MEMORIA DESCRIPTIVA DEL PROYECTO DE 2 NIVELES

1. UBICACIN DEL PROYECTO.-

- Departamento LAMBAYEQUE
- Provincia CHICLAYO
- Distrito CHICLAYO

2. USO DE LA EDIFICACION .-

- Uso : VIVIENDA

3. SISTEMA CONSTRUCTIVO .-

- Sistema APORTICADO

4 . ALTURA TOTAL .-

- H= 19.05 m ( Medido desde el terreno natural)

5 . ESTUDIO DE SUELO .-

- Suelo arcilloso - limoso


6 . CARACTERISTICAS DE LOS MATERIALES .-

CONCRETO ARMADO
- f'c = 210 kg/cm2

ACERO DE REFUERZO
- f'y = 4200 kg/cm2 ( Acero grado 60)
- E = 2173706.511928 kg/cm2

7. SOBRECARGA .-
NORMA E-020
SOBRECARGA PRIMEROS PISOS 200 Kg/m
SOBRECARGA AZOTEA 100 Kg/m
LOSA ALIGERADA (20cm) 300 Kg/m
PESO MUERTO 100 Kg/m
PESO TABIQUERIA EQ. 0 Kg/m
PESO ESPECIFICO DE MURO DE ALBAILERIA: 1350 Kg/m
"DISEO ESTRUCTURAL DE VIVIENDA MULTIFAMILIAR -
2 NIVELES "

CARACTERISTICAS DE LA EDIFICACION

CARACTERISTICAS GEOMETRICAS DE LA ESTRUCTURA

Largo = 19.70 m
Ancho = 10.00 m
N De Prticos X-X = 7
N De Prticos Y-Y = 3
N De Pisos = 2 Pisos
Altura Entre Piso (1 Piso) = 2.500 m
Altura Entre Piso (2 Piso) = 2.500 m
Ancho de Tabiqueria = 0.15 m

CARACTERISTICAS DEL CONCRETO Y ACERO DE REFUERZO

Resistencia a la Compresion = 210 Kg/cm


Peso Especifico del Concreto = 2400 Kg/m
Esfuerzo de Fluencia del Ace = 4200 Kg/cm
Peso Espec. del Muro de Alba = 1800 Kg/m

PESO POR METRO CUADRADO (RNE - E.020 CARGAS)

Vivienda S/C = 200 Kg/m


S/C azotea = 100 Kg/m

CALCULO DE TABIQUERIA EQUIVALENTE


(Tabiquera mnima segn Norma E-0.20)
Tabiquera Equivalente Azotea = 100 Kg/m
Tabiquera Equivalente 1 - 2 Nivel = 168 Kg/m

Peso Tab. Equiv. = (Long.Tab.*e*h*y)/(area techada)

TRAMO LONGITUD Tabiqueria Equivalente


entre eje 1 - 2 3.80 m Long. Tabiq. 44.85 m
entre eje 2 - 3 6.80 m e 0.15 m
entre eje 3 - 4 7.10 m h 2.50 m
entre eje 4 - 5 5.50 m 1800 Kg/m
entre eje 5 - 6 7.30 m Area Techada 179.77 m
entre eje 6 - 7 5.10 m Peso T.E. 168 Kg/m
entre eje A - B 4.25 m 01 PISO - 02 PISO
entre eje B - C 5.00 m
Long. Tabiq. 44.85 m

PREDIMENSIONAMIENTO DE ELEMENTOS ESTRUCTURALES

PREDIMENSIONAMIENTO DE LOSA MACIZA

Tomamos a criterio la luz libre mas larga en cada direccin (Asumiendo columnas de 0.30m x 0.30m)

Direccin X = Ln= 5.125 m TIPO DE LOSA: LOSA EN UNA DIRECCION

Direccin Y- = Ln= 3.750 m PERALTE DE LOSA: L/25

Peralte de la losa Maciza:

H= 0.205 m Adoptamos un H= 0.20 m


En el analisis de cada pao determinamos el espesor maximo que es
0.2005 cm, por tanto elejimos un espesor de 20cm bajo el criterio de
seguridad y economia.

Espesor de la losa: e = 0.200 m

2. PREDIMENSIONAMIENTO DE VIGAS

Determinacin de Wu:
Sobrecarga = 200 Kg/m
P. Aligerado: 300 Kg/m
P. Acabados: 100 Kg/m
Tabiquera equiv.: 168 Kg/m
WD = 568 Kg/m
WL = 200 Kg/m
Wu = 1135.76 kg/cm

=_/((4/) ) 4/(_ )
Usaremos Wu = 0.11 Kg/cm Donde: = 12.06

PAO 1 PAO 2 PAO 3 PAO 4


Lado A= 4.50 m Lado A= 5.25 m Lado A= 4.50 m Lado A= 5.25 m
Lado B= 2.15 m Lado B= 2.15 m Lado B= 3.65 m Lado B= 3.65 m
Ln A= 0.37 m Ln A= 0.44 m Ln A= 0.37 m Ln A= 0.44 m
Ln B= 0.18 m Ln B= 0.18 m Ln B= 0.30 m Ln B= 0.30 m

PAO 5 PAO 6 PAO 7 PAO 8


Lado A= 4.50 m Lado A= 5.25 m Lado A= 4.50 m Lado A= 5.25 m
Lado B= 3.80 m Lado B= 3.80 m Lado B= 3.00 m Lado B= 3.00 m
Ln A= 0.37 m Ln A= 0.44 m Ln A= 0.37 m Ln A= 0.44 m
Ln B= 0.32 m Ln B= 0.32 m Ln B= 0.25 m Ln B= 0.25 m

PAO 9 PAO 10 PAO 11 PAO 12


Lado A= 4.50 m Lado A= 5.25 m Lado A= 4.50 m Lado A= 5.25 m
Lado B= 3.90 m Lado B= 3.90 m Lado B= 2.80 m Lado B= 2.80 m
Ln A= 0.37 m Ln A= 0.44 m Ln A= 0.37 m Ln A= 0.44 m
Ln B= 0.32 m Ln B= 0.32 m Ln B= 0.23 m Ln B= 0.23 m
Se optar por un ancho mnimo de 25cm, ya que es un modelo sismoresistente. El valor del peralte
maximo en direccion "X" es 0.44 m; y el valor del peralte en la direccion "Y" es 0.32 m.

DIMENSIONES DE LA VIGA:
EJE X-X bxh= 0.25 m x 0.45 m
EJE Y-Y bxh= 0.25 m x 0.35 m

PREDIMENSIONAMIENTO DE COLUMNAS

P
bxD=
nxfc

Donde: TIPO - VALORES DE C P n


C1 Columnas Interiores 1.10xPG 0.30
C2,C3Columnas extremas de 1p.25xPG 0.25 f'c = 210 Kg/cm
C4 Columnas Esquinas 1.50xPG 0.20

DATOS A USAR
N De Pisos = 2 Pisos
Altura Primer Piso (1 = 2.50 m VIGAS X-X 0.25 m x 0.45 m
Altura Entre Piso (2 P = 2.50 m VIGAS Y-Y 0.25 m x 0.35 m
Peso Unitario losa = 480 Kg/m VIGA X-Y 0.25 m x 0.20 m
Pisos y Acabados = 100 Kg/m V. CHATAS 0.20 m x 0.20 m
Ancho de Tabiqueria = 0.150 m COLUMNAS 0.25 m x 0.25 m
Espesor de Losa = 0.200 m
Vivienda S/C = 200 Kg/m

AREA TRIBUTARIA MAS DESFAVORABLE SEGN EL TIPO DE COLUMNA

Col. VIGA X-X VIGA Y-Y VIGA X-Y VIGA CH A.T. 1NIVEL A.T. 2NIVEL
3-C (Col. Exterior) 2.56 3.48 0.00 0.00 10.47 10.47
C-7 (Col. Esquina) 2.56 1.28 0.00 0.00 4.29 4.29
3-B(Col. Interior) 4.50 3.48 0.00 0.00 17.69 17.69

COLUMNAS INTERIORES PPRIMER NIVEL


ARE
A
TRIB
UTA
COLUMNA : C1 EJE 3-B(Col. Interior) RIA = 17.690m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 8491.20 kg
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 2978.98 kg
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.97 0.15 m 2.50 4029.75 kg
PESO PISOS Y ACABADOS 100 Kg/m 1769.00 kg
PESO DE VIGA X-X 2400 Kg/m 4.50 0.25 0.45 1215.00 kg
PESO DE VIGA Y-Y 2400 Kg/m 3.48 0.25 0.35 730.80 kg
PESO DE VIGA X-Y 2400 Kg/m 0.25 0.20 0.00 kg
PESO DE VIGA CHATA 2400 Kg/m 0.20 0.20 0.00 kg
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25 0.25 375.00 kg
TOTAL = 19589.73 kg

CM= 19589.73 kg CV= 3538.00 kg PU= 23127.73 kg

ARE
COLUMNAS INTERIORES 2 NIVEL A
TRIB
UTA
COLUMNA : C1 EJE 3-B(Col. Interior) RIA = 17.690m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 8491.20 kg
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 2978.98 kg
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.97 0.15 2.50 4029.75 kg
PESO PISOS Y ACABADOS 100 Kg/m 1769.00 kg
PESO DE VIGA X-X 2400 Kg/m 4.50 0.25 0.45 1215.00 kg
PESO DE VIGA Y-Y 2400 Kg/m 3.48 0.25 0.35 730.80 kg
PESO DE VIGA X-Y 2400 Kg/m 0.25 0.20 0.00 kg
PESO DE VIGA CHATA 2400 Kg/m 0.20 0.20 0.00 kg
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25 0.25 375.00 kg
TOTAL = 19589.73 kg

CM= 19589.73 kg CV= 3538.00 kg PU= 23127.73 kg

ARE
COLUMNAS EXTERIORES PRIMER NIVEL A
TRIB
UTA
COLUMNA : C3 EJE 3-C (Col. Exterior) RIA = 10.470m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 5025.60 kg
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 1763.14 kg
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 6.04 0.15 m 2.50 4077.00 kg
PESO PISOS Y ACABADOS 100 Kg/m 1047.00 kg
PESO DE VIGA X-X 2400 Kg/m 2.56 0.25 0.45 691.20 kg
PESO DE VIGA Y-Y 2400 Kg/m 3.48 0.25 0.35 730.80 kg
PESO DE VIGA X-Y 2400 Kg/m 0.25 0.20 0.00 kg
PESO DE VIGA CHATA 2400 Kg/m 0.20 0.20 0.00 kg
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25 0.25 375.00 kg
TOTAL = 13709.74 kg

CM= 13709.74 kg CV= 2094.00 kg PU= 15803.74 kg


ARE
COLUMNAS EXTERIORES 2 NIVEL A
TRIB
UTA
COLUMNA : C3 EJE 3-C (Col. Exterior) RIA = 10.470m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 5025.60 kg
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 1763.14 kg
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 6.04 0.15 m 2.50 4077.00 kg
PESO PISOS Y ACABADOS 100 Kg/m 1047.00 kg
PESO DE VIGA X-X 2400 Kg/m 2.56 0.25 0.45 691.20 kg
PESO DE VIGA Y-Y 2400 Kg/m 3.48 0.25 0.35 730.80 kg
PESO DE VIGA X-Y 2400 Kg/m 0.25 0.20 0.00 kg
PESO DE VIGA CHATA 2400 Kg/m 0.20 0.20 0.00 kg
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25 0.25 375.00 kg
TOTAL = 13709.74 kg

CM= 13709.74 kg CV= 2094.00 kg PU= 15803.74 kg

ARE
A
COLUMNAS ESQUINERAS PRIMER NIVEL TRIB
UTA
COLUMNA : C4 EJE C-7 (Col. Esquina) RIA = 4.290m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2059.20 kg
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 722.43 kg
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.84 0.15 m 2.50 2592.00 kg
PESO PISOS Y ACABADOS 100 Kg/m 429.00 kg
PESO DE VIGA X-X 2400 Kg/m 2.56 0.25 0.45 691.20 kg
PESO DE VIGA Y-Y 2400 Kg/m 1.28 0.25 0.35 268.80 kg
PESO DE VIGA X-Y 2400 Kg/m 0.25 0.20 0.00 kg
PESO DE VIGA CHATA 2400 Kg/m 0.20 0.20 0.00 kg
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25 0.25 375.00 kg
TOTAL = 7137.63 kg
CM= 7137.63 kg CV= 858.00 kg PU= 7995.63 kg ARE
A
COLUMNAS ESQUINERAS 2 NIVEL TRIB
UTA
COLUMNA : C4 EJE C-7 (Col. Esquina) RIA = 4.290m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2059.20 kg
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 722.43 kg
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.84 0.15 m 2.50 2592.00 kg
PESO PISOS Y ACABADOS 100 Kg/m 429.00 kg
PESO DE VIGA X-X 2400 Kg/m 2.56 0.25 0.45 691.20 kg
PESO DE VIGA Y-Y 2400 Kg/m 1.28 0.25 0.35 268.80 kg
PESO DE VIGA X-Y 2400 Kg/m 0.25 0.20 0.00 kg
PESO DE VIGA CHATA 2400 Kg/m 0.20 0.20 0.00 kg
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25 0.25 375.00 kg
TOTAL = 7137.63 kg

CM= ### CV= 858.00 kg PU= ###

CUADRO RESUMEN

COLUMNAS INTERIORES

NIVEL Pu PG P=1.1xPG n AREA (cm2) SECCION (cm)


1 23127.73 kg
69383.18 kg 76321.5 0.3 1211.45 34.81 x 34.81
2 23127.73 kg

ADOPTAR 35.00 x 35.00

COLUMNAS PERIMETRAL

NIVEL Pu PG P=1.25xPG n AREA (cm2) SECCION (cm)


1 15803.74 kg
47411.21 kg 59264.0 0.25 1128.84 33.60 x 33.60
2 15803.74 kg

ADOPTAR 35.00 x 35.00

COLUMNAS ESQUINERAS
NIVEL Pu PG P=1.50xPG n AREA (cm2) SECCION (cm)
1 7995.63 kg
23986.89 kg 35980.3 0.2 856.67 29.27 x 29.27
2 - 3 7995.63 kg
ADOPTAR 30.00 x 30.00

CORRELACION DE INERCIA 1.52 > 1.2 OK


17.690m
PARCIAL
8491.20 kg
2978.98 kg
4029.75 kg
1769.00 kg
1215.00 kg
730.80 kg
0.00 kg
0.00 kg
375.00 kg
19589.73 kg

17.690m
PARCIAL
8491.20 kg
2978.98 kg
4029.75 kg
1769.00 kg
1215.00 kg
730.80 kg
0.00 kg
0.00 kg
375.00 kg
19589.73 kg

10.470m
PARCIAL
5025.60 kg
1763.14 kg
4077.00 kg
1047.00 kg
691.20 kg
730.80 kg
0.00 kg
0.00 kg
375.00 kg
13709.74 kg

10.470m
PARCIAL
5025.60 kg
1763.14 kg
4077.00 kg
1047.00 kg
691.20 kg
730.80 kg
0.00 kg
0.00 kg
375.00 kg
13709.74 kg

4.290m
PARCIAL
2059.20 kg
722.43 kg
2592.00 kg
429.00 kg
691.20 kg
268.80 kg
0.00 kg
0.00 kg
375.00 kg
7137.63 kg
4.290m
PARCIAL
2059.20 kg
722.43 kg
2592.00 kg
429.00 kg
691.20 kg
268.80 kg
0.00 kg
0.00 kg
375.00 kg
7137.63 kg
METRADO DE CARGAS EN VIGAS

DEL PREDIMENSIONAMIENTO DE ELEMENTOS ESTRUCTURALES:

ESPESOR DE LOSA : 0.20 m

VIGAS X-X: 0.25 m x 0.45 m

VIGAS Y-Y: 0.25 m x 0.35 m

CARGAS

1- 2 PISO

CARGAS MUERTAS (CM) P.UNITARIO TOTAL


Peso de Losa 480 Kg/m2
Peso de Tabiqueria Equivalente 168 Kg/m2 798.40 Kg/m
Peso de Pisos y Acabados 150 Kg/m2
CARGA VIVA (CV) PESO TOTAL
Sobrecarga 200 Kg/m2 200.00 Kg/m

CARGA ULTIMA = 1.4xCm + 1.7xCv = 1457.76 Kg/m

Para determinar la carga ultima, utilizamos los factores de mayoracin de cargas, establecidos en
la norma tcnica de edificacin E-060 concreto armado:

Wu = 1.4*CM + 1.7*CV

1 PISO

VIGAS DIRECCION X-X

EJE 1-1

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 4.950m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 528.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 185.24 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 165.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 1823.24 kg
CM= 1823.24 kg/m CV= 220.00 kg/m Wu= 2.93 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 5.770m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 527.54 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 185.08 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 164.86 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 1822.48 kg

CM= 1822.48 kg/m CV= 219.81 kg/m Wu= 2.93 tn/m

EJE 2-2

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 12.300m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1312.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 460.29 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 410.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 3127.29 kg

CM= 3127.29 kg/m CV= 546.67 kg/m Wu= 5.31 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 14.370m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1313.83 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 460.93 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 410.57 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 3130.33 kg

CM= 3130.33 kg/m CV= 547.43 kg/m Wu= 5.31 tn/m

EJE 3-3

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 15.830m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1688.53 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 592.39 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 527.67 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 3753.59 kg

CM= 3753.59 kg/m CV= 703.56 kg/m Wu= 6.45 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 18.620m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1702.40 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 597.25 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 532.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 3776.65 kg

CM= 3776.65 kg/m CV= 709.33 kg/m Wu= 6.49 tn/m


EJE 4-4

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 14.450m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1541.33 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 540.75 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 481.67 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 3508.75 kg

CM= 3508.75 kg/m CV= 642.22 kg/m Wu= 6.00 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 16.900m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1545.14 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 542.08 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 482.86 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 3515.08 kg

CM= 3515.08 kg/m CV= 643.81 kg/m Wu= 6.02 tn/m

EJE 5-5

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 14.200m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1514.67 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 531.39 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 473.33 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 3464.39 kg

CM= 3464.39 kg/m CV= 631.11 kg/m Wu= 5.92 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 17.100m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1563.43 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 548.50 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 488.57 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 3545.50 kg

CM= 3545.50 kg/m CV= 651.43 kg/m Wu= 6.07 tn/m

EJE 6-6

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 12.350m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1317.33 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 462.16 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 411.67 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 3136.16 kg

CM= 3136.16 kg/m CV= 548.89 kg/m Wu= 5.32 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 15.200m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1389.71 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 487.56 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 434.29 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 3256.56 kg

CM= 3256.56 kg/m CV= 579.05 kg/m Wu= 5.54 tn/m

EJE 7-7

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 4.800m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 512.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 179.63 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 160.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 1796.63 kg

CM= 1796.63 kg/m CV= 213.33 kg/m Wu= 2.88 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 6.220m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 568.69 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 199.51 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 177.71 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 1890.91 kg

CM= 1890.91 kg/m CV= 236.95 kg/m Wu= 3.05 tn/m

VIGAS DIRECCION Y-Y

EJE A-A
TRAMO 1--2 Luz= 2.15 AREA TRIBUTARIA = 5.240m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1169.86 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 410.42 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 365.58 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.15 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.15 0.25 0.35 210.00 kg/m
TOTAL = 2830.87 kg

CM= 2830.87 kg/m CV= 487.44 kg/m Wu= 4.79 tn/m

TRAMO 2--3 Luz= 2.65 AREA TRIBUTARIA = 8.890m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1610.26 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 564.93 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 503.21 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.65 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.65 0.25 0.35 210.00 kg/m
TOTAL = 3563.40 kg

CM= 3563.40 kg/m CV= 670.94 kg/m Wu= 6.13 tn/m

TRAMO 3--4 Luz= 3.80 AREA TRIBUTARIA = 6.990m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 882.95 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 309.77 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 275.92 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.80 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.80 0.25 0.35 210.00 kg/m
TOTAL = 2353.63 kg

CM= 2353.63 kg/m CV= 367.89 kg/m Wu= 3.92 tn/m


TRAMO 4--5 Luz= 3.00 AREA TRIBUTARIA = 7.250m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1160.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 406.96 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 362.50 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.00 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.00 0.25 0.35 210.00 kg/m
TOTAL = 2814.46 kg

CM= 2814.46 kg/m CV= 483.33 kg/m Wu= 4.76 tn/m

TRAMO 5--6 Luz= 3.90 AREA TRIBUTARIA = 7.960m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 979.69 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 343.71 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 306.15 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.90 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.90 0.25 0.35 210.00 kg/m
TOTAL = 2514.55 kg

CM= 2514.55 kg/m CV= 408.21 kg/m Wu= 4.21 tn/m

TRAMO 6--7 Luz= 2.78 AREA TRIBUTARIA = 7.130m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1231.08 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 431.90 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 384.71 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.78 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.78 0.25 0.35 210.00 kg/m
TOTAL = 2932.69 kg

CM= 2932.69 kg/m CV= 512.95 kg/m Wu= 4.98 tn/m

EJE B-B
TRAMO 1--2 Luz= 2.30 AREA TRIBUTARIA = 10.540m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2199.65 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 771.71 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 687.39 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.30 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.30 0.25 0.35 210.00 kg/m
TOTAL = 4543.75 kg
CM= 4543.75 kg/m CV= 916.52 kg/m Wu= 7.92 tn/m

TRAMO 2--3 Luz= 2.65 AREA TRIBUTARIA = 16.150m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2925.28 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 1026.28 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 914.15 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.65 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.65 0.25 0.35 210.00 kg/m
TOTAL = 5750.71 kg

CM= 5750.71 kg/m CV= 1218.87 kg/m Wu= 10.12 tn/m

TRAMO 3--4 Luz= 3.80 AREA TRIBUTARIA = 18.280m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2309.05 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 810.09 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 721.58 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.80 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.80 0.25 0.35 210.00 kg/m
TOTAL = 4725.72 kg

CM= 4725.72 kg/m CV= 962.11 kg/m Wu= 8.25 tn/m

TRAMO 4--5 Luz= 3.00 AREA TRIBUTARIA = 13.770m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2203.20 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 772.95 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 688.50 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.00 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.00 0.25 0.35 210.00 kg/m
TOTAL = 4549.65 kg

CM= 4549.65 kg/m CV= 918.00 kg/m Wu= 7.93 tn/m

TRAMO 5--6 Luz= 3.90 AREA TRIBUTARIA = 18.520m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2279.38 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 799.68 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 712.31 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.90 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.90 0.25 0.35 210.00 kg/m
TOTAL = 4676.37 kg

CM= 4676.37 kg/m CV= 949.74 kg/m Wu= 8.16 tn/m

TRAMO 6--7 Luz= 2.78 AREA TRIBUTARIA = 10.030m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1731.80 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 607.57 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 541.19 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.78 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.78 0.25 0.35 210.00 kg/m
TOTAL = 3765.55 kg

CM= 3765.55 kg/m CV= 721.58 kg/m Wu= 6.50 tn/m

EJE C-C
TRAMO 1--2 Luz= 2.30 AREA TRIBUTARIA = 1.540m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 321.39 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 112.75 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 100.43 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.30 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.30 0.25 0.35 210.00 kg/m
TOTAL = 1419.58 kg

CM= 1419.58 kg/m CV= 133.91 kg/m Wu= 2.22 tn/m

TRAMO 2--3 Luz= 2.65 AREA TRIBUTARIA = 10.270m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1860.23 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 652.63 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 581.32 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.65 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.65 0.25 0.35 210.00 kg/m
TOTAL = 3979.17 kg

CM= 3979.17 kg/m CV= 775.09 kg/m Wu= 6.89 tn/m

TRAMO 3--4 Luz= 3.80 AREA TRIBUTARIA = 7.800m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 985.26 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 345.66 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 307.89 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.80 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.80 0.25 0.35 210.00 kg/m
TOTAL = 2523.82 kg

CM= 2523.82 kg/m CV= 410.53 kg/m Wu= 4.23 tn/m

TRAMO 4--5 Luz= 3.00 AREA TRIBUTARIA = 8.400m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1344.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 471.52 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 420.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.00 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.00 0.25 0.35 210.00 kg/m
TOTAL = 3120.52 kg

CM= 3120.52 kg/m CV= 560.00 kg/m Wu= 5.32 tn/m

TRAMO 5--6 Luz= 3.90 AREA TRIBUTARIA = 9.320m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1147.08 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 402.43 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 358.46 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.90 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.90 0.25 0.35 210.00 kg/m
TOTAL = 2792.97 kg

CM= 2792.97 kg/m CV= 477.95 kg/m Wu= 4.72 tn/m

TRAMO 6--7 Luz= 2.78 AREA TRIBUTARIA = 7.870m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1358.85 kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m 476.73 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 424.64 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.78 0.15 2.5 675.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.78 0.25 0.35 210.00 kg/m
TOTAL = 3145.22 kg

CM= 3145.22 kg/m CV= 566.19 kg/m Wu= 5.37 tn/m


RESUMEN 1 PISO

DIRECCION X-X

PORTICO TRAMO CM CV Wu
A-B 1823.24 kg/m 220.00 kg/m 2.93 tn/m
1--1
B-C 1822.48 kg/m 219.81 kg/m 2.93 tn/m
A-B 3127.29 kg/m 546.67 kg/m 5.31 tn/m
2--2
B-C 3130.33 kg/m 547.43 kg/m 5.31 tn/m
A-B 3753.59 kg/m 703.56 kg/m 6.45 tn/m
3--3
B-C 3776.65 kg/m 709.33 kg/m 6.49 tn/m
A-B 3508.75 kg/m 642.22 kg/m 6.00 tn/m
4--4
B-C 3515.08 kg/m 643.81 kg/m 6.02 tn/m
A-B 3464.39 kg/m 651.43 kg/m 5.96 tn/m
5--5
B-C 3464.39 kg/m 631.11 kg/m 5.92 tn/m
A-B 3136.16 kg/m 548.89 kg/m 5.32 tn/m
6--6
B-C 3256.56 kg/m 579.05 kg/m 5.54 tn/m
A-B 1796.63 kg/m 213.33 kg/m 2.88 tn/m
7--7
B-C 1890.91 kg/m 236.95 kg/m 3.05 tn/m

DIRECCION Y-Y

PORTICO TRAMO CM CV Wu
1--2 2830.87 kg/m 487.44 kg/m 4.79 tn/m
2--3 3563.40 kg/m 670.94 kg/m 6.13 tn/m
3--4 2353.63 kg/m 367.89 kg/m 3.92 tn/m
A--A
4--5 2814.46 kg/m 483.33 kg/m 4.76 tn/m
5--6 2514.55 kg/m 408.21 kg/m 4.21 tn/m
6--7 2932.69 kg/m 512.95 kg/m 4.98 tn/m
1--2 4543.75 kg/m 916.52 kg/m 7.92 tn/m
2--3 5750.71 kg/m 1218.87 kg/m 10.12 tn/m
3--4 4725.72 kg/m 962.11 kg/m 8.25 tn/m
B--B
4--5 4549.65 kg/m 918.00 kg/m 7.93 tn/m
5--6 4676.37 kg/m 949.74 kg/m 8.16 tn/m
6--7 3765.55 kg/m 721.58 kg/m 6.50 tn/m
1--2 1419.58 kg/m 133.91 kg/m 2.22 tn/m
2--3 3979.17 kg/m 775.09 kg/m 6.89 tn/m
3--4 2523.82 kg/m 410.53 kg/m 4.23 tn/m
C--C
4--5 3120.52 kg/m 560.00 kg/m 5.32 tn/m
C--C

5--6 2792.97 kg/m 477.95 kg/m 4.72 tn/m


6--7 3145.22 kg/m 566.19 kg/m 5.37 tn/m
as, establecidos en

4.950m
PARCIAL
528.00 kg/m
185.24 kg/m
165.00 kg/m
675.00 kg/m
270.00 kg/m
1823.24 kg
2.93 tn/m

5.770m
PARCIAL
527.54 kg/m
185.08 kg/m
164.86 kg/m
675.00 kg/m
270.00 kg/m
1822.48 kg

2.93 tn/m

12.300m
PARCIAL
1312.00 kg/m
460.29 kg/m
410.00 kg/m
675.00 kg/m
270.00 kg/m
3127.29 kg

5.31 tn/m

14.370m
PARCIAL
1313.83 kg/m
460.93 kg/m
410.57 kg/m
675.00 kg/m
270.00 kg/m
3130.33 kg

5.31 tn/m

15.830m
PARCIAL
1688.53 kg/m
592.39 kg/m
527.67 kg/m
675.00 kg/m
270.00 kg/m
3753.59 kg

6.45 tn/m

18.620m
PARCIAL
1702.40 kg/m
597.25 kg/m
532.00 kg/m
675.00 kg/m
270.00 kg/m
3776.65 kg

6.49 tn/m
14.450m
PARCIAL
1541.33 kg/m
540.75 kg/m
481.67 kg/m
675.00 kg/m
270.00 kg/m
3508.75 kg

6.00 tn/m

16.900m
PARCIAL
1545.14 kg/m
542.08 kg/m
482.86 kg/m
675.00 kg/m
270.00 kg/m
3515.08 kg

6.02 tn/m

14.200m
PARCIAL
1514.67 kg/m
531.39 kg/m
473.33 kg/m
675.00 kg/m
270.00 kg/m
3464.39 kg

5.92 tn/m

17.100m
PARCIAL
1563.43 kg/m
548.50 kg/m
488.57 kg/m
675.00 kg/m
270.00 kg/m
3545.50 kg

6.07 tn/m

12.350m
PARCIAL
1317.33 kg/m
462.16 kg/m
411.67 kg/m
675.00 kg/m
270.00 kg/m
3136.16 kg

5.32 tn/m

15.200m
PARCIAL
1389.71 kg/m
487.56 kg/m
434.29 kg/m
675.00 kg/m
270.00 kg/m
3256.56 kg

5.54 tn/m

4.800m
PARCIAL
512.00 kg/m
179.63 kg/m
160.00 kg/m
675.00 kg/m
270.00 kg/m
1796.63 kg

2.88 tn/m

6.220m
PARCIAL
568.69 kg/m
199.51 kg/m
177.71 kg/m
675.00 kg/m
270.00 kg/m
1890.91 kg

3.05 tn/m

5.240m
PARCIAL
1169.86 kg/m
410.42 kg/m
365.58 kg/m
675.00 kg/m
210.00 kg/m
2830.87 kg

4.79 tn/m

8.890m
PARCIAL
1610.26 kg/m
564.93 kg/m
503.21 kg/m
675.00 kg/m
210.00 kg/m
3563.40 kg

6.13 tn/m

6.990m
PARCIAL
882.95 kg/m
309.77 kg/m
275.92 kg/m
675.00 kg/m
210.00 kg/m
2353.63 kg

3.92 tn/m
7.250m
PARCIAL
1160.00 kg/m
406.96 kg/m
362.50 kg/m
675.00 kg/m
210.00 kg/m
2814.46 kg

4.76 tn/m

7.960m
PARCIAL
979.69 kg/m
343.71 kg/m
306.15 kg/m
675.00 kg/m
210.00 kg/m
2514.55 kg

4.21 tn/m

7.130m
PARCIAL
1231.08 kg/m
431.90 kg/m
384.71 kg/m
675.00 kg/m
210.00 kg/m
2932.69 kg

4.98 tn/m

10.540m
PARCIAL
2199.65 kg/m
771.71 kg/m
687.39 kg/m
675.00 kg/m
210.00 kg/m
4543.75 kg
7.92 tn/m

16.150m
PARCIAL
2925.28 kg/m
1026.28 kg/m
914.15 kg/m
675.00 kg/m
210.00 kg/m
5750.71 kg

10.12 tn/m

18.280m
PARCIAL
2309.05 kg/m
810.09 kg/m
721.58 kg/m
675.00 kg/m
210.00 kg/m
4725.72 kg

8.25 tn/m

13.770m
PARCIAL
2203.20 kg/m
772.95 kg/m
688.50 kg/m
675.00 kg/m
210.00 kg/m
4549.65 kg

7.93 tn/m

18.520m
PARCIAL
2279.38 kg/m
799.68 kg/m
712.31 kg/m
675.00 kg/m
210.00 kg/m
4676.37 kg

8.16 tn/m

10.030m
PARCIAL
1731.80 kg/m
607.57 kg/m
541.19 kg/m
675.00 kg/m
210.00 kg/m
3765.55 kg

6.50 tn/m

1.540m
PARCIAL
321.39 kg/m
112.75 kg/m
100.43 kg/m
675.00 kg/m
210.00 kg/m
1419.58 kg

2.22 tn/m

10.270m
PARCIAL
1860.23 kg/m
652.63 kg/m
581.32 kg/m
675.00 kg/m
210.00 kg/m
3979.17 kg

6.89 tn/m

7.800m
PARCIAL
985.26 kg/m
345.66 kg/m
307.89 kg/m
675.00 kg/m
210.00 kg/m
2523.82 kg

4.23 tn/m

8.400m
PARCIAL
1344.00 kg/m
471.52 kg/m
420.00 kg/m
675.00 kg/m
210.00 kg/m
3120.52 kg

5.32 tn/m

9.320m
PARCIAL
1147.08 kg/m
402.43 kg/m
358.46 kg/m
675.00 kg/m
210.00 kg/m
2792.97 kg

4.72 tn/m

7.870m
PARCIAL
1358.85 kg/m
476.73 kg/m
424.64 kg/m
675.00 kg/m
210.00 kg/m
3145.22 kg

5.37 tn/m
2 PISO

VIGAS DIRECCION X-X

EJE 1-1

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 4.950m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 528.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 110.00 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 165.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 1343.00 kg

CM= 1343.00 kg/m CV= 110.00 kg/m Wu= 2.07 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 5.770m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 527.54 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 109.90 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 164.86 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 1342.30 kg

CM= 1342.30 kg/m CV= 109.90 kg/m Wu= 2.07 tn/m

EJE 2-2

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 12.300m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1312.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 273.33 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 410.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 2535.33 kg

CM= 2535.33 kg/m CV= 273.33 kg/m Wu= 4.01 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 14.370m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1313.83 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 273.71 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 410.57 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 2538.11 kg

CM= 2538.11 kg/m CV= 273.71 kg/m Wu= 4.02 tn/m

EJE 3-3

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 15.830m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1688.53 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 351.78 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 527.67 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 3107.98 kg

CM= 3107.98 kg/m CV= 351.78 kg/m Wu= 4.95 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 18.620m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1702.40 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 354.67 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 532.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 3129.07 kg

CM= 3129.07 kg/m CV= 354.67 kg/m Wu= 4.98 tn/m

EJE 4-4

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 14.450m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1541.33 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 321.11 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 481.67 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 2884.11 kg

CM= 2884.11 kg/m CV= 321.11 kg/m Wu= 4.58 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 16.900m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1545.14 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 321.90 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 482.86 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 2889.90 kg

CM= 2889.90 kg/m CV= 321.90 kg/m Wu= 4.59 tn/m


EJE 5-5
TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 14.200m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1514.67 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 315.56 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 473.33 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 2843.56 kg

CM= 2843.56 kg/m CV= 315.56 kg/m Wu= 4.52 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 17.100m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1563.43 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 325.71 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 488.57 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 2917.71 kg

CM= 2917.71 kg/m CV= 325.71 kg/m Wu= 4.64 tn/m

EJE 6-6

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 12.350m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1317.33 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 274.44 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 411.67 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 2543.44 kg

CM= 2543.44 kg/m CV= 274.44 kg/m Wu= 4.03 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 15.200m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1389.71 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 289.52 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 434.29 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 2653.52 kg
CM= 2653.52 kg/m CV= 289.52 kg/m Wu= 4.21 tn/m

EJE 7-7

TRAMO A-B Luz= 4.50 AREA TRIBUTARIA = 4.800m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 512.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 106.67 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 160.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 4.50 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 4.50 0.25 0.45 270.00 kg/m
TOTAL = 1318.67 kg

CM= 1318.67 kg/m CV= 106.67 kg/m Wu= 2.03 tn/m

TRAMO B-C Luz= 5.25 AREA TRIBUTARIA = 6.220m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 568.69 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 118.48 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 177.71 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.25 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 5.25 0.25 0.45 270.00 kg/m
TOTAL = 1404.88 kg

CM= 1404.88 kg/m CV= 118.48 kg/m Wu= 2.17 tn/m

VIGAS DIRECCION Y-Y

EJE A-A
TRAMO 1--2 Luz= 2.15 AREA TRIBUTARIA = 5.240m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1169.86 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 243.72 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 365.58 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.15 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.15 0.25 0.35 210.00 kg/m
TOTAL = 2259.16 kg

CM= 2259.16 kg/m CV= 243.72 kg/m Wu= 3.58 tn/m

TRAMO 2--3 Luz= 2.65 AREA TRIBUTARIA = 8.890m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1610.26 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 335.47 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 503.21 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.65 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.65 0.25 0.35 210.00 kg/m
TOTAL = 2928.94 kg

CM= 2928.94 kg/m CV= 670.94 kg/m Wu= 5.24 tn/m

TRAMO 3--4 Luz= 3.80 AREA TRIBUTARIA = 6.990m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 882.95 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 183.95 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 275.92 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.80 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.80 0.25 0.35 210.00 kg/m
TOTAL = 1822.82 kg

CM= 1822.82 kg/m CV= 183.95 kg/m Wu= 2.86 tn/m

TRAMO 4--5 Luz= 3.00 AREA TRIBUTARIA = 7.250m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1160.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 241.67 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 362.50 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.00 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.00 0.25 0.35 210.00 kg/m
TOTAL = 2244.17 kg

CM= 2244.17 kg/m CV= 241.67 kg/m Wu= 3.55 tn/m

TRAMO 5--6 Luz= 3.90 AREA TRIBUTARIA = 7.960m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 979.69 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 204.10 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 306.15 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.90 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.90 0.25 0.35 210.00 kg/m
TOTAL = 1969.95 kg

CM= 1969.95 kg/m CV= 204.10 kg/m Wu= 3.10 tn/m

TRAMO 6--7 Luz= 2.78 AREA TRIBUTARIA = 7.130m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1231.08 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 256.47 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 384.71 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.78 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.78 0.25 0.35 210.00 kg/m
TOTAL = 2352.27 kg

CM= 2352.27 kg/m CV= 256.47 kg/m Wu= 3.73 tn/m

EJE B-B

TRAMO 1--2 Luz= 2.30 AREA TRIBUTARIA = 10.540m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2199.65 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 458.26 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 687.39 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.30 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.30 0.25 0.35 210.00 kg/m
TOTAL = 3825.30 kg

CM= 3825.30 kg/m CV= 458.26 kg/m Wu= 6.13 tn/m

TRAMO 2--3 Luz= 2.65 AREA TRIBUTARIA = 16.150m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2925.28 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 609.43 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 914.15 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.65 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.65 0.25 0.35 210.00 kg/m
TOTAL = 4928.87 kg

CM= 4928.87 kg/m CV= 609.43 kg/m Wu= 7.94 tn/m

TRAMO 3--4 Luz= 3.80 AREA TRIBUTARIA = 18.280m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2309.05 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 481.05 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 721.58 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.80 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.80 0.25 0.35 210.00 kg/m
TOTAL = 3991.68 kg

CM= 3991.68 kg/m CV= 481.05 kg/m Wu= 6.41 tn/m


TRAMO 4--5 Luz= 3.00 AREA TRIBUTARIA = 13.770m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2203.20 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 459.00 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 688.50 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.00 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.00 0.25 0.35 210.00 kg/m
TOTAL = 3830.70 kg

CM= 3830.70 kg/m CV= 459.00 kg/m Wu= 6.14 tn/m

TRAMO 5--6 Luz= 3.90 AREA TRIBUTARIA = 18.520m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 2279.38 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 474.87 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 712.31 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.90 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.90 0.25 0.35 210.00 kg/m
TOTAL = 3946.56 kg

CM= 3946.56 kg/m CV= 474.87 kg/m Wu= 6.33 tn/m

TRAMO 6--7 Luz= 2.78 AREA TRIBUTARIA = 10.030m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1731.80 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 360.79 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 541.19 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.78 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.78 0.25 0.35 210.00 kg/m
TOTAL = 3113.78 kg

CM= 3113.78 kg/m CV= 360.79 kg/m Wu= 4.97 tn/m

EJE C-C
TRAMO 1--2 Luz= 2.30 AREA TRIBUTARIA = 1.540m
ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 321.39 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 66.96 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 100.43 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.30 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.30 0.25 0.35 210.00 kg/m
TOTAL = 968.78 kg

CM= 968.78 kg/m CV= 66.96 kg/m Wu= 1.47 tn/m

TRAMO 2--3 Luz= 2.65 AREA TRIBUTARIA = 10.270m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1860.23 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 387.55 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 581.32 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.65 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.65 0.25 0.35 210.00 kg/m
TOTAL = 3309.09 kg

CM= 3309.09 kg/m CV= 387.55 kg/m Wu= 5.29 tn/m

TRAMO 3--4 Luz= 3.80 AREA TRIBUTARIA = 7.800m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 985.26 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 205.26 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 307.89 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.80 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.80 0.25 0.35 210.00 kg/m
TOTAL = 1978.42 kg

CM= 1978.42 kg/m CV= 205.26 kg/m Wu= 3.12 tn/m

TRAMO 4--5 Luz= 3.00 AREA TRIBUTARIA = 8.400m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1344.00 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 280.00 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 420.00 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.00 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.00 0.25 0.35 210.00 kg/m
TOTAL = 2524.00 kg

CM= 2524.00 kg/m CV= 280.00 kg/m Wu= 4.01 tn/m

TRAMO 5--6 Luz= 3.90 AREA TRIBUTARIA = 9.320m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1147.08 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 238.97 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 358.46 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.90 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 3.90 0.25 0.35 210.00 kg/m
TOTAL = 2224.51 kg

CM= 2224.51 kg/m CV= 238.97 kg/m Wu= 3.52 tn/m

TRAMO 6--7 Luz= 2.78 AREA TRIBUTARIA = 7.870m


ELEMENTOS P . UNIT Largo Ancho Alto PARCIAL
PESO DE LOSA 480 Kg/m 1358.85 kg/m
PESO DE TABIQUERIA EQUIVALENTE 100 Kg/m 283.09 kg/m
PESO PISOS Y ACABADOS 150 Kg/m 424.64 kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 2.78 0.15 1 270.00 kg/m
PESO PROPIO DE VIGA 2400 Kg/m 2.78 0.25 0.35 210.00 kg/m
TOTAL = 2546.58 kg

CM= 2546.58 kg/m CV= 283.09 kg/m Wu= 4.05 tn/m

RESUMEN

DIRECCION X-X

PORTICO TRAMO CM CV Wu
A- 1343.00 kg/m 110.00 kg/m 2.07 tn/m
1--1
B-C 1342.30 kg/m 109.90 kg/m 2.07 tn/m
A-B 2535.33 kg/m 273.33 kg/m 4.01 tn/m
2--2
B-C 2538.11 kg/m 273.71 kg/m 4.02 tn/m
A-B 3107.98 kg/m 351.78 kg/m 4.95 tn/m
3--3
B-C 3129.07 kg/m 354.67 kg/m 4.98 tn/m
A-B 2884.11 kg/m 321.11 kg/m 4.58 tn/m
4--4
B-C 2889.90 kg/m 321.90 kg/m 4.59 tn/m
A-B 2843.56 kg/m 325.71 kg/m 4.53 tn/m
5--5
B-C 2917.71 kg/m 315.56 kg/m 4.62 tn/m
A-B 2543.44 kg/m 274.44 kg/m 4.03 tn/m
6--6
B-C 2653.52 kg/m 289.52 kg/m 4.21 tn/m
A-B 1318.67 kg/m 106.67 kg/m 2.03 tn/m
7--7
B-C 1404.88 kg/m 118.48 kg/m 2.17 tn/m
DIRECCION Y-Y

PORTICO TRAMO CM CV Wu
1--2 2259.16 kg/m 243.72 kg/m 3.58 tn/m
2--3 2928.94 kg/m 670.94 kg/m 5.24 tn/m
3--4 1822.82 kg/m 183.95 kg/m 2.86 tn/m
A--A
4--5 2244.17 kg/m 241.67 kg/m 3.92 tn/m
5--6 1969.95 kg/m 204.10 kg/m 3.79 tn/m
6--7 2352.27 kg/m 256.47 kg/m 4.11 tn/m
1--2 3825.30 kg/m 458.26 kg/m 5.47 tn/m
2--3 4928.87 kg/m 609.43 kg/m 7.56 tn/m
3--4 3991.68 kg/m 481.05 kg/m 6.41 tn/m
B--B
4--5 3830.70 kg/m 459.00 kg/m 6.14 tn/m
5--6 3946.56 kg/m 474.87 kg/m 6.33 tn/m
6--7 3113.78 kg/m 360.79 kg/m 4.97 tn/m
1--2 968.78 kg/m 66.96 kg/m 1.47 tn/m
2--3 3309.09 kg/m 387.55 kg/m 5.29 tn/m
3--4 1978.42 kg/m 205.26 kg/m 3.12 tn/m
C--C
4--5 2524.00 kg/m 280.00 kg/m 4.01 tn/m
5--6 2224.51 kg/m 238.97 kg/m 3.52 tn/m
6--7 2546.58 kg/m 283.09 kg/m 4.05 tn/m
4.950m
PARCIAL
528.00 kg/m
110.00 kg/m
165.00 kg/m
270.00 kg/m
270.00 kg/m
1343.00 kg

2.07 tn/m

5.770m
PARCIAL
527.54 kg/m
109.90 kg/m
164.86 kg/m
270.00 kg/m
270.00 kg/m
1342.30 kg

2.07 tn/m

12.300m
PARCIAL
1312.00 kg/m
273.33 kg/m
410.00 kg/m
270.00 kg/m
270.00 kg/m
2535.33 kg

4.01 tn/m

14.370m
PARCIAL
1313.83 kg/m
273.71 kg/m
410.57 kg/m
270.00 kg/m
270.00 kg/m
2538.11 kg

4.02 tn/m

15.830m
PARCIAL
1688.53 kg/m
351.78 kg/m
527.67 kg/m
270.00 kg/m
270.00 kg/m
3107.98 kg

4.95 tn/m

18.620m
PARCIAL
1702.40 kg/m
354.67 kg/m
532.00 kg/m
270.00 kg/m
270.00 kg/m
3129.07 kg

4.98 tn/m

14.450m
PARCIAL
1541.33 kg/m
321.11 kg/m
481.67 kg/m
270.00 kg/m
270.00 kg/m
2884.11 kg

4.58 tn/m

16.900m
PARCIAL
1545.14 kg/m
321.90 kg/m
482.86 kg/m
270.00 kg/m
270.00 kg/m
2889.90 kg

4.59 tn/m
14.200m
PARCIAL
1514.67 kg/m
315.56 kg/m
473.33 kg/m
270.00 kg/m
270.00 kg/m
2843.56 kg

4.52 tn/m

17.100m
PARCIAL
1563.43 kg/m
325.71 kg/m
488.57 kg/m
270.00 kg/m
270.00 kg/m
2917.71 kg

4.64 tn/m

12.350m
PARCIAL
1317.33 kg/m
274.44 kg/m
411.67 kg/m
270.00 kg/m
270.00 kg/m
2543.44 kg

4.03 tn/m

15.200m
PARCIAL
1389.71 kg/m
289.52 kg/m
434.29 kg/m
270.00 kg/m
270.00 kg/m
2653.52 kg
4.21 tn/m

4.800m
PARCIAL
512.00 kg/m
106.67 kg/m
160.00 kg/m
270.00 kg/m
270.00 kg/m
1318.67 kg

2.03 tn/m

6.220m
PARCIAL
568.69 kg/m
118.48 kg/m
177.71 kg/m
270.00 kg/m
270.00 kg/m
1404.88 kg

2.17 tn/m

5.240m
PARCIAL
1169.86 kg/m
243.72 kg/m
365.58 kg/m
270.00 kg/m
210.00 kg/m
2259.16 kg

3.58 tn/m

8.890m
PARCIAL
1610.26 kg/m
335.47 kg/m
503.21 kg/m
270.00 kg/m
210.00 kg/m
2928.94 kg

5.24 tn/m

6.990m
PARCIAL
882.95 kg/m
183.95 kg/m
275.92 kg/m
270.00 kg/m
210.00 kg/m
1822.82 kg

2.86 tn/m

7.250m
PARCIAL
1160.00 kg/m
241.67 kg/m
362.50 kg/m
270.00 kg/m
210.00 kg/m
2244.17 kg

3.55 tn/m

7.960m
PARCIAL
979.69 kg/m
204.10 kg/m
306.15 kg/m
270.00 kg/m
210.00 kg/m
1969.95 kg

3.10 tn/m

7.130m
PARCIAL
1231.08 kg/m
256.47 kg/m
384.71 kg/m
270.00 kg/m
210.00 kg/m
2352.27 kg

3.73 tn/m

10.540m
PARCIAL
2199.65 kg/m
458.26 kg/m
687.39 kg/m
270.00 kg/m
210.00 kg/m
3825.30 kg

6.13 tn/m

16.150m
PARCIAL
2925.28 kg/m
609.43 kg/m
914.15 kg/m
270.00 kg/m
210.00 kg/m
4928.87 kg

7.94 tn/m

18.280m
PARCIAL
2309.05 kg/m
481.05 kg/m
721.58 kg/m
270.00 kg/m
210.00 kg/m
3991.68 kg

6.41 tn/m
13.770m
PARCIAL
2203.20 kg/m
459.00 kg/m
688.50 kg/m
270.00 kg/m
210.00 kg/m
3830.70 kg

6.14 tn/m

18.520m
PARCIAL
2279.38 kg/m
474.87 kg/m
712.31 kg/m
270.00 kg/m
210.00 kg/m
3946.56 kg

6.33 tn/m

10.030m
PARCIAL
1731.80 kg/m
360.79 kg/m
541.19 kg/m
270.00 kg/m
210.00 kg/m
3113.78 kg

4.97 tn/m

1.540m
PARCIAL
321.39 kg/m
66.96 kg/m
100.43 kg/m
270.00 kg/m
210.00 kg/m
968.78 kg

1.47 tn/m

10.270m
PARCIAL
1860.23 kg/m
387.55 kg/m
581.32 kg/m
270.00 kg/m
210.00 kg/m
3309.09 kg

5.29 tn/m

7.800m
PARCIAL
985.26 kg/m
205.26 kg/m
307.89 kg/m
270.00 kg/m
210.00 kg/m
1978.42 kg

3.12 tn/m

8.400m
PARCIAL
1344.00 kg/m
280.00 kg/m
420.00 kg/m
270.00 kg/m
210.00 kg/m
2524.00 kg

4.01 tn/m

9.320m
PARCIAL
1147.08 kg/m
238.97 kg/m
358.46 kg/m
270.00 kg/m
210.00 kg/m
2224.51 kg

3.52 tn/m

7.870m
PARCIAL
1358.85 kg/m
283.09 kg/m
424.64 kg/m
270.00 kg/m
210.00 kg/m
2546.58 kg

4.05 tn/m
CARGA POR CULUMNA: ESFUERZO SOB
V11 V12
C6 C12 C18

V25 V26 V27


V9 V10
C5 C11 C17
PESO POR NIVEL
NIVEL PESO V22 V23 V24
7 152.24 Tn V7 V8
6 157.69 Tn C4 C10 C16
5 157.69 Tn
4 157.69 Tn V19 V20 V21
3 157.69 Tn V5 V6
2 157.69 Tn C3 C9 C15
1 191.92 Tn
V16 V17 V18
V3 V4
C2 C8 C14

V13 V14 V15


V1 V2
C1 C7 C13

PESO POR NIVEL(1.4 CM+1.7CV)


COL A.TRIB TOTAL
1 2 3 4 5 6 7
1 2.59 m 3.386201 2.78219 2.78219 2.78219 2.78219 2.78219 2.68597 19.98 Tn
2 6.66 m 8.721397 7.16572 7.16572 7.16572 7.16572 7.16572 6.91789 51.47 Tn
3 8.35 m 10.92956 8.98 8.98 8.98 8.98 8.98 8.66943 64.50 Tn
4 5.22 m 6.831303 5.61277 5.61277 5.61277 5.61277 5.61277 5.41865 40.31 Tn
5 6.19 m 8.102274 6.65703 6.65703 6.65703 6.65703 6.65703 6.4268 47.81 Tn
6 4.48 m 5.86924 4.82231 4.82231 4.82231 4.82231 4.82231 4.65553 34.64 Tn
7 4.71 m 6.167676 5.06751 5.06751 5.06751 5.06751 5.06751 4.89226 36.40 Tn
8 13.67 m 17.89568 14.7035 14.7035 14.7035 14.7035 14.7035 14.195 105.61 Tn
9 18.10 m 23.6877 19.4624 19.4624 19.4624 19.4624 19.4624 18.7893 139.79 Tn
10 16.51 m 21.61435 17.7589 17.7589 17.7589 17.7589 17.7589 17.1447 127.55 Tn
11 17.00 m 22.2518 18.2826 18.2826 18.2826 18.2826 18.2826 17.6503 131.32 Tn
12 6.43 m 8.411181 6.91083 6.91083 6.91083 6.91083 6.91083 6.67183 49.64 Tn
13 2.90 m 3.801131 3.1231 3.1231 3.1231 3.1231 3.1231 3.01509 22.43 Tn
14 5.09 m 6.658524 5.47081 5.47081 5.47081 5.47081 5.47081 5.2816 39.29 Tn
15 9.75 m 12.75814 10.4824 10.4824 10.4824 10.4824 10.4824 10.1199 75.29 Tn
16 6.08 m 7.9596 6.5398 6.5398 6.5398 6.5398 6.5398 6.31363 46.97 Tn
17 7.66 m 10.0264 8.23794 8.23794 8.23794 8.23794 8.23794 7.95303 59.17 Tn
18 5.23 m 6.850937 5.6289 5.6289 5.6289 5.6289 5.6289 5.43423 40.43 Tn
SUMA 146.63 m
ESFUERZO SOBRE VIGA DE CIMENTACION

SECCION b = 0.30 m
h = 0.50 m 0.50 m

Esfuerzo del terreno = 1.40 Kg/cm2


0.30 m
Esfuerzo del Peso propio de
VIGA Total
suelo en vigas viga
1 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
2 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
3 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
4 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
5 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
6 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
7 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
8 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
9 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
10 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
11 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
12 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
13 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
14 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
15 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
16 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
17 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
18 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
19 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
20 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
21 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
22 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
23 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
24 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
25 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
26 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
27 4.20 Tn/m 0.36 Tn/m 3.84 Tn/m
PARRILLAS

DIRECCION X--X
BARRA 1,3,5,7,9,11 Matriz de Transformacion.-
b 0.30 m 1.00 0.00
t 0.50 m 0.00 1.00
L 4.50 m 0.00 0.00
ngulo 0.00 T= 0.00 0.00
E 2173706.51 tn/m2 0.00 0.00
J 0.01 m4 0.00 0.00
I 0.003 m4
G 939041.21 tn/m2
Seno 0.00
Cos 1.00
v 0.43
fy 1.20
y 0.41
Matriz de Rigidez en Coordena

2608.45 0.00 0.00 -2608.45 0.00 0.00


0.00 4717.80 -1425.90 0.00 1698.76 1425.90
K'= 0.00 -1425.90 633.73 0.00 -1425.90 -633.73
-2608.45 0.00 0.00 2608.45 0.00 0.00
0.00 1698.76 -1425.90 0.00 4717.80 4717.80
0.00 1425.90 -633.73 0.00 4717.80 633.73

Matriz de Rigidez en Coordena

1 2 3 4 5 6
2608.45 0.00 0.00 -2608.45 0.00 0.00
0.00 4717.80 -1425.90 0.00 1698.76 1425.90
K1= 0.00 -1425.90 633.73 0.00 -1425.90 -633.73
-2608.45 0.00 0.00 2608.45 0.00 0.00
0.00 1698.76 -1425.90 0.00 4717.80 4717.80
0.00 1425.90 -633.73 0.00 4717.80 633.73

10 11 12 13 14 15
2608.447814 0 0 -2608.4478 0 0
0 4717.795151 -1425.9008 0 1698.7583 1425.900773
K3= 0 -1425.900773 633.73368 0 -1425.901 -633.733677
-2608.447814 0 0 2608.44781 0 0
0 1698.758328 -1425.9008 0 4717.7952 4717.795151
0 1425.900773 -633.73368 0 4717.7952 633.7336769

19 20 21 22 23 24
2608.447814 0 0 -2608.4478 0 0
0 4717.795151 -1425.9008 0 1698.7583 1425.900773
K5= 0 -1425.900773 633.73368 0 -1425.901 -633.733677
-2608.447814 0 0 2608.44781 0 0
0 1698.758328 -1425.9008 0 4717.7952 4717.795151
0 1425.900773 -633.73368 0 4717.7952 633.7336769

28 29 30 31 32 33
2608.447814 0 0 -2608.4478 0 0
0 4717.795151 -1425.9008 0 1698.7583 1425.900773
K7= 0 -1425.900773 633.73368 0 -1425.901 -633.733677
-2608.447814 0 0 2608.44781 0 0
0 1698.758328 -1425.9008 0 4717.7952 4717.795151
0 1425.900773 -633.73368 0 4717.7952 633.7336769

37 38 39 40 41 42
2608.447814 0 0 -2608.4478 0 0
0 4717.795151 -1425.9008 0 1698.7583 1425.900773
K9= 0 -1425.900773 633.73368 0 -1425.901 -633.733677
-2608.447814 0 0 2608.44781 0 0
0 1698.758328 -1425.9008 0 4717.7952 4717.795151
0 1425.900773 -633.73368 0 4717.7952 633.7336769

46 47 48 49 50 51
2608.447814 0 0 -2608.4478 0 0
0 4717.795151 -1425.9008 0 1698.7583 1425.900773
K11= 0 -1425.900773 633.73368 0 -1425.901 -633.733677
-2608.447814 0 0 2608.44781 0 0
0 1698.758328 -1425.9008 0 4717.7952 4717.795151
0 1425.900773 -633.73368 0 4717.7952 633.7336769
MATRIZ DE RIGIDEZ ENSAMBLADA [K] COORDENADAS GLOBALES

1 2 3 4 5 6 7
1 13530.44 0.00 2991.71 -2608.45 0.00 0.00 0
2 0.00 14349.41 -1425.90 0.00 1698.76 1425.90 0
3 2991.71 -1425.90 12291.47 0.00 -1425.90 -633.73 0
4 -2608.45 0.00 0.00 21049.06 0.00 2991.71 -2235.8124
5 0.00 1698.76 -1425.90 0.00 23906.58 3582.37 0
6 0.00 1425.90 -633.73 2991.71 3582.37 23289.63 0
7 0 0 0 -2235.812 0 0 13912.49
8 0 0 0 0 1686.6155 -1135.42 0.00
9 0 0 0 0 1135.4242 -432.543 2991.71
10 487.06 0.00 2991.71 0 0 0 0
11 0.00 -5103.48 0.00 0 0 0 0
12 -2991.71 0.00 -2601.48 0 0 0 0
13 0 0 0 487.06 0.00 2991.71 0
14 0 0 0 0.00 -5103.48 0.00 0
15 0 0 0 -2991.71 0.00 -2601.48 0
16 0 0 0 0 0 0 487.06
17 0 0 0 0 0 0 0.00
18 0 0 0 0 0 0 -2991.71
19 0 0 0 0 0 0 0
20 0 0 0 0 0 0 0
21 0 0 0 0 0 0 0
22 0 0 0 0 0 0 0
23 0 0 0 0 0 0 0
24 0 0 0 0 0 0 0
25 0 0 0 0 0 0 0
26 0 0 0 0 0 0 0
27 0 0 0 0 0 0 0
28 0 0 0 0 0 0 0
29 0 0 0 0 0 0 0
30 0 0 0 0 0 0 0
31 0 0 0 0 0 0 0
32 0 0 0 0 0 0 0
33 0 0 0 0 0 0 0
34 0 0 0 0 0 0 0
35 0 0 0 0 0 0 0
36 0 0 0 0 0 0 0
37 0 0 0 0 0 0 0
38 0 0 0 0 0 0 0
39 0 0 0 0 0 0 0
40 0 0 0 0 0 0 0
41 0 0 0 0 0 0 0
42 0 0 0 0 0 0 0
43 0 0 0 0 0 0 0
44 0 0 0 0 0 0 0
45 0 0 0 0 0 0 0
46 0 0 0 0 0 0 0
47 0 0 0 0 0 0 0
48 0 0 0 0 0 0 0
49 0 0 0 0 0 0 0
50 0 0 0 0 0 0 0
51 0 0 0 0 0 0 0
52 0 0 0 0 0 0 0
53 0 0 0 0 0 0 0
54 0 0 0 0 0 0 0
4.00 m

3.00 m

3.80 m

3.65 m

2.30 m

4.50 m 5.25 m

BARRA 2,4,6,8,10,12
0.00 0.00 0.00 0.00 b 0.30 m
0.00 0.00 0.00 0.00 t 0.50 m
1.00 0.00 0.00 0.00 L 5.25 m
0.00 1.00 0.00 0.00 ngulo 0.00
0.00 0.00 1.00 0.00 E 2173706.51 tn/m2
0.00 0.00 0.00 1.00 J 0.01 m4
I 0.00 m4
G 939041.21 tn/m2
Seno 0.00
Cos 1.00
v 0.43
fy 1.20
y 0.30
Rigidez en Coordenadas LOCALES

2235.81 0.00 0.00 -2235.81 0.00


0.00 4274.36 -1135.42 0.00 1686.62
K'= 0.00 -1135.42 432.54 0.00 -1135.42
-2235.81 0.00 0.00 2235.81 0.00
0.00 1686.62 -1135.42 0.00 4274.36
0.00 1135.42 -432.54 0.00 4274.36

Rigidez en Coordenadas GLOBALES

4 5 6 7 8
1 2235.81241 0 0 -2235.81241 0
2 0 4274.3614 -1135.42418 0 1686.6155
3 K2 0 -1135.4242 432.542544 0 -1135.4242
4 -2235.81241 0 0 2235.81241 0
5 0 1686.6155 -1135.42418 0 4274.3614
6 0 1135.4242 -432.542544 0 4274.3614

13 14 15 16 17
10 2608.44781 0 0 -2608.44781 0
11 0 4717.7952 -1425.90077 0 1698.7583
12 K4= 0 -1425.9008 633.733677 0 -1425.9008
13 -2608.44781 0 0 2608.44781 0
14 0 1698.7583 -1425.90077 0 4717.7952
15 0 1425.9008 -633.733677 0 4717.7952

22 23 24 25 26
19 2608.44781 0 0 -2608.44781 0
20 0 4717.7952 -1425.90077 0 1698.7583
21 K6= 0 -1425.9008 633.733677 0 -1425.9008
22 -2608.44781 0 0 2608.44781 0
23 0 1698.7583 -1425.90077 0 4717.7952
24 0 1425.9008 -633.733677 0 4717.7952

31 32 33 34 35
28 2608.44781 0 0 -2608.44781 0
29 0 4717.7952 -1425.90077 0 1698.7583
30 K8= 0 -1425.9008 633.733677 0 -1425.9008
31 -2608.44781 0 0 2608.44781 0
32 0 1698.7583 -1425.90077 0 4717.7952
33 0 1425.9008 -633.733677 0 4717.7952

40 41 42 43 44
37 2608.44781 0 0 -2608.44781 0
38 0 4717.7952 -1425.90077 0 1698.7583
39 K10= 0 -1425.9008 633.733677 0 -1425.9008
40 -2608.44781 0 0 2608.44781 0
41 0 1698.7583 -1425.90077 0 4717.7952
42 0 1425.9008 -633.733677 0 4717.7952

49 50 51 52 53
46 2608.44781 0 0 -2608.44781 0
47 0 4717.7952 -1425.90077 0 1698.7583
48 K12= 0 -1425.9008 633.733677 0 -1425.9008
49 -2608.44781 0 0 2608.44781 0
50 0 1698.7583 -1425.90077 0 4717.7952
51 0 1425.9008 -633.733677 0 4717.7952
LES

8 9 10 11 12 13 14 15
0 0 487.06 0.00 2991.71 0 0 0
0 0 0.00 -5103.48 0.00 0 0 0
0 0 -2991.71 0.00 -2601.48 0 0 0
0 0 0 0 0 487.06 0.00 2991.71
1686.61555 1135.4242 0 0 0 0.00 -5103.48 0.00
-1135.4242 -432.54254 0 0 0 -2991.71 0.00 -2601.48
0.00 2991.71 0 0 0 0 0 0
14660.66 4274.36 0 0 0 0 0 0
4274.36 13599.65 0 0 0 0 0 0
0 0 26012.14 0.00 -4511.83 -2608.4478 0 0
0 0 0.00 24751.24 -1425.90 0 1698.7583 1425.9008
0 0 -4511.83 -1425.90 27694.59 0 -1425.9008 -633.7337
0 0 -2608.4478 0 0 42286.99 0.00 -4511.83
0 0 0 1698.75833 -1425.901 0.00 43135.44 3291.89
0 0 0 1425.90077 -633.7337 -4511.83 3291.89 55661.14
0.00 2991.71 0 0 0 -2608.4478 0 0
-5103.48 0.00 0 0 0 0 1698.7583 -1425.901
0.00 -2601.48 0 0 0 0 1425.9008 -633.7337
0 0 1573.66 0.00 1882.03 0 0 0
0 0 0.00 -3215.89 0.00 0 0 0
0 0 -1882.03 0.00 -1031.25 0 0 0
0 0 0 0 0 1573.66 0.00 1882.03
0 0 0 0 0 0.00 -3215.89 0.00
0 0 0 0 0 -1882.03 0.00 -1031.25
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
DIRECCION Y-Y
BARRA 13,14,15
b 0.30 m
t 0.50 m
L 2.30 m
ngulo 90.00 T=
E 2173706.51 tn/m2
J 0.01 m4
I 0.00 m4
G 939041.21 tn/m2
Seno 1.00
Cos 0.00
v 0.43
fy 1.20
y 1.58

5103.48 0.00 0.00 -5103.48 0.00


0.00 6393.87 -2991.71 0.00 487.06
K'13--15 0.00 -2991.71 2601.48 0.00 -2991.71
-5103.48 0.00 0.00 5103.48 0.00
0.00 487.06 -2991.71 0.00 6393.87
0.00 2991.71 -2601.48 0.00 6393.87

1 2 3 10 11
6393.87 0.00 2991.71 487.06 0.00
0.00 5103.48 0.00 0.00 -5103.48
K13 2991.71 0.00 2601.48 2991.71 0.00
487.06 0.00 2991.71 6393.87 0.00
0.00 -5103.48 0.00 0.00 5103.48
-2991.71 0.00 -2601.48 -6393.87 0.00

4 5 6 13 14
6393.87 0.00 2991.71 487.06 0.00
K14 0.00 5103.48 0.00 0.00 -5103.48
2991.71 0.00 2601.48 2991.71 0.00
487.06 0.00 2991.71 6393.87 0.00
0.00 -5103.48 0.00 0.00 5103.48
-2991.71 0.00 -2601.48 -6393.87 0.00

7 8 9 16 17
K15 6393.87 0.00 2991.71 487.06 0.00
0.00 5103.48 0.00 0.00 -5103.48
2991.71 0.00 2601.48 2991.71 0.00
487.06 0.00 2991.71 6393.87 0.00
0.00 -5103.48 0.00 0.00 5103.48
0.00 -2991.71 0.00 -2601.48 -6393.87 0.00
1135.42
-432.54 BARRA 19,20,21
0.00 b 0.30 m
4274.36 t 0.50 m
432.54 L 3.80 m
ngulo 90.00 T=
E 2173706.51 tn/m2
J 0.01 m4
9 I 0.00 m4
0 4 G 939041.21 tn/m2
1135.4242 5 Seno 1.00
-432.54254 6 Cos 0.00
0 7 v 0.43
4274.3614 8 fy 1.20
432.54254 9 y 0.58

18 3088.95 0.00 0.00 -3088.95 0.00


0 13 0.00 5187.98 -1789.68 0.00 1612.81
1425.9008 14 K'19-21 0.00 -1789.68 941.94 0.00 -1789.68
-633.73368 15 -3088.95 0.00 0.00 3088.95 0.00
0 16 0.00 1612.81 -1789.68 0.00 5187.98
4717.7952 17 0.00 1789.68 -941.94 0.00 5187.98
633.73368 18

27 19 20 21 28 29
0 22 5187.98 0.00 1789.68 1612.81 0.00
1425.9008 23 0.00 3088.95 0.00 0.00 -3088.95
-633.73368 24 K19 1789.68 0.00 941.94 1789.68 0.00
0 25 1612.81 0.00 1789.68 5187.98 0.00
4717.7952 26 0.00 -3088.95 0.00 0.00 3088.95
633.73368 27 -1789.68 0.00 -941.94 -5187.98 0.00

36 22 23 24 31 32
0 31 5187.98 0.00 1789.68 1612.81 0.00
1425.9008 32 0.00 3088.95 0.00 0.00 -3088.95
-633.73368 33 K20 1789.68 0.00 941.94 1789.68 0.00
0 34 1612.81 0.00 1789.68 5187.98 0.00
4717.7952 35 0.00 -3088.95 0.00 0.00 3088.95
633.73368 36 -1789.68 0.00 -941.94 -5187.98 0.00

45 25 26 27 34 35
0 40 5187.98 0.00 1789.68 1612.81 0.00
1425.9008 41 0.00 3088.95 0.00 0.00 -3088.95
-633.73368 42 K21 1789.68 0.00 941.94 1789.68 0.00
0 43 1612.81 0.00 1789.68 5187.98 0.00
4717.7952 44 0.00 -3088.95 0.00 0.00 3088.95
633.73368 45 -1789.68 0.00 -941.94 -5187.98 0.00

54 BARRA 25,26,27
0 49 b 0.30 m
1425.9008 50 t 0.50 m
-633.73368 51 L 4.00 m
0 52 ngulo 90.00 T=
4717.7952 53 E 2173706.51 tn/m2
633.73368 54 J 0.01 m4
I 0.00 m4
G 939041.21 tn/m2
Seno 1.00
Cos 0.00
v 0.43
fy 1.20
y 0.52

Matriz de Rigidez en Coordenadas Locales.


K'25-27 2934.50 0.00 0.00 -2934.50 0.00
0.00 5048.10 -1674.95 0.00 1651.68
0.00 -1674.95 837.47 0.00 -1674.95
-2934.50 0.00 0.00 2934.50 0.00
0.00 1651.68 -1674.95 0.00 5048.10
0.00 1674.95 -837.47 0.00 5048.10

Matriz de Rigidez en Coordenadas GLOBALES


37 38 39 46 47
K25 5048.10 0.00 1674.95 1651.68 0.00
0.00 2934.50 0.00 0.00 -2934.50
1674.95 0.00 837.47 1674.95 0.00
1651.68 0.00 1674.95 5048.10 0.00
0.00 -2934.50 0.00 0.00 2934.50
-1674.95 0.00 -837.47 -5048.10 0.00

40 41 42 49 50
K26 5048.10 0.00 1674.95 1651.68 0.00
0.00 2934.50 0.00 0.00 -2934.50
1674.95 0.00 837.47 1674.95 0.00
1651.68 0.00 1674.95 5048.10 0.00
0.00 -2934.50 0.00 0.00 2934.50
-1674.95 0.00 -837.47 -5048.10 0.00

43 44 45 52 53
5048.10 0.00 1674.95 1651.68 0.00
0.00 2934.50 0.00 0.00 -2934.50
K27 1674.95 0.00 837.47 1674.95 0.00
1651.68 0.00 1674.95 5048.10 0.00
0.00 -2934.50 0.00 0.00 2934.50
-1674.95 0.00 -837.47 -5048.10 0.00

16 17 18 19 20 21 22 23 24
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
487.06 0.00 2991.71 0 0 0 0 0
0.00 -5103.48 0.00 0 0 0 0 0 0
-2991.71 0.00 -2601.48 0 0 0 0 0 0
0 0 0 1573.66 0.00 1882.03 0 0 0
0 0 0 0.00 -3215.89 0.00 0 0 0
0 0 0 -1882.03 0.00 -1031.25 0 0 0
-2608.448 0 0 0 0 0 1573.66 0.00 1882.03
0 1698.75833 1425.9008 0 0 0 0.00 -3215.89 0.00
0 -1425.9008 -633.7337 0 0 0 -1882.03 0.00 -1031.25
26012.14 0.00 -4511.83 0 0 0 0 0 0
0.00 24751.24 4717.80 0 0 0 0 0 0
-4511.83 4717.80 27694.59 0 0 0 0 0 0
0 0 0 27759.38 0.00 -3506.08 -2608.448 0 0
0 0 0 0.00 25689.83 -1425.90 0 1698.7583 1425.9008
0 0 0 -3506.08 -1425.90 31941.30 0 -1425.901 -633.7337
0 0 0 -2608.448 0 0 47479.54 0.00 -3506.08
0 0 0 0 1698.7583 -1425.9008 0.00 47519.34 3291.89
0 0 0 0 1425.9008 -633.73368 -3506.08 3291.89 66798.47
1573.66 0.00 1882.03 0 0 0 -2608.448 0 0
0.00 -3215.89 0.00 0 0 0 0 1698.7583 -1425.901
-1882.03 0.00 -1031.25 0 0 0 0 1425.9008 -633.7337
0 0 0 1612.81 0.00 1789.68 0 0 0
0 0 0 0.00 -3088.95 0.00 0 0 0
0 0 0 -1789.68 0.00 -941.94 0 0 0
0 0 0 0 0 0 1612.81 0.00 1789.68
0 0 0 0 0 0 0.00 -3088.95 0.00
0 0 0 0 0 0 -1789.68 0.00 -941.94
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
Matriz de Transformacion.- BARRA 16,17,18
0.00 1.00 0.00 0.00 0.00 0.00 b 0.30
-1.00 0.00 0.00 0.00 0.00 0.00 t 0.50
0.00 0.00 1.00 0.00 0.00 0.00 L 3.65
0.00 0.00 0.00 0.00 1.00 0.00 ngulo 90.00
0.00 0.00 0.00 -1.00 0.00 0.00 E 2173706.51
0.00 0.00 0.00 0.00 0.00 1.00 J 0.01
I 0.00
G 939041.21
Seno 1.00
Cos 0.00
v 0.43
fy 1.20
y 0.63
Matriz de Rigidez en Coordenadas Locales.

0.00 3215.89 0.00 0.00 -3215.89


2991.71 0.00 5295.76 -1882.03 0.00
-2601.48 K'16-18 0.00 -1882.03 1031.25 0.00
0.00 -3215.89 0.00 0.00 3215.89
6393.87 0.00 1573.66 -1882.03 0.00
2601.48 0.00 1882.03 -1031.25 0.00

Matriz de Rigidez en Coordenadas GLOBALES


12 10 11 12 19
-2991.71 1 5295.76 0.00 1882.03 1573.66
0.00 2 0.00 3215.89 0.00 0.00
-2601.48 3 K16 1882.03 0.00 1031.25 1882.03
-6393.87 10 1573.66 0.00 1882.03 5295.76
0.00 11 0.00 -3215.89 0.00 0.00
2601.48 12 -1882.03 0.00 -1031.25 -5295.76

15 13 14 15 22
-2991.71 4 5295.76 0.00 1882.03 1573.66
0.00 5 0.00 3215.89 0.00 0.00
-2601.48 6 K17 1882.03 0.00 1031.25 1882.03
-6393.87 13 1573.66 0.00 1882.03 5295.76
0.00 14 0.00 -3215.89 0.00 0.00
2601.48 15 -1882.03 0.00 -1031.25 -5295.76

18 16 17 18 25
-2991.71 7 5295.76 0.00 1882.03 1573.66
0.00 8 0.00 3215.89 0.00 0.00
-2601.48 9 K18 1882.03 0.00 1031.25 1882.03
-6393.87 16 1573.66 0.00 1882.03 5295.76
0.00 17 0.00 -3215.89 0.00 0.00
2601.48 18 -1882.03 0.00 -1031.25 -5295.76

Matriz de Transformacion.- BARRA 22,23,24


0.00 1.00 0.00 0.00 0.00 0.00 b 0.30
-1.00 0.00 0.00 0.00 0.00 0.00 t 0.50
0.00 0.00 1.00 0.00 0.00 0.00 L 3.00
0.00 0.00 0.00 0.00 1.00 0.00 ngulo 90.00
0.00 0.00 0.00 -1.00 0.00 0.00 E 2173706.51
0.00 0.00 0.00 0.00 0.00 1.00 J 0.01
I 0.00
G 939041.21
Seno 1.00
Cos 0.00
v 0.43
fy 1.20
y 0.93
Matriz de Rigidez en Coordenadas Locales.
0.00 3912.67 0.00 0.00 -3912.67
1789.68 0.00 5791.33 -2351.37 0.00
-941.94 K'22-24 0.00 -2351.37 1567.58 0.00
0.00 -3912.67 0.00 0.00 3912.67
5187.98 0.00 1262.77 -2351.37 0.00
941.94 0.00 2351.37 -1567.58 0.00

Matriz de Rigidez en Coordenadas GLOBALES


30 28 29 30 37
-1789.68 19 5791.33 0.00 2351.37 1262.77
0.00 20 0.00 3912.67 0.00 0.00
-941.94 21 K22 2351.37 0.00 1567.58 2351.37
-5187.98 28 1262.77 0.00 2351.37 5791.33
0.00 29 0.00 -3912.67 0.00 0.00
941.94 30 -2351.37 0.00 -1567.58 -5791.33

33 31 32 33 40
-1789.68 22 5791.33 0.00 2351.37 1262.77
0.00 23 0.00 3912.67 0.00 0.00
-941.94 24 K23 2351.37 0.00 1567.58 2351.37
-5187.98 31 1262.77 0.00 2351.37 5791.33
0.00 32 0.00 -3912.67 0.00 0.00
941.94 33 -2351.37 0.00 -1567.58 -5791.33

36 34 35 36 43
-1789.68 25 5791.33 0.00 2351.37 1262.77
0.00 26 0.00 3912.67 0.00 0.00
-941.94 27 K24 2351.37 0.00 1567.58 2351.37
-5187.98 34 1262.77 0.00 2351.37 5791.33
0.00 35 0.00 -3912.67 0.00 0.00
941.94 36 -2351.37 0.00 -1567.58 -5791.33

Matriz de Transformacion.-
0.00 1.00 0.00 0.00 0.00 0.00
-1.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 1.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 1.00 0.00
0.00 0.00 0.00 -1.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00 1.00

0.00
1674.95
-837.47
0.00
5048.10
837.47

48
-1674.95 37
0.00 38
-837.47 39
-5048.10 46
0.00 47
837.47 48

51
-1674.95 40
0.00 41
-837.47 42
-5048.10 49
0.00 50
837.47 51

54
-1674.95 43
0.00 44
-837.47 45
-5048.10 52
0.00 53
837.47 54

25 26 27 28 29 30 31 32 33
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
1573.66 0.00 1882.03 0 0 0 0 0 0
0.00 -3215.89 0.00 0 0 0 0 0 0
-1882.03 0.00 -1031.25 0 0 0 0 0 0
0 0 0 1612.81 0.00 1789.68 0 0 0
0 0 0 0.00 -3088.95 0.00 0 0 0
0 0 0 -1789.68 0.00 -941.94 0 0 0
-2608.448 0 0 0 0 0 1612.81 0.00 1789.68
0 1698.7583 1425.9008 0 0 0 0.00 -3088.95 0.00
0 -1425.901 -633.7337 0 0 0 -1789.68 0.00 -941.94
27759.38 0.00 -3506.08 0 0 0 0 0 0
0.00 25689.83 4717.80 0 0 0 0 0 0
-3506.08 4717.80 31941.30 0 0 0 0 0 0
0 0 0 26975.25 0.00 -2836.62 -2608.448 0 0
0 0 0 0.00 25106.92 -1425.90 0 1698.7583 1425.90077
0 0 0 -2836.62 -1425.90 29918.25 0 -1425.9008 -633.73368
0 0 0 -2608.448 0 0 45202.45 0.00 -2836.62
0 0 0 0 1698.75833 -1425.901 0.00 45443.46 3291.89
0 0 0 0 1425.90077 -633.7337 -2836.62 3291.89 61789.48
1612.81 0.00 1789.68 0 0 0 -2608.448 0 0
0.00 -3088.95 0.00 0 0 0 0 1698.7583 -1425.9008
-1789.68 0.00 -941.94 0 0 0 0 1425.9008 -633.73368
0 0 0 1262.77 0.00 2351.37 0 0 0
0 0 0 0.00 -3912.67 0.00 0 0 0
0 0 0 -2351.37 0.00 -1567.58 0 0 0
0 0 0 0 0 0 1262.77 0.00 2351.37
0 0 0 0 0 0 0.00 -3912.67 0.00
0 0 0 0 0 0 -2351.37 0.00 -1567.58
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
6,17,18
m
m
m

tn/m2
m4
m4
tn/m2

0.00 0.00
1573.66 1882.03
-1882.03 -1031.25
0.00 0.00
5295.76 5295.76
5295.76 1031.25

20 21
0.00 -1882.03 10
-3215.89 0.00 11
0.00 -1031.25 12
0.00 -5295.76 19
3215.89 0.00 20
0.00 1031.25 21

23 24
0.00 -1882.03 13
-3215.89 0.00 14
0.00 -1031.25 15
0.00 -5295.76 22
3215.89 0.00 23
0.00 1031.25 24

26 27
0.00 -1882.03 16
-3215.89 0.00 17
0.00 -1031.25 18
0.00 -5295.76 25
3215.89 0.00 26
0.00 1031.25 27

2,23,24
m
m
m

tn/m2
m4
m4
tn/m2

0.00 0.00
1262.77 2351.37
-2351.37 -1567.58
0.00 0.00
5791.33 5791.33
5791.33 1567.58

38 39
0.00 -2351.37 28
-3912.67 0.00 29
0.00 -1567.58 30
0.00 -5791.33 37
3912.67 0.00 38
0.00 1567.58 39

41 42
0.00 -2351.37 31
-3912.67 0.00 32
0.00 -1567.58 33
0.00 -5791.33 40
3912.67 0.00 41
0.00 1567.58 42

44 45
0.00 -2351.37 34
-3912.67 0.00 35
0.00 -1567.58 36
0.00 -5791.33 43
3912.67 0.00 44
0.00 1567.58 45
34 35 36
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
1612.81 0.00 1789.68
0.00 -3088.95 0.00
-1789.68 0.00 -941.94
0 0 0
0 0 0
0 0 0
-2608.4478 0 0
0 1698.7583285 1425.90077
0 -1425.900773 -633.73368
26975.25 0.00 -2836.62
0.00 25106.92 4717.80
-2836.62 4717.80 29918.25
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
1262.77 0.00 2351.37
0.00 -3912.67 0.00
-2351.37 0.00 -1567.58
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
MATRIZ DE RIGIDEZ DEL SUELO -TIPO RESORTE

COLUN C1 COLUN C6 COLUN C13


Kb 3500 tn/m3 Kb 3500 tn/m3 Kb 3500 tn/m3
f 30 f 30 f 30
Seno 0.50 Seno 0.50 Seno 0.50
l1y 2.30 m l1y 4.00 m l1y 2.30 m
l1x 4.50 m l1x 5.25 m l1x 5.25 m
K1x 4528.1 K1x 9187.5 K1x 5282.8
K1y 4528.1 K1y 9187.5 K1y 5282.8
K1z 9056.3 K1z 18375.0 K1z 10565.6

COLUN C2 COLUN C3 COLUN C4


Kb 3500 tn/m3 Kb 3500 tn/m3 Kb 3500 tn/m3
f 30 f 30 f 30
Seno 0.50 Seno 0.50 Seno 0.50
l1y 2.30 m l1y 3.65 m l1y 3.80 m
l2y 3.65 m l2y 3.80 m l2y 3.00 m
l1x 4.50 m l1x 4.50 m l1x 4.50 m
K1x 11714.1 K1x 14667.2 K1x 13387.5
K1y 11714.1 K1y 14667.2 K1y 13387.5
K1z 23428.1 K1z 29334.4 K1z 26775.0

COLUN 12 COLUN 14 COLUN 15


Kb 3500 tn/m3 Kb 3500 tn/m3 Kb 3500 tn/m3
f 30 f 30 f 30
Seno 0.50 Seno 0.50 Seno 0.50
l1x 4.50 m l1y 2.30 m l1y 3.65 m
l2x 5.25 m l2y 3.65 m l2y 3.80 m
l1y 4.00 m l1x 4.50 m l1x 4.50 m
K1x 17062.5 K1x 11714.1 K1x 14667.2
K1y 17062.5 K1y 11714.1 K1y 14667.2
K1z 34125.0 K1z 23428.1 K1z 29334.4

COLUN C8 COLUN C9 COLUN C10


Kb 3500 tn/m3 Kb 3500 tn/m3 Kb 3500 tn/m3
f 30 f 30 f 30
Seno 0.50 Seno 0.50 Seno 0.50
l1y 2.30 m l1y 3.65 m l1y 3.80 m
l2y 3.65 m l2y 3.80 m l2y 3.00 m
l1x 4.50 m l1x 4.50 m l1x 4.50 m
l2x 5.25 m l2x 5.25 m l2x 5.25 m
K1x 25380.5 K1x 31778.9 K1x 29006.3
K1y 25380.5 K1y 31778.9 K1y 29006.3
K1z 50760.9 K1z 63557.8 K1z 58012.5

Rigideces en resortes
1 2 3 10 11
4528.1 0 01 11714.1 0
Kc1= 0 4528.1 02 Kc2= 0 11714.1
0 0 9056.3 3 0 0

28 29 30 37 38
13387.5 0 0 28 13781.3 0
Kc4= 0 13387.5 0 29 Kc5= 0 13781.3
0 0 26775.0 30 0 0

4 5 6 13 14
9810.9 0 04 25380.5 0
Kc7= 0 9810.9 05 Kc8= 0 25380.5
0 0 19621.9 6 0 0

31 32 33 40 41
29006.3 0 0 31 29859.4 0
Kc10= 0 29006.3 0 32 Kc11= 0 29859.4
0 0 58012.5 33 0 0

7 8 9 16 17
5282.8 0 07 11714.1 0
Kc13= 0 5282.8 08 Kc14= 0 11714.1
0 0 10565.6 9 0 0

34 35 36 43 44
13387.5 0 0 34 13781.3 0
Kc16= 0 13387.5 0 35 Kc17= 0 13781.3
0 0 26775.0 36 0 0
37 38 39 40 41 42 43 44 45
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
1262.77 0.00 2351.37 0 0 0 0 0 0
0.00 -3912.67 0.00 0 0 0 0 0 0
-2351.37 0.00 -1567.58 0 0 0 0 0 0
0 0 0 1262.77 0.00 2351.37 0 0 0
0 0 0 0.00 -3912.67 0.00 0 0 0
0 0 0 -2351.37 0.00 -1567.58 0 0 0
0 0 0 0 0 0 1262.77 0.00 2351.37
0 0 0 0 0 0 0.00 -3912.67 0.00
0 0 0 0 0 0 -2351.37 0.00 -1567.58
27229.12 0.00 -4116.38 -2608.4478 0 0 0 0 0
0.00 25346.22 -1425.90 0 1698.75833 1425.90077 0 0 0
-4116.38 -1425.90 30601.28 0 -1425.9008 -633.73368 0 0 0
-2608.4478 0 0 45915.69 0.00 -4116.38 -2608.4478 0 0
0 1698.758328 -1425.9008 0.00 46142.14 3291.89 0 1698.75833 1425.90077
0 1425.900773 -633.73368 -4116.38 3291.89 63391.27 0 -1425.9008 -633.73368
0 0 0 -2608.4478 0 0 27229.12 0.00 -4116.38
0 0 0 0 1698.75833 -1425.9008 0.00 25346.22 4717.80
0 0 0 0 1425.90077 -633.73368 -4116.38 4717.80 30601.28
1651.68 0.00 1674.95 0 0 0 0 0 0
0.00 -2934.50 0.00 0 0 0 0 0 0
-1674.95 0.00 -837.47 0 0 0 0 0 0
0 0 0 1651.68 0.00 1674.95 0 0 0
0 0 0 0.00 -2934.50 0.00 0 0 0
0 0 0 -1674.95 0.00 -837.47 0 0 0
0 0 0 0 0 0 1651.68 0.00 1674.95
0 0 0 0 0 0 0.00 -2934.50 0.00
0 0 0 0 0 0 -1674.95 0.00 -837.47
COLUN C18
Kb 3500 tn/m3
f 30
Seno 0.50
l1y 4.00 m
l1x 5.25 m
K1x 9187.5
K1y 9187.5
K1z 18375.0

COLUN C5 COLUN C7
Kb 3500 tn/m3 Kb 3500 tn/m3
f 30 f 30
Seno 0.50 Seno 0.50
l1y 3.00 m l1x 4.50 m
l2y 4.00 m l2x 5.25 m
l1x 4.50 m l1y 2.30 m
K1x 13781.3 K1x 9810.9
K1y 13781.3 K1y 9810.9
K1z 27562.5 K1z 19621.9

COLUN 16 COLUN 17
Kb 3500 tn/m3 Kb 3500 tn/m3
f 30 f 30
Seno 0.50 Seno 0.50
l1y 3.80 m l1y 3.00 m
l2y 3.00 m l2y 4.00 m
l1x 4.50 m l1x 4.50 m
K1x 13387.5 K1x 13781.3
K1y 13387.5 K1y 13781.3
K1z 26775.0 K1z 27562.5

COLUN C11
Kb 3500 tn/m3
f 30
Seno 0.50
l1y 3.00 m
l2y 4.00 m
l1x 4.50 m
l2x 5.25 m
K1x 29859.4
K1y 29859.4
K1z 59718.8

12 19 20 21
0 10 14667.2 0 0 19
0 11 Kc3= 0 14667.2 0 20
23428.1 12 0 0 29334.4 21

39 46 47 48
0 37 9187.5 0 0 46
0 38 Kc6= 0 9187.5 0 47
27562.5 39 0 0 18375.0 48

15 22 23 24
0 13 31778.9 0 0 22
0 14 Kc9= 0 31778.9 0 23
50760.9 15 0 0 63557.8 24

42 49 50 51
0 40 17062.5 0 0 49
0 41 Kc12= 0 17062.5 0 50
59718.8 42 0 0 34125.0 51

18 25 26 27
0 16 14667.2 0 0 25
0 17 Kc15= 0 14667.2 0 26
23428.1 18 0 0 29334.4 27

45 52 53 54
0 43 9187.5 0 0 52
0 44 Kc18= 0 9187.5 0 53
27562.5 45 0 0 18375.0 54
46 47 48 49 50 51 52 53
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
1651.68 0.00 1674.95 0 0 0 0 0
0.00 -2934.50 0.00 0 0 0 0 0
-1674.95 0.00 -837.47 0 0 0 0 0
0 0 0 1651.68 0.00 1674.95 0 0
0 0 0 0.00 -2934.50 0.00 0 0
0 0 0 -1674.95 0.00 -837.47 0 0
0 0 0 0 0 0 1651.68 0.00
0 0 0 0 0 0 0.00 -2934.50
0 0 0 0 0 0 -1674.95 0.00
16844.05 0.00 -5048.10 -2608.4478 0 0 0 0
0.00 16839.80 -1425.90 0 1698.75833 1425.90077 0 0
-5048.10 -1425.90 19846.21 0 -1425.9008 -633.73368 0 0
-2608.4478 0 0 27327.49 0.00 -5048.10 -2608.448 0
0 1698.75833 -1425.9008 0.00 29432.59 3291.89 0 1698.7583
0 1425.90077 -633.73368 -5048.10 3291.89 36229.94 0 -1425.901
0 0 0 -2608.4478 0 0 16844.05 0.00
0 0 0 0 1698.75833 -1425.9008 0.00 16839.80
0 0 0 0 1425.90077 -633.73368 -5048.10 4717.80
CALCULO DE FIJACIONES Y-Y

EJE A-A
BARRA 13 16 19 22 25
CARGA -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m
LONG 2.30 m 3.65 m 3.80 m 3.00 m 4.00 m
Mx1 20.31 51.16 55.45 34.56 61.44
My1 0 0 0 0 0
Fz1 -4.42 -7.01 -7.30 -5.76 -7.68
Mx2 -20.31 -51.16 -55.45 -34.56 -61.44
My2 0 0 0 0 0
Fz2 -4.42 -7.01 -7.30 -5.76 -7.68

EJE C-C
BARRA 15 18 21 24 27
CARGA -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m
LONG 2.30 m 3.65 m 3.80 m 3.00 m 4.00 m
Mx1 20.31 51.16 55.45 34.56 61.44
My1 0 0 0 0 0
Fz1 -4.42 -7.01 -7.30 -5.76 -7.68
Mx2 -20.31 -51.16 -55.45 -34.56 -61.44
My2 0 0 0 0 0
Fz2 -4.42 -7.01 -7.30 -5.76 -7.68

fijaciones coordenadas locales

20.31 1 20.31 4
0.00 2 0.00 5
f'13= -4.42 3 f'14= -4.42 6
-20.31 10 -20.31 13
0.00 11 0.00 14
-4.42 12 -4.42 15

51.16 16 55.45 19
0.00 17 0.00 20
f'18= -7.01 18 f'19= -7.30 21
-51.16 25 -55.45 28
0.00 26 0.00 29
-7.01 27 -7.30 30

34.56 31 34.56 34
0.00 32 0.00 35
f'23= -5.76 33 f'24= -5.76 36
-34.56 40 -34.56 43
0.00 41 0.00 44
-5.76 42 -5.76 45

fijaciones coordenadas GLOBALES

0.00 1 0.00 4
20.31 2 20.31 5
f13= -4.42 3 f14= -4.42 6
0.00 10 0.00 13
-20.31 11 -20.31 14
-4.42 12 -4.42 15

0.00 16 0.00 19
51.16 17 55.45 20
f18= -7.01 18 f19= -7.30 21
0.00 25 0.00 28
-51.16 26 -55.45 29
-7.01 27 -7.30 30

0.00 31 0.00 34
34.56 32 34.56 35
f23= -5.76 33 f24= -5.76 36
0.00 40 0.00 43
-34.56 41 -34.56 44
-5.76 42 -5.76 45

CALCULO DE FIJACIONES X-X

EJE 2-2 EJE 3-3


BARRA 1 2 BARRA 3
CARGA -3.84 Tn/m -3.84 Tn/m CARGA -3.84 Tn/m
LONG 4.50 m 5.25 m LONG 4.50 m
Mx1 0 0 Mx1 0
My1 77.76 105.84 My1 77.76
Fz1 -8.64 -10.08 Fz1 -8.64
Mx2 0 0 Mx2 0
My2 -77.76 -105.84 My2 -77.76
Fz2 -8.64 -10.08 Fz2 -8.64
EJE 6-6 EJE 7-7
BARRA 9 10 BARRA 11
CARGA -3.84 Tn/m -3.84 Tn/m CARGA -3.84 Tn/m
LONG 4.50 m 5.25 m LONG 4.50 m
Mx1 0 0 Mx1 0
My1 77.76 105.84 My1 77.76
Fz1 -8.64 -10.08 Fz1 -8.64
Mx2 0 0 Mx2 0
My2 -77.76 -105.84 My2 -77.76
Fz2 -8.64 -10.08 Fz2 -8.64

fijaciones coordenadas locales y globales

0.00 1 0.00 4
77.76 2 105.84 5
f1= -8.64 3 f2= -10.08 6
0.00 4 0.00 7
-77.76 5 -105.84 8
-8.64 6 -10.08 9

0.00 22 0.00 28
105.84 23 77.76 29
f6= -10.08 24 f7= -8.64 30
0.00 25 0.00 31
-105.84 26 -77.76 32
-10.08 27 -8.64 33

0.00 43 0.00 49
77.76 44 105.84 50
f11= -8.64 45 f12= -10.08 51
0.00 46 0.00 52
-77.76 47 -105.84 53
-8.64 48 -10.08 54

FUERZAS EXTERNAS

F Fe

0.00 1 0.00 1
20.31 2 0.00 2
-4.42 3 19.98 3
0.00 4 0.00 4
20.31 5 0.00 5
-4.42 6 36.40 6
0.00 7 0.00 7
20.31 8 0.00 8
-4.42 9 22.43 9
0.00 10 0.00 10
30.84 11 0.00 11
-11.42 12 51.47 12
0.00 13 0.00 13
30.84 14 0.00 14
-11.42 15 105.61 15
0.00 16 0.00 16
30.84 17 0.00 17
-11.42 18 39.29 18
0.00 19 0.00 19
4.29 20 0.00 20
-14.30 21 64.50 21
0.00 22 0.00 22
4.29 23 0.00 23
-14.30 24 139.79 24
54 0.00 25 0.00 25
01 4.29 26 0.00 26
02 -14.30 27 75.29 27
03 0.00 28 0.00 28
04 -20.89 29 0.00 29
05 -13.06 30 40.31 30
06 0.00 31 0.00 31
07 -20.89 32 0.00 32
08 -13.06 33 127.55 33
09 0.00 34 0.00 34
0 10 -20.89 35 0.00 35
0 11 -13.06 36 46.97 36
0 12 0.00 37 0.00 37
0 13 26.88 38 0.00 38
0 14 -13.44 39 47.81 39
0 15 0.00 40 0.00 40
0 16 26.88 41 0.00 41
0 17 -13.44 42 131.32 42
0 18 0.00 43 0.00 43
0 19 26.88 44 0.00 44
0 20 -13.44 45 59.17 45
0 21 0.00 46 0.00 46
0 22 -61.44 47 0.00 47
0 23 -7.68 48 34.64 48
0 24 0.00 49 0.00 49
0 25 -61.44 50 0.00 50
0 26 -7.68 51 49.64 51
0 27 0.00 52 0.00 52
0 28 -61.44 53 0.00 53
0 29 -7.68 54 40.43 54
0 30
0 31
0 32
0 33
0 34
0 35
0 36
0 37
0 38
0 39
0 40
0 41
0 42
1674.95 43
0.00 44
-837.47 45
0 46
0 47
0 48
0 49
1425.9008 50
-633.7337 51
-5048.10 52
4717.80 53
19846.21 54
EJE B-B
BARRA 14 17 20 23 26
CARGA -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m -3.84 Tn/m
LONG 2.30 m 3.65 m 3.80 m 3.00 m 4.00 m
Mx1 20.31 51.16 55.45 34.56 61.44
My1 0 0 0 0 0
Fz1 -4.42 -7.01 -7.30 -5.76 -7.68
Mx2 -20.31 -51.16 -55.45 -34.56 -61.44
My2 0 0 0 0 0
Fz2 -4.42 -7.01 -7.30 -5.76 -7.68

20.31 7 51.16 10 51.16


0.00 8 0.00 11 0.00
f'15= -4.42 9 f'16= -7.01 12 f'17= -7.01
-20.31 16 -51.16 19 -51.16
0.00 17 0.00 20 0.00
-4.42 18 -7.01 21 -7.01

55.45 22 55.45 25 34.56


0.00 23 0.00 26 0.00
f'20= -7.30 24 f'21= -7.30 27 f'22= -5.76
-55.45 31 -55.45 34 -34.56
0.00 32 0.00 35 0.00
-7.30 33 -7.30 36 -5.76

61.44 37 61.44 40 61.44


0.00 38 0.00 41 0.00
f'25= -7.68 39 f'26= -7.68 42 f'27= -7.68
-61.44 46 -61.44 49 -61.44
0.00 47 0.00 50 0.00
-7.68 48 -7.68 51 -7.68

0.00 7 0.00 10 0.00


20.31 8 51.16 11 51.16
f15= -4.42 9 f16= -7.01 12 f17= -7.01
0.00 16 0.00 19 0.00
-20.31 17 -51.16 20 -51.16
-4.42 18 -7.01 21 -7.01

0.00 22 0.00 25 0.00


55.45 23 55.45 26 34.56
f20= -7.30 24 f21= -7.30 27 f22= -5.76
0.00 31 0.00 34 0.00
-55.45 32 -55.45 35 -34.56
-7.30 33 -7.30 36 -5.76

0.00 37 0.00 40 0.00


61.44 38 61.44 41 61.44
f25= -7.68 39 f26= -7.68 42 f27= -7.68
0.00 46 0.00 49 0.00
-61.44 47 -61.44 50 -61.44
-7.68 48 -7.68 51 -7.68

3-3 EJE 4-4 EJE 5-5


4 BARRA 5 6 BARRA 7
-3.84 Tn/m CARGA -3.84 Tn/m -3.84 Tn/m CARGA -3.84 Tn/m
5.25 m LONG 4.50 m 5.25 m LONG 4.50 m
0 Mx1 0 0 Mx1 0
105.84 My1 77.76 105.84 My1 77.76
-10.08 Fz1 -8.64 -10.08 Fz1 -8.64
0 Mx2 0 0 Mx2 0
-105.84 My2 -77.76 -105.84 My2 -77.76
-10.08 Fz2 -8.64 -10.08 Fz2 -8.64
CALCULO DE F EXTERNAS
12
-3.84 Tn/m C1 19.98 Tn C3 64.50 Tn
5.25 m C7 36.40 Tn C9 139.79 Tn
0 C13 22.43 Tn C15 75.29 Tn
105.84
-10.08
0 C2 51.47 Tn C4 40.31 Tn
-105.84 C8 105.61 Tn C10 127.55 Tn
-10.08 C14 39.29 Tn C16 46.97 Tn

0.00 10 0.00 13 0.00


77.76 11 105.84 14 77.76
f3= -8.64 12 f4= -10.08 15 f5= -8.64
0.00 13 0.00 16 0.00
-77.76 14 -105.84 17 -77.76
-8.64 15 -10.08 18 -8.64

0.00 31 0.00 37 0.00


105.84 32 77.76 38 105.84
f8= -10.08 33 f9= -8.64 39 f10= -10.08
0.00 34 0.00 40 0.00
-105.84 35 -77.76 41 -105.84
-10.08 36 -8.64 42 -10.08

VECTOR DE FUERZAS (F-Fe) DESPLAZAMIENTOS FINALES [U]

F-Fe [U]

0.00 1 0.00129 1
20.31 2 0.00183 2
-24.40 3 -0.00258 3
0.00 4 0.00099 4
20.31 5 0.00109 5
-40.81 6 -0.00242 6
0.00 7 0.00153 7
20.31 8 0.00295 8
-26.85 9 -0.00389 9
0.00 10 0.00004 10
30.84 11 0.00159 11
-62.89 12 -0.00240 12
0.00 13 -0.00008 13
30.84 14 0.00087 14
-117.03 15 -0.00226 15
0.00 16 -0.00002 16
30.84 17 0.00214 17
-50.72 18 -0.00250 18
0.00 19 -0.00016 19
4.29 20 0.00022 20
-78.80 21 -0.00255 21
0.00 22 -0.00010 22
4.29 23 0.00032 23
-154.09 24 -0.00238 24
0.00 25 -0.00026 25
4.29 26 0.00051 26
-89.59 27 -0.00303 27
0.00 28 -0.00001 28
-20.89 29 -0.00065 29
-53.37 30 -0.00200 30
0.00 31 0.00008 31
-20.89 32 -0.00016 32
-140.61 33 -0.00241 33
0.00 34 0.00001 34
-20.89 35 -0.00050 35
-60.03 36 -0.00208 36
0.00 37 -0.00015 37
26.88 38 0.00093 38
-61.25 39 -0.00210 39
0.00 40 -0.00010 40
26.88 41 0.00064 41
-144.76 42 -0.00242 42
0.00 43 -0.00027 43
26.88 44 0.00122 44
-72.61 45 -0.00267 45
0.00 46 -0.00090 46
-61.44 47 -0.00359 47
-42.32 48 -0.00278 48
0.00 49 -0.00040 49
-61.44 50 -0.00158 50
-57.32 51 -0.00155 51
0.00 52 -0.00034 52
-61.44 53 -0.00287 53
-48.11 54 -0.00190 54
13
14
15
22
23
24

28
29
30
37
38
39

43
44
45
52
53
54

13
14
15
22
23
24

28
29
30
37
38
39

43
44
45
52
53
54

8
-3.84 Tn/m
5.25 m
0
105.84
-10.08
0
-105.84
-10.08
C5 47.81 Tn
C11 131.32 Tn
C17 59.17 Tn

C6 34.64 Tn
C12 49.64 Tn
C18 40.43 Tn

19
20
21
22
23
24

40
41
42
43
44
45

ALES [U]
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

"DISEO ESTRUCTURAL DE VIVIENDA MULTIFAMILIAR - 2 NIVELES "

CARACTERISTICAS DE LA EDIFICACION

CARACTERISTICAS GEOMETRICAS DE LA ESTRUCTURA

Largo = 19.70 m
Ancho = 10.00 m
N De Prticos X-X = 7
N De Prticos Y-Y = 3
N De Pisos = 2 Pisos
Altura Entre Piso (1 Piso) = 2.500 m
Altura Entre Piso (2 Piso) = 2.500 m
Ancho de Tabiqueria = 0.15 m

CARACTERISTICAS DEL CONCRETO Y ACERO DE REFUERZO

Resistencia a la Compresion f'c = 210 Kg/cm


Peso Especifico del Concreto c = 2400 Kg/m
Esfuerzo de Fluencia del Acero fy = 4200 Kg/cm
Peso Espec. del Muro de Albaileria = 1800 Kg/m

PESO POR METRO CUADRADO (RNE - E.020 CARGAS)

Vivienda S/C = 200 Kg/m


S/C azotea = 100 Kg/m

CALCULO DE TABIQUERIA EQUIVALENTE

Tabiquera Equivalente Azotea = 100 Kg/m (Tabiquera mnima segn Norma E-0.20)
Tabiquera Equivalente 1 - 2 Nivel = 168 Kg/m

Peso Tab. Equiv. = (Long.Tab.*e*h*y)/(area techada)

Tabiqueria Equivalente
TRAMO LONGITUD Long. Tabiq. 44.85 m
entre eje 1 - 2 3.80 m e 0.15 m
entre eje 2 - 3 6.80 m h 2.50 m
entre eje 3 - 4 7.10 m 1800 Kg/m
entre eje 4 - 5 5.50 m Area Techada 179.77 m
entre eje 5 - 6 7.30 m Peso T.E. 168 Kg/m
entre eje 6 - 7 5.10 m 01 PISO - 02 PISO

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

entre eje A - B 4.25 m


entre eje B - C 5.00 m
Long. Tabiq. 44.85 m

PREDIMENSIONAMIENTO DE ELEMENTOS ESTRUCTURALES

PREDIMENSIONAMIENTO DE LOSA MACIZA

Tomamos a criterio la luz libre mas larga en cada direccin (Asumiendo columnas de 0.30m x 0.30m)

Direccin X-X = Ln= 5.125 m TIPO DE LOSA: LOSA EN DOS DIRECCIONES

Direccin Y-Y = Ln= 3.750 m PERALTE DE LOSA: H=Ln/40, H=2P/180

Peralte de la losa Maciza: Ln=Luz Libre

H= 0.128 m Adoptamos un H= 0.150 m


H= 0.099 m

PREDIMENSIONAMIENTO DE VIGAS

b 25 cm
h L/12 (VIGAS X-X) L=Luz a ejes
h L/12 (VIGAS Y-Y)

Tomamos a criterio la luz a ejes mas larga en cada direccin

Peralte de Vigas (h)

Direccin X-X = Ln= 5.300 m h= 0.44 m h=

Direccin Y-Y = Ln= 3.950 m h= 0.33 m h=

Ancho de Vigas (h)

Direccin X-X = Ln= 0.450 m b= 0.23 m b=

Direccin Y-Y = Ln= 0.350 m b= 0.18 m b=

Adoptamos :
direccion X-X 0.25 m x 0.45 m

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

direccion Y-Y 0.25 m x 0.35 m

PREDIMENSIONAMIENTO DE COLUMNAS

P
bxD=
nxfc

Donde: TIPO - VALORES DE C P n


C1 Columnas Interiores 1.10xPG 0.30
f'c = 210 Kg/cm C2,C3 Columnas extremas de porticos interiores 1.25xPG 0.25
C4 Columnas Esquinas 1.50xPG 0.20

DATOS A USAR VIGAS X-X


N De Pisos = 2 Pisos VIGAS Y-Y
Altura Primer Piso (1 Piso) = 2.50 m VIGA X-Y
Altura Entre Piso (2 Piso) = 2.50 m V. CHATAS
Peso Unitario losa = 360 Kg/m COLUMNAS
Pisos y Acabados = 100 Kg/m
Ancho de Tabiqueria = 0.150 m
Espesor de Losa = 0.150 m
Vivienda S/C = 200 Kg/m

AREA TRIBUTARIA MAS DESFAVORABLE SEGN EL TIPO DE COLUMNA


Col. VIGA X-X VIGA Y-Y VIGA X-Y VIGA CH
3-C (Col. Exterior) 2.56 3.48 0.00 0.00
C-7 (Col. Esquina) 2.56 1.28 0.00 0.00
3-B(Col. Interior) 4.50 3.48 0.00 0.00

COLUMNAS INTERIORES PRIMER NIVEL

COLUMNA : C1 EJE 3-B(Col. Interior) AREA TRIBUTARIA =


ELEMENTOS P . UNIT Largo Ancho
PESO DE LOSA 360 Kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.97 0.15 m
PESO PISOS Y ACABADOS 100 Kg/m
PESO DE VIGA X-X 2400 Kg/m 4.50 0.25

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

PESO DE VIGA Y-Y 2400 Kg/m 3.48 0.25


PESO DE VIGA X-Y 2400 Kg/m 0.25
PESO DE VIGA CHATA 2400 Kg/m 0.20
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25

CM= 17466.93 kg CV= 3538.00 kg

COLUMNAS EXTERIORES PRIMER NIVEL

COLUMNA : C3 EJE 3-C (Col. Exterior) AREA TRIBUTARIA =


ELEMENTOS P . UNIT Largo Ancho
PESO DE LOSA 360 Kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 6.04 0.15 m
PESO PISOS Y ACABADOS 100 Kg/m
PESO DE VIGA X-X 2400 Kg/m 2.56 0.25
PESO DE VIGA Y-Y 2400 Kg/m 3.48 0.25
PESO DE VIGA X-Y 2400 Kg/m 0.25
PESO DE VIGA CHATA 2400 Kg/m 0.20
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25

CM= 12453.34 kg CV= 2094.00 kg

COLUMNAS ESQUINERAS PRIMER NIVEL


COLUMNA : C4 EJE C-7 (Col. Esquina) AREA TRIBUTARIA =
ELEMENTOS P . UNIT Largo Ancho
PESO DE LOSA 360 Kg/m
PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m
PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.84 0.15 m
PESO PISOS Y ACABADOS 100 Kg/m
PESO DE VIGA X-X 2400 Kg/m 2.56 0.25
PESO DE VIGA Y-Y 2400 Kg/m 1.28 0.25
PESO DE VIGA X-Y 2400 Kg/m 0.25
PESO DE VIGA CHATA 2400 Kg/m 0.20
PESO DE COLUMNAS 2400 Kg/m 2.50 0.25

CM= 6622.83 kg CV= 858.00 kg

CUADRO RESUMEN

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

COLUMNAS INTERIORES

NIVEL Pu PG P=1.1xPG n AREA (cm2) SECCION (cm)


1 21004.93 kg
63014.78 kg 69316.3 0.3 1100.26 33.17
2 21004.93 kg

ADOPTAR 35.00 x 35.00

COLUMNAS PERIMETRAL

NIVEL Pu PG P=1.25xPG n AREA (cm2) SECCION (cm)


1 14547.34 kg
43642.01 kg 54552.5 0.25 1039.10 32.24
2 14547.34 kg

ADOPTAR 30.00 x 30.00

COLUMNAS ESQUINERAS

NIVEL Pu PG P=1.50xPG n AREA (cm2) SECCION (cm)


1 7480.83 kg
22442.49 kg 33663.7 0.2 801.52 28.31
2 - 3 7480.83 kg

ADOPTAR 30.00 x 30.00

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

R - 2 NIVELES "

mnima segn Norma E-0.20)

44.85 m
0.15 m
2.50 m
1800 Kg/m
179.77 m
168 Kg/m

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

LOSA EN DOS DIRECCIONES

H=Ln/40, H=2P/180

Ln=Luz Libre

L=Luz a ejes

0.45 m

0.35 m

0.25 m

0.25 m

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

0.25 m x 0.45 m
0.25 m x 0.35 m
0.25 m x 0.15 m
0.20 m x 0.15 m
0.25 m x 0.25 m

A.T. 1NIVEL A.T. 2NIVEL


10.47 10.47
4.29 4.29
17.69 17.69

COLUMNAS INTERIORES 2NIVEL

RIA = 17.690m COLUMNA : C1 EJE 3-B(Col. Interior) AREA TRIBUTARIA =


Alto PARCIAL ELEMENTOS P . UNIT Largo
6368.40 kg PESO DE LOSA 360 Kg/m
2978.98 kg PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m
2.50 4029.75 kg PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 5.97
1769.00 kg PESO PISOS Y ACABADOS 100 Kg/m
0.45 1215.00 kg PESO DE VIGA X-X 2400 Kg/m 4.50

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

0.35 730.80 kg PESO DE VIGA Y-Y 2400 Kg/m 3.48


0.15 0.00 kg PESO DE VIGA X-Y 2400 Kg/m
0.15 0.00 kg PESO DE VIGA CHATA 2400 Kg/m
0.25 375.00 kg PESO DE COLUMNAS 2400 Kg/m 2.50
TOTAL 17466.93 kg

PU= 21004.93 kg CM= 17466.93 kg CV= 3538.00 kg

COLUMNAS EXTERIORES 2 NIVEL

RIA = 10.470m COLUMNA : C3 EJE 3-C (Col. Exterior) AREA TRIBUTARIA =


Alto PARCIAL ELEMENTOS P . UNIT Largo
3769.20 kg PESO DE LOSA 360 Kg/m
1763.14 kg PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m
2.50 4077.00 kg PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 6.04
1047.00 kg PESO PISOS Y ACABADOS 100 Kg/m
0.45 691.20 kg PESO DE VIGA X-X 2400 Kg/m 2.56
0.35 730.80 kg PESO DE VIGA Y-Y 2400 Kg/m 3.48
0.15 0.00 kg PESO DE VIGA X-Y 2400 Kg/m
0.15 0.00 kg PESO DE VIGA CHATA 2400 Kg/m
0.25 375.00 kg PESO DE COLUMNAS 2400 Kg/m 2.50
TOTAL 12453.34 kg

PU= 14547.34 kg CM= 12453.34 kg CV= 2094.00 kg

COLUMNAS ESQUINERAS 2 NIVEL


RIA = 4.290m COLUMNA : C4 EJE C-7 (Col. Esquina) AREA TRIBUTARIA =
Alto PARCIAL ELEMENTOS P . UNIT Largo
1544.40 kg PESO DE LOSA 360 Kg/m
722.43 kg PESO DE TABIQUERIA EQUIVALENTE 168 Kg/m
2.50 2592.00 kg PESO DE TABIQUERIA EN VIGAS 1800 Kg/m 3.84
429.00 kg PESO PISOS Y ACABADOS 100 Kg/m
0.45 691.20 kg PESO DE VIGA X-X 2400 Kg/m 2.56
0.35 268.80 kg PESO DE VIGA Y-Y 2400 Kg/m 1.28
0.15 0.00 kg PESO DE VIGA X-Y 2400 Kg/m
0.15 0.00 kg PESO DE VIGA CHATA 2400 Kg/m
0.25 375.00 kg PESO DE COLUMNAS 2400 Kg/m 2.50
TOTAL 6622.83 kg

PU= 7480.83 kg CM= 6622.83 kg CV= 858.00 kg

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

SECCION (cm)

x 33.17

SECCION (cm)

x 32.24

SECCION (cm)

x 28.31

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

PREDIMENSIONAMIENTO DE VIGAS

b 25 cm O b=H/2 -------> b= 20.000 cm

1.1.1 ) PARA VIGAS PRINCIPALES MAS DESFAVORABLES

h Luz/12

VIGAS LUZ h h a tomar b a tomar


PRINCIPALES 5.25 0.44 45 25

1.1.2 ) PARA VIGAS SECUNDARIAS MAS DESFAVORABLES

h Luz/14

VIGAS LUZ h h a tomar b a tomar


SECUNDARIAS 3.90 0.28 35 25

Vigas Direccin X-X 0.25 m x 0.45 m

Vigas Direccin Y-Y 0.25 m x 0.35 m

PREDIMENSIONAMIENTO DE LOSAS

h Ln/25
h= 5.25/25 = 0.20 m

Determinamos el espesor de la losa siguiendo la norma E.0.60 y ACI


* simplemente apoyada h Luz/16 --------
* con un extremo continuo h Luz/18.5 0.151
FACTORES
* ambos extremos continuo h Luz/21 0.180
* en voladizo h luz/8 0.150

ESPERSOR DE LOSA e= 20

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

AREA TRIBUTARIA = 17.690m


Ancho Alto PARCIAL
6368.40 kg
2978.98 kg
0.15 2.50 4029.75 kg
1769.00 kg
0.25 0.45 1215.00 kg

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
UNIVERSIDAD NACIONAL PEDRO RUIZ GALLO
FACULTAD DE INGENIERA CIVIL, SISTEMAS Y ARQUITECTURA
Escuela Profesional de Ingeniera Civil

0.25 0.35 730.80 kg


0.25 0.15 0.00 kg
0.20 0.15 0.00 kg
0.25 0.25 375.00 kg
TOTAL = 17466.93 kg

PU= 21004.93 kg

AREA TRIBUTARIA = 10.470m


Ancho Alto PARCIAL
3769.20 kg
1763.14 kg
0.15 m 2.50 4077.00 kg
1047.00 kg
0.25 0.45 691.20 kg
0.25 0.35 730.80 kg
0.25 0.15 0.00 kg
0.20 0.15 0.00 kg
0.25 0.25 375.00 kg
TOTAL = 12453.34 kg

PU= 14547.34 kg

AREA TRIBUTARIA = 4.290m


Ancho Alto PARCIAL
1544.40 kg
722.43 kg
0.15 m 2.50 2592.00 kg
429.00 kg
0.25 0.45 691.20 kg
0.25 0.35 268.80 kg
0.25 0.15 0.00 kg
0.20 0.15 0.00 kg
0.25 0.25 375.00 kg
TOTAL = 6622.83 kg

PU= 7480.83 kg

PREDIMENSIONAMIENTO
PARIAHUACHE PUELLES CHRISTIAN
PROYECTO DE 2 PISOS

Segn las caracteristicas de la edificacin, esta se encuentra clasificada en la


Categoria "C", para la cual se consider :
25 % Carga Viva en los entre pisos, para los 2 niveles.

ALTURAS DE ENTREPISO PARA METRADO


h1 2.60 m
h2 2.60 m

1 ENTREPISO (h1)

Metrado de vigas

EJE CANT. LONG. ANCHO PERALTE VOLUMEN


m m m m3
X-X 7 4.50 0.25 0.45 3.544
7 5.25 0.25 0.45 4.134
Y-Y 3 19.28 0.25 0.35 5.061
Volumen Total 12.739

Metrado de Losa 27 10

Area Vacios = 17.23 m


Area Total = 197.00 m
Area de Vigas = 31.52 m
Area de Losa = 148.25 m
Area Total = 148.25 m m2

Metrado de Cielo Raso

Area de Losa = 148.252 m


Espesor = 0.15 m
Volumen Total = 22.238 m3
Metrado de Columnas

TIPO CANT. b t ALTO VOLUMEN


m m m m3
C-1 5 0.35 0.35 2.60 1.593
C-3 12 0.30 0.30 2.60 2.808
C-4 4 0.30 0.30 2.60 0.936
Volumen Total 5.337

Metrado de Tabiquera

rea Total = 148.252 m2

Peso Total del 1,2 Entrepiso

Elemento P. Unitario Unidad Volumen m3 Peso (kg.)


Losa 360 kg/m2 148.252 53370.540
Cielo raso 2000 kg/m3 22.238 44475.450
Vigas 2400 kg/m3 12.739 30573.900
Columnas 2400 kg/m3 5.337 12807.600
Tabiqueria 168 kg/m2 148.252 24965.395
Sobrecarga 25% 200 kg/m2 148.252 74.126
W1 166.27 Tn