ONCOLOGY WARDS & DAY CARE CENTRE AT THE ROYAL HOSPITAL

SCHEDULE OF SMOKE EXTRACT FANS & EXTRACT FANS.

Air Flow Power Motor


Sr no Zone Tag no Equipment Model
L/s kw Phase

1 FF - Pediatric Ward EF - 1 Smoke Extract Fan AX100AA-423A7 6507.0 5.50 3 Phase


2 FF - Adult Onco. Ward EF - 2 Smoke Extract Fan AX100AA-423A7 6807.0 5.50 3 Phase
3 SF - Day care ward EF - 3 Smoke Extract Fan AX100AC-423A7 8059.0 7.50 3 Phase
4 SF - Adult onco ward EF - 4 Smoke Extract Fan AX100AC-443A7 8354.0 11.00 3 Phase
5 FF - Extract EF - 5 Twin Extract Fan NALTRF12-B2G 1180.0 2.20 3 Phase
6 FF - Extract EF - 6 Twin Extract Fan NALTRF12-B2G 1180.0 2.20 3 Phase
7 SF - Extract EF - 7 Twin Extract Fan NALTRF12-B2G 1240.0 2.20 3 Phase
8 SF - Extract EF - 8 Twin Extract Fan NALTRF12-B2G 1240.0 2.20 3 Phase
9 FF & SF - Private Room - 4 EF - 9 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
10 FF & SF - Private Room - 3 EF - 10 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
11 FF & SF - Private Room - 2 EF - 11 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
12 FF & SF - Private Room - 1 EF - 12 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
13 FF & SF - Private Room - 5 EF - 13 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
14 FF & SF - Private Room - 6 EF - 14 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
15 FF & SF - Private Room - 7 EF - 15 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
16 FF & SF - Private Room - 8 EF - 16 Smoke Extract Fan/Extract fan AX40F-413A7 158.0 0.55 3 Phase
17 FF & SF - Consultant Suit - 1 & 2 EF - 17 Twin Extract Fan NALTRF3-B2G 90.0 0.22 1 Phase
18 UPS Battery Room EF - 18A & 18B Victoris Explosion proof fan-(Duty+ Sy By) 190.0 0.55 3 Phase
19 FF & SF - Consultant Suit - 1 & 2 EF - 19 Smoke Extract Fan AX80P-423A7 Additional 2.20 3 Phase
20 SF Maintanance workshop store EF - 20 Extract Fan NALSRF3-B2G Additional 0.22 1 Phase
PROJECT ONCOLOGY WARDS & DAY CARE CENTRE AT ROYAL HOSPITAL
CLIENT MINISTRY OF HEALTH
CONSULTANT GULF ENGINEERING CONSULTANCY
MAIN CONTRACTOR PREMIER INTERNAL PROJECTS L.L.C
MEP CONTRACTOR GALFAR ENGINEERING & CONTRACTING S.A.O.G

SCHEDULE OF SMOKE EXTRACT FANS & EXTRACT FANS.

Air Flow
Specified Offered
flow flow Power Static Motor
Sr no Zone Tag no Equipment Model Concept RPM
Phase

L/s L/s kw Pa
1 FF - Pediatric Ward EF - 1 Smoke Extract Fan AX100AA-423A7 Linked with AHU - 1 6507.0 6787.0 5.50 400.0 1455.0 3 Phase
2 FF - Adult Onco. Ward EF - 2 Smoke Extract Fan AX100AA-423A7 Linked with AHU - 2 6807.0 6815.0 5.50 400.0 1455.0 3 Phase
3 SF - Day care ward EF - 3 Smoke Extract Fan AX100AC-423A7 Linked with AHU - 3 8059.0 8118.0 7.50 400.0 1455.0 3 Phase
4 SF - Adult onco ward EF - 4 Smoke Extract Fan AX100AC-443A7 Linked with AHU - 4 8354.0 8464.0 11.00 400.0 1455.0 3 Phase
5 FF - Extract EF - 5 Twin Extract Fan NALTRF12-B2G Always Duty 1180.0 1342.0 2.20 250.0 1040.0 3 Phase
6 FF - Extract EF - 6 Twin Extract Fan NALTRF12-B2G Always Duty 1180.0 1342.0 2.20 250.0 1040.0 3 Phase
7 SF - Extract EF - 7 Twin Extract Fan NALTRF12-B2G Always Duty 1240.0 1342.0 2.20 250.0 1040.0 3 Phase
8 SF - Extract EF - 8 Twin Extract Fan NALTRF12-B2G Always Duty 1240.0 1342.0 2.20 250.0 1040.0 3 Phase
9 FF & SF - Private Room - 4 EF - 9 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
10 FF & SF - Private Room - 3 EF - 10 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
11 FF & SF - Private Room - 2 EF - 11 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
12 FF & SF - Private Room - 1 EF - 12 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
13 FF & SF - Private Room - 5 EF - 13 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
14 FF & SF - Private Room - 6 EF - 14 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
15 FF & SF - Private Room - 7 EF - 15 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
16 FF & SF - Private Room - 8 EF - 16 Smoke Extract Fan/Extract fan AX40F-413A7 Always Duty 158.0 298.0 0.55 150.0 1415.0 3 Phase
17 FF & SF - Consultant Suit - 1 & 2 EF - 17 Twin Extract Fan NALTRF3-B2G Always Duty 90.0 101.0 0.22 150.0 1264.0 1 Phase
18 UPS Battery Room EF - 18A & 18B Victoris Explosion proof fan-(Duty+ Sy By) Always Duty 190.0 380.0 0.55 150.0 3 Phase
19 FF & SF - Consultant Suit - 1 & 2 EF - 19 Smoke Extract Fan AX80P-423A7 Linked with AHU - 13 Additional 3800.00 2.20 250.00 1435.00 3 Phase
20 SF Maintanance workshop store EF - 20 Extract Fan NALSRF3-B2G Always Duty Additional 115.0 0.22 125.0 1264.0 1 Phase