Masterpact: connection

wiring diagrams
STR 18 M / 28 D / 38 S / 58 U
E30721

CHASSIS AUXILIARIES CONTROL UNIT BREAKER AUXILIARIES


CN 1 - CN +
Fu

AT ready
BPO to
close

BPF
connected disconnected fault closed open
springs
charged

314 312 324 322 334 332 344 342 352 354 362 364 372 374 82 84 212 222 234 244 12 14 22 24 32 34 42 44 D4 C12 C2 A4 252 254 262 B4

CE
or

M
MN
or MX XF
MNR
MX
OF

F F O O

SDE CH

processing
unit PF

CD CT

311 321 331 341 351 361 371 81 211 221 231 241 11 21 31 41 D1 C11 C1 A1 251 B1

Fu

CN2 - CN

AT: emergency off c diagram shown with circuits deenergised, Wiring of the MNR (modified diagram).
BPO: "open" pushbutton breaker open and in "connected" position, Instantaneous tripping with MNR when
BPF: "close" pushbutton springs charged and relays in released contact 254-262 opens.
CE: "connected" position contact position;
(10 A/240 V AC) c accessories such as pushbuttons, lamps
E30718

M: spring charging motor and fuses are not supplied with the circuit D4 254 262
(180 VA/240 V AC) breaker.
XF: closing release MNR
(20 VA/240 V AC)
MX: shunt release (20 VA/240 V AC) D1
MN: undervoltage release
(20 VA/240 V AC)
Note: the wiring of the external contact
MNR: time delayed undervoltage release
replaces the spring charged indication and
(20 VA/240 AC)
the contact PF.
OF: auxiliary changeover contacts
(10 A/240 V AC)
O: 2 auxiliary NO contacts
(10 A/240 V AC)
F: 2 auxiliary NC contacts
(10 A/240 V AC)
SDE: fault trip indication contact
(10 A/240 V AC)
CH: charging motor limit switch contact
PF: "ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
CD: "disconnected" position contact
(10 A/240 V AC)
CT: test posiiton contact
(10 A/240 V AC)

66 Merlin Gerin
Masterpact: connection
wiring diagrams
STR 28 D / 38 S / 58 U with options
E30720

CHASSIS AUXILIARIES CONTROL UNIT BREAKER AUXILIARIES


CN 1 - CN +
Fu

P1 S1
AT ready
BPO to
P2 S2 close
(4) (4)
BPF
connected disconnected LR fault closed open
(2) alarm springs
Ic1 Ic2
charged
(5)
362
364
372
374
344
342
314
312
324
322

352
334
332

354

Z11 Z12 LR2 T2 T1 V2 R1 R2 e+ e 82 84 212 222 234 244 12 14 22 24 32 34 42 44 D4 C12 C2 A4 252 254 262 B4

CE

or

M
MN
or MX XF
MNR
T
MX
OF

F F O O
F V
CH
SDE

ammeter
ALR
PF
proce-
ssing C
R
unit

CD CT

311 321 331 341 351 361 371


Z21 Z22 LR1 F2 F1 V1 C 81 211 221 231 241 11 21 31 41 D1 C11 C1 A1 251 B1

(3) power supply


(1)

Fu
CN2 - CN

AT: emergency off CD: "disconnected" position contact Wiring of the MNR (modified diagram).
BPO: "open" pushbutton (10 A/240 V AC) Instantaneous tripping with MNR when
BPF: "close" pushbutton CT: test position contact (10 A/240 V AC) contact 254-262 opens.
LR: long time trip (LT) indicating lamp C: communication.
CR: short time trip (ST) indicating lamp
E30718

T: earth fault trip indicating lamp c Ic1: load shedding command according to D4 254 262
CE: "connected" position contact Ic1 setting
(10 A/240 V AC) Ic2: load shedding command according to MNR
M: spring charging motor Ic2 setting;
(180 VA/240 V AC) c diagram shown with circuits deenergised, D1
R: load monitoring and control breaker open and in "connected" position,
XF: closing release (20 VA/240 V AC) springs charged and relays in released
Note: the wiring of the external contact
T: earth fault protection (EZ and SZ: position;
replaces the spring charged indication and
input and output for zone selective c accessories such as pushbuttons, lamps
the contact PF.
interlocking) and fuses are not supplied with the circuit
MX: shunt release (20 VA/240 V AC) breaker.
MN: undervoltage release
(20 VA/240 V AC) V contact wiring:
MNR: time delayed undervoltage release for breaker locking, depending on the
(20 VA/240 V AC) selected fault.
OF: auxiliary changeover contacts
(10 A/240 V AC)
E30719

CN1/CN +
O: 2 auxiliary NC contacts BPO
(10 A/240 V AC)
F: 2 auxiliary NC contacts V C2
(10 A/240 V AC)
V MX
SDE: fault trip indication contact
(1) Power supply terminals for I or T or F options
(10 A/240 V AC) (AD module with BAT battery module for backup V C1
CH: charging motor limit switch contact power). CN2/CN
F: fault trip local indicator (2) Zone selective interlocking with line side
FV: segregated fault trip indication contact breaker.
(5 A/240 V AC) (3) Zone selective interlocking with load side Selective locking needs:
breaker (remove jumper). c external power supply (F1, F2);
PF: "ready to close" contact (4) DC power supply. R contacts reset request
(10 A/240 V AC) (closing possible if c an additional terminal (BS).
wiring of an external contact.
breaker is open, not locked and (5) With Z and/or C options, terminal 84 is not
operating mechanism charged) available.

Merlin Gerin 67