USERS MANUAL
ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
TABLE OF CONTENTS
1. INTRODUCTION..........................................................................................................11
1.1. Description ........................................................................................................................ 11
1.2. Summary of Features......................................................................................................... 12
PROTECTION ................................................................................................................. 12
MONITORING ................................................................................................................ 12
METERING ..................................................................................................................... 13
COMMUNICATIONS ..................................................................................................... 13
RECORDER..................................................................................................................... 13
USER INTERFACE ......................................................................................................... 13
AUXILIARY OUTPUTS - Option................................................................................... 14
AUXILIARY INPUTS - Option....................................................................................... 14
4 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
2.5. Monitoring......................................................................................................................... 23
2.6. Recorder ............................................................................................................................ 24
WAVEFORM CAPTURE ................................................................................................ 24
SYSTEM EVENT RECORDER...................................................................................... 24
DIAGNOSTIC EVENT RECORDER ............................................................................. 25
LOAD PROFILE.............................................................................................................. 25
COUNTER ....................................................................................................................... 25
RECLOSER WEAR......................................................................................................... 25
2.7. Communications................................................................................................................ 26
4. SYSTEM SETUP........................................................................................................... 43
ENHANCED TECHNOLOGY 5
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
5. PROTECTION .............................................................................................................. 52
Protective Elements - ANSI Designations........................................................................ 53
5.1. Phase (Fast/Delay) Time Overcurrents (51P).................................................................... 54
5.2. Phase High Current Trip (50P-1)....................................................................................... 58
5.3. Phase High Current Lockout Element (50P-2).................................................................. 60
5.4. Ground (Fast/Delay) Time Overcurrent (51G).................................................................. 62
5.5. Ground High Current Trip (50G-1) ................................................................................... 65
5.6. Ground High Current Lockout (50G-2) ............................................................................ 67
5.7. Sensitive Earth Fault (SEF) ............................................................................................... 69
5.8. Negative Sequence (Fast/Delay) Time Overcurrent (46) ..................................................................... 71
5.9. Negative Sequence High Current Trip (46(50)-1)............................................................. 73
5.10. Negative Sequence High Current Lockout (46(50)-2) ....................................................................... 75
6 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
7. MONITORING............................................................................................................ 143
7.1. Demand ........................................................................................................................... 143
7.1.1. Description ........................................................................................................... 143
7.1.2. Related Setting Menu ........................................................................................... 143
7.2. SYNCHRONISM CHECK ............................................................................................. 146
7.3. TRIP COUNTER............................................................................................................. 146
7.3.1. Trip Counter Explanation ..................................................................................... 146
7.3.2. Related Setting Menu ........................................................................................... 146
ENHANCED TECHNOLOGY 7
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
8 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
9.4. RTU Communication Setup (DNP 3.0 & MODBUS Protocol) - Option................................................ 169
ENHANCED TECHNOLOGY 9
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
10 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
1. INTRODUCTION
1.1. Description
y EVRC2A with the microprocessor-based digital control technology is designed to provide
protective coordination and fault clearance of distribution systems for the continuous best
quality of electric service.
y Remote monitoring and control can be provided by RTU(Remote Terminal Unit - Option)
which fundamentally installed.
y EVRC2A provides protection, control, and monitoring functions with both local and remote. It
also displays the present trip/alarm conditions, and measured system parameters.
y Recording of past trip, alarm or control events, maximum demand levels, and energy metering
is also performed.
y Users can operate Close and Trip, and also control EVRC2A with key buttons on the user
interface panel; Protection Enabled, Ground Enabled, SEF Enabled, Reclose Enabled, Control
Locked, Remote enabled, Alternate-settings, Program 1, Program 2, Hot line tag.
y Users can manage the Recloser interface software using a portable PC for modification of
settings, acquisition of event data, and management of operation history.
y EVRC2A contains many T-C characteristic curves developed by IEEE C37.112, IEC255-3,
McGraw Edison, and KEPCO to provide fully protective coordination for the continuous best
quality of electric distribution. Users can select any time of current curve simply by
programming and modifying.
ENHANCED TECHNOLOGY 11
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
MONITORING
y Fault Locator
y Demand trip and alarm(Ia, Ib, Ic, Ig, I2)
y Trip Counter Limit
y Synchronism Check
y Recloser main contact Wear(Per Phase)
y Recloser Operation Failure
y Voltage Transformer Failure
y Battery Automatic Load Test
y Recloser Gas Over and Low pressure
y Breaker Failure with Current Supervision
12 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
METERING
y Phase, Ground and Sensitive Ground Current Phasors
y Line and Phase Voltage Phasors
y Current and Voltage Symmetrical Component Phasors
y Frequency Magnitude and Rate
y Synchronizing Voltage Phasor
y Synchronizing Voltage Frequency
y Synchronizing Delta, Delta
y Single and Three Phase Power(MW, Mvar, MVA, PF)
y Energy(MWh, Mvarh)
y Maximum Demand(Ia, Ib, Ic, MW, Mvar, MVA)
COMMUNICATIONS
y Front Panel COM1 RS232 Serial Port : EVRC2A interface software
y Rear Terminal COM2 RS232 Serial Port : DNP 3.0 Protocol - Option
y Rear Terminal COM3 RS485/422 Serial Port : Modbus - Option
RECORDER
y Trip and fault counter
y System event recorder - last 512 events
y Diagnostic event recorder - last 100 events
y Load profile recorder - last 42days
y Fault Waveform - 15 cycles16
USER INTERFACE
y Fault indicators
y Manual Battery Load Test: Battery Voltage and Charge Voltage
y Dual Functional keypads
y 204 Character Display(LCD or VFD : Vacuum Fluorescent Display)
y 32 LED indicators - Fault indications, sequence status, battery status, etc
y RS232 port
y Context Help Messages
y Access Security(Passcode)
ENHANCED TECHNOLOGY 13
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
14 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
2. TECHNICAL SPECIFICATIONS
2.1. Inputs and Outputs
Systems
y 3phase-3wire or 3phase-4wire, 38 maximum, 800 Amp maximum
Frequency
y 50 / 60 system and ABC/ACB phase rotation
ENHANCED TECHNOLOGY 15
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
16 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Impulse Voltage
y IEEE C62.45 (1992) Withstand Capability of Relay Systems to Radiated Electromagnetic
Interference Transceivers, 6(1.250), 3(820)
ENHANCED TECHNOLOGY 17
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Vibration Test
y IEC 255-21-1 - 1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2
18 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
POWER Phase A, B, C
Rate 0.05 0.02 -1.00 to 1.00
FACTOR 3 Phase
Phase A, B, C
3REAL POWER MW 3% 2% 320.00 to 320.00
3 Phase
3REACTIVE Phase A, B, C
Mvar 3% 2% 320.00 to 320.00
POWER 3 Phase
3APPARENT Phase A, B, C
MVA 3% 2% 320.00 to 320.00
POWER 3 Phase
Phase A, B, C
WATT-HOURS MW/h 5% 3% 32000 to 32000
3 Phase
If the VT connection type is set to delta, all single phase voltage quantities are displayed as zero.
ENHANCED TECHNOLOGY 19
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
20 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Reclose Control
Operations to Lockout - phase trip ............................ 1 to 5 in steps of 1
Operations to Lockout - ground trip.......................... 1 to 5 in steps of 1
Operations to Lockout - SEF trip .............................. 1 to 5 in steps of 1
Operations to Lockout - Negative Seq trip............... 1 to 5 in steps of 1
Operations of Fast curve - phase trip ........................ 0 to 5 in steps of 1
Operations of Fast curve - ground trip ...................... 0 to 5 in steps of 1
Operations of Fast curve - Negative Seq trip ........... 0 to 5 in steps of 1
ENHANCED TECHNOLOGY 21
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
22 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Underfrequency 1/2
Minimum Voltage...................................................... 0.00 to 1.25 in steps of 0.01 x VT in Phase A
Pickup Level.............................................................. 40.00 to 65.00 in steps of 0.01
Dropout Level ........................................................... at VT Pickup + 0.02
at CVD Pickup+0.05
Time Delay ................................................................ 0.00 to 600.00 in steps of 0.01s (definite time)
Level Accuracy.......................................................... at VT 0.02, at CVD 0.05
Timing Accuracy ....................................................... 2cycle
2.5. Monitoring
Demand
Measured Values ....................................................... Phase A/B/C/G Current(A)
Phase A/B/C/G 3 Real Power(MW)
Phase A/B/C/G 3 Reactive Power(Mvar)
Phase A/B/C/G 3 Apparent Power(MVA)
Measurement Type .................................................... Thermal Exponential/Rolling Demand
Time Constant ........................................................... 5, 10, 15, 20, 30 or 60 min.
Phase Pickup Level ................................................... 0.04 to 3.20 in steps of 0.01 x CT
Ground Pickup Level ................................................ 0.02 to 3.20 in steps of 0.01 x CT
Negative Seq Pickup Level ...................................... 0.04 to 3.20 in steps of 0.01 x CT
Level Accuracy.......................................................... 5%
Synchronism Check
Dead Voltage Maximum............................................ 0.00 to 1.25 in steps of 0.01 x VT
Live Voltage Maximum............................................. 0.00 to 1.25 in steps of 0.01 x VT
Maximum Voltage Difference ................................... 0.00 to 1.25 in steps of 0.01 x VT
Maximum Angle Difference...................................... 0 to 100 in steps of 1
Maximum Frequency Difference .............................. 0.00 to 5.00 in steps of 0.01
Synchro-check Phase ................................................ R(AB), S(CB), T of Load side
Trip Counters
Number of Pickup Limit ........................................... 1 to 20000 in steps of 1
Trip Counter Set ........................................................ 0 to 10000 in steps of 1
ENHANCED TECHNOLOGY 23
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Recloser Wear
Pickup Wear...............................................................0 to 100% in steps of 0.1
Rate System...............................................................15, 27, 38
Rate Interrupt() ......................................................5.0 to 50.0 in steps of 0.1
Number of Maximum Interruption............................1 to 999 in steps of 1
Set Phase A Wear.......................................................0.0 to 100.0 % in steps of 0.1
Set Phase B Wear.......................................................0.0 to 100.0 % in steps of 0.1
Set Phase C Wear.......................................................0.0 to 100.0 % in steps of 0.1
2.6. Recorder
WAVEFORM CAPTURE
y Trigger Source
Protection pickup Elements
Trip command active
y Data Channels
4 currents, 3 voltages, Frequency, 32 logic input states, 8ch output relays, 8ch Input
y Sample Rate : 16 per cycle
y Trigger Position : 1 to 15cycle
y Storage capacity : 16 events with 15cycle
24 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
LOAD PROFILE
y Trigger Source
Demand Current(A, B, C, G)
Demand Real Power(A, B, C, 3)
Demand Reactive Power(A, B, C, 3)
Trigger Time : 5, 10, 15, 20, 30, 60minute
y Storage Capacity : Total 1024 Events, 42days/60min.
COUNTER
y Trip : 0 to 65534
y Fault : 0 to 65534
y System Restart : 0 to 65534
RECLOSER WEAR
y Phase A Wear : 0.0 to 100.0%
y Phase B Wear : 0.0 to 100.0%
y Phase C Wear : 0.0 to 100.0%
ENHANCED TECHNOLOGY 25
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
2.7. Communications
Table 2-2. Communications
RS232, 19200bps, No Parity, 8 Data Bits, 1 Stop bit
Front Panel COM1
EVRC2A interface software
RS232, 1200-19200bps, No Parity, 8 Data bits, 1 Stop bit
Rear Terminal COM2 - Option
DNP 3.0 Protocol
RS485/422, 1200-19200bps, No Parity, 8 Data bits, 1 Stop bit
Rear Terminal COM3 - Option
Modbus Protocol
26 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ENHANCED TECHNOLOGY 27
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
3.1. Construction
Panel consists of 8 sections as below;
y Operation section
y Local control section
y Fault indication section
y Voltage elements section
y Sequence status section
y System diagnostic section
y Battery test section
y Menu control section
OPEN
Pressing OPEN push-button sends a trip signal to the Recloser.
CLOSE
Pressing CLOSE push-button sends a close signal to the Recloser.
Units operating with firmware version 2.18 or later have a feature of Close Time Delay. The Close
Time Delay allows a delay of 0.00 to 600.00 seconds after pressing the close push-button before
closing the recloser
POSITION LED
Indicates the position of the Recloser. Position indicator is based on the Recloser 52a contacts.
28 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
All indicators show status of Control function. The indicators are continuously ON when the
control function is enable and the indicators are continuously OFF when control function is
DISABLE. The push-button toggles Enable/Disable
PROTECTION ENABLED
All Protection elements are enabled
GROUND ENABLED
Ground Protection elements are disabled
SEF ENABLED
SEF Protection elements are disabled
RECLOSE ENABLED
Reclose function is enabled
CONTROL LOCKED
Front panel function is unlocked
REMOTE ENABLED
Remote control is disabled
ALTERNATE SETTINGS
Alternate setting is disable Figure 3-3. Local Control Section
Primary Setting is enable
PROGRAM 1
Program 1 function is disabled
PROGRAM 2
Program 2 function is disabled
HOT LINE TAG
Hot Line Tag function is disabled
ENHANCED TECHNOLOGY 29
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Protection Enabled
When illuminated, all protection elements are enabled. The protection enabled condition can be
disabled by pressing the Protection Enabled push button on the front panel. The front panel LED
will illuminate on either source of all protection enabling.
When Protection Enable LED is on, protection elements are enabled. The enabled protection can be
disabled by pressing the Protection Enabled push-button on the front panel.
NOTE : Although all protection elements are enabled, ground protection elements and SEF
element are operated individually
Ground Enabled
When Ground Enable LED is ON, the ground over-current elements are enabled. The enabled
Ground can be disabled by pressing the Ground Enabled push-button on the front panel.
SEF Enabled
When SEF Enable LED is on, the Sensitive Earth Fault(SEF) element is enabled. The enabled SEF
can be disabled by pressing the SEF Enabled push-button on the front panel.
Reclose Enabled
When Reclose Enable LED is on, the reclose(79) element is enabled. The enabled reclose element
can be disabled by pressing the Rcloser Enabled push-button on the front panel.
Control Locked
When Control Locked LED is on, all functions in operation section and all functions in Local
control section are locked. These can be unlocked by pressing the Control Locked push-button on
the front panel
NOTE : Even though Control Locked function is locked, OPEN, Lamp Test, Battery Load Test
and menu control section can be normally operated.
Remote Enabled
When Remote Enabled LED is on, all remote control function (e.g. SCADA system) are enabled.
This can be disabled by pressing the Remote Enabled push-button on the front panel. SCADA
control refers to supported communications protocol such as DNP3.0
Alternate Enabled
When Alternate Enabled LED is on, the Alternate setting is activated.
When Alternate Enabled LED is off, the primary setting is activated.
30 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Program 1
A function installed in Program1 is operated when Program1 LED is On.
Depending on users request, Manufacturer sets a function in Program1.
Program 2
A function installed in Program2 is operated when Program1 LED is On.
Depending on users request, Manufacturer sets a function in Program2.
Indicates current on the phase or neutral lines is above the minimum pickup setting as programmed
in any of the EVRC2A over-current elements
ENHANCED TECHNOLOGY 31
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
TRIP TYPE
y INST : Shows instantaneous trip
y DELAY : Shows delay trip
y HIGH CURR : Shows high current trip
FAULT INDICATION
y A, B, C : Indicates an over-current fault has occurred on one of the phase lines
y G : Indicates an over-current fault has occurred on the neutral line
y SEF : Indicates a sensitive earth fault has occurred on the neutral line
y FI RESET : Reset fault indication/Lamp test
32 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Indicates Diagnostic status of the EVRC2A. Control run indicates (green) the EVRC2A has
successfully passed its internal diagnostic test. Self Check (Red) indicates the EVRC2A has failed
its internal diagnostic test.
CONTROL RUN
Status of EVRC2A systems shows normal
SELF CHECK
Status of EVRC2A systems shows warning
NOTE : Control Run LED is blinking when system functional status is normal
Indicates the system power status of the EVRC2A. AC supply indicates the EVRC2A has external
power source. Charge indicates the EVRC2A is charging Battery. Discharge indicates the EVRC2A
has failed battery load testing.
ENHANCED TECHNOLOGY 33
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
AC SUPPLY
Status of supplying the external AC power.
CHARGE
Status of charging the battery.
DISCHARGE
Status of discharged battery. Figure 3-8. Battery Test Section
BATTERY LOAD TEST
Push-button for battery load test.
The Liquid Crystal Display (LCD) of the EVRC2A displays four lines of twenty characters each.
LCD DISPLAY
4x20 Characters display
CONTROL KEYS
[] [] [] []
Arrow keys are used for the moving between the menu window and the changing of the setting
value
[] (METER) : Up arrow key is used to move to the meter menu, operable in menu starting mode
[] (AWAKE) : Down arrow key is used for panel awake from sleep mode
[] (EVENT) : Left arrow key is used to move to the event menu, operable in menu starting mode
[] (SET) : Right arrow key is used to move to the setting menu, operable in menu starting mode
[FUN] : To move to main menu when present mode is in starting mode
[ESC] : To cancel for data input mode or return the display to the previous level
[ENT] : To select sub menu or data input
34 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
[FUN] Key
Press [FUN] key to enter Main menu for displaying information or changing settings. [FUN] key is
also used to display a help message in setting change mode and to cancel the help message display.
[ESC] Key
The ESC key can be used to cancel data input mode and return to the previous menu.
[ENT] Key
ENT key is used to select a menu by using Up and Down arrow key. Enter key is also used to
accept a new setting by using Up or down arrow key.
[] [] Key
Use the left and right arrow keys to move cursor when you are in the data input mode and when
you change display message.
[] [] Key
Use Up and Down arrow keys to move through the various menus and to decrease or increase value
when you are in the data input mode.
ENHANCED TECHNOLOGY 35
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
36 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
3.2.4. STATUS
OPTO INPUT : Shows status of External port.
RELAY OUTPUT : Shows status of Output port.
CLOCK : Shows the present time.
CONTROL TYPE : Shows specs of Hardware.
3.2.5. METERING
Shows metering values. For more details, refer to (see 6. METERING)
3.2.6. MAINTENANCE
COUNTER : Shows counters related with SYSTEM.
WEAR MONITOR : Shows any damage Interrupter.
RELAY OUTPUT TEST : Test External Output port.
For more details, refer to (see 7. MONITORING)
ENHANCED TECHNOLOGY 37
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
[RELAY
[RELAY SETTUP]
SETTUP]
1.PASSCODE
1.PASSCODE
2.COMMUNICATION
2.COMMUNICATION
3.CLOCK
3.CLOCK
4.EVENT
4.EVENT RECORDER
RECORDER
5.CLEAR
5.CLEAR SAVED
SAVED DATA
DATA
[LINE
[LINE CURRENT(A)]
CURRENT(A)] 6.FACTORY
6.FACTORY DEBUG
DEBUG
A:
A: 00 B:B: 00
C:
C: 00 G:G: 00
SG:
SG: 0 I2:
0 I2: 00
[ZERO
[ZERO SEQ
SEQ CURRENT]
CURRENT] [SYSTEM
[SYSTEM SETUP]
SETUP]
00 AA 000.0
000.0 Leg
Leg 1.CURRENT
1.CURRENT SENSING
SENSING
[POS
[POS SEQ
SEQ CURRENT]
CURRENT] 2.LINE
2.LINE VT
VT SENSING
SENSING
00 AA 000.0
000.0 Leg
Leg 3.LINE
3.LINE VL
VL SETTING
SETTING
[NEG
[NEG SEQ CURRENT]
SEQ CURRENT] 4.SYSTEM
4.SYSTEM POWER
POWER
00 AA 000.0
000.0 Leg
Leg 5.PANEL
5.PANEL SLEEP
SLEEP TIME
TIME
[SENSTV
[SENSTV CURRENT]
CURRENT] 6.OPTO
6.OPTO INPUT
INPUT SET
SET
00 AA 000.0
000.0 Leg
Leg 7.OUTPUT
7.OUTPUT RELAY
RELAY SET
SET
[PHASE
[PHASE CC CURRENT]
CURRENT]
00 AA 000.0 Leg
000.0 Leg
[GROUND
[GROUND CURRENT]
CURRENT]
00 AA 0.00.0 Leg
Leg [PRIMARY
[PRIMARY SETTING]
SETTING] [PROTECTION]
[PROTECTION]
[PHASE
[PHASE AA CURRENT]
CURRENT] 1.RELAY
1.RELAY SETUP
SETUP 1.OPERATIONS
1.OPERATIONS [DIRECTION
00 AA 000.0
000.0 Leg
Leg 2.SYSTEM 2.INTERVALS [DIRECTION ELEMENT]
ELEMENT]
[PHASE 2.SYSTEM SETUP
SETUP 2.INTERVALS 1.PHASE
1.PHASE DIRECTION
[PHASE BB CURRENT]
CURRENT] 3.PICKUP DIRECTION
00 AA 000.0
3.PROTECTION
3.PROTECTION 3.PICKUP CURRENT
CURRENT 2.GROUND
2.GROUND DIRECTION
000.0 Leg
Leg 4.PHASE DIRECTION
4.MONITORING
4.MONITORING 4.PHASE FAST
FAST 3.SEF
3.SEF DIRECTION
DIRECTION
5.SAVE
5.SAVE SETTINGS
SETTINGS 5.PHASE
5.PHASE DELAY
DELAY 4.NEG
6.GROUND 4.NEG DIRECTION
DIRECTION
6.GROUND FAST
FAST
7.GROUND
7.GROUND DELAY
DELAY
8.SEF
8.SEF ELEMENT
ELEMENT
[ALTERNATE
[ALTERNATE SETTING]
SETTING] 9.NEGATIVE
9.NEGATIVE FAST
FAST [VOLTAGE]
[VOLTAGE]
RECLOSER
RECLOSER CONTROL
CONTROL 1.RELAY
1.RELAY SETUP
SETUP 10.NEGATIVE
10.NEGATIVE DELAY
DELAY 1.UNDER
1.UNDER VOLTAGE
VOLTAGE 11
EVERC2
EVERC2 2.SYSTEM
2.SYSTEM SETUP
SETUP 11.H/C
11.H/C TRIP-PHA
TRIP-PHA 2.UNDER
2.UNDER VOLTAGE
VOLTAGE 22
3.PROTECTION
3.PROTECTION 12.H/C
12.H/C TRIP-GND
TRIP-GND 3.OVER
3.OVER VOLTAGE
VOLTAGE 11
ENTEC
ENTEC E&E
E&E CO.
CO. V3.01
V3.01 4.MONITORING
4.MONITORING 13.H/C
13.H/C TRIP-NEG
TRIP-NEG 4.OVER
4.OVER VOLTAGE 22
VOLTAGE
5.SAVE
5.SAVE SETTINGS
SETTINGS 14.H/C
14.H/C LOCKOUT-PHA
LOCKOUT-PHA
FUN 15.H/C
15.H/C LOCKOUT-GND
LOCKOUT-GND
16.H/C LOCKOUT-NEG
16.H/C LOCKOUT-NEG
17.COLD [FREQUENCY]
17.COLD LOAD
LOAD PICKUP
PICKUP [FREQUENCY]
[MAIN 18.DIRECTION 1.UNDER
1.UNDER FREQUENCY
[MAIN MENU]
MENU] 18.DIRECTION FREQUENCY
1.PRIMARY
1.PRIMARY SETTING
SETTING [STATUS]
[STATUS] 19.VOLTAGE
19.VOLTAGE
2.ALTERNATE
2.ALTERNATE SETTING
SETTING 1.OPTO
1.OPTO INPUTS
INPUTS 20.FREQUENCY
20.FREQUENCY
3.STATUS
3.STATUS 2.RELAY
2.RELAY OUTPUTS
OUTPUTS 21.OTHER
21.OTHER ELEMENT
ELEMENT
4.METERING
4.METERING 3.CLOCK
3.CLOCK 22.USER
22.USER CURVE
CURVE SET
SET
5.MAINTENANCE
5.MAINTENANCE 4.CONTROL
4.CONTROL TYPE
TYPE
6.EVENT [USER
[USER CURVE
CURVE SET]
SET]
6.EVENT RECORDER
RECORDER 1.USER
1.USER CURVE
CURVE 11
[MONITORING]
[MONITORING] 2.USER
2.USER CURVE
CURVE 22
[METERING]
[METERING] 1.DEMAND
1.DEMAND 3.USER
3.USER CURVE
CURVE 33
1.CURRENT
1.CURRENT 2.SYNCHROCHECK
2.SYNCHROCHECK 4.USER
4.USER CURVE
CURVE 44
2.VOLTAGE
2.VOLTAGE 3.TRIP
3.TRIP COUNTER
COUNTER
3.FREQUENCY
3.FREQUENCY 4.RECLOSER
4.RECLOSER WEAR
WEAR
4.SYNCHRO
4.SYNCHRO VOLTAGE
VOLTAGE 5.BATT
5.BATT TEST
TEST TIME
TIME
5.POWER
5.POWER 6.FAULT
6.FAULT LOCATOR
LOCATOR
6.ENERGY
6.ENERGY
7.DEMAND
7.DEMAND
8.SYSTEM
8.SYSTEM
[SAVE
[SAVE SETTING]
SETTING]
SETTING
SETTING VALUE
VALUE SAVE
SAVE
[MAINTENANCE] <ENT>:SETTING
[MAINTENANCE] <ENT>:SETTING SAVE
SAVE
1.COUNTERS
1.COUNTERS
2.WEAR
2.WEAR MONITOR
MONITOR
3.OUTPUT
3.OUTPUT RELAY
RELAY TEST
TEST
[EVENT
[EVENT RECORDER]
RECORDER]
1.FAULT
1.FAULT CYCLE
CYCLE
2.SYSTEM
2.SYSTEM STATUS
STATUS
3.LOAD
3.LOAD PROFILE
PROFILE
4.DIAGNOSTIC
4.DIAGNOSTIC
Please press the [ENT] key to select an INITIAL LOGO among (1), (2), (3)
(Control Firmware Version 3.01 higher support)
Figure 3-12. Menu Structure Tree
38 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
MAIN MENU
ENHANCED TECHNOLOGY 39
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
2) As above screen, to move to Phase, use [] [] key and press [ENT] key to move into value
column.
40 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
<ENT>:SETTING SAVE 3) If screen appears, press [ENT] key to save changed value.
System will restart with changed values. Screen shows SAVE
SETTING is done.
SETTING CHANGE
!! SYSTEM STOP !!
SETTING CHANGE
!!SYSTEM RESTART !!
ENHANCED TECHNOLOGY 41
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
42 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
4. SYSTEM SETUP
Sets following items for System
y CT Ratio
y VT or PT Ratio
y Power Line Frequency, Phase rotation
y Panel sleep time
y Opto-Input setting
y Relay output setting
For additional details on CT connections, refer to (see 10.12. Current Inputs Wiring Diagram).
4.1.2. Setting
PRIMARY SETTING / SYSTEM SETUP / CURRENT SENSING / PHA CT Ratio
[CURRENT SENSING] Range 1 ~ 1200
>PHA CT Ratio: 1000
GND CT Ratio: 1000 Default 1000 Step 1
SEF CT Ratio: 1000
ENHANCED TECHNOLOGY 43
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
4.2.2. Setting
PRIMARY SETTING / SYSTEM SETUP / LINE VT SENSING / Connect Type
[LINE VT SENSING] Range NONE, WYE, DELTA, CVD-W, CVD-D
>Connect Type: NONE
VT 2nd(v): 100.0 Default NONE Step ~
VT Ratio: 86.6
Enter None if line VTs are not to be used.
NONE : VT uninstalled.
If used, external PT by user, enter the VT connection made to the
system as Wye or Delta.
WYE : Install type wye.
DELTA : Install type delta.
If installed VT of Capacitor Voltage Divide type.
CVD-W : If the user system made to 3 phase 4 wire.
CVD-D : If the user system made to 3 phase 3 wire.
44 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Hence,
15- = 8.66-N, therefore 8.66-N = 100(V) 86.6
If user line voltage between phases (Voltage-) is 11, set VT2nd(v) of 73.3V and set VT Ratio of
86.6 (11- => 6.35-N, 6.35 = 73.3(V) 86.6)
27- = 15.59-N, therefore 15.59-N = 100(V) 155.9
38- = 21.94-N, therefore 21.94-N = 100(V) 219.4
ENHANCED TECHNOLOGY 45
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Line with Delta connection type and has V-= 15. If external rated PT is 14400 : 120, then VT
Ratio is 14400/120 and VT2nd(v) is 15- / 120 = 125V
120 120
15 100 86.6 71.2 125
(14400:120) (14400:120)
215 215
27 100 155.9 72.5 125.6
(25800:120) (25800:120)
300 300
38 100 219.4 73.1 126.7
(36000:120) (36000:120)
46 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
4.3.2. Setting
PRIMARY SETTING / SYSTEM SETUP / LINE VL SENSING / Connect Type
[LINE VL SENSING] Range NONE, WYE, DELTA, CVD-W, CVD-D
>Connect Type: NONE
VL 2nd(v): 100.0 Default NONE Step ~
VL Ratio: 86.6
Enter None if line VLs are not to be used.
NONE : VL uninstalled.
If used, external PT by user, enter the VL connection made to the
system as Wye or Delta.
WYE : Install type wye.
DELTA : Install type delta.
If installed VT of Capacitor Voltage Divide type.
CVD-W : If the user system made to 3 phase 4 wire.
CVD-D : If the user system made to 3 phase 3 wire.
ENHANCED TECHNOLOGY 47
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
4.4.2. Setting
PRIMARY SETTING / SYSTEM SETUP / SYSTEM POWER / Frequency
[SYSTEM POWER] Range 50, 60
>Frequency: 50
Phase Rotation: ABC Default 50 Step ~
Select the nominal power system frequency. This value is used as a
default to set the optimal digital sampling rate.
4.5.2. Setting
PRIMARY SETTING / SYSTEM SETUP / PANEL SLEEP TIME
[PANEL SLEEP TIME] Range OFF, 1 ~ 100 minute
>Interval(m): 5
Default 5 minute Step 1 minute
Enter the sleep mode entering time
Setting the interval time of which Panel indicator turns into Sleep mode
48 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
4.6.2. Setting
PRIMARY SETTING / SYSTEM SETUP / OPTO INPUT SET / I1 Func
[OPTO INPUT SET] Range NONE, TRIP, , OUT8 RESET
>I1 Func: NONE
I1 Debounce: 0.02 Default NONE Step ~
I2 Func: NONE
Enter the function of External input terminal Opto input can have
following functions;
4.6.3. Setting
PRIMARY SETTING / SYSTEM SETUP / OPTO INPUT SET / I1 Debounce
[OPTO INPUT SET] Range 0.01 ~ 9.99
I1 Func: NONE
>I1 Debounce: 0.02 Default 0.02 Step 0.01
I2 Func: NONE
ENHANCED TECHNOLOGY 49
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
4.7.2. Setting
PRIMARY SETTING / SYSTEM SETUP / OUTPUT RELAY SET / O1 Func
[OUTPUT RELAY SET] Range NONE, TRIP, , INPUT08
>O1 Func: NONE
O1 Type: S/R LATCH Default NONE Step ~
O1 Pulse T: 0.05
Enter the function of External output terminal.
Output Relay can have following function;
ALTERNATE SETTINGS
PROGRAM1 Enable PROGRAM2 Enable
Enable
52A INPUT 1~ 8
50 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ENHANCED TECHNOLOGY 51
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
5. PROTECTION
Protective Elements Block diagram - ANSI Designations
SOURCE
EVRC2A
OPTION 1
CVD
VT V1, V2, 3V0
3VT
VT
OPTION 2
3CVD 27 59 50P 51P
CVD 81
TRANSDUCER
1,2 1,2 1,2 1,2
Metering 67P
V, I, Watt, var, Hz, PF 1,2
CT
3WYE
25 79
1-4
I1
RECLOSER
3I0
27
OPTION 2
1CVD
CVD
TRANSDUCER
OPTION 1
50G 51G 67G 51 67
VT 81 1,2 1,2 1,2 SEF SEF
1VT
ZCT
3I0
LOAD
52 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ENHANCED TECHNOLOGY 53
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Multiple time curves and time dials are available for the phase time overcurrent element to
respectively coordinate with other protection elements in the EVRC2A and other external devices
on the distribution system. ANSI, IEC, ESB, USER and non-standard time current curves are
included in the EVRC2A.
A User Programmable curve option is also available for user to allow creating customs time
current curves for more enhanced coordination than the standard curve types.
The Reset type can be either instantaneous or linear. The phase time delay reset mode applies to the
ANSI, IEC, ESB, USER curves. The instantaneous mode is used to coordinate with other
instantaneous reset devices such as a recloser or other protective equipment on the distribution
system. In the instantaneous mode, the time overcurrent element will reset instantaneously when
the measured current level drops below the pickup setting for one cycle.
If the recloser is closed by pressing the CLOSE button on the front panel, or by an remote control
or via SCADA, the phase time overcurrent element is prevented from tripping for a period
specified by the Cold load pickup scheme.
54 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The following setting is used to program the phase fast time overcurrent element.
Selects the relays required to operate when the feature generates a Trip.
ENHANCED TECHNOLOGY 55
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
56 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The phase delay time overcurrent settings process is very similarly to the phase fast time
overcurrent.
ENHANCED TECHNOLOGY 57
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The phase high current trip element in the following five settings should be enabled for phase high
current trip.
Selects the required relays to operate when the feature generates a Trip.
58 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ENHANCED TECHNOLOGY 59
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
When high current lockout element is enabled, high current lockout element is operated prior to
any other phase protection elements. If a fault current is higher than the pickup setting value,
Lockout is operated.
The phase high current lockout element can be set by a number of its active trip that is applied to
the full operation to lockout, time delay and fault current.
This function is very useful to prevent widespread line faults due to reclosing operations in case of
permanent fault.
The operating time of phase high current lockout element should be set for equal to or faster than
and phase high current trip element. The phase high current lockout element is enabled in the
Primary, Alternate setting and PROTECTION ENABLED in user interface panel.
The phase high current lockout element is not affected by the cold load pickup scheme.
The phase high current lockout element in the following five setting should be enabled for phase
high current trip.
Selects the required relays to operate when the feature generates a Trip.
60 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ENHANCED TECHNOLOGY 61
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
If the recloser is closed by pressing the CLOSE button on the front panel, or by an remote control
or via SCADA, the ground time overcurrent element is prevented from tripping for a period
specified by the Cold load pickup scheme.
The following setting is used to program the ground time overcurrent element.
62 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Selects the relays required to operate when the feature generates a Trip.
ENHANCED TECHNOLOGY 63
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
64 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The ground high current trip element in the following five settings should be enabled for ground
high current trip.
Selects the required relays to operate when the feature generates a Trip.
ENHANCED TECHNOLOGY 65
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
66 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The ground high current lockout element in the following five settings should be enabled for
ground high current lockout.
Selects the required relays to operate when the feature generates a Trip.
ENHANCED TECHNOLOGY 67
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
68 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
For user systems, a directional SEF is available. The directional control is polarized by a zero
sequence voltage(V0). The CVD or PTs should be connected Wye-grounded.
ENHANCED TECHNOLOGY 69
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Selects the relays required to operate when the feature generates a Trip.
70 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
If the recloser is closed by pressing the CLOSE button on the front panel, or by an remote control
or via SCADA, the negative sequence time overcurrent element is prevented from tripping for a
period specified by the Cold load pickup scheme.
ENHANCED TECHNOLOGY 71
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Selects the relays required to operate when the feature generates a Trip.
The negative sequence delay time overcurrent setting process is very similar the negative sequence
fast time overcurrent setting process.
72 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The ground high current trip element in the following five settings should be enabled for negative
sequence high current trip.
Selects the required relays to operate when the feature generates a Trip.
ENHANCED TECHNOLOGY 73
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
74 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The negative sequence high current lockout element in the following five settings should be
enabled for the negative sequence high current lockout.
Selects the required relays to operate when the feature generates a Trip.
ENHANCED TECHNOLOGY 75
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
76 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
If directional controls are selected, it will determine whether current flow in each phase is in
forward or reverse direction, as determined by the connection of the phase CTs, selected Maximum
Torque Angle (MTA), voltage and current phasors. To increase security of all directional controls,
add one power frequency cycle of intentional delay to prevent incorrect operation.
The directional controls have each three settings. The directional controls settings can be different
in the Primary and Alternate settings.
ENHANCED TECHNOLOGY 77
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The phase direction control can be programmed for non-direction or to provide a trip for current
flow in the forward or reverse direction only.
following diagram shows the phasor diagram for I1 directional polarization in the complex plane.
Polarizing Referance
Voltage:
V1
ine
orq
ueL
ue
I1 T orq
Lin
um
im
e
x
Ma
a rd
rw
Fo
rse
ve
Re
78 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The phase direction control in the following four settings should be enabled.
ENHANCED TECHNOLOGY 79
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The ground direction control can be programmed to either non-direction or provide a trip for
current flow in the forward or reverse direction only.
The following diagram shows the phasor diagram for Ig directional polarization in the complex
plane.
-V0
ne
Li
ue
Fault Current
rq
Ze
To
Ig
ro
um
To
im
rq
ax
ue
M
Li
ne
d
ar
rw
Fo
e
rs
ve
Re
Polarizing Referance
V0
Voltage:
80 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The ground direction control in the following four settings should be enabled.
ENHANCED TECHNOLOGY 81
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The SEF direction control process a very similar method to the ground directional controls.
The negative sequence direction control can be programmed for non-direction or to provide a trip
for current flow in the forward or reverse direction only.
82 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The following diagram shows the phasor diagram for I2 directional polarization in the complex
plane.
-V2
ne
Li
ue
Fault Current
rq
Ze
To
I2
ro
um
To
im
rq
ax
ue
M
Li
ne
d
ar
rw
Fo
e
rs
ve
Re
Polarizing Referance
Voltage:
V2
The negative sequence directional controls in the following four settings should be enabled.
ENHANCED TECHNOLOGY 83
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
84 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
If the fault is transient, then the reclose logic is reset by the reset logic.
The reclosing element can be disabled in the Primary, Alternate settings by one operating lockout
or by RECLOSE ENABLED push button on user interface panel.
ENHANCED TECHNOLOGY 85
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
86 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ENHANCED TECHNOLOGY 87
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
88 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
5.12.1. Lockout
The lockout state occurs under any of the following conditions :
y After a fault of distribution systems, the RECLOSE ENABLED LED in user interface panel is
not lighted(ON).
y When the high current lockout has occurred.
y The recloser is manually closed and a fault occurs before the expiration of the reset time.
y When recloser is manually opened.
y After TRIP occurs, the fault current is not removed or the reclosers 52a contacts do not change
status of the recloser opened.
y The close power waiting time delay has expired.
The Lockout State is cleared when the recloser has been manually closed by local/remote control
and the reset time has expired.
The following diagram shows the typical full protection sequence containing 2F2D (two fast and
two delay) operations followed by lockout.
AMP
(1) (2) (3) (4) (5) (6) (7)
FAULT
CURRENT
* LOCK-OUT *
PICKUP
CURRENT
NORMAL
CURRENT
TIME
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time
(7) 4th Trip - 4th TCC
ENHANCED TECHNOLOGY 89
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
5.12.2. Reset
If the faulted current is cleared before the lockout condition, the reclosing sequence automatically
reset after passing the reset time interval.
If the fault condition occurs again during the reset time, the recloser will operate lockout after the
completion of the remaining sequence.
The following block diagram shows the reset sequence operation after the 3rd reclosing as the fault
current is cleared.
AMP
(1) (2) (3) (4) (5)
FAULT
CURRENT
AUTO RESET
TIME
* RESET *
PICKUP
CURRENT
NOMAL
CURRENT
TIME
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC
Figure 5-6. Reset Sequence operation after the 3rd reclosing as the fault current is cleared
90 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
If cold load pickup feature is activated and the Recloser is closed manually by local/remote control,
the overcurrent elements are operated considering the cold load pickup feature.
EVRC2A can be programmed to prevent the overcurrent elements and to raise the pickup level of
time overcurrent elements when a cold load pickup feature is detected. Under normal operating
conditions, the actual load on the distribution system is less than the maximum connected load.
When the distribution system is closed after a prolonged outage, the inrush current may be above
some overcurrent settings. Such the overcurrent elements are operated due to the fast overcurrent
elements are disabled and the delay overcurrent elements and SEF element are activated.
If the fault of the distribution system occurs, the overcurrent element is operated due to the cold
load pickup feature and the recloser will be lockout after one TRIP.
The cold load pickup feature is initiated and overcurrent settings are altered when the recloser is
opened for an amount of time greater than the outage time. The cold load pickup feature is
immediately activated by asserting the cold load pickup current. The overcurrent settings are
returned to normal after any phase current is restored to the nominal load, and then a timer of
duration equal to the restore minimum time expires.
Outage
Restore Minimum Time
Time
Current
Inrrush Current 1
TRIP
Cold load
Pickup Level
Overcurrent
Pickup Level
Inrrush Current 2
Time
ENHANCED TECHNOLOGY 91
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The cold load pickup feature will be operated by the following Rules;
When The cold load pickup feature is selected for ON and the cold load pickup level for
overcurrent elements are preset, The cold load pickup feature is activated by the overcurrent higher
than the cold load pickup level that is detected during the manual closing by local/remote control.
The cold load pickup feature is activated with the delay time overcurrent curve only when the
inrush current higher than the cold load pickup level or the fault current comes into existence.
If transient current remains below the cold load pickup level and the restore minimum time expires,
CLPU sequence is changed to the normal sequence. At this time, the cold load pickup level is
restored to the nominal pickup current. When fault current, the sequence will be lockout after one
TRIP.
If High Current Lockout feature is enabled and fault current is higher than the High Current
Lockout setting, High Current Lockout feature will be operated prior to the cold load pickup
feature.
Delay Curve
Current
Overcurrent Cold load
Pickup Level Pickup Level
92 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
The Cold Load Pickup feature in the following settings should be enabled.
Selects the relays required to operate when the feature generates a Trip.
ENHANCED TECHNOLOGY 93
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
94 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ENHANCED TECHNOLOGY 95
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
96 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
1) The same characteristics of fast and delay operations in the total number of the trip operations
and identical basic Time Current Curves should be set for all Reclosers connected in series.
2) The identical reclose interval time should be set for all Reclosers in series.
3) To coordinate the protection characteristics, an additional delay operation time (at least 100 ms)
should be applied to the Time Current Curve characteristics of Back-up Recloser, not to those
of Down-line Reclosers.
4) The reset time of Back-up Recloser should be set longer than any reclose interval time of all
Down-line Reclosers. This setting will prevent the reset operation of Back-up Recloser during
the reclose operation of Down-lines.
ENHANCED TECHNOLOGY 97
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
Starting
Reset Time
Counter
Close
Close
Down line EVR 2
Lockout Status
Open
Time
Faulted
98 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
ANSI/IEEE
Trip Time(Sec) = TD ( / (M-1) + )
IEC
Trip Time(Sec) = TD ( / (M-1))
ESB
Trip Time(Sec) = TD ( / (M-1) + )
USER-DEFINED
Trip Time(Sec) = TD ( / (M-1) + )
Reset Time(Sec) = TD (Rt / (1-M2))
Recloser clearing time curves are used when rated voltage of recloser is 15 or 27,
otherwise which added 30(4) are used when it is 38.
ENHANCED TECHNOLOGY 99
RECLOSER CONTROL EVRC2A http://www.entecene.co.kr
1) USER CURVE 1
PRIMARY SETTING / PROTECTION / USER CURVE SET / USER CURVE 1 / Factor a
[USER CURVE 1] Range 0.0000 ~ 150.9999
>Factor a: 59.5000
Factor b: 2.0000 Default 59.5000 Step 0.0001
Factor r: 1.8000
2) USER CURVE 2, 3, 4 :
USER CURVE 2 ~ 4, the same as USER CURVE 1 above
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI MODERATELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
13.00
2 2
11.00
TIME(SECONDS)
9.00
7.00
1 1
0.9 0.9
0.8
5.00 0.8
0.7 4.00 0.7
0.6 0.6
0.5 3.00 0.5
0.4 0.4
2.00
0.3 0.3
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08
0.05 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
6k
8k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI NORMALLY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
13.00
2 11.00 2
9.00
TIME(SECONDS)
7.00
1 1
0.9 5.00 0.9
0.8 0.8
0.7 4.00 0.7
0.6 0.6
3.00
0.5 0.5
0.4 0.4
2.00
0.3 0.3
0.2 0.2
1.00
0.1 0.1
0.09 0.50 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
15.00
13.00
1
11.00 1
0.9 9.00 0.9
0.8 0.8
0.7 7.00 0.7
0.6 0.6
0.5 5.00 0.5
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 70
RECLOSER CLEARING TIME CURVE
60 60
: ANSI EXTREMELY INVERSE
50 50
CURVES ARE AVERAGE CLEARING TIME
40 VARIATIONS 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 15.00 0.6
0.5 13.00 0.5
11.00
0.4 0.4
9.00
0.3 0.3
7.00
4.00
3.00
0.1 0.1
0.09 0.09
0.08 2.00 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.03 0.03
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
6k
7k
8k
9k
1k
2k
3k
4k
5k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI SHORT TIME INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 15.00 1
0.9 13.00 0.9
0.8 0.8
0.7 11.00 0.7
0.6 9.00 0.6
0.5 7.00 0.5
0.4 0.4
5.00
0.3 0.3
4.00
2.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 1.00 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.50
0.03 0.03
0.02 0.02
0.01 0.01
1k
3k
4k
5k
10k
100
200
300
400
500
600
700
800
900
2k
6k
7k
8k
9k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI SHOTR TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 15.00 0.7
0.6 13.00 0.6
11.00
0.5 0.5
9.00
0.4 0.4
7.00
0.3 0.3
5.00
0.2 4.00 0.2
3.00
0.04 0.04
0.03 0.03
0.50
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC STANDARD INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 1 2
TIME(SECONDS)
0.8
0.7
0.6
1 0.5 1
0.9 0.9
0.8 0.4 0.8
0.7 0.7
0.6 0.3 0.6
0.5 0.5
0.3 0.3
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
500
600
700
800
400
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1.00
0.4 0.4
0.8
0.3 0.7 0.3
0.6
0.5
0.2 0.2
0.4
0.3
0.1 0.1
0.09 0.2 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.1
0.04 0.04
0.03 0.03
0.05
0.02 0.02
0.01 0.01
4k
6k
7k
9k
1k
2k
3k
5k
8k
100
200
300
400
500
600
700
800
900
10k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC EXTREMELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08
1.00 0.08
0.07 0. 8 0.07
0.06 0. 7 0.06
0.05 0.6 0.05
0.3
0.02 0.02
0. 2
0.1
0.05
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC LONG TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
1.00
4 4
0.8
3 0. 7 3
0. 6
0. 5
2 2
0. 4
TIME(SECONDS)
0. 3
1 1
0.9 0.2 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.1
0.4 0.4
0.3 0.3
0.05
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
300
200
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC SHORT TIME INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
1.00
0.3 0.3
0.8
0.7
0.2 0.6 0.2
0.5
0.4
0.04 0.04
0.1
0.03 0.03
0.02 0.02
0.05
0.01 0.01
4k
200
400
500
600
700
1k
2k
3k
5k
6k
7k
8k
9k
10k
100
300
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ESB INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 15.00 3
13.00
2
11.00 2
9.00
TIME(SECONDS)
7.00
1 5.00 1
0.9 0.9
0.8 4.00 0.8
0.7 0.7
0.6 3.00 0.6
0.5 0.5
0.3 0.3
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
100
200
300
400
500
600
700
800
900
10k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ESB VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS 5% 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
15.00
TIME(SECONDS)
13.00
11.00
1 9.00 1
0.9 0.9
0.8 7.00 0.8
0.7 0.7
0.6 0.6
5.00
0.5 0.5
4.00
0.4 0.4
3.00
0.3 0.3
2.00
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ESB LONG TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 15.00 7
6 6
13.00
5 11.00 5
4 9.00 4
3 7.00 3
5.00
2 2
4.00
TIME(SECONDS)
3.00
1 1
0.9 2.00 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1.00
0.4 0.4
0.3 0.3
0.50
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
300
200
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : D1, D2 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 D2 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 D1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
4k
200
400
500
600
700
1k
2k
3k
5k
6k
7k
8k
9k
10k
100
300
800
900
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : A, B, C, D, E 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 C 0.09
0.08 0.08
0.07 0.07
B
0.06 D E 0.06
0.05 0.05
A
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
8k
1k
2k
3k
4k
5k
6k
7k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : KP, L, M, N 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
KP
0.1 0.1
0.09 L 0.09
0.08 M 0.08
0.07 0.07
N
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
10k
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
100
200
300
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : P, R, T, V 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
V
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1
T 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 R 0.06
0.05 P 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
2k
4k
5k
6k
7k
100
200
300
400
500
600
700
800
900
1k
3k
8k
9k
10k
100
300
200
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : W, Y, Z 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
Z
0.4 0.4
0.3 0.3
W
0.2 0.2
Y
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
4k
200
400
500
600
700
1k
2k
3k
5k
6k
7k
8k
9k
10k
100
300
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
6k
7k
8k
9k
5k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : 1, 2, 3, 4, 5 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 3 0.9
0.8 0.8
0.7 0.7
0.6 0.6
2
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 4 0.07
0.06 1 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
500
600
700
800
400
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 60
: 6, 7, 8, 8*, 9
50 CURVES ARE AVERAGE CLEARING TIME 50
30 7 30
20 20
10 10
9 9
8 8
7 7
6 6
5 9 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
8
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 8* 0.05
6
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
6k
7k
10k
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
8k
9k
22) Non Standard Curves (11, 13, 14, 15, 16, 17, 18)
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 70
RECLOSER CLEARING TIME CURVE
60 60
: 11, 13, 14, 15, 16, 17, 18
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 11 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 18 0.6
0.5 0.5
14
0.4 0.4
0.3 0.3
0.2 0.2
13
0.1 0.1
0.09 0.09
0.08 17 16 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04
15 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
Figure 5-31. Non Standard Curves (11, 13, 14, 15, 16, 17, 18)
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : F, H, J, KG 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
F J
0.1 KG 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
H
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
Selects the relays required to operate when the feature generates a Trip.
Selects the relays required to operate when the feature generates a Trip.
The underfrequency load shedding element is activated to trip when the distribution system
frequency drops below a specified frequency pickup for a specified time.
The underfrequency minimum voltage and underfrequency minimum current are used to prevent
incorrect operation when the recloser is closed by a local/remote control and the underfrequency
load shedding is disabled from tripping for cold load pickup during periods.
The underfrequency load shedding element should be enabled to the following settings.
Selects the relays required to operate when the feature generates a Trip.
When either or both of the synchronism check voltages are de-energized, the synchronism check
can allow for local/remote close.
If EVRC2A is the type of CVD, the synchronism check voltage input VL is connected to load
side(VR phase) in recloser. The other synchronizing phase can be connected for phase-neutral
voltage Vr, Vs or Vt; for phase-phase voltages Vab or Vcb. on load side in recloser.
mZ (1-m)Z
IA
IF L
O
VA A
RF
D
6. METERING
The following values are contained in the metering elements of EVRC2A.
y Current
y Voltage
y Frequency
y Synchronism Voltage
y Power
y Energy
y Demand
y System.
6.1.2. Voltage
The following values are contained in the voltage metering.
VA-N : Displays the measured A-N RMS voltage and phasor(, deg)
VB-N : Displays the measured B-N RMS voltage and phasor(, deg)
VC-N : Displays the measured C-N RMS voltage and phasor(, deg)
VA-B : Displays the measured A-B RMS voltage and phasor(, deg)
VB-C : Displays the measured B-C RMS voltage and phasor(, deg)
VC-A : Displays the measured C-A RMS voltage and phasor(, deg)
VAP : Displays the calculated average of the RMS phase voltage()
VAL : Displays the calculated average of the RMS line voltage()
V1 : Displays the calculated positive sequence RMS voltage and phasor(, deg)
V2 : Displays the calculated negative sequence RMS voltage and phasor(, deg)
V0 : Displays the calculated zero sequence RMS voltage and phasor (kV, deg)
6.1.3. Frequency
The following values are contained in the frequency metering.
y Frequency()
y Frequency decay rate(/Sec)
6.1.5. Power
The following values are contained in the power metering.
y Real power(MW)
y Reactive power(Mvar)
y Apparent power(MVA)
y Power factor(%)
6.1.6. Energy
The following values are contained in the energy metering.
y Positive watthour(MWh)
y Negative watthour(MWh)
y Positive varhour(Mvar)
y negative varhour(Mvar)
The updated rate of the energy meters is based on the Time Constant setting MAIN MENU /
SETTING / MONITORING / DEMAND The meters will update every 1/15 of the Demand
Constant. For example : if the Demand Constant is set to 15 minutes, the energy meters will update
every 1 minute (15min 1/15 = 1 min)
The watt-hour and VAR-hour meters can be reset to 0 through PRIMARY SETTING / RELAY
SETUP / CLEAR SAVED DATA / MAX DEMAND
6.1.7. Demand
The following values are contained in the demand metering.
Actual demand & maximum demand with Value (Current, Real power, Reactive power) and Date
(Year/Month/Date Hour:Minute,Second)
Energy value & start date (Year/Month/Date Hour:Minute,Second)
During each demand value, the EVRC2A also captures and stores maximum values for the
measurements listed below. It functions as a standard maximum meter. When a new maximum
value is determined, the old value is replaced. A time stamp in the following format (Date:
Year/Month/Day and Time: Hour:Minute,Second), is placed with the latest maximum values.
The Max demand meters can be reset to 0 through PRIMARY SETTING / RELAY SETUP /
CLEAR SAVED DATA / MAX DEMAND
6.1.8. System
The following values are contained in the system metering.
y Board power(12, +5V)
y Temperature()
y Battery voltage(V)
y Gas pressure(Bar)
6.2. Accuracy
The harmonic components of current and voltage are removed from input voltage and current
parameters, so all measurements based on these quantities respond to the fundamental component
only.
POWER Phase A, B, C
Rate 0.05 0.02 -1.00 to 1.00
FACTOR 3 Phase
Phase A, B, C
3REAL POWER MW 3% 2% 320.00 to 320.00
3 Phase
3REACTIVE Phase A, B, C
Mvar 3% 2% 320.00 to 320.00
POWER 3 Phase
3APPARENT Phase A, B, C
MVA 3% 2% 320.00 to 320.00
POWER 3 Phase
Phase A, B, C
WATT-HOURS MW/h 5% 3% 32000 to 32000
3 Phase
If the VT connection type is set to delta, all single phase voltage quantities are displayed as zero.
7. MONITORING
EVRC2A has Monitoring function for following items and also has functions for user to output
Alarm signal or Trip signal.
y DEMAND
y SYNCHRO LINE
y TRIP COUNTER
y RECLOSER WEAR
7.1. Demand
7.1.1. Description
EVRC2A is programmed to monitor following items to be operated as user sets.
y Phase Current demand value
y Ground current demand value
y Negative sequence current demand value
2) Pickup Setting
PRIMARY SETTING / MONITORING / TRIP COUNTER / Pickup(%)
[RECLOSER WEAR] Range 0.0 ~ 50.0 %
Function: ALARM
>Pickup(%): 20.0 Default 20.0 Step 0.1
Rated Volt(kV): 15
NOTE
1) The rated voltage determines the Recloser type.
8. EVENT RECORDER
EVRC2A has recording and maintenance function for following items.
y FAULT CYCLE WAVEFORM CAPTURE
y SYSTEM EVENT RECORDER
y DIAGNOSTIC EVENT RECORDER
y LOAD PROFILE
Move to MAIN MENU / EVENT RECORDER / FAULT CYCLE to see Fault cycle summary.
MAIN MENU / EVENT RECORDER / FAULT CYCLE
[NO-01]TARGET0x00003
IA: 0 IB: 549
IC: 0 IG: 548 Fault cycle summary display.
02/01/14 19:51:58
REAC POW(Mvar)[0001]
A: 0 B: 0
C: 0 G: 0
02/01/22 21:45:00
9. COMMUNICATION
9.1. OVERVIEW
EVRC2A has three ports for communication.
The EVRC2A has the front panel RS232 port, the side panel RS232 port, and the side panel
RS485/422 port.
Each data byte is transmitted in an asynchronous format consisting of 1 start bit, 8 data bits, 1 stop
bit, and no parity bit.
The baud rate is independently programmable for communications port 2. Baud rates of 1200, 2400,
4800, 9600, and 19200 are available.
COM 2 RS-232 1200 - 19200 bps No parity 8 1 User Interface Side Panel
RS-485
COM 3 1200 - 19200 bps None, Odd, Even 7, 8 1, 2 User Interface Side Panel
RS-422
COM 1
A port to interface with Interface Software.
COM 2 Option
A port to remotely operate with DNP Protocol, user can change Interface Speed and DNP Protocol.
A complete description of DNP services is in Appendix F. DNP 3.0 DEVICE PROFILE
COM 3 Option
MODBUS (Communication Protocol)
Option
PRIMARY SETTING/RELAY SETUP/COMMUNICATION / REMOTE METHOD / Select
[REMOTE METHOD] Range DNP3.0, MODBUS
>Select: DNP3.0
Default DNP3.0 Step
DNP 3.0
Move to PRIMARY SETTING / RELAY SETUP / COMMUNICATION / COMM SETTING /
DNP 3.0-COM2 to select setting for DNP Protocol.
(Please refer to 9.2. RTU Communication Setup (DNP 3.0 Protocol) - Option for more detail)
MODBUS
Move to PRIMARY SETTING / RELAY SETUP / COMMUNICATION / COMM SETTING /
MODBUS-COM3 to select setting for MODBUS Protocol.
(Please refer to 9.3. RTU Communication Setup (MODBUS Protocol) - Option for more detail)
10. INSTALLATION
Outer Cover
It is for blocking the direct ray of light to delay raising temperature inside of Control Cubicle. The
gap between control cubicle and cover is 10mm.
Air Vent
To protect control part from humidity by temperature fluctuation, Vents are on left and right side
covered with Outer Cover.
y EVRC2A has Small size and Large size depending on Recloser Type.
y Small size is available for EVR1, EVR2, Large size is available for EVR3.
y Large size is able to make User available Space larger, the space unit is referred to Figure
10-6
y Standard for EVR1, EVR2 is small size and for EVR3 is large size.
y EVR1 (Recloser Rated Voltage : 15.5) / EVR2 (27) / EVR3 (38)
y For installation on a Pole, the lifting hole is indicated.
y Weight of EVRC2A small size is 85 and large size is 90.
y EVRC2A should be fixed top and bottom with 16(5/8") Bolt.
y There is an Exit hole for external cable that can be connected to additional functioning
hardware.
y The diameter of the hole is 22(0.866") and two of Standard Receptacle "MS22" Series can
be extended.
y Shows base plate measurements that can be attached in User Available Space.
y On Base plate, 10/M6 Nut is used to fix the base plate.
y Available space for height of base plate is from 101.6 (4) to 177.8 (7)
y 30W DC Power is provided. In case of the necessity of larger than 30W, additional power
should be attached. For more details, contact manufacturer. Input of the additional power is
referred to Figure 10-7. Terminal Block and Fuses
y Remove cable coating at the end of cable length of 8mm(0.315). With using () CN5
connector terminal on side panel should be connected to Wire size AWG24 up to 12.
y To change Voltage ratings, disconnect Jumper Pin in JP3 Figure 10-31, and connect Jumper
Pin to either JPI (24Vdc) or JP2 (15Vdc). Be sure of the voltage rating due to disassembly.
y When overload, automatically circuit breaks current. In case long-term overload time, there is a
fuse on analog circuits to protect circuits from failure.
NOTE :
1) I/O Terminal (CN10, CN9) has functions to
control basic operation of Recloser and can be
connected with SCADA System for use.
2) Remove the coating of cable length of 8
(0.315"). Side panel connector for user should be
connected to Wire size AWG24 to 12 Figure 10-10. Side Panel
Recloser Phase should match with User system. Refer to Figure 10-15
CT Phase rotation must be arranged comparing with Voltage Inputs Phase rotation.
y CVD (Capacitor Voltage Divider) measures Voltage with using Capacitor installed in each
Bushing of Recloser.
y CVD Type is Optional type. VT (Voltage Transformer) Type is Standard. CVD Type and VT
Type are not exchangeable.
y Current Inputs and Voltage Inputs should be the same phase. If CT Inputs changed Phase
rotation, Voltage Inputs phase should be re-arranged.
y Option CVD 15, 27, 38 Class
Standard
y CVD Type can not be used when VT(Voltage Transformer) Type was selected. VT Type is
Standard
y VT wiring should match Current Inputs.
y For Load Side VT wiring, refer to Figure 10-14
y Voltage Inputs VA, VB, VC and VL Load side
Input Voltage Range : Vphase-Vcom Continuous < 300V
Burden : 0.6VA(300V), 0.2VA(220V), 0.05VA(120V), 0.02VA(67V)
y For Metering accuracy, phase rotations of User system and Recloser should be the same.
y Figure 10-15 shows the same phase rotation between User System and Recloser.
y If the phase rotation is not the same in User system and Recloser, correct CT and CVD wiring
in side panel to be matched.
y EVR Recloser phase A is the Bushing the nearest from Trip lever on the side.
A AC Power Input
B AC Power Input (Neutral)
C not connected
10.21. FUSES
Table 10-4. Fuses
Rating /
Positions Dimensions Purpose
External AC - Power Input
voltage.
10.25. COMMUNICATIONS
1) RS232 Pin Functions for Port1 and Port2
Table 10-6. RS232 Pin Functions for Port1 and Port2
Pin Serial Port1 Serial Port2 Definition
1 N/C DCD Data Carrier Detect
2 RXD RXD Receive Data
3 TXD TXD Transmit Data
4 N/C DTR Data Terminal Ready
5 GND GND Ground
6 N/C DSR Data Set Ready
7 N/C RTS Request To Send
8 N/C CTS Clear To Send
9 N/C N/C No Connection
Positions User Interface Panel(Male) Side Panel (Male)
Cable CC201 CC201,202,203
y Recloser Trip and Close Power is charged from C1, C2, C3 in UPS module.
y C1 is used for Trip power, C2, C3 are used for Close power.
y Trip(Close) runs when IGBT is ON. MC runs and the charged Capacitor transfer the Power
to TC(CC), eventually Recloser runs.
y F1, F2 are Fuses to protect IGBT from MC damage. These are on Analog Board.
y UPS Module charges Capacitor for Trip/Close. Its rated output voltage is 120Vdc.
y Trip and Close Capacitor are individually located and do not affect to each other during Trip
and Close.
y UPS Module runs by 120Vac Power or by Backup Battery.
y Transformer in EVRC2A connected with External AC Power generates 120Vac.
y Sealed lead-acid Type is used for Battery. Battery voltage does not run under 20Vac, runs over
20Vdc.
Indicates Firmware Upgrade Port, RTC(Real Time Clock), and main parts location. Also indicates
backup battery type.
y JP1, JP2, JP3 are Jumper Connecter, defining User Available DC Power Output Rating.
y F1, F2 are use to protect IGBT for Close and Trip.
y F3 is for Relay Module protection.
y JP1, JP2, JP3 are Jumper Connectors and define User Available DC Power rating.
Figure 10-35. Pressure Changes depending on Temperature and Sensor Output voltage
Figure 10-36. User Interface Panel Figure 10-37. Recloser Test Kit
Weigh Body (11), Aluminum case (6), Cable (2), Total weight (19)
Ammeter/Voltage 1% (3 digit)
System : -25+70(-13+158)
Operating Temperature
LCD : 0+70(+32+158)
11. MAINTANANCE
11.1. Warning Events
In control panel warning led if is lighted up bellow table refer and inspects.
1. Check AC supply
1. No problem
SLEEP MODE SLEEP MODE Panel sleep mode
2. Refer to Panel sleep time
POWER DOWN
POWER DOWN Power down mode No problem
MODE
4. Replace Recloser.
4. Replace Recloser
A/D converter
FAIL
SYSTEM RESTART
A/D converter
FAIL
Parallel EEPROM
MEMORY P-ROM FAIL Replace Main Processing Module
FAIL
Serial EEPROM
COMMUNICATION S-ROM FAIL Replace Main Processing Module
FAIL
Communication
Board FAIL
check
check
OPERATION FAIL Operation Fail
- Figure 10-8 - Figure 10-9
4. Replace Recloser
check