Case Correction of service manual


Malfunction code A3

Model VRV series

Please refer to the attached page for correction.


Notice
There are some corrections in the service manual of the following list
VRV series
The corrections will be revised in the next issue.
Applicable book

Code
Si33-002 Si39-409 SiKR38-304
Si33-103 Si39-409J SiKR38-304E
Si33-105 Si39-501 SiKR39-504
Si33-106 Si39-502A SiKR39-504E
Si33-201 Si39-504 SiME34-608
Si341102_A SiARL34-806 SiME34-811
Si34-601A SiARL34-815 SiTW34-808
Si34-601AJ SiBE31-801J SiTW34-808E
Si34-804_D SiBE34-703 SiTW39-507
Si37-701J SiBE34-802 SiUS39-501
Si38-304 SiBR30-602_A SiUS39-505
Si38-606A SiBRL34-807 SiUS39-601
Si38-805 SiCN31-801 SiUS39-602
Si38-819 SiCN33-002
Si39-302 SiCN34-607
Si39-306 SiCN34-607E
Si39-404 SiCN34-607J
Si39-407A SiCN34-803
Si39-407AJ SiCN34-803E

Detail
Malfunction code A3

Wrong connector code for float switch and drain pump is described.
Troubleshooting Si33-002

3.3 Indoor Unit: Malfunction of Drain Level Control System (33H)

Remote Controller A3
Display

Supposed Causes Defect of float switch or short circuit connector


Defect of drain pump
Drain clogging, upward slope, etc.
Defect of indoor unit PC board
Loose connection of connector

Troubleshooting

The float A short


switch is connected to NO NO
circuit connector is Connect either a short circuit
X18A of the indoor unit connected to X18A.
PC board. connector or float switch and turn on
X8A YES X8A again.

The float X8A


switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with the indoor unit PC board Defect of indoor unit PC board.
X18A disconnected) is short circuited
X8A
YES
NO Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's connection
and turn on again.
The drain Y2
pump is connected to NO
X25A or terminals X8S Connect the drain pump and turn on
and X9S of the indoor again.
unit PC board.
Y1
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for clogging or
for the indoor unit. upward slope, etc.

NO
Y2
The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
(within 5minutes of Replace indoor unit PC board.
Y1 resetting the
power
supply).
YES
Replace the drain pump or check for
dirt, etc.
(VF030)

128 Troubleshooting R407C PLUS Series


Si33-103 Troubleshooting

3.3 Indoor Unit: Malfunction of Drain Level Control System


(33H)
Remote A3
Controller
Display

Supposed Defect of float switch or short circuit connector


Causes Defect of drain pump
Drain clogging, upward slope, etc.
Defect of indoor unit PC board
Loose connection of connector

Troubleshooting

The float A short


switch is connected to NO circuit connector is NO
X18A of the indoor unit Connect either a short
connected to X18A. circuit connector or float
PC board.
X8A X8A switch and turn on again.
YES

The float X8A


switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with the indoor unit PC board Defect of indoor unit PC
X18A disconnected) is short circuited. board.
X8A
YES
Loose connection of
NO connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's
connection and turn on
The drain Y2 again.
pump is connected to NO
X25A or terminals X8S Connect the drain pump
and X9S of the indoor and turn on again.
unit PC board.
Y1

YES

The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor unit. clogging or upward slope,
etc.
NO

Y2
The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
(within 5minutes of resetting Replace the indoor unit PC
Y1 the power supply). board.

YES
Replace the drain pump or
check for dirt, etc.

(V2002)

Troubleshooting R407C <Cooling Only> PLUS Series 117


Si33-105 Troubleshooting

3.3 Indoor Unit: Malfunction of Drain Level Control System


(33H)
Remote A3
Controller
Display

Supposed ! Defect of float switch or short circuit connector


Causes ! Defect of drain pump
! Drain clogging, upward slope, etc.
! Defect of indoor unit PC board
! Loose connection of connector

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

The float A short


switch is connected to NO circuit connector is NO
X18A of the indoor unit Connect either a short circuit
connected to X18A.
PC board. connector or float switch and
X8A X8A turn on again.
YES
The float X8A
switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with X18A the indoor unit PC board Defect of indoor unit PC board.
disconnected) is short circuited
X8A
YES Loose connection of connector.
NO

Water builds up NO The float switch NO


functions normally. Replace float switch.
in the drain pan.

YES
YES Modify the float switch's
connection and turn on again.
The drain Y2
pump is connected to NO
X25A or terminals X8S Connect the drain pump and
and X9S of the indoor turn on again.
unit PC board.
Y1

YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor unit. clogging or upward slope, etc.

NO

Y2
The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
Replace indoor unit PC board.
(within 5minutes of
Y1 resetting the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(VF030)

Troubleshooting R407C PLUS Series Heat Recovery System 163


Si33-106 Troubleshooting

4.3 Indoor Unit: Malfunction of Drain Level Control System


(33H)
Remote A3
Controller
Display

Supposed Defect of float switch or short circuit connector


Causes Defect of drain pump
Drain clogging, upward slope, etc.
Defect of indoor unit PC board
Loose connection of connector

Troubleshooting

The float A short


switch is connected to NO circuit connector is NO
X18A of the indoor unit Connect either a short
connected to X18A. circuit connector or float
PC board.
X8A X8A switch and turn on again.
YES

The float X8A


switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with the indoor unit PC board Defect of indoor unit PC
X18A disconnected) is short circuited. board.
X8A
YES
Loose connection of
NO connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's
connection and turn on
The drain Y2 again.
pump is connected to NO
X25A or terminals X8S Connect the drain pump
and X9S of the indoor and turn on again.
unit PC board.
Y1

YES

The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor unit. clogging or upward slope,
etc.
NO

Y2
The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
(within 5minutes of resetting Replace the indoor unit PC
Y1 the power supply). board.

YES
Replace the drain pump or
check for dirt, etc.

(V2152)

Troubleshooting R407C <Cooling Only> Series 103


Troubleshooting by Remote Controller Si33-201

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X18A of the indoor unit connected to Connect either a short circuit
connector or float switch and
X8A PC board. X18A.
turn on again.
YES X8A

The float X8A


switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X18A is short circuited
disconnected) X8A

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's
connection and turn on again.
The drain Y2
pump is connected NO
to X25A or terminals X8S Connect the drain pump and
and X9S of the turn on again.
indoorunit PC
Y1 board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage Y2
of terminals X8S
and X9S or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
Y1 the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

140 Troubleshooting
Troubleshooting by Remote Controller Si341102_A

Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES

A short circuit
The float switch is NO connector is NO
connected to the connected to the Connect either a short circuit
connector (1). connector (1). connector or float switch and
turn ON again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when the NO
(continuity check with connector (1) is Defective indoor unit PCB.
the connector (1) short circuited
disconnected)

NO YES
Loose the connection of
connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace the float switch.

YES YES Modify the float switch's


connection and turn ON again.

The drain NO
pump is connected Connect the drain pump and
to the connector turn ON again.
(2).

YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The
voltage of the
connector (2) is NO
220~240 V (within 5 Replace the indoor unit PCB.
minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Note: 1, 2 Connector
Model 1 Connector for float switch 2 Connector for drain pump
FXFQ X15A X25A
FXZQ X8A X25A
FXDQ-PBVE/NBVE X8A X25A
FXMQ-P X15A X25A
FXHQ X8A X25A
FXAQ X15A

211 Service Diagnosis


Si34-601A Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 223
3.3 A3S1L
1. 5.

NO
220240V
220240V

YES
X8A X15A

NO X8A NO
PX8A

2.
X8A X15A
OFF YES YES
X8A X15A
P
YES NO
X8A X8A P


NO X8A X15A YES

NO NO

3. YES YES


OFF

P
YYX25A NO



YES

YES



4.
NO
1 220 240V
1
YY
X25A NO
200V P
1
1

1 P YES

219
Si34-804_D Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES

A short circuit
The float switch is NO connector is NO
connected to the connected to the Connect either a short circuit
connector (1). connector (1). connector or float switch and
turn ON again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when the NO
(continuity check with connector (1) is Defective indoor unit PCB.
the connector (1) short circuited
disconnected)

NO YES
Loose the connection of
connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace the float switch.

YES YES Modify the float switch's


connection and turn ON again.

The drain
pump is connected NO
to terminals and Connect the drain pump and
connector (2). turn ON again.

YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals and
connector (2) is NO
220~240 V (within 5 Replace the indoor unit PCB.
minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Note: 1, 2 Connector and terminals


Model 1 Connector for float switch 2 Terminals and connector for drain pump
FXFQ X15A X25A
FXZQ X8A X25A
FXCQ X8A Y1, Y2
FXKQ X8A Y1, Y2
FXDQ-PBVE/NBVE X8A X25A
FXMQ-P X15A X25A
FXMQ-MA X8A Y1, Y2
FXHQ X8A X25A
FXAQ X15A ---
FXUQ X15A X25A
FXMQ-MF X8A Y1, Y2

Service Diagnosis 182


A35.
 

NO
220 240V
220 240V

YES
X8A X15A X8A X15A

NO X8A NO
P X8A

1(( YES YES
X8A X15A X8A X15A
P
YES NO
X8A X8A P

NO YES

NO NO

 YES YES

1((
P
Y1 Y2 X25A NO

YES

YES


NO
1 8
1
Y1 Y2
 X25A NO
200V P
1 5
1
12 YES

1


Si38-304 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 181
Si38-606A Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 123
Si38-805 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
YES YES X8A or X15A
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 123
Si38-819 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 203
Si39-302 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
YES X8A or X15A

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 159
Si39-306 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 151
Troubleshooting by Indication on the Remote Controller Si39-404

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

176 Troubleshooting
Si39-407A Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 183
A35.
 

X8A X15A


X8A X15A
1((
X8A X15A

X8A X15A



1((


1 8
1

1
1
12
1


6L 7URXEOHVKRRWLQJE\,QGLFDWLRQRQWKH5HPRWH&RQWUROOHU

7URXEOHVKRRWLQJ
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
YES X8A or X15A

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

7URXEOHVKRRWLQJ 
2.3 A3S1L
1. 5.
FXCQ, FXFQ, FXZQ, FXSQ,
FXKQ, FXDQ, FXMQ, FXUQ,

FXHQ,
FXMQ200250M,
FXAQ, FXMQ-MF NO
220 240V
220 240V

YES
X8A X15A

NO X8A NO
P X8A
2.
X8A X15A
OFF YES YES
X8A X15A
P
YES NO
X8A or X8A P
X15A

X8A X15A
NO YES

NO NO

3. YES YES

OFF
P
Y1 Y2 X25A NO

YES

YES

4.
NO
1 220 240V
1
Y1 Y2
X25A NO
200V P
1 5
1
1 P YES


Si39-501 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 175
Troubleshooting by Indication on the Remote Controller Si39-502A

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

154 Troubleshooting
Si39-504 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 173
SiARL34-806 Deteccin de averas mediante indicacin en el mando a distancia

Deteccin
de averas Asegrese de desconectar el interruptor de alimentacin antes de conectar
Precaucin o desconectar el conector, pueden producirse daos en las piezas.

Se suministra una NO
alimentacin elctrica Suministre alimentacin
de 220~240V? de 220~240 V.
S
El interruptor de NO Un conector de NO
boya est conectado al X8A cortocircuito est Conecte un conector de
de la PCB de la unidad conectado al X8A. cortocircuito o un interruptor
interior. X8A o X15A de boya y vuelva a arrancar.
X8A o X15A
S S

El contacto del X8A o X15A


interruptor de boya Se normaliza
est produciendo un cortocircuito S cuando se cortocircuita NO
(verificacin de continuidad con X8A de la PCB de la Defecto de la PCB de la
X8A o X15A unidad interior unidad interior.
desconectado)

S
Conexin suelta del
NO conector.
NO El interruptor de boya NO
El agua se acumula en la Reemplace el interruptor
bandeja de drenaje. funciona normalmente. de boya.

S S
Modifique la conexin
del interruptor de boya
y vuelva a arrancar
La bomba de drenaje NO
est conectada a X25A o a los
terminales Y1 y Y2 de la PCB Conecte la bomba de
de la unidad drenaje y vuelva a arrancar.
interior.
S

La bomba de drenaje S
funciona cuando se restablece Compruebe si la tubera
la alimentacin de la de drenaje est obstruida
unidad interior. o presenta una pendiente
hacia arriba, etc.
NO

La tensin de los
terminales Y1 y Y2 o X25A NO
es de 220~240 V (5 minutos Reemplace la PCB de la
despus de restablecer la unidad interior.
alimentacin
elctrica)

S Reemplace la bomba de
drenaje o compruebe si hay
suciedad, etc.

(V2778)

Deteccin de averas 253


SiARL34-815 Deteccin de averas mediante indicacin en el mando a distancia

Deteccin de
averas
Asegrese de desconectar el interruptor de alimentacin antes de conectar
Precaucin o desconectar el conector, pueden producirse daos en las piezas.

Se suministra una NO
alimentacin elctrica Suministre alimentacin
de 220~240V? de 220~240 V.

S
El interruptor de NO Un conector de NO
boya est conectado al X8A cortocircuito est Conecte un conector de
de la PCB de la unidad conectado al X8A. cortocircuito o un interruptor
interior. X8A o X15A de boya y vuelva a arrancar.
X8A o X15A
S S

El contacto del
interruptor de boya Se normaliza
est produciendo un cortocircuito S cuando se cortocircuita NO
(verificacin de continuidad con X8A de la PCB de la Defecto de la PCB de la
X8A o X15A unidad interior unidad interior.
desconectado)
X8A o X15A
S
Conexin suelta del
NO conector.
NO El interruptor de boya NO
El agua se acumula en la Reemplace el interruptor
bandeja de drenaje. funciona normalmente. de boya.

S S
Modifique la conexin
del interruptor de boya
y vuelva a arrancar
La bomba de drenaje NO
est conectada a X25A o a los
terminales Y1 y Y2 de la PCB Conecte la bomba de
de la unidad drenaje y vuelva a arrancar.
interior.
S

La bomba de drenaje S
funciona cuando se restablece Compruebe si la tubera
la alimentacin de la de drenaje est obstruida
unidad interior. o presenta una pendiente
hacia arriba, etc.
NO

La tensin de los
terminales Y1 y Y2 o X25A NO
es de 220~240 V (5 minutos Reemplace la PCB de la
despus de restablecer la unidad interior.
alimentacin
elctrica)

S Reemplace la bomba de
drenaje o compruebe si hay
suciedad, etc.

Deteccin de averas 263


A3
 

NO
200 240V 200 240V

YES
X8A X15A

NO X8A NO
P X8A

X8A X15A
1(( YES YES

X8A X15A
P
YES NO
X8A X8A P

X8A X15A
NO YES

NO NO

 YES YES

1((
P


Y1-Y2 X25A NO

YES

YES

 NO

1 8 Y1-Y2


1 X25A NO
P
200V
 5

1
YES
1
12
1


SiBE34-703 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A (or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
X8A(or X15A)
YES YES

The float
switch contact is
forming a short circuit Becomes NO
YES normal when X8A (or X15A) of
(continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 125
SiBE34-802 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A (or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES X8A(or X15A)

The float
switch contact is
forming a short circuit Becomes NO
YES normal when X8A (or X15A) of
(continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 145
SiBR30-602_A Solucionando problemas com indicaes do controle remoto

Soluo
Certifique-se de que a energia est desligada antes de conectar ou
Cuidado desconectar o conector, ou podem ocorrer danos s peas.

Uma fonte NO
de energia de 220~240 V Providencie uma fonte
oferecida? de energia de 220~240 V.
SIM

O interruptor Um conector
de boia est conectado NO NO
de curto-circuito est Conecte um conector de
ao X8A do PCB da conectado ao
unidade interna. curto-circuito ou um interruptor
X8A. de boia e ligue novamente.
X8A ou X15A
SIM X8A ou X15A
SIM

O contato X8A ou X15A


do interruptor de Se torna
boia est em curto-circuito SIM normal quando NO
(verificao de continuidade o X8A do PCB da unidade Avaria no PCB da unidade
com X8A ou X15A interna estiver em interna.
desconectados) curto-circuito

NO SIM Conexo do conector solta.

gua se NO O interruptor NO
acumula no recipiente de de boia funciona Substitua o interruptor
drenagem. normalmente. de boia.
SIM SIM Modifique a conexo do
interruptor de boia e ligue
novamente.
A bomba
de drenagem est
conectada ao X25A ou NO
aos terminais Y1 e Y2 do Conecte a bomba de
PCB da unidade drenagem e ligue
interna. novamente.

SIM

A bomba
de drenagem funciona SIM
quando a fonte de energia Verifique o encanamento de
reiniciada para a drenagem atrs de
unidade entupimento ou inclinao
interna. ascendente, etc.
NO

A voltagem
dos terminais Y1 e
Y2 ou do X25A NO
220~240 V (dentro de 5 Substitua o PCB da
minutos aps reiniciar unidade interna.
a fonte de
energia).

SIM Substitua a bomba de


drenagem ou procure por
sujeira, etc.

(V2778)

Soluo de problemas 161


SiBRL34-807 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5 minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 223
SiCN31-801

X8A X15A
X8A X15A

X8A X15A

(V2778)

199
X8A

X8A
X8A

X8A

Y2-Y1

Y2-Y1
SiCN34-607

X8A X15A

X8A X15A
X8A X15A

(V2778)

203
SiCN34-607 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
YES X8A or X15A
YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 203
A35.
 

X8A X15A X8A X15A


1((
X8A X15A X8A X15A



1((


1 8
1

1
1
12
1


SiCN34-803

X8A X15A X8A X15A

X8A X15A

196
SiCN34-803 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
YES X8A or X15A
YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 197
SiKR38-304

X8A or X15A
X8A or X15A

X8A or X15A

159
SiKR38-304E Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
YES YESX8A or X15A

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 159
SiKR39-504

X8A or X15A
X8A or X15A

X8A or X15A

175
SiKR39-504E Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 175
SiME34-608 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A (or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES X8A (or X15A)

The float
switch contact is
forming a short circuit Becomes NO
YES normal when X8A (or X15A) of
(continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 131
SiME34-811 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 231
SiTW34-808

X8A X15A

X8A X15A

X8A X15A

223
SiTW34-808 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
YES YES X8A or X15A
The float X8A or X15A
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5 minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 223
SiTW39-507 Troubleshooting by Indication on the Remote Controller

7URXEOHVKRRWLQJ
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A is short circuited
disconnected)
X8A or X15A

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 115
6L86 7URXEOHVKRRWLQJE\,QGLFDWLRQRQWKH5HPRWH&RQWUROOHU

7URXEOHVKRRWLQJ
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power supply.

YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A X8A or X15A turn on again.
YES YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A is short circuited
disconnected)
X8A or X15A
NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 105
Troubleshooting by Indication on the Remote Controller SiUS39-505

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

122 Troubleshooting
SiUS39-601 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A turn on again.
X8A or X15A
YES YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 123
Troubleshooting by Indication on the Remote Controller SiUS39-602

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
X8A or X15A X8A or X15A turn on again.
YES YES

The float X8A or X15A


switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

130 Troubleshooting
Troubleshooting Si33-002

3.3 Indoor Unit: Malfunction of Drain Level Control System (33H)

Remote Controller A3
Display

Supposed Causes Defect of float switch or short circuit connector


Defect of drain pump
Drain clogging, upward slope, etc.
Defect of indoor unit PC board
Loose connection of connector

Troubleshooting

The float A short


switch is connected to NO NO
circuit connector is Connect either a short circuit
X18A of the indoor unit connected to X18A.
PC board. connector or float switch and turn on
again.
YES
The float
switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with the indoor unit PC board Defect of indoor unit PC board.
X18A disconnected) is short circuited

YES
NO Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's connection
and turn on again.
The drain
pump is connected to NO
X25A or terminals X8S Connect the drain pump and turn on
and X9S of the indoor again.
unit PC board.

YES
The drain
pump works when YES
the power supply is reset Check the drain piping for clogging or
for the indoor unit. upward slope, etc.

NO

The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
(within 5minutes of Replace indoor unit PC board.
resetting the
power
supply).
YES
Replace the drain pump or check for
dirt, etc.
(VF030)

128 Troubleshooting R407C PLUS Series


Si33-103 Troubleshooting

3.3 Indoor Unit: Malfunction of Drain Level Control System


(33H)
Remote A3
Controller
Display

Supposed Defect of float switch or short circuit connector


Causes Defect of drain pump
Drain clogging, upward slope, etc.
Defect of indoor unit PC board
Loose connection of connector

Troubleshooting

The float A short


switch is connected to NO circuit connector is NO
X18A of the indoor unit Connect either a short
connected to X18A. circuit connector or float
PC board.
switch and turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with the indoor unit PC board Defect of indoor unit PC
X18A disconnected) is short circuited. board.

YES
Loose connection of
NO connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's
connection and turn on
The drain again.
pump is connected to NO
X25A or terminals X8S Connect the drain pump
and X9S of the indoor and turn on again.
unit PC board.

YES

The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor unit. clogging or upward slope,
etc.
NO

The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
(within 5minutes of resetting Replace the indoor unit PC
the power supply). board.

YES
Replace the drain pump or
check for dirt, etc.

(V2002)

Troubleshooting R407C <Cooling Only> PLUS Series 117


Si33-105 Troubleshooting

3.3 Indoor Unit: Malfunction of Drain Level Control System


(33H)
Remote A3
Controller
Display

Supposed ! Defect of float switch or short circuit connector


Causes ! Defect of drain pump
! Drain clogging, upward slope, etc.
! Defect of indoor unit PC board
! Loose connection of connector

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

The float A short


switch is connected to NO circuit connector is NO
X18A of the indoor unit Connect either a short circuit
connected to X18A.
PC board. connector or float switch and
turn on again.
YES
The float
switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with X18A the indoor unit PC board Defect of indoor unit PC board.
disconnected) is short circuited

YES Loose connection of connector.


NO

Water builds up NO The float switch NO


functions normally. Replace float switch.
in the drain pan.

YES
YES Modify the float switch's
connection and turn on again.
The drain
pump is connected to NO
X25A or terminals X8S Connect the drain pump and
and X9S of the indoor turn on again.
unit PC board.

YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor unit. clogging or upward slope, etc.

NO

The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
Replace indoor unit PC board.
(within 5minutes of
resetting the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(VF030)

Troubleshooting R407C PLUS Series Heat Recovery System 163


Si33-106 Troubleshooting

4.3 Indoor Unit: Malfunction of Drain Level Control System


(33H)
Remote A3
Controller
Display

Supposed Defect of float switch or short circuit connector


Causes Defect of drain pump
Drain clogging, upward slope, etc.
Defect of indoor unit PC board
Loose connection of connector

Troubleshooting

The float A short


switch is connected to NO circuit connector is NO
X18A of the indoor unit Connect either a short
connected to X18A. circuit connector or float
PC board.
switch and turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check with the indoor unit PC board Defect of indoor unit PC
X18A disconnected) is short circuited. board.

YES
Loose connection of
NO connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's
connection and turn on
The drain again.
pump is connected to NO
X25A or terminals X8S Connect the drain pump
and X9S of the indoor and turn on again.
unit PC board.

YES

The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor unit. clogging or upward slope,
etc.
NO

The voltage
of terminals X8S and
X9S or X25A is 220~240 V NO
(within 5minutes of resetting Replace the indoor unit PC
the power supply). board.

YES
Replace the drain pump or
check for dirt, etc.

(V2152)

Troubleshooting R407C <Cooling Only> Series 103


Troubleshooting by Remote Controller Si33-201

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X18A of the indoor unit connected to Connect either a short circuit
PC board. X18A. connector or float switch and
turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X18A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X18A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES
Modify the float switch's
connection and turn on again.
The drain
pump is connected NO
to X25A or terminals X8S Connect the drain pump and
and X9S of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals X8S
and X9S or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

140 Troubleshooting
Troubleshooting by Remote Controller Si341102_A

Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES

A short circuit
The float switch is NO connector is NO
connected to the connected to the Connect either a short circuit
connector (1). connector (1). connector or float switch and
turn ON again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when the NO
(continuity check with connector (1) is Defective indoor unit PCB.
the connector (1) short circuited
disconnected)

NO YES
Loose the connection of
connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace the float switch.

YES YES Modify the float switch's


connection and turn ON again.

The drain NO
pump is connected Connect the drain pump and
to the connector turn ON again.
(2).

YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The
voltage of the
connector (2) is NO
220~240 V (within 5 Replace the indoor unit PCB.
minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Note: 1, 2 Connector
Model 1 Connector for float switch 2 Connector for drain pump
FXFQ X15A X25A
FXZQ X8A X25A
FXDQ-PBVE/NBVE X8A X25A
FXMQ-P X15A X25A
FXHQ X8A X25A
FXAQ X15A

211 Service Diagnosis


Si34-601A Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 223
3.3 A3S1L
1. 5.

NO
220240V
220240V

YES

NO X8A NO
PX8A

2.

OFF YES YES

P
YES NO
X8A X8A P


NO YES

NO NO

3. YES YES


OFF

P
YYX25A NO



YES

YES



4.
NO
1 220 240V
1
YY
X25A NO
200V P
1
1

1 P YES

219
Si34-804_D Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES

A short circuit
The float switch is NO connector is NO
connected to the connected to the Connect either a short circuit
connector (1). connector (1). connector or float switch and
turn ON again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when the NO
(continuity check with connector (1) is Defective indoor unit PCB.
the connector (1) short circuited
disconnected)

NO YES
Loose the connection of
connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace the float switch.

YES YES Modify the float switch's


connection and turn ON again.

The drain
pump is connected NO
to terminals and Connect the drain pump and
connector (2). turn ON again.

YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals and
connector (2) is NO
220~240 V (within 5 Replace the indoor unit PCB.
minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Note: 1, 2 Connector and terminals


Model 1 Connector for float switch 2 Terminals and connector for drain pump
FXFQ X15A X25A
FXZQ X8A X25A
FXCQ X8A Y1, Y2
FXKQ X8A Y1, Y2
FXDQ-PBVE/NBVE X8A X25A
FXMQ-P X15A X25A
FXMQ-MA X8A Y1, Y2
FXHQ X8A X25A
FXAQ X15A
FXUQ X15A X25A
FXMQ-MF X8A Y1, Y2

Service Diagnosis 182


A35.
 

NO
220 240V
220 240V

YES

NO X8A NO
P X8A

1(( YES YES

P
YES NO
X8A X8A P

NO YES

NO NO

 YES YES

1((
P
Y1 Y2 X25A NO

YES

YES


NO
1 8
1
Y1 Y2
 X25A NO
200V P
1 5
1
12 YES

1


Si38-304 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 181
Si38-606A Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 123
Si38-805 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 123
Si38-819 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 203
Si39-302 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 159
Si39-306 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 151
Troubleshooting by Indication on the Remote Controller Si39-404

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

176 Troubleshooting
Si39-407A Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 183
A35.
 


1((



1((


1 8
1

1
1
12
1


6L 7URXEOHVKRRWLQJE\,QGLFDWLRQRQWKH5HPRWH&RQWUROOHU

7URXEOHVKRRWLQJ
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

7URXEOHVKRRWLQJ 
2.3 A3S1L
1. 5.
FXCQ, FXFQ, FXZQ, FXSQ,
FXKQ, FXDQ, FXMQ, FXUQ,

FXHQ,
FXMQ200250M,
FXAQ, FXMQ-MF NO
220 240V
220 240V

YES

NO X8A NO
P X8A
2.
OFF YES YES

P
YES NO
X8A or X8A P
X15A

NO YES

NO NO

3. YES YES

OFF
P
Y1 Y2 X25A NO

YES

YES

4.
NO
1 220 240V
1
Y1 Y2
X25A NO
200V P
1 5
1
1 P YES


Si39-501 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 175
Troubleshooting by Indication on the Remote Controller Si39-502A

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

154 Troubleshooting
Si39-504 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 173
SiARL34-806 Deteccin de averas mediante indicacin en el mando a distancia

Deteccin
de averas Asegrese de desconectar el interruptor de alimentacin antes de conectar
Precaucin o desconectar el conector, pueden producirse daos en las piezas.

Se suministra una NO
alimentacin elctrica Suministre alimentacin
de 220~240V? de 220~240 V.
S
El interruptor de NO Un conector de NO
boya est conectado al X8A cortocircuito est Conecte un conector de
de la PCB de la unidad conectado al X8A. cortocircuito o un interruptor
interior. de boya y vuelva a arrancar.
S S

El contacto del
interruptor de boya Se normaliza
est produciendo un cortocircuito S cuando se cortocircuita NO
(verificacin de continuidad con X8A de la PCB de la Defecto de la PCB de la
X8A o X15A unidad interior unidad interior.
desconectado)

S
Conexin suelta del
NO conector.
NO El interruptor de boya NO
El agua se acumula en la Reemplace el interruptor
bandeja de drenaje. funciona normalmente. de boya.

S S
Modifique la conexin
del interruptor de boya
y vuelva a arrancar
La bomba de drenaje NO
est conectada a X25A o a los
terminales Y1 y Y2 de la PCB Conecte la bomba de
de la unidad drenaje y vuelva a arrancar.
interior.
S

La bomba de drenaje S
funciona cuando se restablece Compruebe si la tubera
la alimentacin de la de drenaje est obstruida
unidad interior. o presenta una pendiente
hacia arriba, etc.
NO

La tensin de los
terminales Y1 y Y2 o X25A NO
es de 220~240 V (5 minutos Reemplace la PCB de la
despus de restablecer la unidad interior.
alimentacin
elctrica)

S Reemplace la bomba de
drenaje o compruebe si hay
suciedad, etc.

(V2778)

Deteccin de averas 253


SiARL34-815 Deteccin de averas mediante indicacin en el mando a distancia

Deteccin de
averas
Asegrese de desconectar el interruptor de alimentacin antes de conectar
Precaucin o desconectar el conector, pueden producirse daos en las piezas.

Se suministra una NO
alimentacin elctrica Suministre alimentacin
de 220~240V? de 220~240 V.

S
El interruptor de NO Un conector de NO
boya est conectado al X8A cortocircuito est Conecte un conector de
de la PCB de la unidad conectado al X8A. cortocircuito o un interruptor
interior. de boya y vuelva a arrancar.
S S

El contacto del
interruptor de boya Se normaliza
est produciendo un cortocircuito S cuando se cortocircuita NO
(verificacin de continuidad con X8A de la PCB de la Defecto de la PCB de la
X8A o X15A unidad interior unidad interior.
desconectado)

S
Conexin suelta del
NO conector.
NO El interruptor de boya NO
El agua se acumula en la Reemplace el interruptor
bandeja de drenaje. funciona normalmente. de boya.

S S
Modifique la conexin
del interruptor de boya
y vuelva a arrancar
La bomba de drenaje NO
est conectada a X25A o a los
terminales Y1 y Y2 de la PCB Conecte la bomba de
de la unidad drenaje y vuelva a arrancar.
interior.
S

La bomba de drenaje S
funciona cuando se restablece Compruebe si la tubera
la alimentacin de la de drenaje est obstruida
unidad interior. o presenta una pendiente
hacia arriba, etc.
NO

La tensin de los
terminales Y1 y Y2 o X25A NO
es de 220~240 V (5 minutos Reemplace la PCB de la
despus de restablecer la unidad interior.
alimentacin
elctrica)

S Reemplace la bomba de
drenaje o compruebe si hay
suciedad, etc.

Deteccin de averas 263


A3
 

NO
200 240V 200 240V

YES

NO X8A NO
P X8A

1(( YES YES

P
YES NO
X8A X8A P

NO YES

NO NO

 YES YES

1((
P


Y1-Y2 X25A NO

YES

YES

 NO

1 8 Y1-Y2


1 X25A NO
P
200V
 5

1
YES
1
12
1


SiBE34-703 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A (or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is
forming a short circuit Becomes NO
YES normal when X8A (or X15A) of
(continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 125
SiBE34-802 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A (or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is
forming a short circuit Becomes NO
YES normal when X8A (or X15A) of
(continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 145
SiBR30-602_A Solucionando problemas com indicaes do controle remoto

Soluo
Certifique-se de que a energia est desligada antes de conectar ou
Cuidado desconectar o conector, ou podem ocorrer danos s peas.

Uma fonte NO
de energia de 220~240 V Providencie uma fonte
oferecida? de energia de 220~240 V.
SIM

O interruptor Um conector
de boia est conectado NO NO
de curto-circuito est Conecte um conector de
ao X8A do PCB da conectado ao
unidade interna. curto-circuito ou um interruptor
X8A. de boia e ligue novamente.
SIM
SIM

O contato
do interruptor de Se torna
boia est em curto-circuito SIM normal quando NO
(verificao de continuidade o X8A do PCB da unidade Avaria no PCB da unidade
com X8A ou X15A interna estiver em interna.
desconectados) curto-circuito

NO SIM Conexo do conector solta.

gua se NO O interruptor NO
acumula no recipiente de de boia funciona Substitua o interruptor
drenagem. normalmente. de boia.
SIM SIM Modifique a conexo do
interruptor de boia e ligue
novamente.
A bomba
de drenagem est
conectada ao X25A ou NO
aos terminais Y1 e Y2 do Conecte a bomba de
PCB da unidade drenagem e ligue
interna. novamente.

SIM

A bomba
de drenagem funciona SIM
quando a fonte de energia Verifique o encanamento de
reiniciada para a drenagem atrs de
unidade entupimento ou inclinao
interna. ascendente, etc.
NO

A voltagem
dos terminais Y1 e
Y2 ou do X25A NO
220~240 V (dentro de 5 Substitua o PCB da
minutos aps reiniciar unidade interna.
a fonte de
energia).

SIM Substitua a bomba de


drenagem ou procure por
sujeira, etc.

(V2778)

Soluo de problemas 161


SiBRL34-807 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5 minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 223
SiCN31-801

(V2778)

199
SiCN34-607

(V2778)

203
SiCN34-607 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 203
A35.
 


1((



1((


1 8
1

1
1
12
1


SiCN34-803

196
SiCN34-803 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 197
SiKR38-304

159
SiKR38-304E Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 159
SiKR39-504

175
SiKR39-504E Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 175
SiME34-608 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A (or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is
forming a short circuit Becomes NO
YES normal when X8A (or X15A) of
(continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 131
SiME34-811 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 231
SiTW34-808

223
SiTW34-808 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5 minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

Troubleshooting 223
SiTW39-507 Troubleshooting by Indication on the Remote Controller

7URXEOHVKRRWLQJ
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A is short circuited
disconnected)

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 115
6L86 7URXEOHVKRRWLQJE\,QGLFDWLRQRQWKH5HPRWH&RQWUROOHU

7URXEOHVKRRWLQJ
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power supply.

YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A is short circuited
disconnected)

NO YES
Loose connection of connector.

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoor unit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 105
Troubleshooting by Indication on the Remote Controller SiUS39-505

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

122 Troubleshooting
SiUS39-601 Troubleshooting by Indication on the Remote Controller

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

Troubleshooting 123
Troubleshooting by Indication on the Remote Controller SiUS39-602

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.

Is power supply NO
208~230V provided? Provide 208~230V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES

The float
switch contact is Becomes
forming a short circuit YES normal when X8A of NO
(continuity check the indoor unit PC board Defect of indoor unit PC board.
with X8A or X15A is short circuited
disconnected)

YES
Loose connection of connector.
NO

Water builds up NO The float switch NO


in the drain pan. functions normally. Replace float switch.

YES YES Modify the float switch's


connection and turn on again.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the turn on again.
indoorunit PC
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the indoor clogging or upward slope, etc.
unit.
NO

The voltage
of terminals Y1
and Y2 or X25A is NO
208~230 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).

YES
Replace the drain pump or
check for dirt, etc.

(V2778)

130 Troubleshooting