GWA Gas-Fired Water Boilers – Boiler Manual

GWA
Gas-Fired Water Boilers

Boiler Manual
Contents Page

1 Prepare boiler location ........................................................ 2


2 Prepare boiler ..................................................................... 6
3 Install water piping ............................................................ 10
4 Install gas piping ............................................................... 13
5 Field wiring ....................................................................... 14
6 Start-up ............................................................................ 15
7 Checkout procedure ......................................................... 18
8 Sequence of operation — standing pilot boilers ................. 19
9 Lighting instructions — GWA standing pilot boilers ........... 20
10 Service and maintenance ................................................. 22
11 Troubleshooting ................................................................ 27
12 Replacement parts ........................................................... 29
13 Dimensions ...................................................................... 34
14 Ratings ............................................................................. 35

Hazard definitions
Hazards that will cause severe personal injury, Hazards that will or can cause minor personal injury
death or substantial property damage. or property damage.
Hazards that can cause severe personal injury, Special instructions on installation, operation or
death or substantial property damage. maintenance that are important but not related to
personal injury or property damage.

INSTALLER — Read all instructions before USER — Please read the following. Failure to
installing. Read page 2 first. Follow all instructions comply could result in severe personal injury, death
in proper order to prevent personal injury or death. or substantial property damage.
• Consider piping and installation when determining • This manual is for use only by your qualified
boiler location. heating installer/service technician.
• Any claims for damage or shortage in shipment • Please see the User’s Information Manual for your
must be filed immediately against the transportation reference.
company by the consignee. • Have the boiler serviced by a qualified service
technician, at least annually.

This manual must only be used by a qualified heating installer/service technician. Failure to comply could result in
severe personal injury, death or substantial property damage.

When calling or writing about the boiler— Please have: • boiler model number from the boiler rating label and • CP number
from the boiler jacket. You may list the CP number in the space provided on the “Installation and service certificate” found on
page 18.

36 Part Number 670 01 1001 00 Part Number 670 01 1001 00


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

Read this first! 1 Prepare boiler location 14 Ratings


Failure to adhere to the guidelines below can
result in severe personal injury, death or Codes & checklist
substantial property damage.
Installations must follow these codes:
When servicing boiler — • Local, state, provincial, and national codes, laws, regulations
and ordinances.
DOE
1. To avoid electric shock, disconnect electrical supply • National Fuel Gas Code, ANSI Z223.1–latest edition.
before performing maintenance. Boiler 0–2,000 feet altitude 2,000–4,500 feet altitude Net Boiler DOE Chimney
• Standard for Controls and Safety Devices for Automatically
2. To avoid severe burns, allow boiler to cool before Fired Boilers, ANSI/ASME CSD-1, when required. model (Canada) I=B=R water Seasonal and
performing maintenance. number ratings content efficiency breeching
• National Electrical Code.
(Btuh) (gallons) (% A.F.U.E) size
• For Canada only: B149.1 or B149.2 Installation Code, CSA
Boiler operation — C22.1 Canadian Electrical Code Part 1 and any local codes. Input DOE Heating Capacity Input Output NS NI
3. Do not block flow of combustion or ventilation air to boiler. (Btuh) (Output) (Btuh) (Btuh) (Btuh)
Certification
4. Should overheating occur or gas supply fail to shut off, do
(Note 3) (Note 1) (Note 4) (Note 2) (Note 3)
not turn off or disconnect electrical supply to circulator. The GWA boiler gas manifold and controls met safe
Instead, shut off the gas supply at a location external to lighting and other performance criteria when boiler
the appliance. underwent tests specified in ANSI Z21.13–latest GWA052 52,000 43,000 46,800 37,400 37,000 1.5 80.2 83.0 4"I.D. x 20’
5. Do not use this boiler if any part has been under water. edition.
Immediately call a qualified service technician to inspect
the boiler and to replace any part of the control system Before locating the boiler: GWA070 70,000 58,000 63,000 50,400 50,000 1.5 80.1 82.2 4"I.D. x 20’
and any gas control that has been under water.
❏ Check for nearby connection to:
• System water piping GWA105 105,000 88,000 94,500 75,600 77,000 2.1 80.4 82.9 5"I.D. x 20’
Boiler water — • Venting connections
• Gas supply piping
6. DO NOT use petroleum-based cleaning or sealing
compounds in boiler system. Water seal deterioration will • Electrical power GWA140 140,000 117,000 126,000 100,800 102,000 2.7 80.4 82.5 6"I.D. x 20’
occur, causing leakage between boiler sections, circulator
❏ Check area around boiler. Remove any combustible materials,
flanges, diaphragm tanks or other system components.
gasoline and other flammable liquids. GWA175 175,000 145,000 157,500 126,000 126,000 3.3 80.5 82.2 6"I.D. x 20’
This can result in substantial property damage.
7. DO NOT use "homemade cures" or "boiler patent Failure to keep boiler area clear and free of
medicines". Serious damage to boiler, personnel and/or combustible materials, gasoline and other flammable
property may result. GWA210 210,000 175,000 189,000 151,200 151,000 3.8 80.5 81.8 7"I.D. x 20’
liquids and vapors can result in severe personal
8. Continual fresh makeup water will reduce boiler life. Mineral injury, death or substantial property damage.
buildup in sections reduces heat transfer, overheats cast GWA245 245,000 202,000 220,500 176,400 176,000 4.4 80.5 81.4 7"I.D. x 20’
iron, and causes section failure. Addition of oxygen and ❏ Boiler must be installed so that gas control system components
other gases can cause internal corrosion. Leaks in boiler are protected from dripping or spraying water or rain during
or piping must be repaired at once to prevent makeup operation or service.
water. 1. Based on standard test procedures prescribed by the United States Department of
❏ If new boiler will replace existing boiler, check for and correct Energy.
9. Do not add cold water to hot boiler. Thermal shock can system problems, such as:
cause sections to crack. 2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the
1. System leaks causing oxygen corrosion or section cracks requirements of the building and nothing need be added for normal piping and pickup.
from hard water deposits. Ratings are based on a piping and pickup allowance of 1.15. An additional allowance
2. Incorrectly-sized expansion tank. should be made for unusual piping and pickup loads.
Glycol — potential fire hazard —
3. Lack of antifreeze in boiler water causing system and boiler 3. See information at right for model number suffixes. Letters shown are model number
All glycol is flammable when exposed to high temperatures. If to freeze and leak. suffixes. An “N” after the model number designates natural gas. The letter after the
glycol is allowed to accumulate in or around the boiler or any
“N” designates the pilot ignition system — “S” for standing pilot or “I” for spark-
other potential ignition source, a fire can develop. In order to
ignited pilot. For example, a suffix “NS” means a natural standing pilot boiler.
prevent potential severe personal injury, death or substantial
property damage from fire and/or structural damage: 4. Contact your International Comfort Products dealer regarding information and parts
for high altitude applications.
• Never store glycol of any kind near the boiler or any
potential ignition source.
• Monitor and inspect the system and boiler regularly for
leakage. Repair any leaks immediately to prevent possible
accumulation of glycol.
• Never use automotive antifreeze or ethylene glycol in the
system. Using these glycols can lead to hazardous Install GWA boilers for residential radiant panel systems, converted gravity
leakage of glycol in the boiler system. heating systems or other low water temperature applications per instructions
in this manual to avoid damage due to condensation.
GWA boilers are CSA design certified for installation on combustible
flooring.
GWA boilers are ASME rated for 50 psig working pressure.

2 Part Number 670 01 1001 00 Part Number 670 01 1001 00 35


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

13 Dimensions 1 Prepare boiler location continued

Clearances
Figure 21 Dimensional drawing — ALL DIMENSIONS IN INCHES Service clearances Small space installations
1. Provide minimum clearances for cleaning and servicing the 1. When the boiler is located in a closet or small space, provide
boiler and for access to controls and components as listed in clearances no less than those shown in Figure 1. The clearances
the table below: are required to any surface, whether combustible or non-
2. Provide at least screwdriver clearance to jacket front panel combustible.
screws for removal of front panel for inspection and minor
service. If unable to provide at least screwdriver clearance, Figure 1 Minimum clearances
install unions and shutoff valves in system so boiler can be
moved for servicing.

Service clearances: Minimum


Top (for cleaning flueways) 35"
Front (for access to controls and components) 18"
Back 7"
Left side (for cleaning and servicing) 24"
Right side 7"

Minimum clearance to combustible materials


1. Hot water pipes must be at least ½" from combustible material.
2. Single-wall vent pipe must be at least 6 inches from combustible
material.
3. Type B double-wall metal vent pipe — See vent manufacturer’s
recommendation for clearances to combustible material.
Clearances from combustible materials: Minimum
Front (provide means of access) 3"
Back 7" Residential garage installation
Left side (provide means of access) 6"
Take the following special precautions when installing the boiler in
Right side 2" a residential garage. If the boiler is located in a residential garage,
Top H per ANSI Z223.1, paragraph 5.1.9:
GWA052 to GWA105 35" • Mount the boiler a minimum of 18 inches above the floor of the
GWA140 35½" garage to assure the burner and ignition devices will be no less
GWA175 38½" than 18 inches above the floor.
GWA210 39¾" • Locate or protect the boiler so it cannot be damaged by a moving
GWA245 42½" vehicle.

Table 1 Minimum foundation size Flooring and foundation


Boiler Supply Return Gas connection “A” “D” “W” “H”
model tapping tapping & manifold size Vent Vent Jacket Damper
number (inches NPT) (inches NPT) (Note 3) location diameter width height Boiler Minimum Minimum Flooring
(inches NPT) model foundation foundation The GWA boiler is approved for installation on combustible flooring,
(inches) (inches) (inches) (inches)
length width but must never be installed on carpeting.
GWA052 11/4 11/4 /
12 5 4 10 453/8 GWA052 25" 12" Do not install boiler on carpeting even if foundation is
GWA070 11/4 11/4 /
12 5 4 10 523/8 used. Fire can result, causing severe personal injury,
GWA070 25" 12" death or substantial property damage.
GWA105 11/4 11/4 1/2 61/2 5 13 543/8
GWA105 25" 15"
GWA140 11/4 11/4 1/2 8 6 16 577/8 Foundation
GWA175 GWA140 25" 18"
11/4 11/4 1/2 91/2 6 19 60 7/8 1. Provide a solid brick or minimum 2-inch thick concrete
GWA210 11/4 11/4 3/4 11 7 22 62 1/8 GWA175 25" 21" foundation pad if any of the following is true:
GWA245 11/4 11/4 3/4 121/2 7 25 64 7/8 GWA210 25" 24" • floor can become flooded.
• the boiler mounting area is not level.
Note 3: Size gas piping from meter to boiler per local utility requirements. GWA245 25" 27"
2. See Table 1 for minimum foundation dimensions.

34 Part Number 670 01 1001 00 Part Number 670 01 1001 00 3


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

1 Prepare boiler location continued 12 Replacement parts continued

Vent system Figure 20 Gas control assembly

Failure to follow all instructions can result in flue gas Equipment”, of National Fuel Gas Code, ANSI Z223.1–latest
spillage and carbon monoxide emissions, causing edition and applicable building codes. Canadian installations
severe personal injury or death. must comply with B149.1 or B149.2 Installation Codes.
Inspect existing chimney before installing boiler. 2. See “Ratings” on page 35 for minimum chimney or vent sizes.
Failure to clean or replace perforated pipe or tile lining Chimney or vent termination:
will cause severe personal injury or death. • A chimney, or any vent other than a Type B vent with listed
vent cap, must extend at least 3 feet above the highest point
Do not alter boiler draft hood or place any obstruction where it passes through a roof of a building, and at least
or non-certified vent damper in breeching or vent 2 feet higher than any portion of a building within a horizontal
system. CSA certification will become void. Flue gas distance of 10 feet.
spillage and carbon monoxide emissions will occur
• Type B vents with listed caps may terminate as in Figure 2
causing severe personal injury or death.
if no closer than 8 feet from a vertical wall or similar
The following requirements apply when you remove obstruction.
an existing boiler from a vent system shared with • Otherwise, Type B vents must terminate at least 2 feet above
other appliances. If the new boiler will not use the the roof penetration and at least 2 feet higher than any portion
common vent, you must test (as described below) of a building within 10 feet.
each remaining appliance — operating by itself — to 3. A lined chimney is preferred and must be used when required
verify that the vent system operates adequately. by local, state, provincial and national codes, laws, regulations
and ordinances. Vitreous tile linings with joints that prevent
When removing boiler from existing common vent retention of moisture and linings made of noncorrosive materials
system: are best. Advice for flue connections and chimney linings can
be obtained from local gas utility. Type B double-wall metal vent
At the time of removal of an existing boiler, the following steps shall pipe or single-wall vent pipe may be used as a liner.
be followed with each appliance remaining connected to the common
venting system placed in operation, while the other appliances 4. Cold masonry chimneys, also known as outside chimneys,
remaining connected to the common venting system are not in typically have one or more walls exposed to outside air.
operation. When any atmospheric gas-fired boiler with automatic vent
damper is vented through this type of chimney, the potential
a. Seal any unused openings in the common venting system. exists for condensation to occur. Condensation can damage a
b. Visually inspect the venting system for proper size and horizontal masonry chimney. Williamson-Thermoflo recommends the
pitch and determine there is no blockage or restriction, leakage, following to prevent possible damage.
corrosion or other deficiencies which could cause an unsafe a. Line chimney with corrosion-resistant metal liner such as
condition. AL29-4C® single-wall stainless steel or B-vent. Size liner It em D esc ript ion Manuf ac t urer Manuf ac t urer’s Int ernat ional
c. Test vent system — Insofar as is practical, close all building per National Fuel Gas Code ANSI Z223.1–latest edition. number part number C omfort
doors and windows and all doors between the space in which Produc t s
b. Provide drain trap to remove any condensate.
the appliances remaining connected to the common venting part number
5. Where two or more gas appliances vent into a common
system are located and other spaces of the building. Turn on chimney or vent, equivalent area should be at least equal to St anding pilot — Nat ural gas c omponent s
clothes dryers and any appliance not connected to the common area of vent outlet on largest appliance plus 50 percent of vent 1 Gas valve, 1/2" x 1/2", GWA052 through GWA175 Honeywell VR8200A2116 511044360WT
venting system. Turn on any exhaust fans, such as range hoods outlet area of additional appliance. Robertshaw 7200ER
and bathroom exhausts, so they will operate at maximum speed.
Gas valve, 3/4" x 3/4", GWA210 and GWA245 Honeywell VR8300C4050 511044256WT
Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected. Follow the Figure 2 Terminations with Type B vent fitted with 2 Pilot assembly kit with orifice International Comfort Products 510811005WT
lighting/operating instructions. Adjust thermostat so appliance listed cap, provided vent is at least 8 feet
will operate continuously. from any vertical wall or similar obstruction 3 Tubing, pilot, aluminum 560742860WT

e. Test for spillage at draft hood relief opening after 5 minutes of 4 Tubing, thermocouple 511724254WT
main burner operation. Use the flame of a match or candle.
5 Transformer relay 510312167WT
f. After it has been determined that each appliance remaining
connected to the common venting system properly vents when not Wiring harness 591391862WT
tested as outlined above, return doors, windows, exhaust fans, shown
fireplace dampers, and any other gas-burning appliance to their
previous conditions of use.
Any improper operation of common venting system should be
corrected so the installation conforms with the National Fuel Gas
Code, ANSI Z223.1–latest edition. Correct by resizing to approach
the minimum size as determined using the appropriate tables in
Part 11 of that code. Canadian installations must comply with B149.1
or B149.2 Installation Code.

Chimney or vent requirements


1. Venting must be installed according to Part 7, “Venting of

4 Part Number 670 01 1001 00 Part Number 670 01 1001 00 33


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

12 Replacement parts continued 1 Prepare boiler location continued

Figure 19 Trim assembly Air contamination Air openings


Please review the following information on potential combustion air Combustion air and ventilation openings must comply with Section
contamination problems. 5.3, “Air for Combustion and Ventilation”, of National Fuel Gas Code
See Table 2 for products and areas which may cause contaminated ANSI Z223.1–latest edition, or applicable local building codes.
combustion air. Canadian installations must comply with B149.1 or B149.2
Installation Codes.
To prevent potential of severe personal injury or death, See table below for minimum combustion/ventilation air opening
check for products or areas listed below before sizes. Where openings are required, provide two (2) openings —
installing boiler. If any of these contaminants are found: one within 12 inches of the ceiling, the other within 12 inches of the
• Remove contaminants permanently. floor, as shown in the table illustrations.
— OR — Provide adequate combustion and ventilation air to
• Isolate boiler and provide outside combustion air. See assure proper combustion and reduce the risk of
national, provincial or local codes for further severe personal injury, death or substantial property
information. damage caused by flue gas spillage and carbon
monoxide emissions.

Table 2 Corrosive contaminants and likely locations

Products to avoid
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Item Description Manufacturer Manufacturer’s International
Comfort Hydrochloric acid/muriatic acid
number part number
Products
part number Cements and glues
1 Pressure relief valve, ASME, 30 PSIG, ¾" male inlet Conbraco 10-407-10 Antistatic fabric softeners used in clothes dryers
511546920WT
Watts M330
Pressure relief valve, ASME, 30 PSIG, ¾" female inlet Chlorine-type bleaches, detergents, and cleaning solvents found in
Conbraco 10-408-05
(Fittings shown are factory-installed on boiler.) 511546924WT household laundry rooms
Watts 335
2 Combination pressure-temperature gauge, with 2½" short Ametek PTA-1088 Adhesives used to fasten building products and other similar products
510218099WT
shank ENFM 4104
3 Drain valve, ¾" Conbraco 31-606-01
Areas likely to have contaminants
(Fittings shown are included with boiler.) Hammond Valve 710
511210423WT Dry cleaning/laundry areas and establishments
Matco-Norca 205F04
Watts BD-2C Swimming pools
4 Circulator (Fittings shown are shipped loose with boiler.) Taco 007 511405113WT
Metal fabrication plants
5 Circulator gasket, universal (2 per boiler) International Comfort Products 590317535WT
Beauty shops
not Circulator hardware kit, includes: International Comfort Products
shown 2 flanges, 4 nuts, 4 screws, 2 pipe nipples — Refrigeration repair shops
1" NPT — GWA052 through GWA140 381354525WT
1¼" NPT — GWA175 through GW245 381354526WT Photo processing plants
6 Circulator wiring harness International Comfort Products 591319793WT Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops

32 Part Number 670 01 1001 00 Part Number 670 01 1001 00 5


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

1 Prepare boiler location continued 12 Replacement parts continued

Air openings continued Figure 18 Jacket assembly

Exhaust fans and air movers Motorized air dampers


The appliance space must never be under a negative pressure. If the air openings are fitted with motorized dampers, electrically
Always provide air openings sized not only to the dimensions interlock the damper to:
required for the firing rate of all appliances, but also to handle the air • Prevent the boiler from firing if the damper is not fully open.
movement rate of the exhaust fans or air movers using air from the
building or space. • Shut the boiler down should the damper close during boiler
operation.
To accomplish this interlock, wire an isolated contact (proving the
damper open) in series with the thermostat input to the boiler. The
boiler will not start if this contact is open, and will shut down should
it open during operation.

2 Prepare boiler
3. Level and straighten burners.
Placement and setup Burners must be properly seated in slots in burner
rest with their openings face up. Main burner orifices
Place boiler/crate near position must inject down center of burner. Failure to properly
1. Leave boiler in crate and on pallet until installation site is seat burners will result in severe personal injury,
ready. death or substantial property damage.
2. Move entire crate and pallet next to selected location. 4. Reinstall access panel.
Do not operate boiler without access panel secured
3. Remove crate. Leave boiler on pallet.
in place. Failure to comply could cause momentary
4. Remove boiler from pallet as follows: flame rollout on ignition of main flame, resulting in Item Description International Item Description International
a. Tilt left side of boiler up and place a board under left legs. possible fire or personal injury hazard. number Comfort number Comfort
b. Tilt boiler the other way and place a board under right legs. Products Products
c. Slide boiler backwards off pallet and into position. part number part number
Do not drop boiler or bump jacket on floor or pallet. 1 Junction box, 4 x 4 5 Jacket GWA052 & GWA070 431223433WT
Damage to boiler can result. Table 3 Manifold orifice sizing (Available at local supply house) panel, top GWA105 431223434WT
GWA140 431223435WT
5. Check level. GWA175 431223436WT
Location Natural gas Propane gas 1a Junction box, 2 x 4
a. Shim legs, if necessary. (Available at local supply house) GWA210 431223437WT
b. Do not alter legs. Sea level – over Sea level – over GWA245 431223438WT
U. S. 2,000 ft 2,000 ft 2,000 ft 2,000 ft 6 Jacket GWA052 & GWA070 431223507WT
2 Jacket panel, left side, with 431223425WT cross tie GWA105 431223508WT
2.00 mm (Note 1) 1.30 mm (Note 1) GWA140 431223509WT
insulation
Inspect orifices and burners Sea level – 2,000 – Sea level – 2,000 –
GWA175 431223510WT
3 Jacket panel, right side, with 431223426WT GWA210 431223511WT
1. Remove front jacket door. Remove base access panel (See Canada 2,000 ft 4,500 2,000 ft 4,500 GWA245 431223512WT
insulation
Figure 17, item 4, page 30). 2.00 mm # 49 1.30 mm # 56 7 Jacket GWA052 & GWA070 431223427WT
2. Check for correctly-sized manifold orifices. See Table 3 for sizing. 4 Jacket GWA052 & GWA070 431223450WT panel, GWA105 431223428WT
Note 1: For U. S. elevations above 2,000 feet, contact your International Com- panel, GWA105 431223451WT interior, GWA140 431223429WT
(The orifice size is stamped on the orifice spud barrel.) fort Products supplier for details.
door GWA140 431223452WT with GWA175 431223430WT
Correctly-sized manifold orifices must be used. Failure GWA175 431223453WT insulation GWA210 431223431WT
to do so will result in severe personal injury, death or GWA210 431223454WT GWA245 431223432WT
substantial property damage. GWA245 431223455WT 8 Jacket GWA052 & GWA070 431223444WT
panel, GWA105 431223445WT
rear, with GWA140 431223446WT
insulation GWA175 431223447WT
GWA210 431223448WT
GWA245 431223449WT

The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per
instructions on page 23 of this manual. Failure to comply could result in severe personal injury.

6 Part Number 670 01 1001 00 Part Number 670 01 1001 00 31


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

12 Replacement parts continued 2 Prepare boiler continued

Figure 17 Base assembly, manifold, orifices and burners Pressure test


It em D esc ript ion Int ernat ional Perform hydrostatic pressure test Fill and pressure test
number C omfort Pressure test boiler before attaching water or gas piping or electrical 1. Open the shutoff valves you installed on supply and return
Produc t s
supply (except as noted below). connections.
part number
2. Slowly open boiler drain valve and fresh water supply to fill
Base assembly kit GWA052 & GWA070 381354200WT Prepare boiler for test boiler with water.
GWA105 381354201WT 1. Remove the shipping nipple (from GWA supply tapping) and
GWA140 381354202WT 3. When water flows from shutoff valves, close boiler drain valve.
GWA175 381354203WT remove the boiler relief valve. Temporarily plug the relief valve 4. Close shutoff valves.
GWA210 381354204WT tapping with a ¾" NPT pipe plug.
GWA245 381354205WT 5. Slowly reopen boiler drain valve until test pressure of not more
2. Remove 1¼" nipple, reducing tee and drain valve from than 45 psi is reached on the pressure/temperature gauge.
1 Base side panel (in Base assembly) accessory bag. Install in boiler return connection as shown on
in Figure 19, item 3, page 32. Install circulator on either the 6. Test at no more than 45 psi for no more than 10 minutes.
2 Base front cross-tie assembly (in Base assembly) return or supply.
3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/temperature Do not leave boiler unattended. A cold water fill could
3 Base back cross-tie assembly (in Base assembly) gauge from accessory bag. Pipe to boiler supply connection as expand and cause excessive pressure, resulting in
shown in Figure 19, item 2, page 32. (Use pipe dope sparingly.) severe personal injury, death or substantial property
4 Base access panel (in Base assembly) damage.
4. Connect a hose to boiler drain valve, the other end connected
5 Base pan angle, left side (in Base assembly) to a fresh water supply. Make sure hose can also be used to 7. Make sure constant gauge pressure has been maintained
drain boiler after test. throughout test. Check for leaks. Repair if found.
6 Base pan angle, right side (in Base assembly)
5. Connect a nipple and shutoff valve to system supply connection
7 Base pan (in Base assembly) on the 1¼" tee. This valve will be used to bleed air during the fill. Leaks must be repaired at once. Failure to do so can
(Valve and nipple are not included with boiler.) damage boiler, resulting in substantial property
8 Burner rest (in Base assembly) 6. Connect a nipple and shutoff valve to system return connection damage.
(at circulator flange if circulator installed on return). This valve
9 Base insulation kit GWA052 to GWA140 381354210WT
(includes insulation for GWA175 to GWA245 381354211WT will be used to bleed air during the fill. (Valve and nipple are not Do not use petroleum-based cleaning or sealing
all base parts above included with boiler.) compounds in boiler system. Severe damage to boiler
plus gasket material 7. Temporarily plug the air elimination tapping (next to supply will occur, resulting in substantial property damage.
needed between block
assembly and base) tapping).
Drain and remove fittings
10 Boiler leg kit 590424252WT 1. Disconnect fill water hose from water source.
11 Manifold GWA052 591126615WT
2. Drain boiler at drain valve or out hose, whichever provides best
GWA070 591126616WT access to drain. Remove hose after draining if used to drain
GWA105 591126617WT boiler.
GWA140 591126618WT
GWA175 591126619WT 3. Remove nipples, valves and plus unless they will remain for
GWA210 591126556WT use in the system piping.
GWA245 591126557WT 4. Remove plug from relief valve tapping. See Section 3, page 10,
12 Main burner orifice, sea level 560528997WT
to replace relief valve.

13 Burner, stainless steel 512200077WT

14 Burner with pilot Standing pilot 512200079WT


bracket
(not shown) Spark-ignited pilot 512200078WT

15 Screw, 10-32 x 3/ 8 STP type D hx, washer head available at


slot ZP local supply
house

16 Rollout thermal fuse element 512050230WT

30 Part Number 670 01 1001 00 Part Number 670 01 1001 00 7


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

2 Prepare boiler continued 12 Replacement parts

Draft hood & spill switch Install vent piping Figure 16 Section assembly, flue collector, draft hood and vent damper

Draft hood installation 1. Connect from draft hood or vent damper outlet to chimney or
vent with same size vent connector.
1. Orient draft hood with spill switch mounting holes to front of
boiler as shown in Figure 3. 2. Where possible, vertical venting to the outside from the draft
hood or vent damper outlet will offer best performance.
2. Secure draft hood to outlet at top of boiler with sheet metal
screws. 3. Where horizontal vent connector is used, slope upward at least
¼" per lineal foot toward chimney or vent and support with
3. Bottom of draft hood or skirt must have clearance dimension hangers to prevent sagging.
above jacket top panel as indicated on draft hood. 4. Breeching must not be connected to any portion of a mechanical
Do not alter boiler draft hood or place any draft system that can operate under positive pressure.
obstruction or non-approved vent damper in Long horizontal vent connector, excessive number
breeching or vent system. CSA certification will of elbow or tees, or other obstructions that restrict
become void. Flue gas spillage and carbon the flow of combustion gases should be avoided.
monoxide emissions will occur causing severe Severe personal injury, death or substantial property
personal injury or death. damage could result.
Improper orientation of spill switch may cause
boiler to shut down. The loss of heat can result in
significant damage due to freezing.

Spill switch installation


Vent damper
1. Fasten spill switch to draft hood as shown in Figure 3.
2. See Wiring diagram to connect wires:
These systems are used on gas-fired boilers with
a. Standing pilot boiler — see page 19.
vent dampers as shipped from factory. Boiler will not
b. Spark-ignited pilot boiler — see Control Supplement. operate without vent damper installed.
Only vent dampers listed in the Replacement parts
list on page 29 are certified for use with GWA boilers.
Figure 3 Spill switch with wire harness Any other vent damper installed could cause severe
personal injury or death.

Damper blade
Standing pilot ignition systems— See vent manufacturer’s
instructions to install plug (shipped with damper) in damper hole. Item Description International
Item Description International
For standing pilot boilers only, install plug with 3/8" diameter hole in
number Comfort number Comfort
vent damper hole. Products
Products
Spark-ignited pilot systems— See vent manufacturer’s part number part number
instructions to install plug (shipped with damper) in damper hole.
not shown Replacement GWA052 321114501WT 4 High limit, 30° differential, Honeywell L4080D1036 510312250WT
For spark-ignited pilot boilers only, install plug with no hole in vent
section GWA070 321114501WT with well White-Rodgers 11B81-3
damper hole.
assembly GWA105 321114502WT 5 Spill switch 510350105WT
GWA140 321114503WT
Minimum clearances GWA175 321114504WT
6 Vent 4" GWA052 Effikal RVGP-KS-4BKF 510512350WT
damper GWA070 *Johnson Controls Q35GB-2
Provide a minimum of 6" between the vent damper and any GWA210 321114505WT
combustible material. (See “Minimum clearance to combustible GWA245 321114506WT 5" GWA105 Effikal RVGP-KS-5BKF 510512351WT
materials,” page 3, for minimum clearance from jacket top to ceiling *Johnson Controls Q35GD-2
1 Radiation plate 460003700WT
to maintain this dimension.) (1 per joint) 6" GWA140 Effikal RVGP-KS-6BKF 510512352WT
GWA175 *Johnson Controls Q35GF-2
2 Collector GWA052 381354625WT
hood GWA070 381354626WT 7" GWA210 Effikal RVGP-KS-7BKF 510512353WT
GWA105 381354627WT GWA245 *Johnson Controls Q35GH-2
GWA140 381354628WT * Johnson Controls damper assemblies consist of M35BC
GWA175 381354629WT actuator and Y15 vent pipe
GWA210 381354630WT
7 Vent damper actuator Effikal RVGP only with vent
GWA245 381354631WT
Johnson M35BE-1C damper above
3 Draft hood GWA052 450021270WT
8 Vent damper harness 591391795WT
GWA070 450021271WT
GWA105 450021272WT
GWA140 450021273WT
GWA175 450021274WT
GWA210 450021275WT
GWA245 450021276WT

8 Part Number 670 01 1001 00 Part Number 670 01 1001 00 29


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

11 Troubleshooting continued 2 Prepare boiler continued

Chart 1 — Standing pilot — Boiler will not fire Vent damper continued
Damper installation
Before proceeding, follow "Troubleshooting sequence" on page 27. If problem persists, then:
Do not modify draft hood or vent damper, or make
another connection between draft hood and vent
Is damper harness securely plugged in at both ends? damper or boiler except as noted below. This will void
CSA certification and will not be covered by
Secure connections. No Yes Williamson-Thermoflo warranty. Any changes will
cause severe personal injury, death or substantial
Check for loose wire connections or bad relay on Is 24VAC present across transformer terminals C & Y? property damage.
transformer. 1. Install vent damper horizontally or vertically as shown in vent
No Yes damper manufacturer’s instructions. Vent damper must be
installed so that it serves only one boiler and so damper blade
Check for open thermostat, LWCO, high limit, spill switch or indicator is visible to the user. See Figure 4.
rollout thermal fuse element contacts or check for loose Is 24VAC present across transformer terminal C and yellow
wire connections. wire on vent damper connector? 2. Screws or rivets used to secure the vent damper to the draft
hood must not interfere with rotation of the damper blade.
If LWCO, spill switch or rollout thermal fuse No Yes 3. Install damper harness between damper actuator and hole in
element contacts are open, determine cause
and correct condition. Failure to do so will jacket left side panel. See Figure 3, page 8.
cause severe personal injury, death or Is vent damper rotated open? Use strain relief connectors and locknuts to secure both ends
substantial property damage. of damper harness.
No Yes Keep wiring harness clear of all hot surfaces. Wire
Check/repair out of round stack section. Figure 4 Vent damper assemblies insulation could be damaged, causing risk of electrical
Is 24VAC present across gas valve terminals? short-circuit.
Does vent damper rotate open?
No Yes No Yes 4. Read and apply the harness plug warning label (shown upper-
left) so that it is visible after installation
5. Plug damper harness receptacle into damper harness plug.
• Replace actuator.
• Retest. Is main flame on now? Bypassing (jumpering) vent damper will cause flue
products such as carbon monoxide to escape into
No Yes the house. This will cause severe personal injury or
Open thermostat contacts for 30 seconds. Vent damper will death.
rotate to closed position. Close thermostat contacts. Vent After boiler has operated once, if either end of harness
Retest. is disconnected, the system safety shutdown will
damper will rotate to open position.
Is 24VAC present across gas valve terminals? occur. The boiler will not operate until harness is
Is gas valve cock turned to ON position? reconnected.
No Yes Effikal damper — Damper hold open switch must be
No Yes
in Automatic Operation position for system to operate
properly.

Check continuity of each wire in damper harness. Does


continuity exist for each wire? See Table right.
• Turn gas valve cock to • Replace gas valve.
No Yes ON position. • Retest.
• Retest.
Remove damper harness from
• Replace damper damper harness plug.
wiring harness. TEMPORARILY install jumper
• Retest. between terminal 2 and
terminal 5 on damper plug in
boiler wiring harness. See
Table, right. Does boiler fire?
No Yes

• Replace gas valve. • Replace damper actuator.


• Retest. • Retest.

28 Part Number 670 01 1001 00 Part Number 670 01 1001 00 9


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

3 Install water piping 11 Troubleshooting


Label all wires prior to disconnection when servicing In event of vent damper failure:
General Near-boiler piping continued controls. Wiring errors can cause improper and
dangerous operation. Effikal vent damper
If installation is to comply with ASME or Canadian requirements, Table 4 Water pipe size (based on 20 °F rise) Never jumper (bypass) rollout thermal fuse element If troubleshooting chart recommends replacing actuator and actuator
an additional high temperature limit is needed. Install control in supply or any other device except for momentary testing as
Boiler model To From is not immediately available, damper blade can be fixed in an open
piping between boiler and isolation valve. Set second control to outlined in “Chart 1”, page 28. Severe personal injury, position to allow boiler operation. Manually turning blade can cause
minimum 20 °F above setpoint of first control. Maximum allowable number system system
death or substantial property damage can result. actuator damage. Follow these instructions only in case of no heat
setpoint is 240 °F. See page 19 for wiring.
GWA052 ¾" ¾" Burner access panel must be in position during boiler or damper actuator malfunction.
A low water cutoff device is required when boiler is installed above operation to prevent momentary flame rollout on
GWA070 1" 1" 1. Move damper service switch to Hold Damper Open position.
radiation level or by certain state or local codes or insurance ignition of main flame. Severe personal injury or Apply call for heat to boiler. Damper blade should then rotate to
companies. Use low water cutoff designed for water installations. GWA105 1" 1" substantial property damage will result. Open position and boiler will fire.
Electrode probe-type is recommended. Purchase and install in tee
supply piping above boiler. GWA140 1" 1" 2. If step 1 does not open damper, manually rotate damper blade
GWA175 1¼" 1¼" to open position using wrench or pliers on flat shaft between
Use backflow check valve in cold water supply if required by local
damper and actuator. Boiler will fire. Verify that damper service
codes. GWA210 1¼" 1¼" Before troubleshooting: switch is in Hold Damper Open position. (Figure 15)
GWA245 1½" 1½" 1. Have the following items: 3. Do not leave vent damper permanently in this position. Replace
a. Voltmeter that can check 120 VAC and 24 VAC. actuator immediately. If vent damper is left in Open position,
b. Microammeter with a scale range of 0-10. boiler will not operate at published efficiencies.
Circulator c. Continuity checker. Johnson Controls vent damper
Near-boiler piping d. U-tube manometer.
If troubleshooting chart recommends replacing actuator and actuator
The circulator is shipped loose (wiring pre-attached to boiler) to
See Table 4 and Figure 5 (diaphragm-type or bladder-type expansion allow you to locate it either in the return or supply piping, as desired. 2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) is not immediately available, damper blade can be fixed in an open
tank) or Figure 6 (closed-type expansion tank) on page 11 for near- See page 11 for a typical installation. Pipe the expansion tank to to boiler. position to allow boiler operation. Follow these instructions only in
boiler piping for systems designed for return water at least 130 °F. the suction side of the circulator whenever possible. Install an air 3. Make sure thermostat is calling for heat and contacts (including case of no heat or damper actuator malfunction. See Figure 15.
See page 12 (Figures 8 and 9) for near-boiler piping for low- separator in the supply piping. Connect the expansion tank to the appropriate zone controls) are closed. Check for 24 VAC 1. Turn off power to boiler.
temperature or high-volume systems. air separator only if the separator is on the suction side of the between thermostat wire nuts and ground. Failure to turn off power to boiler can result in severe
circulator. Always install the system fill connection at the same point personal injury, death or substantial property damage.
See page 11 (Figure 7) for boilers used with refrigeration systems. as the expansion tank connection to the system. Figures 5 and 6
show typical near-boiler piping connections. Troubleshooting sequence: 2. See vent damper manufacturer’s instructions for procedure to
Relief valve 1. Before proceeding, check for: fix vent damper in open position.
Expansion tank
Install relief valve vertically in ¾" tapping on side of boiler. See the • Loose connections, blown fuse or service switch off? 3. Turn on power to boiler.
tag attached to the relief valve for manufacturer’s instructions. Diaphragm-type or bladder-type expansion tank — • High limit switch set below boiler water temperature? 4. Using wrench or pliers on flat shaft section, manually rotate
To avoid water damage or scalding due to valve Figure 5 • Thermostat set below room temperature? damper blade until green light turns on. Boiler will fire. (Figure 15)
operation, discharge line must be connected to relief 1. Ensure expansion tank size will handle boiler and system water • Gas not turned on at meter or boiler? 5. Do not leave vent damper permanently in this position. Replace
valve outlet and run to a safe place of disposal. volume and temperature. Tank must be located in boiler return • Incoming gas pressure less than: actuator immediately. If vent damper is left in Open position,
Terminate the discharge line to eliminate possibility piping as close to boiler as possible, before inlet side of circulator. boiler will not operate at published efficiencies.
of severe burns should the valve discharge. 5" w.c. for natural gas? 11" w.c. for propane gas?
See tank manufacturer’s instructions for details.
• Discharge line must be as short as possible and be 2. If all of the above check correctly, check gas pressures:
2. Install an automatic air vent as shown.
the same size as the valve discharge connection a. With boiler off
throughout its entire length. Closed-type expansion tank — Figure 6 • 13" w.c. maximum natural or propane gas pressure
• Discharge line must pitch downward from the valve 1. Ensure expansion tank size will handle boiler and system water upstream of gas valve.
and terminate at least 6" above the floor drain where volume and temperature. See tank manufacturer’s instructions b. With boiler on: Figure 15 Manually opening vent damper
any discharge will be clearly visible. for details. • 5" w.c. minimum natural gas pressure or 11" w.c.
• The discharge line shall terminate plain, not threaded, 2. Connect tank to ½" NPT tapping located behind supply outlet, propane gas pressure upstream of gas valve.
with a material serviceable for temperatures of 375 °F using ½" NPT piping. Pitch any horizontal piping up towards • 3.5" w.c. minimum natural gas pressure or 10" w.c.
or greater. tank 1 inch per 5 feet of piping. propane gas pressure downstream tapping on gas
• Do not pipe the discharge to any place where freezing valve — Can be adjusted by regulator on gas valve.
could occur. Undersized expansion tanks cause system water to
be lost from relief valve and makeup water to be c. If gas pressure is incorrect or gas is not available to boiler,
• No shutoff valve shall be installed between the relief contact gas supplier to correct before proceeding further.
added through fill valve. Eventual section failure can
valve and boiler, or in the discharge line. Do not plug
result. 3. Check pilot operation - Follow “Lighting Instructions”, pages 20
or place any obstruction in the discharge line.
and 21.
• Failure to comply with the above guidelines could
result in failure of the relief valve to operate, resulting • If gas is available and you cannot obtain a pilot flame, try
in possibility of severe personal injury, death or purging the gas line and cleaning pilot and pilot gas tubing.
substantial property damage. Water piping — multiple zone systems Follow “Lighting Instructions” again. If you still cannot obtain
• Test the operation of the valve after filling and Install system piping using either circulator zoning or zone valve a flame, replace pilot burner and gas tubing. If this does not
pressurizing system by lifting the lever. Make sure zoning. Install expansion tank on suction side of system circulator. allow you to obtain a pilot flame, replace gas valve.
the valve discharges freely. If the valve fails to operate Always connect fill line only at the expansion tank — never at • If you obtain a pilot flame, but pilot will not remain on, replace Verify proper operation after servicing. • See vent
correctly, replace it with a new relief valve. another point in the system. thermocouple. If this does not correct problem, replace gas damper manufacturer’s instructions packed with vent
valve and pilot burner. damper for additional information. Failure to comply
• If pilot stays on, but main gas will not come on, proceed to could result in severe personal injury, death or
page 28. substantial property damage.

10 Part Number 670 01 1001 00 Part Number 670 01 1001 00 27


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

10 Service and maintenance continued 3 Install water piping continued

2. After following the preceding warning directions, if the relief valve


❏ Check/test. . . . . . . . . . continued weeps or will not seat properly, replace the relief valve. Ensure Near-boiler piping continued
that the reason for relief valve weeping is the valve and not Use Figure 5 or Figure 6 only for systems designed
Diaphragm- or bladder-type — welded gas tight with a rubber over-pressurization of the system due to expansion tank Figure 5 Diaphragm- or bladder-type expansion tank:
membrane to separate the tank pressurizing air and the water. for return water at least 130 °F. For systems with low
waterlogging or undersizing. Piping to single-zone system using return water temperature possible, such as
May be located at any point in the system, but most often found diaphragm-type or bladder-type expansion
near the boiler. converted gravity systems and radiant heating
tank. See Table 4 for piping sizes. systems, install bypass piping (see page 12) to
• Systems with this type of expansion tank require at least
protect boiler against condensation. Failure to prevent
one automatic air vent, preferably located on top of an air
low return water temperature to the boiler could cause
eliminator, as shown in examples in Manual Section 3,
page 10.
❏ Review with owner corrosion of the boiler sections or burners, resulting
in severe personal injury, death or substantial
2. If relief valve has tended to weep frequently, the expansion tank 1. Review the User’s Information Manual with the owner.
property damage.
may be waterlogged or undersized. 2. Emphasize the need to perform the maintenance schedule
Closed-type tank — tank is most likely waterlogged. Install a specified in the User’s Information Manual (and in this manual If system includes radiant heating circuits, provide
tank fitting if not already installed. Then check fill level per fitting as well). piping and controls to regulate the temperature
manufacturer’s instructions. If fill level is correct, check tank 3. Remind the owner of the need to call in a licensed contractor supplying the radiant circuits. Failure to comply could
size against manufacturer’s instructions. Replace with a larger should the boiler or system exhibit any unusual behavior. result in substantial property damage.
tank if necessary. 4. Remind the owner to follow the proper shutdown procedure
Diaphragm- or bladder-type — first, check tank size to be and to schedule an annual start-up at the beginning of the next Install boiler so that chilled medium is piped in parallel
sure it is large enough for the system. If size is too small, add heating season. with heating boiler (Figure 7). Use appropriate valves
additional tank(s) as necessary to provide sufficient expansion. to prevent chilled medium from entering boiler. Consult
If tank size is large enough, remove tank from system and I=B=R Installation and Piping Guides.
check charge pressure (usually 12 psig for residential If boiler is connected to heating coils located in air
applications). If tank won’t hold pressure, membrane has been handling units where they can be exposed to
damaged. Replace tank.
❏ Cleaning boiler heating surfaces refrigerated air, use flow control valves or other
automatic means to prevent gravity circulation during
Boiler relief valve cooling cycle. Circulation of cold water through the
The boiler contains ceramic fiber and fiberglass
1. Inspect the relief valve and lift the lever to verify flow as in the boiler could result in damage to the heat exchanger,
materials. Use care when handling these materials
following warnings, excerpted from a relief valve manufacturer’s causing possible severe personal injury, death or
per instructions on page 23 of this manual. Failure to
warning label. Before operating any relief valve, ensure that it is substantial property damage.
comply could result in severe personal injury.
piped with its discharge in a safe area to avoid severe scald 1. Shut down boiler:
potential. Read Manual Section 3, page 10, before proceeding
• Follow “To Turn Off Gas to Appliance” instructions on boiler
Water piping — refrigeration systems
further.
and “Lighting or Operating Instructions”. Prevent chilled water from entering boiler
Safety relief valves should be reinspected AT LEAST • Do not drain boiler unless it will be exposed to freezing
ONCE EVERY THREE YEARS, by a licensed plumb- Figure 6 Closed-type expansion tank: Piping to Install boiler so that chilled medium is piped in parallel with the
temperatures. If using antifreeze in system, do not drain.
ing contractor or authorized inspection agency, to single-zone system using closed-type heating boiler. Use appropriate valves to prevent chilled medium
2. Follow shutdown procedure. expansion tank. See Table 4 for piping sizes. from entering boiler. See Figure 7 for typical installation of balancing
ensure that the product has not been affected by
3. Remove venting system connection to boiler. valve and check valve.
corrosive water conditions and to ensure that the
valve and discharge line have not been altered or 4. Remove top jacket panel. Turn back insulation.
tampered with illegally. Certain naturally occurring 5. Remove flue collector. Clean sealant from assembly and Figure 7 Piping refrigeration systems
conditions may corrode the valve or its components sections.
over time, rendering the valve inoperative. Such con- 6. Remove radiation plates hanging between sections.
ditions are not detectable unless the valve and its 7. Remove burners from base. Brush and vacuum burners to
components are physically removed and inspected. remove all dust and lint. Verify that all burner ports are free of
This inspection must only be conducted by a plumb- debris.
ing contractor or authorized inspection agency — not 8. Place newspapers in base of boiler to collect soot.
by the owner. Failure to reinspect the boiler relief valve 9. Clean between sections with wire flue brush.
as directed could result in unsafe pressure buildup, 10. Remove newspaper and soot. Vacuum or brush base and
which can result in severe personal injury, death or surrounding area.
substantial property damage.
11. Reinstall radiation plates.
Following installation, the valve lever must be oper-
ated AT LEAST ONCE A YEAR to ensure that wa- 12. Replace collector box/transition assembly. Seal with sealant.
terways are clear. Certain naturally occurring min- Obtain gas-tight seal to prevent flue gas spillage and carbon
eral deposits may adhere to the valve, rendering it monoxide emissions, resulting in severe personal injury or death.
inoperative. When manually operating the lever, wa- 13. Replace insulation and jacket top panel.
ter will discharge and precautions must be taken to 14. Start up boiler following section 6, pages 15–17 of this manual
avoid contact with hot water and to avoid water dam- and the boiler “Lighting Instructions”, pages 20 and 21.
age. Before operating lever, check to see that a dis- Excessive sooting indicates improper gas combustion. If found,
charge line is connected to this valve directing the check for proper combustion and make any necessary
flow of hot water from the valve to a proper place of adjustments.
disposal otherwise severe personal injury may re-
sult. If no water flows, valve is inoperative. Shut down
boiler until a new relief valve has been installed.

26 Part Number 670 01 1001 00 Part Number 670 01 1001 00 11


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

3 Install water piping continued 10 Service and maintenance continued

Near-boiler piping continued ❏ Service. . . . . . . . . . ❏ Check/test. . . . . . . . . .


Figure 8 System bypass piping in boiler loop with Figure 9 Boiler bypass piping — use only for high Oiled-bearing circulators Air vents and air elimination
separate system circulator, using primary/ water content systems —DO NOT use for 1. The circulator shipped with the GWA boiler is water-lubricated. 1. Inspect automatic air vents (if used). Also inspect air separators
secondary piping. radiant panel systems. No oiling is required. to ensure they are operational.
2. Check other circulators in the system. Oil any circulators 2. The cap must be unscrewed one turn to allow air to escape.
requiring oil, following circulator manufacturer’s instructions. 3. If the air vent is leaking, remove cap and briefly push valve —
Over-oiling will damage the circulator. then release to clean the valve seat.
4. Replace cap by twisting all the way onto valve and then
unscrewing one turn.

Limit controls and cutoffs


❏ Start-up. . . . . . . . . . 1. Inspect and test the boiler limit control. Verify operation by turning
1. Perform start-up procedures Section 6, pages 15–17, including control set point below boiler temperature. Boiler should cycle
“Verify operation” of burners and vent damper on page 17. off. Return dial to original setting.
2. Verify cold fill pressure is correct and that fill system is working 2. Inspect and test additional limit controls or low water cutoffs
properly. installed on system.
3. Verify antifreeze level (if used) is at the right concentration and Expansion tank
that inhibitor level is correct.
1. Expansion tanks provide space for water to move in an out as
4. Check gas piping, per Manual Section 4, page 13 and Section
the heating system water expands due to temperature increase
6, page 15, verifying no indications of leakage and all piping
or contracts as the water cools. Tanks may be open, closed or
and connections are in good condition.
diaphragm or bladder type. See Section 3, page 10 of this
5. Read the “Lighting or Operating Instructions” (Manual Section 9, manual for suggested locations of expansion tanks and air
pages 20 and 21 or Control Supplement) applying to the boiler. eliminators.
6. Start the boiler following the “Lighting or Operating Instructions” Open-type — located above highest radiator or baseboard unit,
(Manual Section 9, pages 20 and 21 or Control Supplement). usually in the attic or closet. Has a gauge glass and overflow
pipe to a drain.
Closed-type — welded gas tight and located above boiler. Tank
is partially filled with water, leaving an air cushion for expansion.
• Make sure this type of tank is fitted with a tank fitting, such
❏ Check/test. . . . . . . . . . as the B & G Tank-Trol or Taco Taco-Trol. This fitting reduces
System bypass method Boiler bypass method gravity circulation of air-saturated tank water back to the
1. Apply bypass piping of Figure 8 to high water content systems, 1. Apply bypass piping of Figure 9 to high water content systems, Gas piping system and prevents the air from bubbling up through the
radiant panel systems or any system that is likely to operate such as converted gravity systems. 1. Sniff near floor and around boiler area for any indication of a water as it returns from the system.
with low return water temperature for extended periods. 2. The bypass arrangement shown protects the boiler from damage gas leak. • Do not use automatic air vents in systems with closed-type
2. The bypass arrangement shown protects the boiler from damage caused by condensate corrosion due to low return water 2. Test gas piping using bubble test, per Section 4, page 13 of this tanks. The air will escape from the system instead of
caused by condensate corrosion due to low return water temperature. This method does not provide protection from high manual, if there is any indication of a leak. returning to the tank. Eventually, the tank will waterlog and
temperature and protects low temperature systems from too temperature water being supplied to the system. no longer control pressurization. The boiler relief valve will
high a supply temperature. 3. DO NOT apply this piping to radiant panel systems. Cold fill and operating pressures weep frequently.
3. Adjust the bypass valves as indicated below. 4. Adjust the bypass valves as indicated below. 1. While the system is cold, note the pressure reading on the boiler
Adjust Bypass valves 1 and 2 as follows: pressure/temperature gauge. Verify that cold fill pressure is
Adjust Bypass valves 1 and 2 as follows: correct.
1. Start with valve 2 fully closed, valve 1 fully open. 1. Start with valve 1 fully closed, valve 2 fully open.
2. Watch the pressure as the boiler and system heat up to ensure
2. Slowly open valve 2 while closing valve 1. Adjust the valves 2. Slowly open valve 1 while closing valve 2. Adjust the valves pressure rise is normal. Too high a rise would indicate a
until the boiler pressure/temperature gauge reads 160 °F or until the boiler pressure/temperature gauge reads approximately waterlogged or undersized expansion tank.
higher. As you open the valves, pause long enough to allow 60 °F higher than the system temperature gauge. As you open
temperatures to level off. It takes a while for the boiler water the valves, pause long enough to allow temperatures to level
temperature to rise as the flow changes. off. It takes a while for the boiler water temperature to rise as
3. Bypass valve 2 allows hot boiler outlet water to blend with colder the flow changes.
return water, raising the supply temperature to the boiler. Bypass 3. Bypass valve 1 controls system flow rate. Bypass valve 2
valve 1 balances the pressure drop through valve 2. controls flow through the boiler.
4. The purpose of this piping is to raise the return water temperature 4. The purpose of this piping is to cause a high enough temperature
to the boiler enough to prevent condensation of flue gases. rise in the boiler that the average temperature will be warm
enough to prevent condensation of flue gases.

Install all components specified above and adjust valves as described to prevent low temperature in the boiler. Failure to
prevent low water temperature in the boiler could cause corrosion of the boiler sections or burners, resulting in severe
personal injury, death or substantial property damage.

12 Part Number 670 01 1001 00 Part Number 670 01 1001 00 25


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

10 Service and maintenance continued 4 Install gas piping


The boiler should be inspected and started annually,
at the beginning of the heating season, only by a ❏ Inspect . . . . . . . . . . Connecting gas supply piping to boiler
qualified service technician. In addition, the
maintenance and care of the boiler designated in Water piping 1. Remove jacket front panel and see Figure 10 to pipe gas to Natural Gas:
Table 6, page 22 and explained on the following pages 1. Check the boiler interior piping and all system piping for signs boiler. 1. See Table 5 for pipe length and diameter. Base on rated
must be performed to assure maximum boiler of leaks. a. Install drip leg at inlet of gas connection to boiler. Where boiler input (divide by 1,000 to obtain cubic feet per hour).
efficiency and reliability. Failure to service and local utility requires drip leg to be extended to the floor, use Table 5 is only for gas with specific gravity 0.60, with a
2. Repair any leaks before proceeding. appropriate length of nipple between cap and tee.
maintain the boiler and system could result in pressure drop through the gas piping of 0.30" w.c. For
equipment failure. b. Install ground joint union for servicing, when required. additional gas pipe sizing information, see ANSI Z223.1
Electrical shock hazard — Turn off power to the boiler Do not use petroleum-based cleaning or sealing c. Install manual shutoff valve in gas supply piping outside (B149.1 or B149.2 for Canadian installations).
before any service operation on the boiler except as compounds in boiler system. Severe damage to boiler boiler jacket when required by local codes or utility
will occur, resulting in substantial property damage. 2. Inlet pressure required at gas valve inlet:
noted otherwise in this manual. Failure to turn off requirements. • Maximum: 13" w.c.
electrical power could result in electrical shock, Eliminate all system or boiler leaks. Continual fresh d. In Canada — When using manual main shutoff valve, it must
causing severe personal injury or death. • Minimum: 5" w.c.
makeup water will reduce boiler life. Minerals can be identified by the installer.
build up in sections, reducing heat transfer, • Manifold gas pressure: 3.5" w.c.
The boiler contains ceramic fiber and fiberglass 2. Support piping with hangers, not by boiler or its accessories.
overheating cast iron, and causing section failure. 3. Install 100% lockup gas pressure regulator in supply line if
materials. Use care when handling these materials Leaking water may also cause severe property 3. Purge all air from gas supply piping. inlet pressure exceeds 13" w.c. Adjust for 13" w.c. maximum.
per instructions on page 23 of this manual. Failure to damage. 4. Before placing boiler in operation, check boiler and its gas
comply could result in severe personal injury. connection for leaks. Propane Gas:
a. Close manual main shutoff valve during any pressure 1. Contact gas supplier to size pipes, tanks and 100% lockup
testing at less than 13" w.c. gas pressure regulator.
Boiler heating surfaces b. Disconnect boiler and gas valve from gas supply piping
2. Adjust propane supply regulator provided by gas supplier
1. Disconnect the vent pipe at the boiler draft hood and remove during any pressure testing greater than 13" w.c.
❏ Inspect . . . . . . . . . . draft hood after turning off power to the boiler. Do not check for gas leaks with an open flame —
for 13" w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
2. Use a bright light to inspect the boiler flue collector and heating Use bubble test. Failure to use bubble test or check
surfaces. • Maximum: 13" w.c.
for gas leaks can cause severe personal injury, death
Reported problems or substantial property damage. • Minimum: 11" w.c.
3. If the vent pipe or boiler interior surfaces show evidence of
Inspect any problems reported by owner and correct before soot, follow “Cleaning boiler heating surfaces” in this manual • Manifold gas pressure: 10" w.c.
5. Use pipe dope compatible with propane gases. Apply sparingly
proceeding. section, page 26. Remove the flue collector and clean the boiler only to male threads of pipe joints so that pipe dope does not
if necessary after closer inspection of boiler heating surfaces. block gas flow. Figure 10 Gas supply piping
Boiler area 4. If there is evidence of rusty scale deposits on boiler surfaces, Failure to apply pipe dope as described in this manual
1. Verify that boiler area is free of any combustible materials, check the water piping and control system to make sure the can result in severe personal injury, death or
gasoline and other flammable vapors and liquids. boiler return water temperature is properly maintained (per this substantial property damage.
2. Verify that boiler area (and air intake) is free of any of the manual).
contaminants listed in Table 2 on page 5 of this manual. If any of 5. Reconnect vent and draft hood. Replace all boiler components
these are present in the boiler intake air vicinity, they must be before returning to service.
removed. If they cannot be removed, install combustion air piping 6. Check inside and around boiler for evidence of any leaks from Table 5 Pipe capacity for 0.60 specific gravity natural gas
to the boiler in accordance with national, provincial or local the boiler. If found, locate source of leaks and repair.
codes. Gas pipe Capacity of pipe for pipe size of:
Burners and base length (Capacity in standard cubic feet gas per hour)
Air openings (feet) ½" ¾" 1" 1¼" 1½"
1. After turning off power to the boiler, remove the jacket door and
1. Verify that combustion and ventilation air openings to the boiler base access panel (Figure 17, item 4, page 30). 10 132 278 520 1050 1600
room and/or building are open and unobstructed. Check
operation and wiring of automatic combustion air dampers, if 2. Inspect burners and all other components in the boiler base. 20 92 190 350 730 1100
used. 3. If burners must be cleaned, raise rear of each burner to release 30 73 152 285 590 860
2. Verify that boiler vent discharge and air intake are clean and from support slot, slide forward and remove. Then brush and 40 63 130 245 500 760
free of obstructions. vacuum the burners thoroughly, making sure all ports are free
50 56 115 215 440 670
of debris. Carefully replace all burners, making sure burner with
pilot bracket is replaced in its original position and all burners 75 45 93 175 360 545
Flue gas vent system
are upright (ports up). 100 38 79 150 305 460
1. Visually inspect entire flue gas venting system for blockage, 4. Inspect the base insulation. 150 31 64 120 250 380
deterioration or leakage. Repair any joints that show signs of
leakage in accordance with vent manufacturer’s instructions. The boiler contains ceramic fiber and fiberglass
materials. Use care when handling these materials
2. Verify that masonry chimneys are lined, lining is in good per instructions on page 23 of this manual. Failure to
condition, and there are not openings into the chimney. comply could result in severe personal injury.
Failure to inspect for the above conditions and have a. Verify that the insulation is intact and secure against all four
them repaired can result in severe personal injury or sides of the base.
death. If insulation is damaged or displaced, do not operate
the boiler. Replace or reposition insulation as
Pilot and main burner flames necessary. Failure to replace damaged insulation can
1. Visually inspect pilot burner and main burner flames as directed result in a fire hazard, causing severe personal injury,
under Section 6, page 17 of this manual. death or substantial property damage.

24 Part Number 670 01 1001 00 Part Number 670 01 1001 00 13


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

5 Field wiring 10 Service and maintenance continued

For your safety, turn off electrical power supply at


service entrance panel before making any electrical
Thermostat Handling ceramic fiber and fiberglass materials
1. Connect thermostat as shown on wiring diagram on boiler.
connections to avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or 2. Install on inside wall away from influences of drafts, hot or cold
death. water pipes, lighting fixtures, television, sunrays or fireplaces.
Wiring must be N.E.C. Class 1. 3. If thermostat has a heat anticipator, set heat anticipator in REMOVAL OF COMBUSTION CHAMBER LINING OR BASE PANELS
If rollout thermal fuse element wire as supplied with thermostat to match power requirements of equipment
boiler must be replaced, type 200 °C wire or equivalent connected to it. If connected directly to boiler, set for 0.4 amps.
For other devices, see manufacturer’s specifications. Wiring The combustion chamber lining or base insulation panels in this product contain ceramic fiber materials. Ceramic
must be used. If other original wiring as supplied with fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research
boiler must be replaced, use only type 105 °C wire or diagram on boiler gives setting for control module and gas valve.
Also see instructions with thermostat. on Cancer (IARC) has concluded, "Crystalline silica inhaled in the form of quartz or cristobalite from occupational
equivalent. sources is carcinogenic to humans (Group 1).":
Boiler must be electrically grounded as required by
Junction box (furnished)
National Electrical Code ANSI/NFPA 70–latest edition. ■ Avoid breathing dust and contact with skin and eyes.
1. Connect 120 VAC power wiring (Figure 11).
Electrical installation must comply with: 2. Fused disconnect or service switch (15 amp. recommended) • Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for
may be mounted on this box. For those installations with local cristobalite at the time this document was written. Other types of respirators may be needed depending on
1. National Electrical Code and any other national, state, provincial the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://
or local codes or regulations. codes which prohibit installation of fused disconnect or service
switch on boiler, install a 2 x 4 cover plate on the boiler junction www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and box and mount the service switch remotely as required by the also listed on this web site.
any local codes. code. • Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Wiring connections ■ Apply enough water to the combustion chamber lining or base insulation to prevent airborne dust.
Wiring multiple zones
Boiler is shipped with controls completely wired, except spill switch See zone valve manufacturer’s literature for wiring and application. ■ Remove combustion chamber lining or base insulation from the boiler and place it in a plastic bag for disposal.
and vent damper. See wiring diagram on page 19 for standing pilot A separate transformer is required to power zone valves. Zoning ■ Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
ignition boiler or Control Supplement for spark-ignited pilot boiler. with circulators requires a relay for each circulator.
Circulator is shipped loose, but wiring harness is pre-attached to NIOSH stated First Aid.
the boiler. Connect wires in circulator junction box.
■ Eye: Irrigate immediately
■ Breathing: Fresh air.
Figure 11 Field wiring connections — service switch and thermostat (or end switch) provided by installer

REMOVAL OF FIBERGLASS WOOL — OR —

INSTALLATION OF FIBERGLASS WOOL, COMBUSTION CHAMBER LINING OR BASE


PANELS:

This product contains fiberglass jacket insulation and ceramic fiber materials in combustion chamber lining or base
panels in gas fired products. Airborne fibers from these materials have been listed by the State of California as a
possible cause of cancer through inhalation.

■ Avoid breathing dust and contact with skin and eyes.


• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for
fiberglass wool at the time this document was written. Other types of respirators may be needed depending
on the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://
www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are
also listed on this web site.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
■ Operations such as sawing, blowing, tear out, and spraying may generate airborne fiber concentration requiring
additional protection.
■ Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
■ Eye: Irrigate immediately
■ Breathing: Fresh air.

14 Part Number 670 01 1001 00 Part Number 670 01 1001 00 23


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

10 Service and maintenance 6 Start-up


Table 6 Service and maintenance schedules (service technician and owner) Fill the system with water
Preparation
1. Close manual and automatic air vents and boiler drain cock.
Check for gas leaks 2. Fill to correct system pressure. Correct pressure will vary
Before starting the boiler, and during initial with each application. Typical cold water fill pressure for a
operation, smell near the floor and around the boiler residential system is 12 psi.
Service technician Owner maintenance for gas odorant or any unusual odor. Do not 3. Purge air from system:
(see following pages for instructions) (see User’s Information Manual for instructions) proceed with start-up if there is any indication of a a. Connect a hose to purge valve or valves, if installed.
gas leak. Repair any leak at once. Route hose to an area where water can drain and be
Propane boilers only — Your propane supplier mixes seen.
❏ Inspect: an odorant with the propane to make its presence
❏ Daily • Check boiler area b. Close the boiler or system isolation valve between the
detectable. In some instances, the odorant can fade purge valve and fill connection to the system.
• Reported problems
and the gas may no longer have an odor. c. Close zone isolation valves.
• Check boiler pressure/
• Boiler area • Propane gas can accumulate at floor level. Smell near d. Open quick-fill valve on cold water makeup line.
temperature gauge
the floor for the gas odorant or any unusual odor. If you e. Open purge valve.
• Air openings suspect a leak, do not attempt to light the pilot.
• Check air openings f. One zone at a time, open the isolation valves. Allow water
• Use caution when attempting to light the propane pilot.
to run through the zone, pushing out the air. Run until no
• Flue gas vent system This should be done by a qualified service technician,
noticeable air flow is present. Close the zone isolation valves
particularly if pilot outages are common.
• Pilot and main burner flames and proceed with the next zone. Follow this procedure until
• Periodically check the odorant level of your gas. all zones are purged.
❏ Monthly • Check boiler piping • Inspect boiler and system at least yearly to make sure
• Water piping g. Close the quick-fill water valve and purge valve and remove
all gas piping is leak-tight.
the hose. Open all isolation valves. Watch that system
• Check venting system • Consult your propane supplier regarding installation
• Boiler heating surfaces pressure rises to correct cold-fill pressure.
of a gas leak detector. There are some products on the
market intended for this purpose. Your supplier may be h. After the system has operated for a while, eliminate any
• Burners, base and inlet air box • Check boiler relief valve
ANNNUAL START-UP

able to suggest an appropriate device. residual air by using the manual air vents located throughout
the system.
❏ Service: • Check automatic air vents (if used) i. If purge valves are not installed in system, open manual air
Determine if water treatment is needed vents in system one at a time, beginning with lowest floor.
• Oiled-bearing circulators • Check pilot and main burner flames Do not use petroleum-based cleaning or sealing Close vent when water squirts out. Repeat with remaining
compounds in boiler system. Severe damage to vents.
❏ Start-up: boiler will occur, resulting in substantial property 4. Open automatic air vent (diaphragm-type or bladder-type
damage. expansion tank systems only) one turn.
• Perform start-up per manual ❏ Periodically • Test low water cutoff (if used) Eliminate all system leaks. Continual fresh makeup
water will reduce boiler life. Minerals can build up 5. Open other vents:
in sections, reducing heat transfer, overheating a. Starting on the lowest floor, open air vents one at a time
❏ Check/test: until water squirts out.
cast iron, and causing section failure.
b. Repeat with remaining vents.
• Gas piping ❏ Every 6 months • Operate relief valve
Verify water chemistry 6. Refill to correct pressure.
• Cold fill and operating pressures Consult local water treatment companies for unusually hard
water areas (above 7 grains hardness) or low pH water conditions Inspect system water piping
• Air vents and air elimination ❏ End of season • Shut down procedure (below 7.0). Boiler water pH of 7.0 to 8.5 is recommended. After filling the boiler and system with water, inspect all piping
throughout the system for leaks. If found, repair immediately. Repeat
• Limit controls and cutoffs Freeze protection (when used) this inspection after the boiler has been started and the system
• Expansion tank Use antifreeze made especially for hydronic systems. Inhibited has heated up.
propylene glycol is recommended. Leaks must be repaired at once. Failure to do so can
• Boiler relief valve Do not use ethylene glycol, automotive or undiluted damage the boiler, resulting in substantial property
antifreeze. Severe personal injury or death can damage.
❏ Review: result. Do not use petroleum-based cleaning or sealing
1. Determine antifreeze quantity according to system water compounds in boiler system. Severe damage to boiler
• Review with owner content. Boiler water content is listed on page 35. Remember will occur, resulting in substantial property damage.
to include expansion tank water content. Inspect base insulation
2. Follow antifreeze manufacturer's instructions. Check to make sure insulation is secure against all four sides of
3. A 50% solution of propylene glycol/water provides maximum the base. If insulation is damaged or displaced, do not operate boiler.
protection to about -30 °F. Replace or reposition insulation.
4. Local codes may require back flow preventer or actual Failure to replace damaged insulation or reposition
disconnect from city water supply. insulation can result in a fire hazard, causing severe
5. When using antifreeze in a system with automatic fill, install personal injury, death or substantial property damage.
Follow the “Service and maintenance” procedures given throughout this manual and in component literature shipped with a water meter to monitor water makeup. Glycol will leak before The boiler contains ceramic fiber and fiberglass
the boiler. See “Read this first” on page 2. Failure to perform the service and maintenance could result in damage to the boiler the water begins to leak, causing glycol level to drop. Added materials. Use care when handling these materials
or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, water will dilute the antifreeze, reducing the freeze protection per instructions on page 23 of this manual. Failure to
death or substantial property damage. level. comply could result in severe personal injury.

22 Part Number 670 01 1001 00 Part Number 670 01 1001 00 15


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

6 Start-up continued 9 Lighting Instructions — GWA standing pilot boilers

Operate boiler Robertshaw 7200 gas valve


DO NOT proceed with boiler operation unless boiler Check system and boiler
and system have been filled with water and all Eliminate all system leaks. Continual fresh makeup
instructions and procedures of previous manual water will reduce boiler life. Minerals can build up in
sections have been completed. Failure to do so could sections, reducing heat transfer, overheating cast iron,
result in severe personal injury, death or substantial and causing section failure. FOR YOUR SAFETY READ BEFORE LIGHTING
property damage. Before starting the boiler . . .
If you discover evidence of any gas leak, shut down
• See pages 20 and 21, for standing pilot boiler “Lighting the boiler at once. Find the leak source with bubble
Instructions”, or the Control Supplement for spark- If you do not follow these instructions exactly, a fire or explosion may result causing
test and repair immediately. Do not start boiler again property damage, personal injury or loss of life.
ignited pilot “Operating Instructions”. until corrected. Failure to comply could result in
• Verify the boiler and system are full of water (or glycol/ severe personal injury, death or substantial property
water mixture, if used). damage. A. This appliance has a pilot, which must be C. Use only your hand to push down the reset button or turn the gas control
• Verify the “Preparation” procedures of page 15 have Do not use petroleum-based cleaning or sealing lighted by hand. When lighting the pilot, follow knob. Never use tools. If the knob or reset button will not operate by hand,
been completed. compounds in boiler system. Severe damage to boiler these instructions exactly. don't try to repair it, call a qualified service technician. Force or attempted
will occur, resulting in substantial property damage. B. Before LIGHTING, smell all around the repair may result in a fire or explosion.
Start the boiler appliance area for gas. Be sure to smell next D. Do not use this appliance if any part has been under water. Immediately call
1. Check system piping for leaks. If found, shut down boiler and
Follow the “Lighting or Operating Boiler Instructions” from: repair immediately. to the floor because some gas is heavier than a qualified service technician to inspect the appliance and to replace any
• Standing pilot boilers — Manual pages 20 and 21. 2. Vent air from system using manual vents. Air in the system will air and will settle on the floor. See below. part of the control system and any gas control, which has been under water.
• Spark-ignited pilot boilers — See Control Supplement. interfere with circulation and cause heat distribution problems
and noise. WHAT TO DO IF YOU SMELL GAS
Remove boiler jacket door and note the gas valve manufacturer
and model number. 3. Inspect vent system thoroughly for signs of deterioration from
corrosion, physical damage or sagging. Verify that masonry • Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s
See either page 20 or page 21, depending on gas valve installed in phone. Follow the gas supplier’s instructions.
boiler. Use only the “Lighting Instruction” which applies to this gas chimney liners are in good condition, with no obstructions, and • Do not touch any electric switch; do not use any phone in
there are no openings into the chimney. your building. • If you cannot reach your gas supplier, call the fire
valve. (The “Lighting Instruction” label on the boiler provides the
4. Check around the boiler for gas odor following the procedure of department.
same information.)
If boiler fails to start, see “If boiler doesn’t start . . . Check for:” on “Check for gas leaks”, page 15. LIGHTING INSTRUCTIONS
this page. 5. Verify operation using procedures below. Perform “Checkout
procedure”, page 18, and fill in the “Installation and service 1. Stop! Read the safety information above on this label. 9. Remove access panel located above burners.
certificate”. 2. Set the thermostat to lowest setting. 10. Find pilot — follow metal tube from gas control.
3. When equipped with Effikal vent damper Model RVGP, place The pilot is between two burners behind the
If boiler doesn’t start . . . Check for: access panel.
service switch in Hold Damper Open position.
1. Loose connections, blown fuse or service switch off? 11. Move selector arm on gas control right
4. Turn off all electrical power to the appliance.
2. High limit switch set below boiler water temperature? to SET position.
5. When equipped with Johnson Controls vent damper Model
3. Thermostat set below room temperature? M35, manually rotate damper blade in direction of arrow to
4. Gas not turned on at meter or boiler? Open position indicated on damper assembly. 12. Hold selector arm in SET position and immediately light the
5. Incoming gas pressure less than: 6. Depress and move selector arm left to OFF. pilot with a match. Continue to hold selector arm to SET for
5" w.c. for natural gas? 11" w.c. for propane gas? 7. When equipped with vent damper, verify damper blade is in about one-half (1/2) minute after the pilot is lit.
6. If none of the above corrects the problem, see full open position. 13. Release selector arm. If pilot does not remain lit, repeat steps
“Troubleshooting”, Section 11, page 27. 6 through 13.
• If the pilot will not stay lit after several tries, move selector
arm left to OFF and call your service technician or gas
supplier.
14. Replace access panel.
15. Turn selector arm left to ON.
16. Turn on all electric power to the appliance.
17. When equipped with Effikal vent damper, place service
8. Wait five (5) minutes to clear out any gas. Then smell for switch in Automatic Operation position.
gas, including near the floor. If you smell gas, STOP! Follow
"B" in the safety information above. If you don't smell gas, 18. Set thermostat to desired setting.
go to the next step. 19. Replace front panel.

TO TURN OFF GAS TO THE APPLIANCE


1. Set the thermostat to lowest setting. 3. Remove front panel.
2. Turn off all electric power to the appliance if service is to be 4. Depress and move selector arm left to OFF.
performed. 5. Replace front panel.

16 Part Number 670 01 1001 00 Part Number 670 01 1001 00 21


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

9 Lighting Instructions — GWA standing pilot boilers 6 Start-up continued

Honeywell VR8200/VR8300 gas valve Verify operation


Check the pilot ignition system used for the boiler. Check burner flames — Main burner
The boiler model suffix will contain an “S” for standing
pilot or an “I” for spark-ignited pilot. See Section 9, Proper main burner flame (see Figure 13):
pages 20 and 21, for standing pilot boiler “Lighting 1. Yellow-orange streaks may appear (caused by dust).
FOR YOUR SAFETY READ BEFORE LIGHTING Instructions”, or the Control Supplement for spark-
ignited pilot “Operating Instructions”. Improper main burner flame:
1. Overfired — Large flames.
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, personal injury or loss of life. 2. Underfired — Small flames.
Check burner flame — Pilot burner
3. Lack of primary air — Yellow tipping on flames (sooting will
Proper pilot flame (see Figure 12): occur).
A. This appliance has a pilot, which must be C. Use only your hand to push down the reset button or turn the gas control
lighted by hand. When lighting the pilot, follow knob. Never use tools. If the knob or reset button will not operate by hand, 1. Blue flame.
these instructions exactly. don't try to repair it, call a qualified service technician. Force or attempted Figure 13 Typical main burner flame
2. Inner cone engulfing thermocouple (standing pilot) or pilot flame
B. Before LIGHTING, smell all around the repair may result in a fire or explosion. sensor (spark-ignited pilot).
appliance area for gas. Be sure to smell next D. Do not use this appliance if any part has been under water. Immediately call 3. Thermocouple or pilot flame sensor glowing cherry red.
to the floor because some gas is heavier than a qualified service technician to inspect the appliance and to replace any
air and will settle on the floor. See below. part of the control system and any gas control, which has been under water. Improper pilot flame:
1. Overfired — Large flame lifting or blowing past pilot flame
WHAT TO DO IF YOU SMELL GAS sensor.
2. Underfired — Small flame. Inner cone not engulfing pilot flame
• Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s phone.
sensor.
• Do not touch any electric switch; do not use any phone in Follow the gas supplier’s instructions.
3. Lack of primary air — Yellow flame tip.
your building. • If you cannot reach your gas supplier, call the fire department.
4. Incorrectly heated pilot flame sensor.
LIGHTING INSTRUCTIONS
Check vent damper operation
1. Stop! Read the safety information above on this label. 9. Remove access panel located above burners.
Figure 12 Typical pilot burner flame 1. Raise room thermostat to call for heat — Vent damper actuator
2. Set the thermostat to lowest setting. 10. Find pilot — follow metal tube from gas control. will slowly open vent damper.
3. When equipped with Effikal vent damper Model RVGP, place The pilot is between two burners behind the
access panel. 2. When vent damper is fully open — Main gas valve will open
service switch in Hold Damper Open position. and main burners will ignite. (Spark-ignited pilot controls will
4. Turn off all electrical power to the appliance. 11. Turn gas control knob counterclockwise to first light pilot, then allow main burners to ignite.)
PILOT.
5. When equipped with Johnson Controls vent damper Model Vent damper must be fully open before main burners
M35, manually rotate damper blade in direction of arrow to 12. Push in red reset button and hold. Immediately light the pilot light. If vent damper does not fully open, flue products
Open position indicated on damper assembly. with a match. Continue to hold reset button in for about one such as carbon monoxide will escape into house,
6. Turn gas control knob clockwise to OFF. (1) minute after the pilot is lit. causing severe personal injury or death.
7. When equipped with vent damper, verify damper blade is in 13. Release reset button. Pilot should remain lit. If pilot goes out, 3. Lower thermostat setting — Main burner flames will go out, then
full open position. repeat steps 6 through 13. vent damper will close.
• If reset button stays depressed after release, stop and 4. Repeat Steps 2 through 4 several times to verify operation.
immediately call your service technician or gas supplier. 5. Return thermostat to normal setting.
• If the pilot will not stay lit after several tries, turn the gas control 6. Set thermostat heat anticipator setting indicated on wiring
knob clockwise to OFF and call your service technician diagram.
or gas supplier.
14. Replace access panel. Check venting system operation
15. Turn gas control knob counterclockwise to ON. 1. With boiler firing, hold a candle or match below lower edge of
16. Turn on all electric power to the appliance. draft hood “skirt.” If flame does not blow out, but burns
undisturbed, the vent system is working properly. If flame blows
8. Wait five (5) minutes to clear out any gas. Then smell for 17. When equipped with Effikal vent damper, place service switch out or flickers severely, the vent system must be checked for
gas, including near the floor. If you smell gas, STOP! Follow in Automatic Operation position. obstructions or other causes of improper venting.
"B" in the safety information above. If you don't smell gas, 18. Set thermostat to desired setting.
go to the next step. 19. Replace front panel.

TO TURN OFF GAS TO THE APPLIANCE


1. Set the thermostat to lowest setting. 3. Remove front panel.
2. Turn off all electric power to the appliance if service is to be 4. Turn gas control knob clockwise to OFF.
performed. 5. Replace front panel.

20 Part Number 670 01 1001 00 Part Number 670 01 1001 00 17


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

circulator continues to run. When the limit circuit closes again, the main gas valve is
circulator are de-energized when call for heat stops. Burners are de-energized, but

3. Limit operation: When a limit control opens, the main gas valve is de-energized, but

4. Thermostat heat anticipator: Set heat anticipator as shown on wiring diagram,


Burners remain ignited until thermostat circuit or limit circuit opens. Burners and
7 Checkout procedure
❏ Boiler and heat distribution units filled with water? gas valve. Manometer should confirm there is no gas
❏ Automatic air vent, if used, open one full turn? flow. Pilot will relight, flame sensing element will sense
pilot flame and main burners reignite.
❏ Air purged from system?
❏ Set limit control(s) to system temperature requirements.
❏ Air purged from gas piping? Piping checked for leaks? Adjust balancing valves and controls to provide design
❏ Correctly-sized manifold orifices installed? See Table 3, temperature to system.
page 6, to check size and fuel type. ❏ For multiple zones, adjust flow so it is about the same in
Correctly sized manifold orifices must be used. each zone.
Failure to do so will cause severe personal injury,
❏ Verify thermostat heat anticipator (if available) set properly?
death or substantial property damage.

circulator remains on, if the limit circuit opens.


See “Field wiring”, Manual Section 5, page 14, “Thermostat”.
❏ Followed “Lighting or Operating Instructions” on boiler or in
Manual Section 9 or Control Supplement for proper start-up? ❏ Cycle boiler with thermostat — Raise to highest setting and
verify boiler goes through normal start-up cycle. Lower to lowest

energized if there is still a call for heat.


Proper burner flame observed? See “Verify operation”, Manual setting and verify boiler goes off.
Section 6, page 17.
❏ Measure natural gas input:
❏ Test limit control — While burners are operating, move indicator

Sequence of operation — standing pilot boilers


a. Operate boiler 10 minutes.
on limit control below actual boiler water temperature. Burners
should go off while circulator continues to operate. Raise setting b. Turn off other appliances.
on limit control above boiler water temperature and burners c. At natural gas meter, measure time (in seconds) required
should reignite. to use one cubic foot of gas.
❏ Test additional field-installed controls — If boiler has a low water d. Calculate gas input:
cutoff, additional high limit or other controls, test for operation 3600 x 1000
= Btuh
as outlined by manufacturer. Burners should be operating and number of seconds from step c
should go off when controls are tested. When controls are

Figure 14.
e. Btuh calculated should approximate input rating on boiler
restored, burners should reignite. rating label.
❏ Button on spill switch pushed in? ❏ Check manifold gas pressure by connecting manometer to
❏ Test ignition system safety device: downstream test tapping on main gas valve. Manifold pressure
a. Standing pilot — Turn gas cock knob to PILOT position for natural gas should be 3.5" w.c. and for propane gas should
and extinguish pilot flame. Pilot gas flow should stop in less be 10" w.c.
than 3 minutes. Put system back into operation (see ❏

1. Standby mode: After pilot is manually lighted, the gas valve provides pilot gas and
operating the boiler. Failure to do so could result in severe personal injury,

maintains pilot as long as the thermocouple is satisfied. If thermocouple signal drops


Follow all procedures given in this manual and “Lighting Instructions” when

for any reason, pilot must be manually lighted, following the “Lighting Instructions” in

2. Call for heat: When thermostat circuit closes, the boiler circulator and vent damper

end switch energizes the main gas valve. This provides gas to the main burners.
are energized. The vent damper drives open. When the vent damper is fully open, its
Observe several operating cycles for proper operation.
Section 6, pages 15-17).
❏ Set room thermostat to desired room temperature.
b. Spark-ignited pilot — Connect manometer to outlet side
of gas valve. Start boiler, allowing for normal start-up cycle ❏ Fill in Installation and service certificate below?

this manual and on boiler. Vent damper will remain closed until a call for heat.
to occur and main burners to ignite. With main burners on, ❏ Review all instructions shipped with this boiler with owner or
manually shut off gas supply at manual main shutoff gas maintenance person. Return instructions to envelope and give
valve. Burners should go off. Open manual main shutoff to owner or place in pocket inside front panel in boiler.

Installation and service certificate

Wiring diagram — Standing pilot system


Boiler model _______________________________________________________________ Series ____________

death or substantial property damage.


CP number _______________________________________ Date installed _________________________________

o Installation instructions have been followed.

Measured Btuh input ____________


o Checkout sequence has been performed.
o Above information is certified to be correct.
o Information received and left with owner/maintenance person.

Installer _______________________ ______________________________ ____________________________


(company) (address) (phone)

Figure 14
_____________________________________
(installer’s signature)
8

18 Part Number 670 01 1001 00 Part Number 670 01 1001 00 19


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

circulator continues to run. When the limit circuit closes again, the main gas valve is
circulator are de-energized when call for heat stops. Burners are de-energized, but

3. Limit operation: When a limit control opens, the main gas valve is de-energized, but

4. Thermostat heat anticipator: Set heat anticipator as shown on wiring diagram,


Burners remain ignited until thermostat circuit or limit circuit opens. Burners and
7 Checkout procedure
❏ Boiler and heat distribution units filled with water? gas valve. Manometer should confirm there is no gas
❏ Automatic air vent, if used, open one full turn? flow. Pilot will relight, flame sensing element will sense
pilot flame and main burners reignite.
❏ Air purged from system?
❏ Set limit control(s) to system temperature requirements.
❏ Air purged from gas piping? Piping checked for leaks? Adjust balancing valves and controls to provide design
❏ Correctly-sized manifold orifices installed? See Table 3, temperature to system.
page 6, to check size and fuel type. ❏ For multiple zones, adjust flow so it is about the same in
Correctly sized manifold orifices must be used. each zone.
Failure to do so will cause severe personal injury,
❏ Verify thermostat heat anticipator (if available) set properly?
death or substantial property damage.

circulator remains on, if the limit circuit opens.


See “Field wiring”, Manual Section 5, page 14, “Thermostat”.
❏ Followed “Lighting or Operating Instructions” on boiler or in
Manual Section 9 or Control Supplement for proper start-up? ❏ Cycle boiler with thermostat — Raise to highest setting and
verify boiler goes through normal start-up cycle. Lower to lowest

energized if there is still a call for heat.


Proper burner flame observed? See “Verify operation”, Manual setting and verify boiler goes off.
Section 6, page 17.
❏ Measure natural gas input:
❏ Test limit control — While burners are operating, move indicator

Sequence of operation — standing pilot boilers


a. Operate boiler 10 minutes.
on limit control below actual boiler water temperature. Burners
should go off while circulator continues to operate. Raise setting b. Turn off other appliances.
on limit control above boiler water temperature and burners c. At natural gas meter, measure time (in seconds) required
should reignite. to use one cubic foot of gas.
❏ Test additional field-installed controls — If boiler has a low water d. Calculate gas input:
cutoff, additional high limit or other controls, test for operation 3600 x 1000
= Btuh
as outlined by manufacturer. Burners should be operating and number of seconds from step c
should go off when controls are tested. When controls are

Figure 14.
e. Btuh calculated should approximate input rating on boiler
restored, burners should reignite. rating label.
❏ Button on spill switch pushed in? ❏ Check manifold gas pressure by connecting manometer to
❏ Test ignition system safety device: downstream test tapping on main gas valve. Manifold pressure
a. Standing pilot — Turn gas cock knob to PILOT position for natural gas should be 3.5" w.c. and for propane gas should
and extinguish pilot flame. Pilot gas flow should stop in less be 10" w.c.
than 3 minutes. Put system back into operation (see ❏

1. Standby mode: After pilot is manually lighted, the gas valve provides pilot gas and
operating the boiler. Failure to do so could result in severe personal injury,

maintains pilot as long as the thermocouple is satisfied. If thermocouple signal drops


Follow all procedures given in this manual and “Lighting Instructions” when

for any reason, pilot must be manually lighted, following the “Lighting Instructions” in

2. Call for heat: When thermostat circuit closes, the boiler circulator and vent damper

end switch energizes the main gas valve. This provides gas to the main burners.
are energized. The vent damper drives open. When the vent damper is fully open, its
Observe several operating cycles for proper operation.
Section 6, pages 15-17).
❏ Set room thermostat to desired room temperature.
b. Spark-ignited pilot — Connect manometer to outlet side
of gas valve. Start boiler, allowing for normal start-up cycle ❏ Fill in Installation and service certificate below?

this manual and on boiler. Vent damper will remain closed until a call for heat.
to occur and main burners to ignite. With main burners on, ❏ Review all instructions shipped with this boiler with owner or
manually shut off gas supply at manual main shutoff gas maintenance person. Return instructions to envelope and give
valve. Burners should go off. Open manual main shutoff to owner or place in pocket inside front panel in boiler.

Installation and service certificate

Wiring diagram — Standing pilot system


Boiler model _______________________________________________________________ Series ____________

death or substantial property damage.


CP number _______________________________________ Date installed _________________________________

o Installation instructions have been followed.

Measured Btuh input ____________


o Checkout sequence has been performed.
o Above information is certified to be correct.
o Information received and left with owner/maintenance person.

Installer _______________________ ______________________________ ____________________________


(company) (address) (phone)

Figure 14
_____________________________________
(installer’s signature)
8

18 Part Number 670 01 1001 00 Part Number 670 01 1001 00 19


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

9 Lighting Instructions — GWA standing pilot boilers 6 Start-up continued

Honeywell VR8200/VR8300 gas valve Verify operation


Check the pilot ignition system used for the boiler. Check burner flames — Main burner
The boiler model suffix will contain an “S” for standing
pilot or an “I” for spark-ignited pilot. See Section 9, Proper main burner flame (see Figure 13):
pages 20 and 21, for standing pilot boiler “Lighting 1. Yellow-orange streaks may appear (caused by dust).
FOR YOUR SAFETY READ BEFORE LIGHTING Instructions”, or the Control Supplement for spark-
ignited pilot “Operating Instructions”. Improper main burner flame:
1. Overfired — Large flames.
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, personal injury or loss of life. 2. Underfired — Small flames.
Check burner flame — Pilot burner
3. Lack of primary air — Yellow tipping on flames (sooting will
Proper pilot flame (see Figure 12): occur).
A. This appliance has a pilot, which must be C. Use only your hand to push down the reset button or turn the gas control
lighted by hand. When lighting the pilot, follow knob. Never use tools. If the knob or reset button will not operate by hand, 1. Blue flame.
these instructions exactly. don't try to repair it, call a qualified service technician. Force or attempted Figure 13 Typical main burner flame
2. Inner cone engulfing thermocouple (standing pilot) or pilot flame
B. Before LIGHTING, smell all around the repair may result in a fire or explosion. sensor (spark-ignited pilot).
appliance area for gas. Be sure to smell next D. Do not use this appliance if any part has been under water. Immediately call 3. Thermocouple or pilot flame sensor glowing cherry red.
to the floor because some gas is heavier than a qualified service technician to inspect the appliance and to replace any
air and will settle on the floor. See below. part of the control system and any gas control, which has been under water. Improper pilot flame:
1. Overfired — Large flame lifting or blowing past pilot flame
WHAT TO DO IF YOU SMELL GAS sensor.
2. Underfired — Small flame. Inner cone not engulfing pilot flame
• Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s phone.
sensor.
• Do not touch any electric switch; do not use any phone in Follow the gas supplier’s instructions.
3. Lack of primary air — Yellow flame tip.
your building. • If you cannot reach your gas supplier, call the fire department.
4. Incorrectly heated pilot flame sensor.
LIGHTING INSTRUCTIONS
Check vent damper operation
1. Stop! Read the safety information above on this label. 9. Remove access panel located above burners.
Figure 12 Typical pilot burner flame 1. Raise room thermostat to call for heat — Vent damper actuator
2. Set the thermostat to lowest setting. 10. Find pilot — follow metal tube from gas control. will slowly open vent damper.
3. When equipped with Effikal vent damper Model RVGP, place The pilot is between two burners behind the
access panel. 2. When vent damper is fully open — Main gas valve will open
service switch in Hold Damper Open position. and main burners will ignite. (Spark-ignited pilot controls will
4. Turn off all electrical power to the appliance. 11. Turn gas control knob counterclockwise to first light pilot, then allow main burners to ignite.)
PILOT.
5. When equipped with Johnson Controls vent damper Model Vent damper must be fully open before main burners
M35, manually rotate damper blade in direction of arrow to 12. Push in red reset button and hold. Immediately light the pilot light. If vent damper does not fully open, flue products
Open position indicated on damper assembly. with a match. Continue to hold reset button in for about one such as carbon monoxide will escape into house,
6. Turn gas control knob clockwise to OFF. (1) minute after the pilot is lit. causing severe personal injury or death.
7. When equipped with vent damper, verify damper blade is in 13. Release reset button. Pilot should remain lit. If pilot goes out, 3. Lower thermostat setting — Main burner flames will go out, then
full open position. repeat steps 6 through 13. vent damper will close.
• If reset button stays depressed after release, stop and 4. Repeat Steps 2 through 4 several times to verify operation.
immediately call your service technician or gas supplier. 5. Return thermostat to normal setting.
• If the pilot will not stay lit after several tries, turn the gas control 6. Set thermostat heat anticipator setting indicated on wiring
knob clockwise to OFF and call your service technician diagram.
or gas supplier.
14. Replace access panel. Check venting system operation
15. Turn gas control knob counterclockwise to ON. 1. With boiler firing, hold a candle or match below lower edge of
16. Turn on all electric power to the appliance. draft hood “skirt.” If flame does not blow out, but burns
undisturbed, the vent system is working properly. If flame blows
8. Wait five (5) minutes to clear out any gas. Then smell for 17. When equipped with Effikal vent damper, place service switch out or flickers severely, the vent system must be checked for
gas, including near the floor. If you smell gas, STOP! Follow in Automatic Operation position. obstructions or other causes of improper venting.
"B" in the safety information above. If you don't smell gas, 18. Set thermostat to desired setting.
go to the next step. 19. Replace front panel.

TO TURN OFF GAS TO THE APPLIANCE


1. Set the thermostat to lowest setting. 3. Remove front panel.
2. Turn off all electric power to the appliance if service is to be 4. Turn gas control knob clockwise to OFF.
performed. 5. Replace front panel.

20 Part Number 670 01 1001 00 Part Number 670 01 1001 00 17


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

6 Start-up continued 9 Lighting Instructions — GWA standing pilot boilers

Operate boiler Robertshaw 7200 gas valve


DO NOT proceed with boiler operation unless boiler Check system and boiler
and system have been filled with water and all Eliminate all system leaks. Continual fresh makeup
instructions and procedures of previous manual water will reduce boiler life. Minerals can build up in
sections have been completed. Failure to do so could sections, reducing heat transfer, overheating cast iron,
result in severe personal injury, death or substantial and causing section failure. FOR YOUR SAFETY READ BEFORE LIGHTING
property damage. Before starting the boiler . . .
If you discover evidence of any gas leak, shut down
• See pages 20 and 21, for standing pilot boiler “Lighting the boiler at once. Find the leak source with bubble
Instructions”, or the Control Supplement for spark- If you do not follow these instructions exactly, a fire or explosion may result causing
test and repair immediately. Do not start boiler again property damage, personal injury or loss of life.
ignited pilot “Operating Instructions”. until corrected. Failure to comply could result in
• Verify the boiler and system are full of water (or glycol/ severe personal injury, death or substantial property
water mixture, if used). damage. A. This appliance has a pilot, which must be C. Use only your hand to push down the reset button or turn the gas control
• Verify the “Preparation” procedures of page 15 have Do not use petroleum-based cleaning or sealing lighted by hand. When lighting the pilot, follow knob. Never use tools. If the knob or reset button will not operate by hand,
been completed. compounds in boiler system. Severe damage to boiler these instructions exactly. don't try to repair it, call a qualified service technician. Force or attempted
will occur, resulting in substantial property damage. B. Before LIGHTING, smell all around the repair may result in a fire or explosion.
Start the boiler appliance area for gas. Be sure to smell next D. Do not use this appliance if any part has been under water. Immediately call
1. Check system piping for leaks. If found, shut down boiler and
Follow the “Lighting or Operating Boiler Instructions” from: repair immediately. to the floor because some gas is heavier than a qualified service technician to inspect the appliance and to replace any
• Standing pilot boilers — Manual pages 20 and 21. 2. Vent air from system using manual vents. Air in the system will air and will settle on the floor. See below. part of the control system and any gas control, which has been under water.
• Spark-ignited pilot boilers — See Control Supplement. interfere with circulation and cause heat distribution problems
and noise. WHAT TO DO IF YOU SMELL GAS
Remove boiler jacket door and note the gas valve manufacturer
and model number. 3. Inspect vent system thoroughly for signs of deterioration from
corrosion, physical damage or sagging. Verify that masonry • Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s
See either page 20 or page 21, depending on gas valve installed in phone. Follow the gas supplier’s instructions.
boiler. Use only the “Lighting Instruction” which applies to this gas chimney liners are in good condition, with no obstructions, and • Do not touch any electric switch; do not use any phone in
there are no openings into the chimney. your building. • If you cannot reach your gas supplier, call the fire
valve. (The “Lighting Instruction” label on the boiler provides the
4. Check around the boiler for gas odor following the procedure of department.
same information.)
If boiler fails to start, see “If boiler doesn’t start . . . Check for:” on “Check for gas leaks”, page 15. LIGHTING INSTRUCTIONS
this page. 5. Verify operation using procedures below. Perform “Checkout
procedure”, page 18, and fill in the “Installation and service 1. Stop! Read the safety information above on this label. 9. Remove access panel located above burners.
certificate”. 2. Set the thermostat to lowest setting. 10. Find pilot — follow metal tube from gas control.
3. When equipped with Effikal vent damper Model RVGP, place The pilot is between two burners behind the
If boiler doesn’t start . . . Check for: access panel.
service switch in Hold Damper Open position.
1. Loose connections, blown fuse or service switch off? 11. Move selector arm on gas control right
4. Turn off all electrical power to the appliance.
2. High limit switch set below boiler water temperature? to SET position.
5. When equipped with Johnson Controls vent damper Model
3. Thermostat set below room temperature? M35, manually rotate damper blade in direction of arrow to
4. Gas not turned on at meter or boiler? Open position indicated on damper assembly. 12. Hold selector arm in SET position and immediately light the
5. Incoming gas pressure less than: 6. Depress and move selector arm left to OFF. pilot with a match. Continue to hold selector arm to SET for
5" w.c. for natural gas? 11" w.c. for propane gas? 7. When equipped with vent damper, verify damper blade is in about one-half (1/2) minute after the pilot is lit.
6. If none of the above corrects the problem, see full open position. 13. Release selector arm. If pilot does not remain lit, repeat steps
“Troubleshooting”, Section 11, page 27. 6 through 13.
• If the pilot will not stay lit after several tries, move selector
arm left to OFF and call your service technician or gas
supplier.
14. Replace access panel.
15. Turn selector arm left to ON.
16. Turn on all electric power to the appliance.
17. When equipped with Effikal vent damper, place service
8. Wait five (5) minutes to clear out any gas. Then smell for switch in Automatic Operation position.
gas, including near the floor. If you smell gas, STOP! Follow
"B" in the safety information above. If you don't smell gas, 18. Set thermostat to desired setting.
go to the next step. 19. Replace front panel.

TO TURN OFF GAS TO THE APPLIANCE


1. Set the thermostat to lowest setting. 3. Remove front panel.
2. Turn off all electric power to the appliance if service is to be 4. Depress and move selector arm left to OFF.
performed. 5. Replace front panel.

16 Part Number 670 01 1001 00 Part Number 670 01 1001 00 21


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

10 Service and maintenance 6 Start-up


Table 6 Service and maintenance schedules (service technician and owner) Fill the system with water
Preparation
1. Close manual and automatic air vents and boiler drain cock.
Check for gas leaks 2. Fill to correct system pressure. Correct pressure will vary
Before starting the boiler, and during initial with each application. Typical cold water fill pressure for a
operation, smell near the floor and around the boiler residential system is 12 psi.
Service technician Owner maintenance for gas odorant or any unusual odor. Do not 3. Purge air from system:
(see following pages for instructions) (see User’s Information Manual for instructions) proceed with start-up if there is any indication of a a. Connect a hose to purge valve or valves, if installed.
gas leak. Repair any leak at once. Route hose to an area where water can drain and be
Propane boilers only — Your propane supplier mixes seen.
❏ Inspect: an odorant with the propane to make its presence
❏ Daily • Check boiler area b. Close the boiler or system isolation valve between the
detectable. In some instances, the odorant can fade purge valve and fill connection to the system.
• Reported problems
and the gas may no longer have an odor. c. Close zone isolation valves.
• Check boiler pressure/
• Boiler area • Propane gas can accumulate at floor level. Smell near d. Open quick-fill valve on cold water makeup line.
temperature gauge
the floor for the gas odorant or any unusual odor. If you e. Open purge valve.
• Air openings suspect a leak, do not attempt to light the pilot.
• Check air openings f. One zone at a time, open the isolation valves. Allow water
• Use caution when attempting to light the propane pilot.
to run through the zone, pushing out the air. Run until no
• Flue gas vent system This should be done by a qualified service technician,
noticeable air flow is present. Close the zone isolation valves
particularly if pilot outages are common.
• Pilot and main burner flames and proceed with the next zone. Follow this procedure until
• Periodically check the odorant level of your gas. all zones are purged.
❏ Monthly • Check boiler piping • Inspect boiler and system at least yearly to make sure
• Water piping g. Close the quick-fill water valve and purge valve and remove
all gas piping is leak-tight.
the hose. Open all isolation valves. Watch that system
• Check venting system • Consult your propane supplier regarding installation
• Boiler heating surfaces pressure rises to correct cold-fill pressure.
of a gas leak detector. There are some products on the
market intended for this purpose. Your supplier may be h. After the system has operated for a while, eliminate any
• Burners, base and inlet air box • Check boiler relief valve
ANNNUAL START-UP

able to suggest an appropriate device. residual air by using the manual air vents located throughout
the system.
❏ Service: • Check automatic air vents (if used) i. If purge valves are not installed in system, open manual air
Determine if water treatment is needed vents in system one at a time, beginning with lowest floor.
• Oiled-bearing circulators • Check pilot and main burner flames Do not use petroleum-based cleaning or sealing Close vent when water squirts out. Repeat with remaining
compounds in boiler system. Severe damage to vents.
❏ Start-up: boiler will occur, resulting in substantial property 4. Open automatic air vent (diaphragm-type or bladder-type
damage. expansion tank systems only) one turn.
• Perform start-up per manual ❏ Periodically • Test low water cutoff (if used) Eliminate all system leaks. Continual fresh makeup
water will reduce boiler life. Minerals can build up 5. Open other vents:
in sections, reducing heat transfer, overheating a. Starting on the lowest floor, open air vents one at a time
❏ Check/test: until water squirts out.
cast iron, and causing section failure.
b. Repeat with remaining vents.
• Gas piping ❏ Every 6 months • Operate relief valve
Verify water chemistry 6. Refill to correct pressure.
• Cold fill and operating pressures Consult local water treatment companies for unusually hard
water areas (above 7 grains hardness) or low pH water conditions Inspect system water piping
• Air vents and air elimination ❏ End of season • Shut down procedure (below 7.0). Boiler water pH of 7.0 to 8.5 is recommended. After filling the boiler and system with water, inspect all piping
throughout the system for leaks. If found, repair immediately. Repeat
• Limit controls and cutoffs Freeze protection (when used) this inspection after the boiler has been started and the system
• Expansion tank Use antifreeze made especially for hydronic systems. Inhibited has heated up.
propylene glycol is recommended. Leaks must be repaired at once. Failure to do so can
• Boiler relief valve Do not use ethylene glycol, automotive or undiluted damage the boiler, resulting in substantial property
antifreeze. Severe personal injury or death can damage.
❏ Review: result. Do not use petroleum-based cleaning or sealing
1. Determine antifreeze quantity according to system water compounds in boiler system. Severe damage to boiler
• Review with owner content. Boiler water content is listed on page 35. Remember will occur, resulting in substantial property damage.
to include expansion tank water content. Inspect base insulation
2. Follow antifreeze manufacturer's instructions. Check to make sure insulation is secure against all four sides of
3. A 50% solution of propylene glycol/water provides maximum the base. If insulation is damaged or displaced, do not operate boiler.
protection to about -30 °F. Replace or reposition insulation.
4. Local codes may require back flow preventer or actual Failure to replace damaged insulation or reposition
disconnect from city water supply. insulation can result in a fire hazard, causing severe
5. When using antifreeze in a system with automatic fill, install personal injury, death or substantial property damage.
Follow the “Service and maintenance” procedures given throughout this manual and in component literature shipped with a water meter to monitor water makeup. Glycol will leak before The boiler contains ceramic fiber and fiberglass
the boiler. See “Read this first” on page 2. Failure to perform the service and maintenance could result in damage to the boiler the water begins to leak, causing glycol level to drop. Added materials. Use care when handling these materials
or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, water will dilute the antifreeze, reducing the freeze protection per instructions on page 23 of this manual. Failure to
death or substantial property damage. level. comply could result in severe personal injury.

22 Part Number 670 01 1001 00 Part Number 670 01 1001 00 15


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

5 Field wiring 10 Service and maintenance continued

For your safety, turn off electrical power supply at


service entrance panel before making any electrical
Thermostat Handling ceramic fiber and fiberglass materials
1. Connect thermostat as shown on wiring diagram on boiler.
connections to avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or 2. Install on inside wall away from influences of drafts, hot or cold
death. water pipes, lighting fixtures, television, sunrays or fireplaces.
Wiring must be N.E.C. Class 1. 3. If thermostat has a heat anticipator, set heat anticipator in REMOVAL OF COMBUSTION CHAMBER LINING OR BASE PANELS
If rollout thermal fuse element wire as supplied with thermostat to match power requirements of equipment
boiler must be replaced, type 200 °C wire or equivalent connected to it. If connected directly to boiler, set for 0.4 amps.
For other devices, see manufacturer’s specifications. Wiring The combustion chamber lining or base insulation panels in this product contain ceramic fiber materials. Ceramic
must be used. If other original wiring as supplied with fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research
boiler must be replaced, use only type 105 °C wire or diagram on boiler gives setting for control module and gas valve.
Also see instructions with thermostat. on Cancer (IARC) has concluded, "Crystalline silica inhaled in the form of quartz or cristobalite from occupational
equivalent. sources is carcinogenic to humans (Group 1).":
Boiler must be electrically grounded as required by
Junction box (furnished)
National Electrical Code ANSI/NFPA 70–latest edition. ■ Avoid breathing dust and contact with skin and eyes.
1. Connect 120 VAC power wiring (Figure 11).
Electrical installation must comply with: 2. Fused disconnect or service switch (15 amp. recommended) • Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for
may be mounted on this box. For those installations with local cristobalite at the time this document was written. Other types of respirators may be needed depending on
1. National Electrical Code and any other national, state, provincial the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://
or local codes or regulations. codes which prohibit installation of fused disconnect or service
switch on boiler, install a 2 x 4 cover plate on the boiler junction www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and box and mount the service switch remotely as required by the also listed on this web site.
any local codes. code. • Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Wiring connections ■ Apply enough water to the combustion chamber lining or base insulation to prevent airborne dust.
Wiring multiple zones
Boiler is shipped with controls completely wired, except spill switch See zone valve manufacturer’s literature for wiring and application. ■ Remove combustion chamber lining or base insulation from the boiler and place it in a plastic bag for disposal.
and vent damper. See wiring diagram on page 19 for standing pilot A separate transformer is required to power zone valves. Zoning ■ Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
ignition boiler or Control Supplement for spark-ignited pilot boiler. with circulators requires a relay for each circulator.
Circulator is shipped loose, but wiring harness is pre-attached to NIOSH stated First Aid.
the boiler. Connect wires in circulator junction box.
■ Eye: Irrigate immediately
■ Breathing: Fresh air.
Figure 11 Field wiring connections — service switch and thermostat (or end switch) provided by installer

REMOVAL OF FIBERGLASS WOOL — OR —

INSTALLATION OF FIBERGLASS WOOL, COMBUSTION CHAMBER LINING OR BASE


PANELS:

This product contains fiberglass jacket insulation and ceramic fiber materials in combustion chamber lining or base
panels in gas fired products. Airborne fibers from these materials have been listed by the State of California as a
possible cause of cancer through inhalation.

■ Avoid breathing dust and contact with skin and eyes.


• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for
fiberglass wool at the time this document was written. Other types of respirators may be needed depending
on the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://
www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are
also listed on this web site.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
■ Operations such as sawing, blowing, tear out, and spraying may generate airborne fiber concentration requiring
additional protection.
■ Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
■ Eye: Irrigate immediately
■ Breathing: Fresh air.

14 Part Number 670 01 1001 00 Part Number 670 01 1001 00 23


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

10 Service and maintenance continued 4 Install gas piping


The boiler should be inspected and started annually,
at the beginning of the heating season, only by a ❏ Inspect . . . . . . . . . . Connecting gas supply piping to boiler
qualified service technician. In addition, the
maintenance and care of the boiler designated in Water piping 1. Remove jacket front panel and see Figure 10 to pipe gas to Natural Gas:
Table 6, page 22 and explained on the following pages 1. Check the boiler interior piping and all system piping for signs boiler. 1. See Table 5 for pipe length and diameter. Base on rated
must be performed to assure maximum boiler of leaks. a. Install drip leg at inlet of gas connection to boiler. Where boiler input (divide by 1,000 to obtain cubic feet per hour).
efficiency and reliability. Failure to service and local utility requires drip leg to be extended to the floor, use Table 5 is only for gas with specific gravity 0.60, with a
2. Repair any leaks before proceeding. appropriate length of nipple between cap and tee.
maintain the boiler and system could result in pressure drop through the gas piping of 0.30" w.c. For
equipment failure. b. Install ground joint union for servicing, when required. additional gas pipe sizing information, see ANSI Z223.1
Electrical shock hazard — Turn off power to the boiler Do not use petroleum-based cleaning or sealing c. Install manual shutoff valve in gas supply piping outside (B149.1 or B149.2 for Canadian installations).
before any service operation on the boiler except as compounds in boiler system. Severe damage to boiler boiler jacket when required by local codes or utility
will occur, resulting in substantial property damage. 2. Inlet pressure required at gas valve inlet:
noted otherwise in this manual. Failure to turn off requirements. • Maximum: 13" w.c.
electrical power could result in electrical shock, Eliminate all system or boiler leaks. Continual fresh d. In Canada — When using manual main shutoff valve, it must
causing severe personal injury or death. • Minimum: 5" w.c.
makeup water will reduce boiler life. Minerals can be identified by the installer.
build up in sections, reducing heat transfer, • Manifold gas pressure: 3.5" w.c.
The boiler contains ceramic fiber and fiberglass 2. Support piping with hangers, not by boiler or its accessories.
overheating cast iron, and causing section failure. 3. Install 100% lockup gas pressure regulator in supply line if
materials. Use care when handling these materials Leaking water may also cause severe property 3. Purge all air from gas supply piping. inlet pressure exceeds 13" w.c. Adjust for 13" w.c. maximum.
per instructions on page 23 of this manual. Failure to damage. 4. Before placing boiler in operation, check boiler and its gas
comply could result in severe personal injury. connection for leaks. Propane Gas:
a. Close manual main shutoff valve during any pressure 1. Contact gas supplier to size pipes, tanks and 100% lockup
testing at less than 13" w.c. gas pressure regulator.
Boiler heating surfaces b. Disconnect boiler and gas valve from gas supply piping
2. Adjust propane supply regulator provided by gas supplier
1. Disconnect the vent pipe at the boiler draft hood and remove during any pressure testing greater than 13" w.c.
❏ Inspect . . . . . . . . . . draft hood after turning off power to the boiler. Do not check for gas leaks with an open flame —
for 13" w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
2. Use a bright light to inspect the boiler flue collector and heating Use bubble test. Failure to use bubble test or check
surfaces. • Maximum: 13" w.c.
for gas leaks can cause severe personal injury, death
Reported problems or substantial property damage. • Minimum: 11" w.c.
3. If the vent pipe or boiler interior surfaces show evidence of
Inspect any problems reported by owner and correct before soot, follow “Cleaning boiler heating surfaces” in this manual • Manifold gas pressure: 10" w.c.
5. Use pipe dope compatible with propane gases. Apply sparingly
proceeding. section, page 26. Remove the flue collector and clean the boiler only to male threads of pipe joints so that pipe dope does not
if necessary after closer inspection of boiler heating surfaces. block gas flow. Figure 10 Gas supply piping
Boiler area 4. If there is evidence of rusty scale deposits on boiler surfaces, Failure to apply pipe dope as described in this manual
1. Verify that boiler area is free of any combustible materials, check the water piping and control system to make sure the can result in severe personal injury, death or
gasoline and other flammable vapors and liquids. boiler return water temperature is properly maintained (per this substantial property damage.
2. Verify that boiler area (and air intake) is free of any of the manual).
contaminants listed in Table 2 on page 5 of this manual. If any of 5. Reconnect vent and draft hood. Replace all boiler components
these are present in the boiler intake air vicinity, they must be before returning to service.
removed. If they cannot be removed, install combustion air piping 6. Check inside and around boiler for evidence of any leaks from Table 5 Pipe capacity for 0.60 specific gravity natural gas
to the boiler in accordance with national, provincial or local the boiler. If found, locate source of leaks and repair.
codes. Gas pipe Capacity of pipe for pipe size of:
Burners and base length (Capacity in standard cubic feet gas per hour)
Air openings (feet) ½" ¾" 1" 1¼" 1½"
1. After turning off power to the boiler, remove the jacket door and
1. Verify that combustion and ventilation air openings to the boiler base access panel (Figure 17, item 4, page 30). 10 132 278 520 1050 1600
room and/or building are open and unobstructed. Check
operation and wiring of automatic combustion air dampers, if 2. Inspect burners and all other components in the boiler base. 20 92 190 350 730 1100
used. 3. If burners must be cleaned, raise rear of each burner to release 30 73 152 285 590 860
2. Verify that boiler vent discharge and air intake are clean and from support slot, slide forward and remove. Then brush and 40 63 130 245 500 760
free of obstructions. vacuum the burners thoroughly, making sure all ports are free
50 56 115 215 440 670
of debris. Carefully replace all burners, making sure burner with
pilot bracket is replaced in its original position and all burners 75 45 93 175 360 545
Flue gas vent system
are upright (ports up). 100 38 79 150 305 460
1. Visually inspect entire flue gas venting system for blockage, 4. Inspect the base insulation. 150 31 64 120 250 380
deterioration or leakage. Repair any joints that show signs of
leakage in accordance with vent manufacturer’s instructions. The boiler contains ceramic fiber and fiberglass
materials. Use care when handling these materials
2. Verify that masonry chimneys are lined, lining is in good per instructions on page 23 of this manual. Failure to
condition, and there are not openings into the chimney. comply could result in severe personal injury.
Failure to inspect for the above conditions and have a. Verify that the insulation is intact and secure against all four
them repaired can result in severe personal injury or sides of the base.
death. If insulation is damaged or displaced, do not operate
the boiler. Replace or reposition insulation as
Pilot and main burner flames necessary. Failure to replace damaged insulation can
1. Visually inspect pilot burner and main burner flames as directed result in a fire hazard, causing severe personal injury,
under Section 6, page 17 of this manual. death or substantial property damage.

24 Part Number 670 01 1001 00 Part Number 670 01 1001 00 13


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

3 Install water piping continued 10 Service and maintenance continued

Near-boiler piping continued ❏ Service. . . . . . . . . . ❏ Check/test. . . . . . . . . .


Figure 8 System bypass piping in boiler loop with Figure 9 Boiler bypass piping — use only for high Oiled-bearing circulators Air vents and air elimination
separate system circulator, using primary/ water content systems —DO NOT use for 1. The circulator shipped with the GWA boiler is water-lubricated. 1. Inspect automatic air vents (if used). Also inspect air separators
secondary piping. radiant panel systems. No oiling is required. to ensure they are operational.
2. Check other circulators in the system. Oil any circulators 2. The cap must be unscrewed one turn to allow air to escape.
requiring oil, following circulator manufacturer’s instructions. 3. If the air vent is leaking, remove cap and briefly push valve —
Over-oiling will damage the circulator. then release to clean the valve seat.
4. Replace cap by twisting all the way onto valve and then
unscrewing one turn.

Limit controls and cutoffs


❏ Start-up. . . . . . . . . . 1. Inspect and test the boiler limit control. Verify operation by turning
1. Perform start-up procedures Section 6, pages 15–17, including control set point below boiler temperature. Boiler should cycle
“Verify operation” of burners and vent damper on page 17. off. Return dial to original setting.
2. Verify cold fill pressure is correct and that fill system is working 2. Inspect and test additional limit controls or low water cutoffs
properly. installed on system.
3. Verify antifreeze level (if used) is at the right concentration and Expansion tank
that inhibitor level is correct.
1. Expansion tanks provide space for water to move in an out as
4. Check gas piping, per Manual Section 4, page 13 and Section
the heating system water expands due to temperature increase
6, page 15, verifying no indications of leakage and all piping
or contracts as the water cools. Tanks may be open, closed or
and connections are in good condition.
diaphragm or bladder type. See Section 3, page 10 of this
5. Read the “Lighting or Operating Instructions” (Manual Section 9, manual for suggested locations of expansion tanks and air
pages 20 and 21 or Control Supplement) applying to the boiler. eliminators.
6. Start the boiler following the “Lighting or Operating Instructions” Open-type — located above highest radiator or baseboard unit,
(Manual Section 9, pages 20 and 21 or Control Supplement). usually in the attic or closet. Has a gauge glass and overflow
pipe to a drain.
Closed-type — welded gas tight and located above boiler. Tank
is partially filled with water, leaving an air cushion for expansion.
• Make sure this type of tank is fitted with a tank fitting, such
❏ Check/test. . . . . . . . . . as the B & G Tank-Trol or Taco Taco-Trol. This fitting reduces
System bypass method Boiler bypass method gravity circulation of air-saturated tank water back to the
1. Apply bypass piping of Figure 8 to high water content systems, 1. Apply bypass piping of Figure 9 to high water content systems, Gas piping system and prevents the air from bubbling up through the
radiant panel systems or any system that is likely to operate such as converted gravity systems. 1. Sniff near floor and around boiler area for any indication of a water as it returns from the system.
with low return water temperature for extended periods. 2. The bypass arrangement shown protects the boiler from damage gas leak. • Do not use automatic air vents in systems with closed-type
2. The bypass arrangement shown protects the boiler from damage caused by condensate corrosion due to low return water 2. Test gas piping using bubble test, per Section 4, page 13 of this tanks. The air will escape from the system instead of
caused by condensate corrosion due to low return water temperature. This method does not provide protection from high manual, if there is any indication of a leak. returning to the tank. Eventually, the tank will waterlog and
temperature and protects low temperature systems from too temperature water being supplied to the system. no longer control pressurization. The boiler relief valve will
high a supply temperature. 3. DO NOT apply this piping to radiant panel systems. Cold fill and operating pressures weep frequently.
3. Adjust the bypass valves as indicated below. 4. Adjust the bypass valves as indicated below. 1. While the system is cold, note the pressure reading on the boiler
Adjust Bypass valves 1 and 2 as follows: pressure/temperature gauge. Verify that cold fill pressure is
Adjust Bypass valves 1 and 2 as follows: correct.
1. Start with valve 2 fully closed, valve 1 fully open. 1. Start with valve 1 fully closed, valve 2 fully open.
2. Watch the pressure as the boiler and system heat up to ensure
2. Slowly open valve 2 while closing valve 1. Adjust the valves 2. Slowly open valve 1 while closing valve 2. Adjust the valves pressure rise is normal. Too high a rise would indicate a
until the boiler pressure/temperature gauge reads 160 °F or until the boiler pressure/temperature gauge reads approximately waterlogged or undersized expansion tank.
higher. As you open the valves, pause long enough to allow 60 °F higher than the system temperature gauge. As you open
temperatures to level off. It takes a while for the boiler water the valves, pause long enough to allow temperatures to level
temperature to rise as the flow changes. off. It takes a while for the boiler water temperature to rise as
3. Bypass valve 2 allows hot boiler outlet water to blend with colder the flow changes.
return water, raising the supply temperature to the boiler. Bypass 3. Bypass valve 1 controls system flow rate. Bypass valve 2
valve 1 balances the pressure drop through valve 2. controls flow through the boiler.
4. The purpose of this piping is to raise the return water temperature 4. The purpose of this piping is to cause a high enough temperature
to the boiler enough to prevent condensation of flue gases. rise in the boiler that the average temperature will be warm
enough to prevent condensation of flue gases.

Install all components specified above and adjust valves as described to prevent low temperature in the boiler. Failure to
prevent low water temperature in the boiler could cause corrosion of the boiler sections or burners, resulting in severe
personal injury, death or substantial property damage.

12 Part Number 670 01 1001 00 Part Number 670 01 1001 00 25


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

10 Service and maintenance continued 3 Install water piping continued

2. After following the preceding warning directions, if the relief valve


❏ Check/test. . . . . . . . . . continued weeps or will not seat properly, replace the relief valve. Ensure Near-boiler piping continued
that the reason for relief valve weeping is the valve and not Use Figure 5 or Figure 6 only for systems designed
Diaphragm- or bladder-type — welded gas tight with a rubber over-pressurization of the system due to expansion tank Figure 5 Diaphragm- or bladder-type expansion tank:
membrane to separate the tank pressurizing air and the water. for return water at least 130 °F. For systems with low
waterlogging or undersizing. Piping to single-zone system using return water temperature possible, such as
May be located at any point in the system, but most often found diaphragm-type or bladder-type expansion
near the boiler. converted gravity systems and radiant heating
tank. See Table 4 for piping sizes. systems, install bypass piping (see page 12) to
• Systems with this type of expansion tank require at least
protect boiler against condensation. Failure to prevent
one automatic air vent, preferably located on top of an air
low return water temperature to the boiler could cause
eliminator, as shown in examples in Manual Section 3,
page 10.
❏ Review with owner corrosion of the boiler sections or burners, resulting
in severe personal injury, death or substantial
2. If relief valve has tended to weep frequently, the expansion tank 1. Review the User’s Information Manual with the owner.
property damage.
may be waterlogged or undersized. 2. Emphasize the need to perform the maintenance schedule
Closed-type tank — tank is most likely waterlogged. Install a specified in the User’s Information Manual (and in this manual If system includes radiant heating circuits, provide
tank fitting if not already installed. Then check fill level per fitting as well). piping and controls to regulate the temperature
manufacturer’s instructions. If fill level is correct, check tank 3. Remind the owner of the need to call in a licensed contractor supplying the radiant circuits. Failure to comply could
size against manufacturer’s instructions. Replace with a larger should the boiler or system exhibit any unusual behavior. result in substantial property damage.
tank if necessary. 4. Remind the owner to follow the proper shutdown procedure
Diaphragm- or bladder-type — first, check tank size to be and to schedule an annual start-up at the beginning of the next Install boiler so that chilled medium is piped in parallel
sure it is large enough for the system. If size is too small, add heating season. with heating boiler (Figure 7). Use appropriate valves
additional tank(s) as necessary to provide sufficient expansion. to prevent chilled medium from entering boiler. Consult
If tank size is large enough, remove tank from system and I=B=R Installation and Piping Guides.
check charge pressure (usually 12 psig for residential If boiler is connected to heating coils located in air
applications). If tank won’t hold pressure, membrane has been handling units where they can be exposed to
damaged. Replace tank.
❏ Cleaning boiler heating surfaces refrigerated air, use flow control valves or other
automatic means to prevent gravity circulation during
Boiler relief valve cooling cycle. Circulation of cold water through the
The boiler contains ceramic fiber and fiberglass
1. Inspect the relief valve and lift the lever to verify flow as in the boiler could result in damage to the heat exchanger,
materials. Use care when handling these materials
following warnings, excerpted from a relief valve manufacturer’s causing possible severe personal injury, death or
per instructions on page 23 of this manual. Failure to
warning label. Before operating any relief valve, ensure that it is substantial property damage.
comply could result in severe personal injury.
piped with its discharge in a safe area to avoid severe scald 1. Shut down boiler:
potential. Read Manual Section 3, page 10, before proceeding
• Follow “To Turn Off Gas to Appliance” instructions on boiler
Water piping — refrigeration systems
further.
and “Lighting or Operating Instructions”. Prevent chilled water from entering boiler
Safety relief valves should be reinspected AT LEAST • Do not drain boiler unless it will be exposed to freezing
ONCE EVERY THREE YEARS, by a licensed plumb- Figure 6 Closed-type expansion tank: Piping to Install boiler so that chilled medium is piped in parallel with the
temperatures. If using antifreeze in system, do not drain.
ing contractor or authorized inspection agency, to single-zone system using closed-type heating boiler. Use appropriate valves to prevent chilled medium
2. Follow shutdown procedure. expansion tank. See Table 4 for piping sizes. from entering boiler. See Figure 7 for typical installation of balancing
ensure that the product has not been affected by
3. Remove venting system connection to boiler. valve and check valve.
corrosive water conditions and to ensure that the
valve and discharge line have not been altered or 4. Remove top jacket panel. Turn back insulation.
tampered with illegally. Certain naturally occurring 5. Remove flue collector. Clean sealant from assembly and Figure 7 Piping refrigeration systems
conditions may corrode the valve or its components sections.
over time, rendering the valve inoperative. Such con- 6. Remove radiation plates hanging between sections.
ditions are not detectable unless the valve and its 7. Remove burners from base. Brush and vacuum burners to
components are physically removed and inspected. remove all dust and lint. Verify that all burner ports are free of
This inspection must only be conducted by a plumb- debris.
ing contractor or authorized inspection agency — not 8. Place newspapers in base of boiler to collect soot.
by the owner. Failure to reinspect the boiler relief valve 9. Clean between sections with wire flue brush.
as directed could result in unsafe pressure buildup, 10. Remove newspaper and soot. Vacuum or brush base and
which can result in severe personal injury, death or surrounding area.
substantial property damage.
11. Reinstall radiation plates.
Following installation, the valve lever must be oper-
ated AT LEAST ONCE A YEAR to ensure that wa- 12. Replace collector box/transition assembly. Seal with sealant.
terways are clear. Certain naturally occurring min- Obtain gas-tight seal to prevent flue gas spillage and carbon
eral deposits may adhere to the valve, rendering it monoxide emissions, resulting in severe personal injury or death.
inoperative. When manually operating the lever, wa- 13. Replace insulation and jacket top panel.
ter will discharge and precautions must be taken to 14. Start up boiler following section 6, pages 15–17 of this manual
avoid contact with hot water and to avoid water dam- and the boiler “Lighting Instructions”, pages 20 and 21.
age. Before operating lever, check to see that a dis- Excessive sooting indicates improper gas combustion. If found,
charge line is connected to this valve directing the check for proper combustion and make any necessary
flow of hot water from the valve to a proper place of adjustments.
disposal otherwise severe personal injury may re-
sult. If no water flows, valve is inoperative. Shut down
boiler until a new relief valve has been installed.

26 Part Number 670 01 1001 00 Part Number 670 01 1001 00 11


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

3 Install water piping 11 Troubleshooting


Label all wires prior to disconnection when servicing In event of vent damper failure:
General Near-boiler piping continued controls. Wiring errors can cause improper and
dangerous operation. Effikal vent damper
If installation is to comply with ASME or Canadian requirements, Table 4 Water pipe size (based on 20 °F rise) Never jumper (bypass) rollout thermal fuse element If troubleshooting chart recommends replacing actuator and actuator
an additional high temperature limit is needed. Install control in supply or any other device except for momentary testing as
Boiler model To From is not immediately available, damper blade can be fixed in an open
piping between boiler and isolation valve. Set second control to outlined in “Chart 1”, page 28. Severe personal injury, position to allow boiler operation. Manually turning blade can cause
minimum 20 °F above setpoint of first control. Maximum allowable number system system
death or substantial property damage can result. actuator damage. Follow these instructions only in case of no heat
setpoint is 240 °F. See page 19 for wiring.
GWA052 ¾" ¾" Burner access panel must be in position during boiler or damper actuator malfunction.
A low water cutoff device is required when boiler is installed above operation to prevent momentary flame rollout on
GWA070 1" 1" 1. Move damper service switch to Hold Damper Open position.
radiation level or by certain state or local codes or insurance ignition of main flame. Severe personal injury or Apply call for heat to boiler. Damper blade should then rotate to
companies. Use low water cutoff designed for water installations. GWA105 1" 1" substantial property damage will result. Open position and boiler will fire.
Electrode probe-type is recommended. Purchase and install in tee
supply piping above boiler. GWA140 1" 1" 2. If step 1 does not open damper, manually rotate damper blade
GWA175 1¼" 1¼" to open position using wrench or pliers on flat shaft between
Use backflow check valve in cold water supply if required by local
damper and actuator. Boiler will fire. Verify that damper service
codes. GWA210 1¼" 1¼" Before troubleshooting: switch is in Hold Damper Open position. (Figure 15)
GWA245 1½" 1½" 1. Have the following items: 3. Do not leave vent damper permanently in this position. Replace
a. Voltmeter that can check 120 VAC and 24 VAC. actuator immediately. If vent damper is left in Open position,
b. Microammeter with a scale range of 0-10. boiler will not operate at published efficiencies.
Circulator c. Continuity checker. Johnson Controls vent damper
Near-boiler piping d. U-tube manometer.
If troubleshooting chart recommends replacing actuator and actuator
The circulator is shipped loose (wiring pre-attached to boiler) to
See Table 4 and Figure 5 (diaphragm-type or bladder-type expansion allow you to locate it either in the return or supply piping, as desired. 2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) is not immediately available, damper blade can be fixed in an open
tank) or Figure 6 (closed-type expansion tank) on page 11 for near- See page 11 for a typical installation. Pipe the expansion tank to to boiler. position to allow boiler operation. Follow these instructions only in
boiler piping for systems designed for return water at least 130 °F. the suction side of the circulator whenever possible. Install an air 3. Make sure thermostat is calling for heat and contacts (including case of no heat or damper actuator malfunction. See Figure 15.
See page 12 (Figures 8 and 9) for near-boiler piping for low- separator in the supply piping. Connect the expansion tank to the appropriate zone controls) are closed. Check for 24 VAC 1. Turn off power to boiler.
temperature or high-volume systems. air separator only if the separator is on the suction side of the between thermostat wire nuts and ground. Failure to turn off power to boiler can result in severe
circulator. Always install the system fill connection at the same point personal injury, death or substantial property damage.
See page 11 (Figure 7) for boilers used with refrigeration systems. as the expansion tank connection to the system. Figures 5 and 6
show typical near-boiler piping connections. Troubleshooting sequence: 2. See vent damper manufacturer’s instructions for procedure to
Relief valve 1. Before proceeding, check for: fix vent damper in open position.
Expansion tank
Install relief valve vertically in ¾" tapping on side of boiler. See the • Loose connections, blown fuse or service switch off? 3. Turn on power to boiler.
tag attached to the relief valve for manufacturer’s instructions. Diaphragm-type or bladder-type expansion tank — • High limit switch set below boiler water temperature? 4. Using wrench or pliers on flat shaft section, manually rotate
To avoid water damage or scalding due to valve Figure 5 • Thermostat set below room temperature? damper blade until green light turns on. Boiler will fire. (Figure 15)
operation, discharge line must be connected to relief 1. Ensure expansion tank size will handle boiler and system water • Gas not turned on at meter or boiler? 5. Do not leave vent damper permanently in this position. Replace
valve outlet and run to a safe place of disposal. volume and temperature. Tank must be located in boiler return • Incoming gas pressure less than: actuator immediately. If vent damper is left in Open position,
Terminate the discharge line to eliminate possibility piping as close to boiler as possible, before inlet side of circulator. boiler will not operate at published efficiencies.
of severe burns should the valve discharge. 5" w.c. for natural gas? 11" w.c. for propane gas?
See tank manufacturer’s instructions for details.
• Discharge line must be as short as possible and be 2. If all of the above check correctly, check gas pressures:
2. Install an automatic air vent as shown.
the same size as the valve discharge connection a. With boiler off
throughout its entire length. Closed-type expansion tank — Figure 6 • 13" w.c. maximum natural or propane gas pressure
• Discharge line must pitch downward from the valve 1. Ensure expansion tank size will handle boiler and system water upstream of gas valve.
and terminate at least 6" above the floor drain where volume and temperature. See tank manufacturer’s instructions b. With boiler on: Figure 15 Manually opening vent damper
any discharge will be clearly visible. for details. • 5" w.c. minimum natural gas pressure or 11" w.c.
• The discharge line shall terminate plain, not threaded, 2. Connect tank to ½" NPT tapping located behind supply outlet, propane gas pressure upstream of gas valve.
with a material serviceable for temperatures of 375 °F using ½" NPT piping. Pitch any horizontal piping up towards • 3.5" w.c. minimum natural gas pressure or 10" w.c.
or greater. tank 1 inch per 5 feet of piping. propane gas pressure downstream tapping on gas
• Do not pipe the discharge to any place where freezing valve — Can be adjusted by regulator on gas valve.
could occur. Undersized expansion tanks cause system water to
be lost from relief valve and makeup water to be c. If gas pressure is incorrect or gas is not available to boiler,
• No shutoff valve shall be installed between the relief contact gas supplier to correct before proceeding further.
added through fill valve. Eventual section failure can
valve and boiler, or in the discharge line. Do not plug
result. 3. Check pilot operation - Follow “Lighting Instructions”, pages 20
or place any obstruction in the discharge line.
and 21.
• Failure to comply with the above guidelines could
result in failure of the relief valve to operate, resulting • If gas is available and you cannot obtain a pilot flame, try
in possibility of severe personal injury, death or purging the gas line and cleaning pilot and pilot gas tubing.
substantial property damage. Water piping — multiple zone systems Follow “Lighting Instructions” again. If you still cannot obtain
• Test the operation of the valve after filling and Install system piping using either circulator zoning or zone valve a flame, replace pilot burner and gas tubing. If this does not
pressurizing system by lifting the lever. Make sure zoning. Install expansion tank on suction side of system circulator. allow you to obtain a pilot flame, replace gas valve.
the valve discharges freely. If the valve fails to operate Always connect fill line only at the expansion tank — never at • If you obtain a pilot flame, but pilot will not remain on, replace Verify proper operation after servicing. • See vent
correctly, replace it with a new relief valve. another point in the system. thermocouple. If this does not correct problem, replace gas damper manufacturer’s instructions packed with vent
valve and pilot burner. damper for additional information. Failure to comply
• If pilot stays on, but main gas will not come on, proceed to could result in severe personal injury, death or
page 28. substantial property damage.

10 Part Number 670 01 1001 00 Part Number 670 01 1001 00 27


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

11 Troubleshooting continued 2 Prepare boiler continued

Chart 1 — Standing pilot — Boiler will not fire Vent damper continued
Damper installation
Before proceeding, follow "Troubleshooting sequence" on page 27. If problem persists, then:
Do not modify draft hood or vent damper, or make
another connection between draft hood and vent
Is damper harness securely plugged in at both ends? damper or boiler except as noted below. This will void
CSA certification and will not be covered by
Secure connections. No Yes Williamson-Thermoflo warranty. Any changes will
cause severe personal injury, death or substantial
Check for loose wire connections or bad relay on Is 24VAC present across transformer terminals C & Y? property damage.
transformer. 1. Install vent damper horizontally or vertically as shown in vent
No Yes damper manufacturer’s instructions. Vent damper must be
installed so that it serves only one boiler and so damper blade
Check for open thermostat, LWCO, high limit, spill switch or indicator is visible to the user. See Figure 4.
rollout thermal fuse element contacts or check for loose Is 24VAC present across transformer terminal C and yellow
wire connections. wire on vent damper connector? 2. Screws or rivets used to secure the vent damper to the draft
hood must not interfere with rotation of the damper blade.
If LWCO, spill switch or rollout thermal fuse No Yes 3. Install damper harness between damper actuator and hole in
element contacts are open, determine cause
and correct condition. Failure to do so will jacket left side panel. See Figure 3, page 8.
cause severe personal injury, death or Is vent damper rotated open? Use strain relief connectors and locknuts to secure both ends
substantial property damage. of damper harness.
No Yes Keep wiring harness clear of all hot surfaces. Wire
Check/repair out of round stack section. Figure 4 Vent damper assemblies insulation could be damaged, causing risk of electrical
Is 24VAC present across gas valve terminals? short-circuit.
Does vent damper rotate open?
No Yes No Yes 4. Read and apply the harness plug warning label (shown upper-
left) so that it is visible after installation
5. Plug damper harness receptacle into damper harness plug.
• Replace actuator.
• Retest. Is main flame on now? Bypassing (jumpering) vent damper will cause flue
products such as carbon monoxide to escape into
No Yes the house. This will cause severe personal injury or
Open thermostat contacts for 30 seconds. Vent damper will death.
rotate to closed position. Close thermostat contacts. Vent After boiler has operated once, if either end of harness
Retest. is disconnected, the system safety shutdown will
damper will rotate to open position.
Is 24VAC present across gas valve terminals? occur. The boiler will not operate until harness is
Is gas valve cock turned to ON position? reconnected.
No Yes Effikal damper — Damper hold open switch must be
No Yes
in Automatic Operation position for system to operate
properly.

Check continuity of each wire in damper harness. Does


continuity exist for each wire? See Table right.
• Turn gas valve cock to • Replace gas valve.
No Yes ON position. • Retest.
• Retest.
Remove damper harness from
• Replace damper damper harness plug.
wiring harness. TEMPORARILY install jumper
• Retest. between terminal 2 and
terminal 5 on damper plug in
boiler wiring harness. See
Table, right. Does boiler fire?
No Yes

• Replace gas valve. • Replace damper actuator.


• Retest. • Retest.

28 Part Number 670 01 1001 00 Part Number 670 01 1001 00 9


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

2 Prepare boiler continued 12 Replacement parts

Draft hood & spill switch Install vent piping Figure 16 Section assembly, flue collector, draft hood and vent damper

Draft hood installation 1. Connect from draft hood or vent damper outlet to chimney or
vent with same size vent connector.
1. Orient draft hood with spill switch mounting holes to front of
boiler as shown in Figure 3. 2. Where possible, vertical venting to the outside from the draft
hood or vent damper outlet will offer best performance.
2. Secure draft hood to outlet at top of boiler with sheet metal
screws. 3. Where horizontal vent connector is used, slope upward at least
¼" per lineal foot toward chimney or vent and support with
3. Bottom of draft hood or skirt must have clearance dimension hangers to prevent sagging.
above jacket top panel as indicated on draft hood. 4. Breeching must not be connected to any portion of a mechanical
Do not alter boiler draft hood or place any draft system that can operate under positive pressure.
obstruction or non-approved vent damper in Long horizontal vent connector, excessive number
breeching or vent system. CSA certification will of elbow or tees, or other obstructions that restrict
become void. Flue gas spillage and carbon the flow of combustion gases should be avoided.
monoxide emissions will occur causing severe Severe personal injury, death or substantial property
personal injury or death. damage could result.
Improper orientation of spill switch may cause
boiler to shut down. The loss of heat can result in
significant damage due to freezing.

Spill switch installation


Vent damper
1. Fasten spill switch to draft hood as shown in Figure 3.
2. See Wiring diagram to connect wires:
These systems are used on gas-fired boilers with
a. Standing pilot boiler — see page 19.
vent dampers as shipped from factory. Boiler will not
b. Spark-ignited pilot boiler — see Control Supplement. operate without vent damper installed.
Only vent dampers listed in the Replacement parts
list on page 29 are certified for use with GWA boilers.
Figure 3 Spill switch with wire harness Any other vent damper installed could cause severe
personal injury or death.

Damper blade
Standing pilot ignition systems— See vent manufacturer’s
instructions to install plug (shipped with damper) in damper hole. Item Description International
Item Description International
For standing pilot boilers only, install plug with 3/8" diameter hole in
number Comfort number Comfort
vent damper hole. Products
Products
Spark-ignited pilot systems— See vent manufacturer’s part number part number
instructions to install plug (shipped with damper) in damper hole.
not shown Replacement GWA052 321114501WT 4 High limit, 30° differential, Honeywell L4080D1036 510312250WT
For spark-ignited pilot boilers only, install plug with no hole in vent
section GWA070 321114501WT with well White-Rodgers 11B81-3
damper hole.
assembly GWA105 321114502WT 5 Spill switch 510350105WT
GWA140 321114503WT
Minimum clearances GWA175 321114504WT
6 Vent 4" GWA052 Effikal RVGP-KS-4BKF 510512350WT
damper GWA070 *Johnson Controls Q35GB-2
Provide a minimum of 6" between the vent damper and any GWA210 321114505WT
combustible material. (See “Minimum clearance to combustible GWA245 321114506WT 5" GWA105 Effikal RVGP-KS-5BKF 510512351WT
materials,” page 3, for minimum clearance from jacket top to ceiling *Johnson Controls Q35GD-2
1 Radiation plate 460003700WT
to maintain this dimension.) (1 per joint) 6" GWA140 Effikal RVGP-KS-6BKF 510512352WT
GWA175 *Johnson Controls Q35GF-2
2 Collector GWA052 381354625WT
hood GWA070 381354626WT 7" GWA210 Effikal RVGP-KS-7BKF 510512353WT
GWA105 381354627WT GWA245 *Johnson Controls Q35GH-2
GWA140 381354628WT * Johnson Controls damper assemblies consist of M35BC
GWA175 381354629WT actuator and Y15 vent pipe
GWA210 381354630WT
7 Vent damper actuator Effikal RVGP only with vent
GWA245 381354631WT
Johnson M35BE-1C damper above
3 Draft hood GWA052 450021270WT
8 Vent damper harness 591391795WT
GWA070 450021271WT
GWA105 450021272WT
GWA140 450021273WT
GWA175 450021274WT
GWA210 450021275WT
GWA245 450021276WT

8 Part Number 670 01 1001 00 Part Number 670 01 1001 00 29


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

12 Replacement parts continued 2 Prepare boiler continued

Figure 17 Base assembly, manifold, orifices and burners Pressure test


It em D esc ript ion Int ernat ional Perform hydrostatic pressure test Fill and pressure test
number C omfort Pressure test boiler before attaching water or gas piping or electrical 1. Open the shutoff valves you installed on supply and return
Produc t s
supply (except as noted below). connections.
part number
2. Slowly open boiler drain valve and fresh water supply to fill
Base assembly kit GWA052 & GWA070 381354200WT Prepare boiler for test boiler with water.
GWA105 381354201WT 1. Remove the shipping nipple (from GWA supply tapping) and
GWA140 381354202WT 3. When water flows from shutoff valves, close boiler drain valve.
GWA175 381354203WT remove the boiler relief valve. Temporarily plug the relief valve 4. Close shutoff valves.
GWA210 381354204WT tapping with a ¾" NPT pipe plug.
GWA245 381354205WT 5. Slowly reopen boiler drain valve until test pressure of not more
2. Remove 1¼" nipple, reducing tee and drain valve from than 45 psi is reached on the pressure/temperature gauge.
1 Base side panel (in Base assembly) accessory bag. Install in boiler return connection as shown on
in Figure 19, item 3, page 32. Install circulator on either the 6. Test at no more than 45 psi for no more than 10 minutes.
2 Base front cross-tie assembly (in Base assembly) return or supply.
3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/temperature Do not leave boiler unattended. A cold water fill could
3 Base back cross-tie assembly (in Base assembly) gauge from accessory bag. Pipe to boiler supply connection as expand and cause excessive pressure, resulting in
shown in Figure 19, item 2, page 32. (Use pipe dope sparingly.) severe personal injury, death or substantial property
4 Base access panel (in Base assembly) damage.
4. Connect a hose to boiler drain valve, the other end connected
5 Base pan angle, left side (in Base assembly) to a fresh water supply. Make sure hose can also be used to 7. Make sure constant gauge pressure has been maintained
drain boiler after test. throughout test. Check for leaks. Repair if found.
6 Base pan angle, right side (in Base assembly)
5. Connect a nipple and shutoff valve to system supply connection
7 Base pan (in Base assembly) on the 1¼" tee. This valve will be used to bleed air during the fill. Leaks must be repaired at once. Failure to do so can
(Valve and nipple are not included with boiler.) damage boiler, resulting in substantial property
8 Burner rest (in Base assembly) 6. Connect a nipple and shutoff valve to system return connection damage.
(at circulator flange if circulator installed on return). This valve
9 Base insulation kit GWA052 to GWA140 381354210WT
(includes insulation for GWA175 to GWA245 381354211WT will be used to bleed air during the fill. (Valve and nipple are not Do not use petroleum-based cleaning or sealing
all base parts above included with boiler.) compounds in boiler system. Severe damage to boiler
plus gasket material 7. Temporarily plug the air elimination tapping (next to supply will occur, resulting in substantial property damage.
needed between block
assembly and base) tapping).
Drain and remove fittings
10 Boiler leg kit 590424252WT 1. Disconnect fill water hose from water source.
11 Manifold GWA052 591126615WT
2. Drain boiler at drain valve or out hose, whichever provides best
GWA070 591126616WT access to drain. Remove hose after draining if used to drain
GWA105 591126617WT boiler.
GWA140 591126618WT
GWA175 591126619WT 3. Remove nipples, valves and plus unless they will remain for
GWA210 591126556WT use in the system piping.
GWA245 591126557WT 4. Remove plug from relief valve tapping. See Section 3, page 10,
12 Main burner orifice, sea level 560528997WT
to replace relief valve.

13 Burner, stainless steel 512200077WT

14 Burner with pilot Standing pilot 512200079WT


bracket
(not shown) Spark-ignited pilot 512200078WT

15 Screw, 10-32 x 3/ 8 STP type D hx, washer head available at


slot ZP local supply
house

16 Rollout thermal fuse element 512050230WT

30 Part Number 670 01 1001 00 Part Number 670 01 1001 00 7


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

1 Prepare boiler location continued 12 Replacement parts continued

Air openings continued Figure 18 Jacket assembly

Exhaust fans and air movers Motorized air dampers


The appliance space must never be under a negative pressure. If the air openings are fitted with motorized dampers, electrically
Always provide air openings sized not only to the dimensions interlock the damper to:
required for the firing rate of all appliances, but also to handle the air • Prevent the boiler from firing if the damper is not fully open.
movement rate of the exhaust fans or air movers using air from the
building or space. • Shut the boiler down should the damper close during boiler
operation.
To accomplish this interlock, wire an isolated contact (proving the
damper open) in series with the thermostat input to the boiler. The
boiler will not start if this contact is open, and will shut down should
it open during operation.

2 Prepare boiler
3. Level and straighten burners.
Placement and setup Burners must be properly seated in slots in burner
rest with their openings face up. Main burner orifices
Place boiler/crate near position must inject down center of burner. Failure to properly
1. Leave boiler in crate and on pallet until installation site is seat burners will result in severe personal injury,
ready. death or substantial property damage.
2. Move entire crate and pallet next to selected location. 4. Reinstall access panel.
Do not operate boiler without access panel secured
3. Remove crate. Leave boiler on pallet.
in place. Failure to comply could cause momentary
4. Remove boiler from pallet as follows: flame rollout on ignition of main flame, resulting in Item Description International Item Description International
a. Tilt left side of boiler up and place a board under left legs. possible fire or personal injury hazard. number Comfort number Comfort
b. Tilt boiler the other way and place a board under right legs. Products Products
c. Slide boiler backwards off pallet and into position. part number part number
Do not drop boiler or bump jacket on floor or pallet. 1 Junction box, 4 x 4 5 Jacket GWA052 & GWA070 431223433WT
Damage to boiler can result. Table 3 Manifold orifice sizing (Available at local supply house) panel, top GWA105 431223434WT
GWA140 431223435WT
5. Check level. GWA175 431223436WT
Location Natural gas Propane gas 1a Junction box, 2 x 4
a. Shim legs, if necessary. (Available at local supply house) GWA210 431223437WT
b. Do not alter legs. Sea level – over Sea level – over GWA245 431223438WT
U. S. 2,000 ft 2,000 ft 2,000 ft 2,000 ft 6 Jacket GWA052 & GWA070 431223507WT
2 Jacket panel, left side, with 431223425WT cross tie GWA105 431223508WT
2.00 mm (Note 1) 1.30 mm (Note 1) GWA140 431223509WT
insulation
Inspect orifices and burners Sea level – 2,000 – Sea level – 2,000 –
GWA175 431223510WT
3 Jacket panel, right side, with 431223426WT GWA210 431223511WT
1. Remove front jacket door. Remove base access panel (See Canada 2,000 ft 4,500 2,000 ft 4,500 GWA245 431223512WT
insulation
Figure 17, item 4, page 30). 2.00 mm # 49 1.30 mm # 56 7 Jacket GWA052 & GWA070 431223427WT
2. Check for correctly-sized manifold orifices. See Table 3 for sizing. 4 Jacket GWA052 & GWA070 431223450WT panel, GWA105 431223428WT
Note 1: For U. S. elevations above 2,000 feet, contact your International Com- panel, GWA105 431223451WT interior, GWA140 431223429WT
(The orifice size is stamped on the orifice spud barrel.) fort Products supplier for details.
door GWA140 431223452WT with GWA175 431223430WT
Correctly-sized manifold orifices must be used. Failure GWA175 431223453WT insulation GWA210 431223431WT
to do so will result in severe personal injury, death or GWA210 431223454WT GWA245 431223432WT
substantial property damage. GWA245 431223455WT 8 Jacket GWA052 & GWA070 431223444WT
panel, GWA105 431223445WT
rear, with GWA140 431223446WT
insulation GWA175 431223447WT
GWA210 431223448WT
GWA245 431223449WT

The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per
instructions on page 23 of this manual. Failure to comply could result in severe personal injury.

6 Part Number 670 01 1001 00 Part Number 670 01 1001 00 31


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

12 Replacement parts continued 1 Prepare boiler location continued

Figure 19 Trim assembly Air contamination Air openings


Please review the following information on potential combustion air Combustion air and ventilation openings must comply with Section
contamination problems. 5.3, “Air for Combustion and Ventilation”, of National Fuel Gas Code
See Table 2 for products and areas which may cause contaminated ANSI Z223.1–latest edition, or applicable local building codes.
combustion air. Canadian installations must comply with B149.1 or B149.2
Installation Codes.
To prevent potential of severe personal injury or death, See table below for minimum combustion/ventilation air opening
check for products or areas listed below before sizes. Where openings are required, provide two (2) openings —
installing boiler. If any of these contaminants are found: one within 12 inches of the ceiling, the other within 12 inches of the
• Remove contaminants permanently. floor, as shown in the table illustrations.
— OR — Provide adequate combustion and ventilation air to
• Isolate boiler and provide outside combustion air. See assure proper combustion and reduce the risk of
national, provincial or local codes for further severe personal injury, death or substantial property
information. damage caused by flue gas spillage and carbon
monoxide emissions.

Table 2 Corrosive contaminants and likely locations

Products to avoid
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Item Description Manufacturer Manufacturer’s International
Comfort Hydrochloric acid/muriatic acid
number part number
Products
part number Cements and glues
1 Pressure relief valve, ASME, 30 PSIG, ¾" male inlet Conbraco 10-407-10 Antistatic fabric softeners used in clothes dryers
511546920WT
Watts M330
Pressure relief valve, ASME, 30 PSIG, ¾" female inlet Chlorine-type bleaches, detergents, and cleaning solvents found in
Conbraco 10-408-05
(Fittings shown are factory-installed on boiler.) 511546924WT household laundry rooms
Watts 335
2 Combination pressure-temperature gauge, with 2½" short Ametek PTA-1088 Adhesives used to fasten building products and other similar products
510218099WT
shank ENFM 4104
3 Drain valve, ¾" Conbraco 31-606-01
Areas likely to have contaminants
(Fittings shown are included with boiler.) Hammond Valve 710
511210423WT Dry cleaning/laundry areas and establishments
Matco-Norca 205F04
Watts BD-2C Swimming pools
4 Circulator (Fittings shown are shipped loose with boiler.) Taco 007 511405113WT
Metal fabrication plants
5 Circulator gasket, universal (2 per boiler) International Comfort Products 590317535WT
Beauty shops
not Circulator hardware kit, includes: International Comfort Products
shown 2 flanges, 4 nuts, 4 screws, 2 pipe nipples — Refrigeration repair shops
1" NPT — GWA052 through GWA140 381354525WT
1¼" NPT — GWA175 through GW245 381354526WT Photo processing plants
6 Circulator wiring harness International Comfort Products 591319793WT Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops

32 Part Number 670 01 1001 00 Part Number 670 01 1001 00 5


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

1 Prepare boiler location continued 12 Replacement parts continued

Vent system Figure 20 Gas control assembly

Failure to follow all instructions can result in flue gas Equipment”, of National Fuel Gas Code, ANSI Z223.1–latest
spillage and carbon monoxide emissions, causing edition and applicable building codes. Canadian installations
severe personal injury or death. must comply with B149.1 or B149.2 Installation Codes.
Inspect existing chimney before installing boiler. 2. See “Ratings” on page 35 for minimum chimney or vent sizes.
Failure to clean or replace perforated pipe or tile lining Chimney or vent termination:
will cause severe personal injury or death. • A chimney, or any vent other than a Type B vent with listed
vent cap, must extend at least 3 feet above the highest point
Do not alter boiler draft hood or place any obstruction where it passes through a roof of a building, and at least
or non-certified vent damper in breeching or vent 2 feet higher than any portion of a building within a horizontal
system. CSA certification will become void. Flue gas distance of 10 feet.
spillage and carbon monoxide emissions will occur
• Type B vents with listed caps may terminate as in Figure 2
causing severe personal injury or death.
if no closer than 8 feet from a vertical wall or similar
The following requirements apply when you remove obstruction.
an existing boiler from a vent system shared with • Otherwise, Type B vents must terminate at least 2 feet above
other appliances. If the new boiler will not use the the roof penetration and at least 2 feet higher than any portion
common vent, you must test (as described below) of a building within 10 feet.
each remaining appliance — operating by itself — to 3. A lined chimney is preferred and must be used when required
verify that the vent system operates adequately. by local, state, provincial and national codes, laws, regulations
and ordinances. Vitreous tile linings with joints that prevent
When removing boiler from existing common vent retention of moisture and linings made of noncorrosive materials
system: are best. Advice for flue connections and chimney linings can
be obtained from local gas utility. Type B double-wall metal vent
At the time of removal of an existing boiler, the following steps shall pipe or single-wall vent pipe may be used as a liner.
be followed with each appliance remaining connected to the common
venting system placed in operation, while the other appliances 4. Cold masonry chimneys, also known as outside chimneys,
remaining connected to the common venting system are not in typically have one or more walls exposed to outside air.
operation. When any atmospheric gas-fired boiler with automatic vent
damper is vented through this type of chimney, the potential
a. Seal any unused openings in the common venting system. exists for condensation to occur. Condensation can damage a
b. Visually inspect the venting system for proper size and horizontal masonry chimney. Williamson-Thermoflo recommends the
pitch and determine there is no blockage or restriction, leakage, following to prevent possible damage.
corrosion or other deficiencies which could cause an unsafe a. Line chimney with corrosion-resistant metal liner such as
condition. AL29-4C® single-wall stainless steel or B-vent. Size liner It em D esc ript ion Manuf ac t urer Manuf ac t urer’s Int ernat ional
c. Test vent system — Insofar as is practical, close all building per National Fuel Gas Code ANSI Z223.1–latest edition. number part number C omfort
doors and windows and all doors between the space in which Produc t s
b. Provide drain trap to remove any condensate.
the appliances remaining connected to the common venting part number
5. Where two or more gas appliances vent into a common
system are located and other spaces of the building. Turn on chimney or vent, equivalent area should be at least equal to St anding pilot — Nat ural gas c omponent s
clothes dryers and any appliance not connected to the common area of vent outlet on largest appliance plus 50 percent of vent 1 Gas valve, 1/2" x 1/2", GWA052 through GWA175 Honeywell VR8200A2116 511044360WT
venting system. Turn on any exhaust fans, such as range hoods outlet area of additional appliance. Robertshaw 7200ER
and bathroom exhausts, so they will operate at maximum speed.
Gas valve, 3/4" x 3/4", GWA210 and GWA245 Honeywell VR8300C4050 511044256WT
Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected. Follow the Figure 2 Terminations with Type B vent fitted with 2 Pilot assembly kit with orifice International Comfort Products 510811005WT
lighting/operating instructions. Adjust thermostat so appliance listed cap, provided vent is at least 8 feet
will operate continuously. from any vertical wall or similar obstruction 3 Tubing, pilot, aluminum 560742860WT

e. Test for spillage at draft hood relief opening after 5 minutes of 4 Tubing, thermocouple 511724254WT
main burner operation. Use the flame of a match or candle.
5 Transformer relay 510312167WT
f. After it has been determined that each appliance remaining
connected to the common venting system properly vents when not Wiring harness 591391862WT
tested as outlined above, return doors, windows, exhaust fans, shown
fireplace dampers, and any other gas-burning appliance to their
previous conditions of use.
Any improper operation of common venting system should be
corrected so the installation conforms with the National Fuel Gas
Code, ANSI Z223.1–latest edition. Correct by resizing to approach
the minimum size as determined using the appropriate tables in
Part 11 of that code. Canadian installations must comply with B149.1
or B149.2 Installation Code.

Chimney or vent requirements


1. Venting must be installed according to Part 7, “Venting of

4 Part Number 670 01 1001 00 Part Number 670 01 1001 00 33


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

13 Dimensions 1 Prepare boiler location continued

Clearances
Figure 21 Dimensional drawing — ALL DIMENSIONS IN INCHES Service clearances Small space installations
1. Provide minimum clearances for cleaning and servicing the 1. When the boiler is located in a closet or small space, provide
boiler and for access to controls and components as listed in clearances no less than those shown in Figure 1. The clearances
the table below: are required to any surface, whether combustible or non-
2. Provide at least screwdriver clearance to jacket front panel combustible.
screws for removal of front panel for inspection and minor
service. If unable to provide at least screwdriver clearance, Figure 1 Minimum clearances
install unions and shutoff valves in system so boiler can be
moved for servicing.

Service clearances: Minimum


Top (for cleaning flueways) 35"
Front (for access to controls and components) 18"
Back 7"
Left side (for cleaning and servicing) 24"
Right side 7"

Minimum clearance to combustible materials


1. Hot water pipes must be at least ½" from combustible material.
2. Single-wall vent pipe must be at least 6 inches from combustible
material.
3. Type B double-wall metal vent pipe — See vent manufacturer’s
recommendation for clearances to combustible material.
Clearances from combustible materials: Minimum
Front (provide means of access) 3"
Back 7" Residential garage installation
Left side (provide means of access) 6"
Take the following special precautions when installing the boiler in
Right side 2" a residential garage. If the boiler is located in a residential garage,
Top H per ANSI Z223.1, paragraph 5.1.9:
GWA052 to GWA105 35" • Mount the boiler a minimum of 18 inches above the floor of the
GWA140 35½" garage to assure the burner and ignition devices will be no less
GWA175 38½" than 18 inches above the floor.
GWA210 39¾" • Locate or protect the boiler so it cannot be damaged by a moving
GWA245 42½" vehicle.

Table 1 Minimum foundation size Flooring and foundation


Boiler Supply Return Gas connection “A” “D” “W” “H”
model tapping tapping & manifold size Vent Vent Jacket Damper
number (inches NPT) (inches NPT) (Note 3) location diameter width height Boiler Minimum Minimum Flooring
(inches NPT) model foundation foundation The GWA boiler is approved for installation on combustible flooring,
(inches) (inches) (inches) (inches)
length width but must never be installed on carpeting.
GWA052 11/4 11/4 /
12 5 4 10 453/8 GWA052 25" 12" Do not install boiler on carpeting even if foundation is
GWA070 11/4 11/4 /
12 5 4 10 523/8 used. Fire can result, causing severe personal injury,
GWA070 25" 12" death or substantial property damage.
GWA105 11/4 11/4 1/2 61/2 5 13 543/8
GWA105 25" 15"
GWA140 11/4 11/4 1/2 8 6 16 577/8 Foundation
GWA175 GWA140 25" 18"
11/4 11/4 1/2 91/2 6 19 60 7/8 1. Provide a solid brick or minimum 2-inch thick concrete
GWA210 11/4 11/4 3/4 11 7 22 62 1/8 GWA175 25" 21" foundation pad if any of the following is true:
GWA245 11/4 11/4 3/4 121/2 7 25 64 7/8 GWA210 25" 24" • floor can become flooded.
• the boiler mounting area is not level.
Note 3: Size gas piping from meter to boiler per local utility requirements. GWA245 25" 27"
2. See Table 1 for minimum foundation dimensions.

34 Part Number 670 01 1001 00 Part Number 670 01 1001 00 3


GWA Gas-Fired Water Boilers – Boiler Manual GWA Gas-Fired Water Boilers – Boiler Manual

Read this first! 1 Prepare boiler location 14 Ratings


Failure to adhere to the guidelines below can
result in severe personal injury, death or Codes & checklist
substantial property damage.
Installations must follow these codes:
When servicing boiler — • Local, state, provincial, and national codes, laws, regulations
and ordinances.
DOE
1. To avoid electric shock, disconnect electrical supply • National Fuel Gas Code, ANSI Z223.1–latest edition.
before performing maintenance. Boiler 0–2,000 feet altitude 2,000–4,500 feet altitude Net Boiler DOE Chimney
• Standard for Controls and Safety Devices for Automatically
2. To avoid severe burns, allow boiler to cool before Fired Boilers, ANSI/ASME CSD-1, when required. model (Canada) I=B=R water Seasonal and
performing maintenance. number ratings content efficiency breeching
• National Electrical Code.
(Btuh) (gallons) (% A.F.U.E) size
• For Canada only: B149.1 or B149.2 Installation Code, CSA
Boiler operation — C22.1 Canadian Electrical Code Part 1 and any local codes. Input DOE Heating Capacity Input Output NS NI
3. Do not block flow of combustion or ventilation air to boiler. (Btuh) (Output) (Btuh) (Btuh) (Btuh)
Certification
4. Should overheating occur or gas supply fail to shut off, do
(Note 3) (Note 1) (Note 4) (Note 2) (Note 3)
not turn off or disconnect electrical supply to circulator. The GWA boiler gas manifold and controls met safe
Instead, shut off the gas supply at a location external to lighting and other performance criteria when boiler
the appliance. underwent tests specified in ANSI Z21.13–latest GWA052 52,000 43,000 46,800 37,400 37,000 1.5 80.2 83.0 4"I.D. x 20’
5. Do not use this boiler if any part has been under water. edition.
Immediately call a qualified service technician to inspect
the boiler and to replace any part of the control system Before locating the boiler: GWA070 70,000 58,000 63,000 50,400 50,000 1.5 80.1 82.2 4"I.D. x 20’
and any gas control that has been under water.
❏ Check for nearby connection to:
• System water piping GWA105 105,000 88,000 94,500 75,600 77,000 2.1 80.4 82.9 5"I.D. x 20’
Boiler water — • Venting connections
• Gas supply piping
6. DO NOT use petroleum-based cleaning or sealing
compounds in boiler system. Water seal deterioration will • Electrical power GWA140 140,000 117,000 126,000 100,800 102,000 2.7 80.4 82.5 6"I.D. x 20’
occur, causing leakage between boiler sections, circulator
❏ Check area around boiler. Remove any combustible materials,
flanges, diaphragm tanks or other system components.
gasoline and other flammable liquids. GWA175 175,000 145,000 157,500 126,000 126,000 3.3 80.5 82.2 6"I.D. x 20’
This can result in substantial property damage.
7. DO NOT use "homemade cures" or "boiler patent Failure to keep boiler area clear and free of
medicines". Serious damage to boiler, personnel and/or combustible materials, gasoline and other flammable
property may result. GWA210 210,000 175,000 189,000 151,200 151,000 3.8 80.5 81.8 7"I.D. x 20’
liquids and vapors can result in severe personal
8. Continual fresh makeup water will reduce boiler life. Mineral injury, death or substantial property damage.
buildup in sections reduces heat transfer, overheats cast GWA245 245,000 202,000 220,500 176,400 176,000 4.4 80.5 81.4 7"I.D. x 20’
iron, and causes section failure. Addition of oxygen and ❏ Boiler must be installed so that gas control system components
other gases can cause internal corrosion. Leaks in boiler are protected from dripping or spraying water or rain during
or piping must be repaired at once to prevent makeup operation or service.
water. 1. Based on standard test procedures prescribed by the United States Department of
❏ If new boiler will replace existing boiler, check for and correct Energy.
9. Do not add cold water to hot boiler. Thermal shock can system problems, such as:
cause sections to crack. 2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the
1. System leaks causing oxygen corrosion or section cracks requirements of the building and nothing need be added for normal piping and pickup.
from hard water deposits. Ratings are based on a piping and pickup allowance of 1.15. An additional allowance
2. Incorrectly-sized expansion tank. should be made for unusual piping and pickup loads.
Glycol — potential fire hazard —
3. Lack of antifreeze in boiler water causing system and boiler 3. See information at right for model number suffixes. Letters shown are model number
All glycol is flammable when exposed to high temperatures. If to freeze and leak. suffixes. An “N” after the model number designates natural gas. The letter after the
glycol is allowed to accumulate in or around the boiler or any
“N” designates the pilot ignition system — “S” for standing pilot or “I” for spark-
other potential ignition source, a fire can develop. In order to
ignited pilot. For example, a suffix “NS” means a natural standing pilot boiler.
prevent potential severe personal injury, death or substantial
property damage from fire and/or structural damage: 4. Contact your International Comfort Products dealer regarding information and parts
for high altitude applications.
• Never store glycol of any kind near the boiler or any
potential ignition source.
• Monitor and inspect the system and boiler regularly for
leakage. Repair any leaks immediately to prevent possible
accumulation of glycol.
• Never use automotive antifreeze or ethylene glycol in the
system. Using these glycols can lead to hazardous Install GWA boilers for residential radiant panel systems, converted gravity
leakage of glycol in the boiler system. heating systems or other low water temperature applications per instructions
in this manual to avoid damage due to condensation.
GWA boilers are CSA design certified for installation on combustible
flooring.
GWA boilers are ASME rated for 50 psig working pressure.

2 Part Number 670 01 1001 00 Part Number 670 01 1001 00 35


GWA Gas-Fired Water Boilers – Boiler Manual

GWA
Gas-Fired Water Boilers

Boiler Manual
Contents Page

1 Prepare boiler location ........................................................ 2


2 Prepare boiler ..................................................................... 6
3 Install water piping ............................................................ 10
4 Install gas piping ............................................................... 13
5 Field wiring ....................................................................... 14
6 Start-up ............................................................................ 15
7 Checkout procedure ......................................................... 18
8 Sequence of operation — standing pilot boilers ................. 19
9 Lighting instructions — GWA standing pilot boilers ........... 20
10 Service and maintenance ................................................. 22
11 Troubleshooting ................................................................ 27
12 Replacement parts ........................................................... 29
13 Dimensions ...................................................................... 34
14 Ratings ............................................................................. 35

Hazard definitions
Hazards that will cause severe personal injury, Hazards that will or can cause minor personal injury
death or substantial property damage. or property damage.
Hazards that can cause severe personal injury, Special instructions on installation, operation or
death or substantial property damage. maintenance that are important but not related to
personal injury or property damage.

INSTALLER — Read all instructions before USER — Please read the following. Failure to
installing. Read page 2 first. Follow all instructions comply could result in severe personal injury, death
in proper order to prevent personal injury or death. or substantial property damage.
• Consider piping and installation when determining • This manual is for use only by your qualified
boiler location. heating installer/service technician.
• Any claims for damage or shortage in shipment • Please see the User’s Information Manual for your
must be filed immediately against the transportation reference.
company by the consignee. • Have the boiler serviced by a qualified service
technician, at least annually.

This manual must only be used by a qualified heating installer/service technician. Failure to comply could result in
severe personal injury, death or substantial property damage.

When calling or writing about the boiler— Please have: • boiler model number from the boiler rating label and • CP number
from the boiler jacket. You may list the CP number in the space provided on the “Installation and service certificate” found on
page 18.

36 Part Number 670 01 1001 00 Part Number 670 01 1001 00