132096 Solution Provided
*id: State:

User Information
Dian Muhammad Adam P.T. Control Systems
Name: Company:

dian.adam@ptcs.co.id None
Email: Rep:

0217807881 +6282112092829
Phone: (Mobile):

Product Information
Remote Automation Solutions
*Product Division: (Software)

Enterprise/Host Software OpenEnterprise-O&G


Product Product
Segment: Platform:

Historian
Product Project:
Subset:

3.2.1
*SW Version: Asset:

Problem Information
OPC connection (DA and HDA)
*Summary:

HI Emerson,
*Description:
i have question regarding the OPC DA and HDA connection to 3rd party, i have setting up all privilege user
to R/W to get Archive (HDA) on table raw9001 (get from nw3000realanalog).
but some how the matrikon OPC DA or HDA cannot get the progID emerson.OEOPCDAServer1 or Iconics.

on this ticket i have attached backup database, result from matrikon Analyzer and Order Acknowledgement
screenshoot for your refference.

kindly your solution and advice to solve it.

OE DATA.zip; OA.png;
Attach file #1: Cogent OPC.png

Additional Notes: [Dian Muhammad Adam Apr 11 2017 07:38:03]

sorry me left 1 things question,


based on OA.Png we can do share items opc to 3rd party like Matrikon_OPC which DA or HDA?

[Art Velezis Apr 11 2017 13:26:57]

How is the system architecture configured?


Is the OE server and the 3rd party OPC client on the same computer?

If you are using a 3rd party OPC client you will also need to manually add the proper OPC tags to the 3rd
party client. The OE server cannot be browsed.

If the OE server and 3rd party OPC client are on the same computer. The OPC tag format added to the client
would be as shown in the example (realanalog signal) below. Tew:R1.DP_INP would be replaced with the
signal name that you require from the OE database.

"rtrdb1"."realanalog"."name:varchar:Tew:R1.DP_INP"."value:float"

If the 3rd party OPC client exists on a different computer then DCOM settings must be configured.

[Dian Muhammad Adam Apr 13 2017 04:55:37]

How is the system architecture configured?Attached Is the OE server and the 3rd party OPC client on the

1 of 3 5/24/17, 1:44 AM
View Record https://emerson.agiloft.com/gui2/tables/record/update.do;en;page=403...

same computer? not, separate PC.

[Dian Muhammad Adam Apr 13 2017 04:56:36]

How is the system architecture configured?


cogent OPC.png

[Art Velezis Apr 13 2017 13:16:05]

If you are using the Cogent OPC Tunnel then DCOM should not be an issue.

As I said before in the client you will need to manually add the OE OPC tag.

"Servername:rtrdb1"."realanalog"."name:varchar:Tew:R1.DP_INP"."value:float"

The OE OPC server must also be defined. (Emerson.OEOPCDAServer)

I am not familiar with the Cogent configuration but this is normally the information required for client pulling
data from an OE OPCDA Server .

Emerson.OEOPCDAServer\"Servername:rtrdb1"."realanalog"."name:varchar:Tew:R1.DP_INP"."value:float"

Where Servername is the OE servers name.

[Art Velezis Apr 13 2017 13:49:11]

Currently Open Enterprise supports OPC DA and OPC A&E.

[Dian Muhammad Adam Apr 17 2017 08:22:06]

so, how we can access data from OE distinguished historian's already installed? whether to renew a license
or what?

[Art Velezis Apr 18 2017 15:26:00]

Currently we do not support OPC HDA.

What are you looking to do with the OE Historical data?

[Dian Muhammad Adam May 12 2017 02:34:08]

our customer needed to get data monthly and hourly from OE Archive.

[Art Velezis May 15 2017 17:34:14]

Is it possible the customer can use a Report or an sql query to create an output file that runs monthly for the
monthly data?

[Dian Muhammad Adam May 16 2017 02:17:46]

the report only for administration data local, they are want OE integrate to system they are (another place)
via OPC for Remote monitoring.

any advice ?

[Art Velezis May 23 2017 13:22:29]

Using ODBC is an option.

Resolution
How is the system architecture configured?
Solution: Is the OE server and the 3rd party OPC client on the same computer?

If you are using a 3rd party OPC client you will also need to manually add the proper OPC tags to the 3rd
party client. The OE server cannot be browsed.

If the OE server and 3rd party OPC client are on the same computer. The OPC tag format added to the client
would be as shown in the example (realanalog signal) below. Tew:R1.DP_INP would be replaced with the
signal name that you require from the OE database.

"rtrdb1"."realanalog"."name:varchar:Tew:R1.DP_INP"."value:float"

If the 3rd party OPC client exists on a different computer then DCOM settings must be configured.

Background