ANALYSIS OF EFFECTS CAUSED BY ARMONICS IN THE ELECTRICAL
NETWORKS
Harmonic distortion levels have increased significantly in recent years mainly due to the
increase in the number of electronic devices connected to the network. The improvement of
our standard of living is accompanied by a growing increase of elements such as personal
computers, air conditioners and heat pumps, better and more complex components in
industrial processes. In contrast, these devices lead to an increase in distortion levels in the
voltage wave. This distortion in the voltage wave results in a variation of its frequency and
nominal amplitude values, and in wave form different from the sinusoidal causing the
distribution of electrical energy to undergo disturbances and that the quality of the power is
not optimal. To attenuate the harmonics in the electrical networks, there are three different
types of solutions: Modifications in the installations, Special devices in the feeding system,
Filters; obtaining adequate diagnoses to know the harmonic contamination and in this way
to minimize economic consequences, increase of the costs of the energy, premature aging of
the equipment and losses of production.
Key words: Harmonics, Frequency, Sinusoidal, Filters, Nominal Amplitude.
INTRODUCCIN
Los armnicos se definen habitualmente con los dos datos ms importantes que les
caracterizan, que son:
Para eliminar los armnicos se procede colocando filtros. Estos Filtros estn constituidos
por conjuntos de conexiones de reactancias y capacidades. Segn las frecuencias que
eliminan estos filtros, pueden denominarse filtros pasa bajos (dejan pasar los armnicos de
bajas frecuencias y cortocircuitan o eliminan los armnicos de altas frecuencias), o bien se
denominan filtros pasa altos (en este caso actan de forma inversa a lo descrito). Garca, A.
Alabern, X (2013). Instalaciones Elctricas.
Armnicos de corriente y tensin, existentes en las redes de Media Tensin y Baja Tensin,
pueden comprometer fuertemente los transformadores hasta destruirlos. Trashorras, J.
(2013). Desarrollo de Redes Elctricas y Centros de Transformacin.
La distorsin armnica total es la relacin del valor rms de la distorsin al valor rms de la
fundamental. Debido a que la fundamental no contribuye a la distorsin, el valor efectivo de
la distorsin es la raz de la suma de los cuadrados de los valores rms de las armnicas.
Acevedo, S. & Bez, A. (2004). Armnicas En Sistemas Elctricos Industriales.
Para averiguar la calidad de la red elctrica y determinar los armnicos se emplean los
analizadores de redes. Estos equipos proporcionan diversa informacin, entre ella el factor
de distorsin armnica total THD % por siglas en ingls (Total Harmonic Distortion), que es
el valor porcentual de todos los armnicos en relacin a la frecuencia fundamental. Cerd,
L. & Blanco, P (2005). Electricidad y Automatismos Elctricos.
Los dispositivos y los sistemas que producen armnicos se encuentran presentes en todos los
sectores, es decir, el industrial, el comercial y el residencial. Los armnicos se producen por
cargas no lineales (es decir, cargas que, al ser alimentadas por una tensin senoidal, dan como
respuesta una onda de intensidad deformada, no lineal).
Las cargas no lineales generan las corrientes armnicas que circulan por la red de
distribucin. Las tensiones armnicas se producen por el flujo de corrientes armnicas a
travs de las impedancias de los circuitos de alimentacin (transformador y red de
distribucin similares a los mostrados en la Figura 1.1)
Figura 1.1. Diagrama de una sola lnea que muestra la impedancia del circuito de
alimentacin de un armnico de rango h.
La reactancia de un conductor aumenta en funcin de la frecuencia de la corriente que circula
a travs del conductor. Para cada intensidad armnica (rango h), existe una impedancia Zh
en el circuito de alimentacin. Cuando la intensidad armnica de rango h circula a travs de
la impedancia Zh, crea una tensin armnica Uh, donde Uh = Zh * Ih (ley de Ohm). Por lo
tanto, la tensin en el punto B se distorsiona. Todos los dispositivos que reciben la
alimentacin a travs del punto B reciben una tensin distorsionada. Para una intensidad
armnica determinada, la distorsin es proporcional a la impedancia en la red de distribucin.
Observemos el siguiente diagrama simplificado (ver Figura 1.2) que representa una
instalacin compuesta por:
Un transformador de alimentacin.
Cargas lineales.
Cargas no lineales que generan corrientes armnicas.
Condensadores de potencia para la correccin del factor de potencia.
=
1 2
Despreciar R y donde:
Ir = Intensidad armnica.
CASO DE ESTUDIO
Prdidas en Conductores
Por un lado, las intensidades armnicas conducen a un aumento del valor eficaz de la
corriente en los conductores, lo que puede ocasionar actuaciones intempestivas de las
protecciones. Por otro lado, a medida que aumenta la frecuencia se hacen ms pronunciados,
reduciendo la seccin efectiva del conductor. En consecuencia, se incrementan las cadas de
tensin y se sobrecalientan los conductores.
= ( )1
1
Las siglas THD equivalen a Total Harmonic Distortion, tasa de distorsin total H %
armnica, y es un indicador ampliamente utilizado en la definicin del nivel de contenido
armnico en seales senoidales.
En el caso de las cargas trifsicas y existencia de conductor neutro, si las intensidades que
consumen estas cargas generan armnicos de orden mltiplo de tres, stos circulan por el
conductor del neutro puesto que su suma no es cero, lo que produce calentamientos y su
posible destruccin si no se ha dimensionado correctamente teniendo en cuenta la naturaleza
de las cargas conectadas. Adems, pueden aparecer ruidos de frecuencia audible en cables
instalados en bandeja debido a las vibraciones y valores de tensin entre neutro y tierras
grandes.
Imaginemos un sistema compuesto por una fuente trifsica equilibrada y tres cargas
monofsicas idnticas conectadas entre las fases y el neutro (ver Figura 1.5).
Figura 1.4. Flujo de corrientes en los diferentes conductores conectados a una conexin
trifsica.
Figura 1.5. Ejemplo de las corrientes que circulan en los diferentes conductores conectados
a una carga trifsica (In = Ir + Is + It).
La Figura 1.6, muestra un ejemplo de las corrientes que circulan en las tres fases y la corriente
resultante en el conductor neutro. En este ejemplo, la corriente en el conductor neutro
presenta un valor rms superior al valor rms de la corriente en una fase mediante un factor
igual a la raz cuadrada de 3. Por lo tanto, el conductor neutro se debe sobredimensionar.
Las tensiones de armnicos (de rango h) aplicadas a las mquinas asncronas producen en el
rotor corrientes con frecuencias superiores a 50/60 Hz que son la causa de prdidas
adicionales.
rdenes de magnitud
RESULTADOS
Impacto Econmico
Al preparar el diagrama de una sola lnea, los dispositivos no lineales deben separarse del
resto (ver Figura 1.6).
En el intento de limitar los armnicos, se puede obtener una mejora adicional alimentando
las cargas no lineales desde una fuente independiente del resto de cargas de la instalacin
(ver Figura 1.7). La desventaja es un aumento del coste de la instalacin.
Filtros armnicos
En los casos en los que la accin preventiva indicada anteriormente sea insuficiente, es
necesario equipar la instalacin con sistemas de filtrado. Existen tres tipos de filtros:
Por otro lado, la mejor solucin, tanto desde el punto de vista tcnico como econmico, se
basa en los resultados de un estudio detallado.
Utilizando los servicios de un especialista se asegura que la solucin propuesta tenga los
resultados esperados (un THDu mximo garantizado).