Features and Benefits The ABQM temperature control valve provides consumption which increases T
pressure independent regulation of flow while Three required valve functions; control,
also providing flow limiting system balance. The balance and flow limitation in one compact
valve internally contains a unique differential valve design
pressure regulator which automatically adjusts to Flow parameter is the only consideration,
normal changes in system pressure from valves reducing valve selection engineering
opening and closing or changing of pump speed. Constant flow regulation limitation through
As a result of maintaining a constant pressure for independent pressure balancing
the control valve, valve authority is maintained User adjustable flow setting for maximum flow
at 100%. This allows for precise interaction with limitation
the temperature controller and unparalleled Maintains linear characteristic of flow when
system operation as indicated by assuring the installed with a Danfoss proportional actuator.
highest possible coil log mean temperature Actuator options with equal percentage flow
difference (T). The valve is easily set and characteristics.
adjusted to provide the precise flow required
for each terminal unit. Design calculation and Benefits:
commissioning effort normally required for it's Flow will match the load
control and balance valves are virtually eliminated Eliminate coil over flows
because of the built in automatic pressure control Installation of the ABQM reduces time and
regulator. A wide selection of actuators are materials
available for the ABQM providing further control Simple flow setting procedure; reduced time
features for the valve, making it an ideal selection involved for field commissioning
for the simplest of two position control strategies Valve allows maximum coil and system differential
to the precision required for modulating control temperature drops for optimum efficiency
and variable speed pump optimization. Operation costs reduced as much as 90 % or
more when properly applied with variable speed
Features: pumping
ABQM maintains a stable flow through its "Plug and Play" for quick setup for balancing
range of operation unaffected by changes allowing immediate start up of unit
in system differential pressure 100 % valve Commissioning accomplished without use of
authority allows lower pump head than specialized equipment
traditional valves and reduces energy Compact design allows installations in areas with
limited space such as stand alone fan coils
Contact Danfoss for lower p valve bodies in sizes from 1/2" to 1/4"
ABQM Accessories
Code No. Description
003Z0695 Brass handle for ABQM 1" thru 4"
003Z0696 Brass handle for ABQM 5" thru 6"
003Z0697 Brass handle for ABQM 8" thru 10"
ABQM MNPT THREADED TAILPIECE KIT (two kits required per valve)
Code No. Size Connection Type Description
003Z0282 "
003Z0283 "
003Z0284 1" One Nut + One Threaded Tailpiece
NPT (Male)
003Z0285 1" + One Gasket
003Z0286 1"
003Z0287 2"
Accessories
Code No. Description
Brass shut-off & protection cap, Max 232psi (16 bar)
003Z0230
(for use with to 1 ABQM valve)
Locking Ring - installed to inhibit the unintentional changing of the ABQM valve setting, 5pcs.
003Z0236
(for use with " to 1" ABQM valve)
Type Lenght Size Code No. Type Lenght Size Code No.
NY050FM24 NY050SM24
LF NY050LFFM24 LF NY050LFSM24
24" NY075FM24 24" NY075SM24
1 NY100FM24 1 NY100SM24
Female NPSH Hose 1 NY125FM24 Female Solder Hose 1 NY125SM24
Connection NY050FM Connection NY050SM
LF NY050LFFM LF NY050LFSM
36" NY075FM 36" NY075SM
1 NY100FM 1 NY100SM
1 NY125FM 1 NY125SM
1)
Available battery backup assembly for safety function, AM-PBU25, 082H7090, one per AME85QM actuator
Application:
The ABQM is a versatile device that can be commissioning to properly match the required
used as an actuated or non-actuated balance setting to the applications, sometimes over
valve / flow limiter. With an actuator mounted several seasons of operation. The ABQM
to the ABQM valve, the assembly is a pressure differential pressure regulator acts as an extra
independent control valve. Utilizing a sub-master controller and makes tuning the main
proportioning controller, the ABQM creates controllers easier and less time consuming.
a robust and stable energy management sub Smaller building HVAC sub-systems such as fan
system using only the required flow and energy coil units, or terminal unit heating coils and newer
to offset facility heat transfer gains and losses. modern designs such as chilled beams or radiant
cooling panels greatly benefit from ABQM
The integrated ABQM differential pressure application even when applied with simple
regulator virtually eliminates the problem thermostatic operation. No pressure calculations
of fluctuating pressures on control valve are required, valve authority doesn't need to
performance. The ABQM regulator immediately be calculated and no calculations have to be
reacts to all changes in system pressure creating performed to pre-set a balancing valve. If extra
the stability to make the valve flow and control flow is determined to be required while tuning
predictable and controllers and valves work as the installation, it's easy for the commissioning
intended. Energy is saved taking advantage of agent to reset the ABQM for any flow up to the
the greatly reduced amount of flow required rated range of the valve. The HVAC units and
for heat transfer of full valve authority for an controllers will benefit from greatly enhanced
air handling unit (AHU), fan coil, etc. With the ability to control, with no overflow. ABQM
ABQM the required design flow to the AHU is allows hydronic HVAC systems to achieve the
met, subsequently simplifying the balancing green and sustainable performance envisioned
of the system. Air handling units react quickly by their designers and owners. Owners benefit
to changes in the building load and simple in significant reductions in commissioning time,
proportional control will not accurately energy cost in operation from reduced flow and
regulate these systems. Using control integral reduced complaints associated with improper
action to adjust for this requires skill and extra temperatures within the building.
Minimum Pressure Drop To verify that an installation functions according pressure will automatically be throttled. If there is
to the design specifications checking the critical not enough differential pressure the valve cannot
valve in the installation is needed . The critical reach the set flow. Therefore the critical valve
valve is the furthest valve away on the branch must have the minimum differential pressure for
or loop and has the lowest available differential the pressure regulator to properly operate, all
pressure. The AB-QM maintains a constant prior AB-QM valves will function properly.
differential pressure over the valve and any excess
P1 Available Pressure
P2 Regulated inlet pressure to control valve
P3 Exit pressure of valve
Differential Pressure Flow enters the valve through the differential A nominal 5 psi differential is required from P1
Regulator pressure regulator, which maintains a constant to P3 for the valve and flow regulator operation.
pressure difference across the control valve The regulator controls the range of system
orifice. As entering pressure increases or differential pressure to 60 psi (140 FOH). Under
decreases in reaction to changes in flow and normal system operation such as in variable
pump speed in the piping system, the regulator speed pumping, as system flow is reduced,
diaphragm is balanced with the force of the controlled pump speed reduces the system
spring keeping a constant pressure difference (P2- differential pressure (head) of the pump. In
P3) between the water entering the temperature constant speed pumping applications reductions
control valve and the leaving side of the valve. As in system flow may result in increased system
a result the differential pressure across the control differential pressure (head) of the pump.
valve (P2-P3) is at a constant level.
ABQM 5"-6"
1. Valve body
2. Valve seat
3. DPC cone
4. Cv cone
5. Controller casting
6. Rolling diaphragm
7. Adjusting screw
8. Bellow for pressure relief
on DPC cone ABQM 2"- 4" ABQM 5"-6"
ABQM 8-10
1. Valve body
2. Valve seat
3. DPC cone
4. CV cone
5. Controller casting
6. Rolling diaphragm
7. Adjusting screw P1 P3
8. Bellow for pressure relief on
DPC cone
Control Valve Flow The linear characteristic of the valve allows for
Coefficient and STROKE Valve Stem Travel application flexibility. By adjusting the maximum
Characteristic, Cv valve stem travel is also adjusted. Even through
this adjustment the control performance
is not compromised. On-Off controls will
cycle between full and no flow positions, and
proportional control actuators upon reset will self
calibrate to the new adjusted stem travel, and still
utilize the entire input signal range. Maintaining
a linear characteristic allows for the predictability
required to characterize the control signal when
needed in an application. Signal characterization
is optimally done in the controller, but may be
Q, Cv done through an available actuator which allows
matching to the terminal unit characteristic.
h h+ 2 mm, DN 10-20
h+ 4 mm, DN 25-32
Flow Adjustment
(continuous) 1 "-4" Sizes
Max 25Nm
5"-10" Sizes
+
Setting 60%
+
Note: 1 turn = 5,0 %
Typical Specification Revised Construction Specifications Institute a. provide integrated pressure regulator;
standard numbering is utilized. The Specifier regulator to control pressure across control
is advised to coordinate product provisions valve orifice
with other speciality specification areas as b. provide regulator incorporating EPDM
more than one may apply. The model for this diaphragm, stainless steel spring and pressure
specification and suggested placement is based control disc. Pressure control seat shall be
on the "Unified Facilities Guide Specifications" brass construction with vulcanized EPDM
downloadable form the Whole Building Design c. provide counterbalance of supply pipe
Guide web site (www.wbdg.org) and found under pressure to return pipe pressure across
the "Documents & References" specifications diaphragm to prevent diaphragm damage
library. The WBDG web site is offered as an when control valve is closed
assistance to the building community by d. provide user adjustable maximum flow within
the National Institute of Building Sciences valve control range; Adjustment method shall
(NIBS) through funding support of several US indicate percentage of valve flow range and
government agencies. utilize spring locked method of adjustment
e. regulate internal control valve differential
SECTION 23 09 23 pressure to provide 100 % control valve
authority
DIRECT DIGITAL CONTROL FOR HVAC AND OTHER f. shall have linear flow characteristic
LOCAL BUILDING SYSTEMS g. provide back seated globe design to allow
PART 2 PRODUCTS service of packing under pressure without
leakage
2.6 automatic control valves h. provide entering to leaving (P1-P3) pressure
control across valve " in size from 2.3-60 PSI
Valves shall have stainless-steel stems and i. provide entering to leaving (P1-P3) pressure
stuffing boxes with extended necks to clear the control across valves "-1" in size from
piping insulation. Valves bodies shall meet ASME 5-60PSI
B16.34 or ASME B16.15 pressure and temperature j. provide entering to leaving (P1-P3 pressure
class ratings based on the design operating control across valves 1"-10" in size from
temperature and 150 percent of the system 4-60PSI
design operating pressure. k. provide entering to leaving (P1-P3) pressure
control across valves 5HF 10HF in size from
Unless otherwise specified or shown, valve 8.760PSI
leakage shall meet FCI 70-2 Class IV leakage l. provide union connections
rating (0.01 percent of valve Kv). Unless otherwise m. utilize stainless steel internal trim with brass
specified or shown, valves shall be two way globe seat
pressure independent globe-style bodies. Unless n. utilize threaded actuator connection
otherwise specified: o. flow requirements shall be sized to provide
a. bodies for valves 2 inches and smaller shall be nominal body selection no more than one
brass or bronze, with union ends size smaller to corresponding nominal pipe
b. bodies for valves 2 to 3 inches shall be of brass, connection
bronze or iron. a. " bodies shall be utilized for " pipe and may
c. bodies of valves 2 inches and larger shall be be utilized for " pipe connection and
provided with flanged-end connections flow less than 5 GPM
d. valve and actuator combination shall be b. " bodies may be utilized for " pipe and may
normally open or normally closed as shown be applied to 1" pipe connection with
flow less than 7,5 GPM
2.6.1 Two-Way Pressure Independent Globe c. 1" bodies may be utilized for 1' pip and may
Valves be applied to 1" pipe connection with
flow less than 12 GPM
Two-way modulating valves used for liquids. d. 1"bodies may be utilized for 1" and
The valve shall be two way globe style with may be applied to 1" pipe connection
integrated differential pressure control regulator. with flow less than 17.5 GPM
Where indicated modulating proportional valve e. 1" bodies may be utilized for 1" pipe
application shall utilize controller or actuator to and may be applied to 2" pipe connection
match required control signal to complement with flows less than 33 GPM
controlled coil heat transfer characteristic for f. flows less than 55 GPM may use 2" bodies
linear control, the valve shall: g. flows less than 85 GPM may use 2" bodies
h. flows less than 120 GPM may use 3" bodies
i. flows less than 165 GPM may use 4" bodies
j. flows less than 395 GPM may use 5"bodies
Typical Specification k. flows less than 640 GPM may use 6" bodies d. provide flexible piping for connection to coil.
(continuous) l. flows less than 836 GPM may use 8 bodies Piping shall be configured such that unions
m. flows less than 1232 GPM may use 10 bodies are hard mounted to coil either directly or with
n. flows less than 484 GPM may use 5HF elbows as appropriate to allow straight flexible
bodies connection without ninety degree change
o. flows less than 836 GPM may use 6HF in direction. Flexible pipe shall be mounted
bodies between coil union and control valve or
p. flows less than 1100 GPM may use 8HF strainer valve.
bodies
q. flows less than 1629 GPM may use 10HF
bodies
H1
b
H2
L1 L2
H5
H4
H3
L4 L5 L6
TWA-Z + ABQM ABN A5, ABNM A5 + ABQM AMV (E) 110 NL(X) + ABQM
AMI 140 + ABQM
H3
H1
b
H2
H3
H1
a
H2
H1
H1
a
a
H2
H2
L1 L1
H3
H3
H1
a
H2
L1
B*
Supply
A
Return
Materials
Isolation Valve and Strainer:
Body Grey cast iron A48 No. 35A
Valve bodies,
end pieces Forged brass ASTM B283
Strainer cap Forged brass ASTM B283
Filter screen 304 Stainless steel
Handle & nut Zinc plated
Ball Hard chrome plated brass
Ball seals Teflon
Shaft Brass
Shaft seals Dual FKM o-rings
Union seals FKM o-rings
Cap seals FKM o-rings
Braided Hose:
Core Fabric Reinforced EPDM
Braid Stainless steel
Fitting Brass OT58
Gasket EPDM
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary eady agreed.