Koordinasi Rele Arus Lebih PDF
Koordinasi Rele Arus Lebih PDF
BUS TRAFO
SUMBER KIT AMBIL
150 KV DAYA BUS
DATA Z
20 KV
DARI SISTEM 100 %
150 KV, P3B DI GARDU
HITUNG
INDUK Z POS.
25% Z
AMBIL DATA Z NOL
SCC LEVEL HITUNG
AMBIL DATA
50 % Z
IMPEDANSI
MVA, KV dll UNTUK
HITUNG HITUNG
SIMULASI
Z SUMBER 75 % Z
LOKASI GANG.
KOORDINASI RELAI ARUS LEBIH & GROUND
transmisi
150 2
MAKA, XS = = 45 OHM INGAT NILAI INI DISISI 150 KV
500
KARENA AKAN MENGHITUNG I GANGG. SISI 20 KV,MAKA
IMPEDANSI DISISI 150 KV, TRANSFER KE SISI 20 KV CARANYA
150 KV 20 KV
45 OHM ?
20 KV
KOORDINASI RELAI ARUS LEBIH & GROUND
DASAR HITUNGANNYA
MAKA 20 2
Z2 = x 45 OHM
150 2
PERHITUNGAN :
IMPEDANSI DASAR PADA TRAFO (100 % ) SISI 20 KV
20 KV 2
ZB = = 40 OHM
10 MVA
REAKTANSI TRAFO = 10 %
XT = 10 % x 40 OHM
IMPEDANSI PENYULANG
DATA IMPEDANSI PENYULANG DIDAPAT DIHITUNG
DARI TABEL
PER KM
IMPEDANSI PENYULANG PANJANG PENYULANG x Z PER KM
U/ %
IMPEDANSI Z0
PANJANG
TERGANTUNG
INGAT HITUNGAN INGAT HITUNGAN LOKASI GANG.
IMPEDANSI SUMBER IMPEDANSI TRAFO
= j 4.8 + Z1 penyulang
U/ %
IMPEDANSI Z1 , Z2 eki
PANJANG
25 % j0.48 + (0.3 + j 0.575) OHM = (0.3 + j 5.375) OHM
50 % j0.48 + (0.6 + j 1.150) OHM = (0.6 + j 5.950) OHM
HITUNGAN Z0
IMPEDANSI PENYULANG
= 3 x j 4.0 = j 12 OHM
3 RN = 3 x 40 = 120 OHM
PERHITUNGAN Z0 EKIVALEN
Z0 eki = Z0 T + 3 RN + Z0 penyulang
TERGANTUNG
INGAT HITUNGAN INGAT TAHANAN LOKASI GANG.
Z0 TRAFO PENTANAHAN
= j 12 + 120 + Z0 penyulang
U/ %
PANJANG IMPEDANSI Z0 eki
Z = IMPEDANSI Z1 ekivalen
20.000/ 3
GANGGUAN DI 25 % PANJANG PENYULANG I =
(0.3 + j 5.375)
IMPEDANSI MASIH
DALAM KOMPLEKS
KARENA DIAMBIL MAGNITUTE
20.000/ 3
I = = 2144.9 AMPER
(0.3 + 5.375 )
2 2
KOORDINASI RELAI ARUS LEBIH & GROUND
U/ GANGG. DI
% PANJANG ARUS GANGGUAN 3 FASA
20.000/ 3
25 % I = = 2144.9 AMPER
(0.3 + 5.375 )
2 2
20.000/ 3
50 % I = = 1930.9 AMPER
(0.62 + 5.9502 )
20.000/ 3
75 % I = = 1753.06 AMPER
(0.92 + 6.5252 )
20.000/ 3
100 % I = = 1603.60 AMPER
(1.22 + 7.1002 )
KOORDINASI RELAI ARUS LEBIH & GROUND
Z = IMPEDANSI ( Z1 + Z2 )ekivalen
20.000
GANGGUAN DI 25 % PANJANG PENYULANG I =
2 x (0.3 + j 5.375)
IMPEDANSI MASIH
DALAM KOMPLEKS
KARENA DIAMBIL MAGNITUTE
20.000
I = = 1857.6 AMPER
(2x0.3) + (2x5.375)
2 2
KOORDINASI RELAI ARUS LEBIH & GROUND
U/ GANGG. DI
% PANJANG ARUS GANGGUAN 2 FASA
20.000
25 % I = = 1857.6 AMPER
(2x0.3) + (2x5.375)
2 2
20.000
50 % I = = 1672.2 AMPER
(2x0.6)2 + (2x5.950)2
20.000
75 % I = = 1518.2 AMPER
(2x0.9)2 + (2x6.525)2
20.000
100 % I = = 1388.8 AMPER
(2x1.2)2 + (2x7.10)2
KOORDINASI RELAI ARUS LEBIH & GROUND
Z = IMPEDANSI ( Z1 + Z2 + Z0 )ekivalen
U/ GANGG. DI
% PANJANG ARUS GANGGUAN 1 FASA KETANAH
3 x 20.000/ 3
25 % I = = 280.67 A
(2x0.3 + 120.45) + (2x5.375 + 13.325)
2 2
3 x 20.000/ 3
50 % I = = 277.23 A
(2x0.6 + 120.9)2 + (2x5.950 + 14.65)2
3 x 20.000/ 3
75 % I = = 273.79 A
(2x0.9 + 121.35)2 + (2x6.525 + 15.975)2
3 x 20.000/ 3
100 % I = = 270.35 A
(2x1.2 + 121.8)2 + (2x7.10 + 17.3)2
KOORDINASI RELAI ARUS LEBIH & GROUND
PENYULANG 20 KV
BUS TRAFO
SUMBER KIT 150 KV DAYA BUS 25% Z 75% Z
DARI SISTEM
20 KV
150 KV, P3B
50% Z 100% Z
SIMULASI
LOKASI GANG.
KOORDINASI RELAI ARUS LEBIH & GROUND
PENYULANG 20 KV :
MISAL ARUS BEBAN PENYULANG = 100 AMPER
RATIO C.T = 150 : 5 AMPER
.tms = 0.13
KOORDINASI RELAI ARUS LEBIH & GROUND
INCOMING 20 KV :
ARUS BEBAN TRAFO DIHITUNG DARI KAPASITAS TRAFO
KAPASITAS TRAFO = 10 MVA ,In SISI 20 KV = 288.7 A
.tms = 0.2
KOORDINASI RELAI ARUS LEBIH & GROUND
.tms = 0.1
KOORDINASI RELAI ARUS LEBIH & GROUND
INCOMING 20 KV :
CATATAN : SETELAN ARUS RELAI GANGGUAN TANAH DI
INCOMING 20 KV HARUS LEBIH SENSITIVE
FUNGSINYA : CADANGAN BAGI RELAI DI PENYULANG 20 KV
DIBUAT 8% x ARUS GANGGUAN TANAH TERKECIL
.tms = 0.26
KOORDINASI RELAI ARUS LEBIH & GROUND
0.14 x 0.13
.t = HITUNG PULA WAKTU
2144.9 0.02
KERJA RELAI UNTUK
- 1
105 ARUS GANGGUAN DI
LOKASI 50%, 75% DAN
.t = 0.3 100% PJ PENYULANG
KOORDINASI RELAI ARUS LEBIH & GROUND