N2XSH RM 6/10 kV LV and MV cables for T & D


Phone: +49 511 676 3161
mv-team.nd@nexans.com

Single-core XLPE-insulated cables, longitudinally watertight, with flame retardant


halogen-free sheath, qualified also for laying in ground

DESCRIPTION
Construction
stranded copper conductor - conductor screen of semiconducting compound - XLPE
insulation - core screen of semiconducting compound - copper wire screen -
separation tape - flame retardant halogenfree sheath

Application
especially flame retardant; in ground, outdoors, in cable ducts and indoors.
ALSECURE. On request we also delivering with higher flame retardance, e. d.
according to ICE 60 332-3 STANDARDS
International IEC 60332-1;
IEC 60332-3; IEC 60754;
IEC 61034

National DIN VDE 0276 part 622

CHARACTERISTICS
Construction characteristics
Conductor shape Circular stranded (RM)
Insulation XLPE (chemical)
Halogen free IEC 60754
Usage characteristics
Packaging Drum
Minimum operating temperature -40 C
Minimum installation temperature -20 C
Bending factor when laying 15 (xD)
Smoke density IEC 61034
Flame retardant IEC 60332-1&3
Gases corrosivity IEC 60754
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C

Halogen free Minimum operating Minimum Bending factor Smoke density Flame retardant Gases corrosivity Max.conductor
IEC 60754 temperature installation when laying IEC 61034 IEC 60332-1&3 IEC 60754 temp.in service
-40 C temperature 15 (xD) 90 C
-20 C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 1.2 Generated 8/29/17 www.nexans.de Page 1 / 2
Contact
N2XSH RM 6/10 kV LV and MV cables for T & D
Phone: +49 511 676 3161
mv-team.nd@nexans.com

PRODUCT LIST
Nexans ref. Cross Nom. Screen Nom. Min. Max. Approx. Perm. current current
section insulation section outer outer outer weight rating buried rating in
[mm] thick. [mm] sheath diam. diam. [kg/km] 20C - trefoil air 30C -
[mm] thick. [mm] [mm] formation trefoil
[mm] [A] [A]
VCU135H10
35 3.4 16 2.5 23.0 28.0 1000 187 197
New
VCU150H10
50 3.4 16 2.5 24.0 29.0 1050 220 236
New
22080111
70 3.4 16 2.5 26.0 31.0 1375 268 294
New
VCU195H10
95 3.4 16 2.5 26.0 32.0 1650 320 358
New
VCU1120H1
0 120 3.4 16 2.5 28.0 34.0 1925 363 413
New
VCU1150H1
0 150 3.4 25 2.5 29.0 35.0 2300 405 468
New
VCU1185H1
0 185 3.4 25 2.5 31.0 37.0 2650 456 535
New
22080411
240 3.4 25 2.5 33.0 39.0 3250 526 631
New
VCU1300H1
0 300 3.4 25 2.5 36.0 41.0 3850 591 722
New
22060213
400 3.4 35 2.5 40.0 45.0 4850 662 827
New
VCU1500H1
0 500 3.4 35 2.5 43.0 48.0 5950 744 949
New
= Make to order, = In stock

SELLING INFORMATION

Note: On request we are delivering single core cables with cross sections up to 1000 mm.

Halogen free Minimum operating Minimum Bending factor Smoke density Flame retardant Gases corrosivity Max.conductor
IEC 60754 temperature installation when laying IEC 61034 IEC 60332-1&3 IEC 60754 temp.in service
-40 C temperature 15 (xD) 90 C
-20 C