of realkalisation due to cathodic tion of the treatment seem to be a key factor. For instance,
reaction is lower compared to chloride-free concrete: this is Figure 6 shows the values of corrosion rate measured on
also visible in Figure 5 and it can be attributed to the contri- steel bars embedded in concrete with different composition,
bution of chloride ions to the transport of current, which is before and after the treatment, during exposure to a wet envi-
beneficial in moving chlorides away from steel surface, but ronment. Corrosion rate was measured through the linear
reduces the amount of hydroxyl ions that contribute to the polarisation resistance technique and expressed as current
current, and so the thickness of realkalisation will be more density (Andrade & Gonzlez, 1978; Stern & Geary, 1957).
localised around the steel bar. A decrease in the corrosion rate was observed on specimens
The evaluation of the effectiveness of ER cannot neglect that had been exposed to a wet environment for a period of
the durability of its effects, i.e., of concrete realkalisation, about three months before and after the application of ER: for
since, after the treatment, the concrete will be in contact with instance, in concrete made with limestone portland cement
the same environment as before, and thus will be again sub- and w/c of 0.55, the corrosion rate passed from 11 mA/m2 to
ject to carbonation. As it was mentioned earlier, very few data 4 mA/m2, in concrete made with limestone portland cement,
exist on this issue. The alkaline electrolyte penetrating from w/c of 0.55 and 0.4% of chlorides with respect to cement
the surface into the concrete pores has a pH of about 10.5, not mass, it changed from 20 mA/m2 to 8 mA/m2 and in con-
exceeding 11, that may not be able to passivate the steel by crete made with slag cement and w/c of 0.55 from 12 mA/m2
itself. On the other hand, the alkaline solution is believed to to 4 mA/m2. In these cases, although the values after the
buffer pH, hindering further carbonation: indeed, some stud- treatment cannot be considered negligible, the effect of the
ies on realkalised structures demonstrate that the alkalinity of treatment in reducing corrosion activity of steel is evident.
treated concrete is kept in time (Tong et al., 2009) and that Some other specimens were exposed to the wet environment
the sodium carbonate introduced into carbonated zones does for a period of a year before the treatment, in order to pro-
not migrate away at an easily measurable rate (Miller, 1998). mote some pre-corrosion of steel bars, which is what may be
It has also been suggested that ER leads to a densification expected to occur in real structures before the application of
of concrete (Banfill, 1997; Yeih & Chang, 2005), especially ER treatment. In this case, the corrosion rate measured after
around the steel reinforcement, and this is also expected to ER was even higher than before: i.e., it passed from 13 mA/m2
prevent future carbonation. to 24 mA/m2 in concrete with w/c of 0.7 without chlorides and
Potentially, a number of side effects may also occur in con- from 26 mA/m2 to 42 mA/m2 in concrete with the same w/c
crete following the application of ER, such as any other elec- and 0.4% of chlorides (Figure 6). This effect was also con-
trochemical treatment (Page, 1992). Latent alkali-aggregate firmed on similar specimens exposed to a dry environment
reaction (AAR) may be triggered by the increased amount
of alkali in concrete. This could only occur if aggregates are
susceptible to this attack, and this type of damage has never
been reported in connection with ER treatment (Mietz, 1995);
nevertheless, if the risk of AAR cannot be neglected, lithium-
based electrolytes have been proposed. Also the risk of reduc-
tion of bond strength due to the impressed current should be
considered as potential side effect: this is believed to become
significant above levels of circulated charge much higher
than usually applied. A proper condition evaluation before the
application of the treatment is necessary to prevent these side
effects.

2.2. Effects of ER on steel

Obviously the aim of ER treatment is not the realkalisation


of concrete itself, but rather the interruption of corrosion on Figure 6 Average values of corrosion rate of steel measured with
steel reinforcement. As it was mentioned in the previous sec- polarisation resistance technique, in a wet environment, before
tion, according to the theory of corrosion a pH value higher and after ER treatment, for different concrete mixes (Redaelli &
than 11.5 is necessary to passivate the steel (Pourbaix, 1974), Bertolini, 2011a).

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
184 E. Redaelli et al.: Electrochemical techniques in carbonated concrete

(Redaelli & Bertolini, 2011a). It should be noted that poten- effect of the applied cathodic current, which is consistent with
tial measurements carried out on the same specimens showed the theory of corrosion, i.e., with the progressive beneficial
that steel potential increased in all cases after the treatment, effect of an applied cathodic current in the protection of steel
which would suggest changes towards repassivation. It should from corrosion. These results are in agreement with similar
also be noted that the evaluation of corrosion conditions of tests that were previously reported (Mietz, 1995).
steel after the application of electrochemical treatments by It should be observed that, also from the point of view of the
means of electrochemical technique has been questioned steel behaviour, possible side effects of ER can be considered.
(Mietz, 1998). So the increase of corrosion rate may be due These are mainly related to possible induction of hydrogen
to unsuitability of linear polarisation technique, however it is embrittlement on high strength steel. Since the application of
not clear why the increase is observed only on pre-corroded high cathodic currents may promote hydrogen evolution at the
steel. Also to this regard, further tests are being carried out to steel surface, ER is considered unsuitable in the case of pre-
clarify these aspects. It should also be noted that the increase stressed structures with high strength steel (COST 534, 2009).
in corrosion rate after ER treatment has also been reported by
direct measurements of weight loss (Kubo, Sawada, Page, &
Page, 2008). It has even been suggested that ER may only be 2.3. On-site applications in Italy
effective as a preventative measure against corrosion, before
the carbonation front reaches the steel or for steel repassiva- An on-site application of ER was done on the church of S.
tion at an early corrosion stage (Gonzlez, Cobo, Gonzlez, Antonio abate in Valmadrera, in Italy. The church was built
& Otero, 2000). in 19261930 and includes a bell tower, in the upper part
In those cases when the effectiveness of ER in reducing of which is located a small circular temple made of eight
corrosion rate has been assessed, the circulated charge is an columns overhung by a dome (Bertolini et al., 2008). All
important factor in determining the level of protection reached the columns are made of reinforced concrete and they are
by the steel: for instance, Figure 7 shows the current density hollow: the thickness of the concrete wall ranges from 55 mm
measured during potentiostatic anodic tests with an applied to 78 mm. Owing to its high historical value and architec-
potential value of 150 mV vs. SSC, on specimens subject tural significance, the church is part of the Italian National
to ER with applied current of 0.5 A/m2 for different periods Cultural Heritage. A preliminary survey showed that cracks,
(7, 14 and 21 days), i.e., different circulated charge density delaminations and spalling of the concrete cover were pres-
(84, 168 and 252 Ah/m2). The polarisation current measured ent on the columns (Figure 8). Afterwards, measurements of
during polarisation tests may be used to discriminate condi-
tions of passivity (expected low values of current density)
from conditions of activity (high values of current density).
The current measured during potentiostatic tests was around
2000 mA/m2 for the reference specimens (i.e., active steel in
carbonated concrete), and decreased to 40, 4 and 2.5 mA/m2
increasing the circulated charge density from 84 to 252 Ah/m2
(Bertolini et al., 2012). The reduction of the measured current
density obtained increasing the duration indicates a beneficial

Figure 7 Current density measured during anodic potentiostatic


tests on specimens subject to ER treatment with different durations Figure 8 View of reinforced concrete columns on the bell tower
(7, 14 and 21 days) and on the reference specimen (Ref). Applied of the church of S. Antonio abate in Valmadrera (Bertolini et al.,
potential value: +150 mV vs. SSC (Bertolini et al., 2012). 2008).

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
E. Redaelli et al.: Electrochemical techniques in carbonated concrete 185

carbonation depth, steel potential and thickness of concrete


cover were carried out. Carbonation depth showed a very
uneven distribution: the thickness of the carbonated concrete
ranged from 1 mm to 55 mm (equal to the whole thickness
of the concrete wall). Similarly, the thickness of the concrete
cover showed an irregular distribution. It was decided to
make an intervention on the columns in order to stop steel
corrosion, by applying ER treatment with a current density
of 0.8 A/m2 for 21 days. Figure 9 shows the potential of steel
measured with internal reference electrodes during and after
the application of the current: the steel reached very nega-
tive potential values, between -1 and -2 V vs. CSE. After the
end of the treatment, the steel potential increased and reached
potential values of about -350 mV vs. CSE more than a month
after the end of the treatment. Phenolphthalein tests on cores
taken from the columns indicated complete alkalinity of con-
crete, mainly due to the cathodic reaction which had a domi-
nant effect compared to the ingress of alkaline electrolyte.
A trial application of ER was also carried out on the pillars
of the church of Santa Maria dellAnnunciata at the San Carlo
Borromeo hospital in Milan that was designed by the architect
Gio Ponti and was built in 19641967 (Bertolini et al., 2010).
The structure of the church is made of reinforced concrete;
externally the walls are covered with ceramic tiles, while the
pillars are in fair-faced concrete. The pillars showed deterio-
Figure 10 View of corrosion-induced damage on a reinforced con-
ration phenomena due to reinforcement corrosion (Figure 10).
crete pillar of the church of Santa Maria dellAnnunciata at the San
In this case, a study aimed at comparing the effectiveness of Carlo Borromeo hospital in Milan (Bertolini et al., 2010).
different repair strategies on selected areas of the pillars was
carried out. The evolution of the ER treatment was evaluated
with potential measurements and phenolphthalein tests on Although it is usually believed that ER treatment does not
concrete cores (Figure 11). Comparing the potential of steel require any monitoring after application, in the opinion of the
in different areas of the pillars (Figure 12), it can be observed authors it is advisable not only to check its proper functioning
that, whilst reference non-treated concrete is characterised during and at end of current application, but also to anticipate
by higher steel potential values compared to realkalised con- future monitoring. While the measurement of corrosion rate
crete, the potential decrease observed after artificial wetting on-site is rather complex, the corrosion potential is easier to
of concrete surface (simulating wetting from the rain) is lower detect, also with embedded reference electrodes that allow
in realkalised concrete, indicating a lower effect of humidity a continuous monitoring. Nevertheless, as it was mentioned
which is consistent with steel repassivation. earlier, potential measurements after electrochemical treat-
ments are not easy to interpret and may not be directly related
to corrosion conditions of steel reinforcement. Anyway,
investigations carried out on real structures may be helpful in
the understanding of effects of ER treatment, in particular in
the long-term.

3. Cathodic protection

Cathodic protection (CP) is a permanent technique that


applies current densities around 510 mA/m2 with respect to
steel surface, much lower compared to that used in ER. CP
of steel in concrete was initially introduced in the 1970s to
stop chloride-induced corrosion on highway bridges contami-
nated by de-icing salts (Lazzari & Pedeferri, 2006; Stratfull,
1974); in this field, as well as for structures and buildings
exposed to marine environments, CP is recognised as the only
Figure 9 Steel potential measured on the eight columns (AH) repair technique that can stop chloride-induced corrosion
before, during and after the treatment of realkalisation (Bertolini (Wyatt, 1993). Initially CP was not applied on carbonated
et al., 2008). concrete, that was considered much less aggressive compared

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
186 E. Redaelli et al.: Electrochemical techniques in carbonated concrete

Figure 11 Phenolphthalein tests carried out on cores taken in two adiacent areas from a pillar of the church of Santa Maria dellAnnunciata
at the San Carlo Borromeo hospital in Milan: before (A) and after (B) realkalisation (Bertolini et al., 2010).

to chloride-contaminated concrete, and the repair of carbon- the current they supply is determined by the driving voltage
ated concrete was carried out in the conventional way, that and the electrical resistance between steel and anode. In the
was considered more than suitable. P. Pedeferri, in the 1990s, case of impressed systems, attention should be paid to avoid
introduced advantages of CP in carbonated concrete explain- direct contact between steel and anode; in the case of sacrifi-
ing that it acts with a mechanism similar to ER, which he cial systems, the anode is directly connected to the steel and
called continuous realkalisation. The small cathodic cur- this often allows the need of connecting cables to be avoided.
rent provided by CP may, in time, promote realkalisation of Both in impressed current and sacrificial CP systems, the
a thin layer of concrete surrounding the steel bars in carbon- anode can be distributed, i.e., applied on the whole concrete
ated concrete, inducing steel repassivation (Pedeferri, 1996). surface, or localised, i.e., applied in small areas of the surface
Today CP is considered as one of the possible effective options or inserted in cavities in the concrete.
for the repair of structures, buildings and facades suffering It was shown that repassivation of steel may be favoured
carbonation-induced corrosion. Similarly to ER, it allows the by the application of an initial high initial current density
original concrete to be preserved, but being a continuous tech- that promotes faster realkalisation of concrete. For instance,
nique, it has to be applied throughout the residual service life with laboratory tests it was shown that current densities of
of the structure in order to keep corrosion rate under control. 70100 mA/m2 applied for a few weeks to steel in carbonated
This, however, requires constant monitoring in time. concrete may be effective in promoting steel repassivation,
The current is traditionally applied with impressed cur- while several months were required with a current density
rent distributed inert anodes, as metallic meshes embedded of 10 mA/m2. Once repassivation of steel is achieved, this
in mortar or conductive coatings, although other anodic con- is subsequently maintained with lower current densities of
figurations are possible and the use of sacrificial anodes is 510 mA/m2 (Bertolini, Pastore, Pedeferri, & Redaelli, 2003).
increasing (Page & Sergi, 2000). Impressed systems allow Therefore, in the design of CP for carbonated concrete struc-
the applied current to be adjusted in case of under protection tures, the benefit of an initial start-up current may be taken
or over protection; sacrificial anodes are self-regulating since into consideration.

Figure 12 Average potential of steel in reference areas (A) and realkalised areas (B). Dotted lines indicate artificial wettings and their dura-
tion, while grey area indicates ER treatment (Bertolini et al., 2010).

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
E. Redaelli et al.: Electrochemical techniques in carbonated concrete 187

Since CP relies on the application of a continuous cur- 3.1. Case study on CP with localised anodes
rent, the protection from corrosion needs to be properly
monitored in time to check the correct functioning of the An alternative to ordinary CP applied with distributed anodic
system. The need for a monitoring system differentiates system, which causes the complete alteration of the concrete
CP from temporary techniques. Although several methods surface, is the use of localised anodes. Localised anodes can
have been proposed in the literature (Bennet & Broomfield, have the shape of small cylinders to be inserted inside con-
1997; Glass, Hassanein, & Buenfeld, 1997; Rizzo, 1988), crete or thin stripes or wires to be placed on the concrete sur-
monitoring of reinforcement under CP is usually based on face. In principle, localised anodes can be used either with
measurement of absolute potential or potential decay (ISO impressed current or as sacrificial anodes; however, sacrifi-
DIS 12696, 2009), the latter being more reliable since the cial anodes are more suitable for the use as localised anodes
absolute potential depends on many factors in concrete. since, being directly connected with steel reinforcement, they
Steel potential has to be measured with on-off techniques do not require external cables for connection to power supply
to avoid ohmic contribution. According to the potential and/or monitoring system. The use of localised anodes has
decay criterion, it is usually assumed that steel under CP been introduced as a preventative measure in patch-repaired
can be considered protected from corrosion if the poten- concrete (Page & Sergi, 2000); later on, it was also suggested
tial decay measured after interruption of the current is to use localised anodes in hybrid systems, i.e., initially
higher than 100 mV in a period of 4 or 24 h. This is the with impressed current and then as sacrificial anodes (Glass,
100-mV criterion, which is a semi-empirical criterion for Roberts, & Davison, 2008). These applications, however,
atmospherically exposed structures. It relies on the increase were mainly concerned with concrete suffering chloride-
of steel potential after depolarisation that is expected after induced corrosion and limited area to be protected. Advantages
steel repassivation, which is not merely connected with the of sacrificial anodes have also been shown for the prevention
potential decrease due to the applied current, but also with of corrosion initiation in the splash zone of marine structures
the chemical changes induced by the current at the steel (Bertolini, Gastaldi, Pedeferri, & Redaelli, 2002; Bertolini &
surface, typically the local increase of concrete alkalin- Redaelli, 2009).
ity and the migration of chlorides (if present) towards the Carbonated concrete, in spite of being a less aggressive
anode (Glass & Chadwick, 1994). environment towards steel, is characterised by higher electri-
Whilst many publications investigate the effectiveness of cal resistivity and it is usually exposed to atmospheric condi-
CP in chloride-contaminated concrete structures, much less tions, and problems connected with current distribution typical
investigations have been devoted to CP in carbonated con- of localised anodes are thus emphasised: reinforcement closer
crete. Among these, an experimental research studied the to the anode will receive higher currents, thus undergoing a
effect of concrete composition, environmental conditions higher risk of problems connected with the application of a
and pre-corrosion of steel on the effects of CP applied with high cathodic current density (e.g., hydrogen embrittlement
a current density of 10 mA/m2 preceded by a start-up value in the presence of high strength steels), whilst reinforcement
of 100 mA/m2 for three weeks (Redaelli & Bertolini, 2011b). far from the anode will receive low or no current, thus lack-
The results obtained indicate that the realkalised thickness of ing protection from corrosion. As a consequence, the use of
concrete around the steel after the start-up period is of the localised sacrificial anodes should always be preceded by
order of few millimetres, and with such small values no effect a careful study of current and potential distribution, either
of water/cement ratio, cement type or chloride content has experimental or by means of numerical simulations, with the
been detected. However, the presence of this layer of alkaline aim of determining the number of anodes and their position
concrete, detected with phenolphthalein indicator, is (again) so that the cathodic current supplied will be able to reach all
not correlated to corrosion conditions of steel that were inves- the steel reinforcement that need protection, avoiding regions
tigated with 4 h depolarisation tests and indicated that only of overprotection.
specimens made with chloride-free concrete have 4-h decays For instance, a study carried out through numerical simula-
higher than 100 mV. Afterwards, during the continuous appli- tions of current distribution in carbonated concrete showed
cation of 10 mA/m2, the 4-h decay progressively increases, that, in the presence of elements with slender geometry, the
however for a given concrete composition pre-corroded rein- number of anodes that are necessary to protect all the rein-
forcement always has lower 4-h decays compared to non- forcement may partly reduce the advantages connected with
pre-corroded specimens, in particular in the wet environment. localised anodes. Figure 13 shows, as an example, the polari-
As for ER, also for CP the protection of steel from corro- sation and current density along the height of the reinforce-
sion is reached with more difficulty if steel is pre-corroded, ment of a concrete element containing longitudinal steel bars
and so the sooner it is applied, the more effective it will be. in the front and in the rear part, with three sacrificial anodes
However, unlike in ER treatment, in CP the lack of protection placed in the front part. It was assumed that concrete was car-
indicated by 4-h decays lower than 100 mV can be overcome bonated in the front part (in contact with the atmosphere) and
(in impressed current systems) increasing the applied cur- alkaline in the rear part (embedded in masonry), and proper
rent in order to reach more stable conditions of protection or conditions describing the behaviour of steel were specified as
reducing the time necessary to protect the steel. This should a function of humidity and alkalinity/carbonation of concrete
always be carefully considered in the design phase if hydro- (Redaelli, Lollini, & Bertolini, 2011). It can be seen that only
gen evolution has to be avoided. parts of rebar close to the localised sacrificial anodes receive

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
188 E. Redaelli et al.: Electrochemical techniques in carbonated concrete

Figure 13 Reinforced concrete element subject to CP with localised sacrificial anodes (A), distributions of cathodic polarisation (B) and of
current density (C) obtained by FEM numerical simulations.

enough current to be protected (in this case, protection was a consequence, the use of electrochemical techniques is
evaluated with a modified decay criterion), while parts far increasing. In the case of carbonation-induced corrosion, two
from the anode do not receive enough current. With similar techniques can be used: electrochemical realkalisation and
simulations it was estimated that full protection of steel in cathodic protection.
carbonated concrete during wetting periods can be achieved In the case of the temporary technique of electrochemi-
by placing anodes at a distance of 0.5 m from each other. cal realkalisation, the realkalisation of concrete detected
Although current distribution is likely to be the major with phenolphthalein test is mainly affected by the circulated
problem connected with the application of CP with loca- charge density, however also concrete porosity, cement type,
lised sacrificial anodes in carbonated concrete, another factor and the presence of chloride may play a role. The mechanisms
that should be considered is the consumption of the anode involved in realkalisation due to electrolyte penetration, as
material due the anodic reaction of metal dissolution. These well as the physical changes induced in the concrete, have
anodes are usually made of zinc embedded in an activating not been clarified yet. Also the parameters that may affect the
medium. The smaller is the anode, the higher is the current corrosion conditions of steel after the treatment need further
density supplied and therefore, according to Faradays law, investigation, in order to assess the complete reliability of the
the higher is the rate of consumption of zinc. This factor may technique and the possible ways to determine it, in particular
limit the time duration of the anodic system, however it is in the presence of high level of steel corrosion prior to the
difficult to estimate in advance since it depends on all the fac- application of the treatment.
tors influencing the current, such as the number of anodes and In the case of cathodic protection, which is based on the
their position and the trend of environmental conditions (that application of a continuous current, steel pre-corrosion as
determines the electrical resistivity of concrete). Also in this well as the presence of chlorides also have an effect on the
regard, experimental trials or numerical simulations are nec- fulfilment of protection on steel, in particular in wet environ-
essary to make an estimation of the current, and therefore, of ments. However, in this case a lack or reduced protection can
the anode duration, in particular if on-site monitoring is not be overcome by a proper increase in the applied current, pro-
feasible. vided no risk of hydrogen embrittlement occurs.
Works reported in the literature show that under specific
conditions the electrochemical techniques of ER and CP are
4. Concluding remarks effective in controlling the corrosion rate of steel in carbonated
concrete, preserving meanwhile concrete. Nevertheless, as dis-
The repair of reinforced concrete buildings, facades or monu- cussed in the paper, there are still several open questions which
ments that have a high cultural, historical and architectural need further research in order to provide input data regarding
value requires the original materials to be preserved as much the selection of the technique and the most appropriate moment
as possible and reduce the alteration of the surface and, as to apply it (especially in the case of temporary treatment).

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
E. Redaelli et al.: Electrochemical techniques in carbonated concrete 189

Furthermore, there is still opportunity for improvement in the Bertolini L, Lupica Spagnolo S, Redaelli E. Electrochemical realka-
application of electrochemical methods. For instance, the appli- lisation as a conservation technique for reinforced concrete. Int J
cation of cathodic protection with localised and sacrificial anodes Archit Herit 2012; 6: DOI: 10.1080/15583058.2010.528147.
has been introduced recently with the aim of reducing the inva- BRE Digest 444-3. Corrosion of steel in concrete Part 3: Protection
and remediation, Building Research Establishment, Garston,
siveness of the technique and the alteration of the surface. When
UK, 2000.
considering such intervention, it should be considered that the
CEN/TS 14038-1. Electrochemical realkalization and chloride extrac-
durability of the anode is expected to be lower compared to inert tion treatments for reinforced concrete-Part 1: Realkalization
anodic systems due to anode consumption. The study of current 2004.
distribution, either by means of trial tests or numerical simula- COST Action 521. Corrosion of steel in reinforced concrete struc-
tions, may allow to determine the anode configuration (in terms tures, Final Report 2003.
of number and position of anodes) that optimises protection to COST Action 534. New materials, systems, methods and concepts
steel and also to estimate anode consumption. for prestressed concrete structures. Final Report 2009.
De Jonge W. Concrete repair and material authenticity: electrochem-
ical preservation techniques. APT Bulletin 1997; 28: 5157.
Acknowledgements Elsener B, Zimmermann L, Brchler D, Bhni H. Repair of rein-
forced concrete structures by electrochemical techniques field
The authors would like to dedicate this paper to the memory of Pietro experience. In: Proceedings of Eurocorr, Trondheim, Norway,
Pedeferri acknowledging his great contribution to the development 1997. pp. 517522.
of electrochemical techniques in reinforced concrete. EN 1504-9. Products and systems for the protection and repair of
concrete structures definitions, requirements, quality control
and evaluation of conformity Part 9: general principles for the
References use of products and systems. 2009.
Glass GK, Page CL, Short NR. Factors affecting the corrosion rate of
ACI 546R-96. Concrete repair guide. Farmington Hills, MI: American steel in carbonated mortars. Corros Sci 1991; 32: 12831294.
Concrete Institute, 1996. Glass GK, Chadwick JR. An investigation into the mechanisms of
Andrade C, Gonzlez JA. Quantitative measurements of corrosion protection afforded by a cathodic current and the implications
rate of reinforcing steels embedded in concrete using polarization for advances in the field of cathodic protection. Corros Sci 1994;
resistance measurements. Mater Corros 1978; 29: 515519. 36: 21932209.
Andrade C, Castellote M, Sarra J, Alonso C. Evolution of pore solu- Glass GK, Hassanein AM, Buenfeld NR. Monitoring the passivation
tion chemistry, electro-osmosis and rebar corrosion rate induced of steel in concrete induced by cathodic protection. Corros Sci
by realkalisation. Mater Struct 1999; 32: 427436. 1997; 39: 14511458.
Banfill PF. Re-alkalisation of carbonated concrete effect on con- Glass GK, Roberts AC, Davison N. Hybrid corrosion protection of
crete properties. Constr Build Mater 1997; 11: 255258. chloride-contaminated concrete. Proc Inst Civ Eng Constr Mater
Bennet J, Broomfield JP. Analysis of studies on cathodic protection 2008; 161: 163172.
criteria for steel in concrete. Mater Perform 1997; 36: 1621. Gonzlez JA, Cobo A, Gonzlez MN, Otero E. On the effec-
Bertolini L, Gastaldi M, Pedeferri MP, Redaelli E. Prevention of steel tiveness of realkalisation as a rehabilitation method for cor-
corrosion in concrete exposed to seawater with submerged sacri- roded reinforced concrete structures. Mater Corros 2000; 51:
ficial anodes. Corros Sci 2002; 44: 14971513. 97103.
Bertolini L, Pastore T, Pedeferri P, Redaelli E. Repassivation of steel Heinemann HA, Van Hees RP, Nijland TG. Concrete: too young for
in carbonated concrete induced by cathodic protection. Mater conservation? In: DAyala D, Fodde E, editors. Structural analy-
Corros 2003; 54: 163175. sis of historic construction: preserving safety and significance.
Bertolini L, Elsener B, Pedeferri P, Polder R. Corrosion of steel in London: Taylor & Francis, 2008. pp. 151159.
concrete. Prevention, diagnosis and repair. Weinheim: Wiley- ISO DIS 12696. Cathodic protection of steel in concrete, Draft
VCH, 2004. International Standard. 2009.
Bertolini L, Carsana M, Redaelli E. Conservation of historical rein- Kubo J, Sawada S, Page CL, Page MM. Electrochemical inhibitor
forced concrete structures by means of electrochemical realka- injection for control of reinforcement corrosion in carbonated
lisation. In: Proceedings of the 2nd FIB International Congress. concrete. Mater Corros 2008; 59: 107114.
Naples, Italy. 2006 Bertolini L. Steel corrosion and service life Lazzari L, Pedeferri P. Cathodic protection. Milan: Polipress, 2006.
of reinforced concrete structures. Struct Infrastruct Eng 2008; 4: Liu Y, Shi X. Electrochemical chloride extraction and electrochemi-
123137. cal injection of corrosion inhibitor in concrete: state of the knowl-
Bertolini L, Carsana M, Redaelli E. Conservation of historical rein- edge. Corros Rev 2009; 27: 5381.
forced concrete structures damaged by carbonation induced cor- Mietz J. Electrochemical realkalisation for rehabilitation of rein-
rosion by means of electrochemical realkalisation. J Cult Herit forced concrete structures. Mater Corros 1995; 46: 527533.
2008; 9: 376385. Mietz J, editor. Electrochemical rehabilitation methods for reinforced
Bertolini L, Redaelli E. Throwing power of cathodic prevention concrete structures. A state of the art report. EFC Pubblication,
applied by means of sacrificial anodes to partially submerged no. 24. 1998.
marine reinforced concrete piles: results of numerical simula- Miller JB. The perception of the ASR problem with particular ref-
tions. Corros Sci 2009; 51: 22182230. erence to electrochemical treatments of reinforced concrete. In:
Bertolini L, Redaelli E, Lattanzi D, Mapelli M. Conservation tech- Mietz J, Elsener B, Polder R, editors. Corrosion of reinforcement
niques on the reinforced concrete pillars of the church of the San in concrete. Monitoring, prevention and rehabilitation. EFC
Carlo Borromeo hospital in Milan. Eur J Environ Civ Eng 2010; Pubblication, no. 25. Cambridge, UK: Woodhead Publishing
14: 411425. Limited: 1998. pp. 141149.

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM
190 E. Redaelli et al.: Electrochemical techniques in carbonated concrete

Noteby (Norsk Teknisk Byggekontrol). Norwegian Patent Application Redaelli E, Lollini F, Bertolini L. Throwing power of cathodic protec-
No. 875438. 1987. tion with localised anodes in slender reinforced concrete elements
Odden L. In: Swamy RN, editor. Corrosion and corrosion protec- in atmospheric environment. In: Proc Int Symposium on Cement
tion of steel in concrete. Sheffield: Sheffield Academic Press, & Concrete Materials. Ningbo, China, 2011.
1994. Rizzo FE. Flexible cathodic protection criteria. Mater Perform 1988;
Page CL. Interfacial effects of elettrochemical protection method 27: 1719.
applied to steel in chloride containing concrete. In: Ho DW, Schiessl P, editor. Draft recommendation for repair strategies for con-
Collins F, editors. Proceedings of the Int. RILEM/CSIRO/ACRA crete structures damaged by reinforcement corrosion. RILEM
Conference, Melbourne, Australia, 1992. pp. 179187. Technical Committee 124-SRC. Mater Struct 1994; 27: 415436.
Page CL, Sergi G. Developments in cathodic protection applied to Stern M, Geary AL. Electrochemical polarization. I. A theoretical
reinforced concrete. J Mater Civ Eng 2000; 12: 815. analysis of the shape of polarization curves. J Electrochem Soc
Pedeferri P. Cathodic protection and cathodic prevention. Constr 1957; 104: 5663.
Build Mater 1996; 10: 391402. Stratfull RF. Cathodic protection of a bridge deck. Mater Perform
Polder RB, Van den Hondel HJ. Electrochemical realkalisation and 1974; 13: 2425.
chloride removal of concrete. State of the art, laboratory and field Tong YY, Bouteiller V, Marie-Victoire E, Joiret S. Electrochemical
experience. In: Proceedings of the RILEM International Conference realkalisation of carbonated reinforced concrete using impressed
on Rehabilitation of Concrete Structures, Melbourne, Australia, current or sacrificial anodes 2.5 years durability. In: Proceedings
1992. of Eurocorr. Nice, France, 2009.
Pollet V, Guerin R, Tourneur C, Mahouche H, Raharinaivo A. Tuutti K. Corrosion of steel in concrete, Stockholm: Swedish
Concrete realkalisation using sacrificial anode. In: Proceedings Foundation for Concrete Research, Stockholm, 1982.
of Eurocorr, Trondheim, Norway, 1997. pp. 523528. Velivasakis EE, Henriksen SK, Whitmore D. Chloride extraction
Pourbaix M. Atlas of electrochemical equilibria in acqueous solu- and realkalisation of reinforced concrete stop steel corrosion.
tions. Houston: National Association of Corrosion Engineers, J Perform Constr Facil 1998; 12: 7784.
1974. Vennesland O, Miller JB. Electrochemical realkalisation of concrete.
Redaelli E, Bertolini L. Electrochemical repair techniques in car- European Patent Specification No. 0264421. 1992.
bonated concrete. Part I: electrochemical realkalisation. J Appl Wyatt BS. Cathodic protection of steel in concrete. Corros Sci 1993;
Electrochem 2011; 41: 817827. 35: 16011615.
Redaelli E, Bertolini L. Electrochemical repair techniques in carbo- Yeih W, Chang JJ. A study on the efficiency of electrochemical real-
nated concrete. Part II: cathodic protection. J Appl Electrochem kalisation of carbonated concrete. Constr Build Mater 2005; 19:
2011; 41: 829837. 516524.

Brought to you by | University of Queensland - UQ Library


Authenticated
Download Date | 6/13/15 10:02 PM

Anda mungkin juga menyukai