Anda di halaman 1dari 1

SODIUM DRIFT EVAPORATION COAGULANT COAGULANT AID SODIUM

HYPOCHLORITE BISULFITE
0.6 GPM 2524 GPM 23 GPH 1 GPH
12 GPH 0.6 GPM 1205 GPM 2 GPH

UNITS 6&7 COOLING 7572 GPM 5047 GPM SAND FILTERS 5037 GPM 5103 GPM
COOLING TOWER
WATER DISCHARGE 3615 GPM 2409 GPM 2405 GPM 2432 GPM
CANAL
9 GPH 10 GPM
36 GPH 5 GPM UNITS 6&7
FROM ULTRAFILTER SCALE INHIBITOR SULFURIC ACID OUTFALL 002
BACKWASH EVAPORATION TO SOLIDS DEWATERING
COAGULANT SODIUM
86 GPM HYPOCHLORITE 80 GPM COOLING TOWER
4 GPH 20 GPM 14 GPM BLOWDOWN TREATMENT
2 GPH 66 GPM
Blowdown 28 GPM
RIVER 804 GPM CLARIFIER (INCL. 899 GPM 100 GPM 20 GPM
CLARIFIED WATER EVAPORATIVE
SOLIDS CONTACT WASTEWATER SUMP
WATER 188 GPM 212 GPM TANK 18 GPM COOLER 4 GPM
UNIT)
SODIUM
UF COAGULANT SODIUM ANTISCALANT HYDROXIDE
0.2 GPH 899 GPM BISULFITE 90 GPM AMMONIA 46 GPM Blowdown
212 GPM 4 GPH 0.1 GPH 1 GPH 16 GPM 1 GPH 24 GPM
COAGULANT AID 7 GPH
LEASED MIXED 2 GPH Phosphate
SOLIDS TO SOLIDS 0.1 GPH DEWATERING 865 ULTRAFILTER 778 GPM REVERSE OSMOSIS 467 GPM BED 467 GPM DEMIN WATER TANK 531 GPM
DEWATERING (INCL. FILTRATE (INCL. RO DEMINERALIZER HRSG STEAM CYCLE
LANDFILL POLYMER 196 176 GPM 106 GPM 106 GPM (Note 4) 90 GPM
(INCL. THICKENER) TANK) PERMEATE TANK) (REGENERATED
OFFSITE)
1 GPH
10 GPM 86 GPM 2 GPH OXYGEN 0.5 GPH 23 GPM
5 GPM 20 GPM BACKWASH RAW WATER SCAVENGER 12 GPM
34 GPM ACID PRETREATMENT &
FROM COOLING TOWER 16 GPM TO CLARIFIER BACKWASH SODIUM 311 GPM PROCESS WATER EVAPORATION NON-RECOVERABLE
BLOWDOWN TREATMENT HYPOCHLORITE 71 GPM TREATMENT 462 GPM 462 GPM LOSSES
SYSTEM
54 GPM 54 GPM

LEGEND: POWER
FLOW PATH OR UNIT (ORIGINAL AFC) AUGMENTATION
FLOW PATH OR UNIT (AMENDED AFC) SERVICE WATER 10 GPM
TREATMENT SYSTEM BOUNDARY (EXISTING AFC) TANK 2 GPM
TREATMENT SYSTEM BOUNDARY (AMENDED AFC)
CHEMICAL FEED (ORIGINAL AFC)
CHEMICAL FEED (AMENDED AFC)
UNITS 1-5
DISCHARGE
NOTES: OUTFALL 001
1. FLOWS ARE IN GALLONS PER MINUTE.
2. FLOWS IN BOLD ARE MAXIMUM DAILY FLOWS
3. FLOWS IN ITALICS ARE AVERAGE DAILY UNITS 1-5
FLOWS BASED ON 1000 HOURS PER YEAR OF 24 GPM 24 GPM OIL WATER 24 GPM DISCHARGE
PLANT AND
14 GPM SEPARATOR (INCL. 14 GPM
OPERATION WITH POWER AUGMENTATION AND EQUIPMENT DRAINS 14 GPM OUTFALL 001
INSPECTION TANK)
3944 HOURS PER YEAR WITHOUT POWER
AUGMENTATION AVERAGED OVER ONE YEAR
OIL WATER
OF OPERATION. SEPARATOR
4. MAXIMUM DAILY FLOWS TO AND FROM THE
DEMINERALIZED WATER TANK DO NOT BALANCE.
SURGE CAPACITY IN THE TANK WILL BE USED TO
SUPPORT USERS REQUIRING DEMINERALIZED CHEMICAL AREA CHEMICAL WASTE
WHEN DEMANDS ARE AT THEIR PEAK. DRAINS SUMP
5. ALL CHEMICAL FEED RATES ARE APPROXIMATE
AND ARE BASED ON THE MAXIMUM WATER FLOW
RATES. CHEMICALS AND FEED RATES ARE
REPRESENTATIVE OF THOSE ANTICIPATED FOR CITY 0.5 GPM POTABLE WATER 0.5 GPM EXISTING
THE WATER TO BE TREATED AND THE EQUIPMENT WATER 0.5 GPM USERS 0.5 GPM SANITARY SYSTEM
USED FOR THE TREATMENT. CHEMICALS
FED, FEED POINTS AND FEED RATES ARE
SUBJECT TO ADJUSTMENT OVER THE COURSE OF
DETAILED DESIGN.
CASE 1 COMBUSTION TURBINE FUEL NATURAL GAS CONDENSER COOLING WET TOWER MIRANT CORPORATION Project Drawing Rev
TOTAL ANNUAL HOURS OF OPERATION 4944 hr/yr PLANT OUTPUT MAX. AVG. CYCLES OF CONCENTRATION 1.5 CONTRA COSTA UNIT 8 65108 WMB-1 D
EVAPORATIVE COOLER 4944 hr/yr DRY BULB TEMP (F) 86 60 DRIFT 0.0005% WATER MASS BALANCE
COMB. TURBINE STEAM AUG. 1000 hr/yr RELATIVE HUMIDITY 33% 68% CYCLE MAKEUP RATE 2% Eng: JDC Dwg: JDC MAXIMUM DAILY AND
DUCT FIRING 1000 hr/yr TURBINE CONFIGURATION 2 x 1 7FAs Check: Date: 1/10/2006 AVERAGE DAILY FLOWS

Anda mungkin juga menyukai