Automatic Main Failure Module RS3R12 & RS3R24

ILLUSTRATING VIEW

2 1 12
3 11

10
5
6
9
7 8
(1) Model number (7) Cool button
(2) Fuses (8) Heat button
(3)12V DC for RS3R12 or 24V DC for RS3R24 input (9) Start button
(4) 220V AC input (10) Starter + DC positive+ valve
(5) Remote start + oil protection (11) Dry contact NC or NO
(6) ON – OFF oil protection button (12) 4 Fixing holes

TECHNICAL SPECIFICATIONS

- Operation Temperature range: -30ºC to +70ºC


- Maximum humidity: 95%
- Dimensions: 16.6 x 7.3 cm
- Weight: 140 gram
- Input DC voltage: 12v for RS3R12 model, 24V for RS3R24 model
- Two possibilities for dry contact signal: Alarm or Load (depending of programming)
- In order to provide extra security the RS3R12 & RS3R24 give alarm signal with slow beeping
sound and shutting down in the following cases:
• Low oil pressure,
• AC current feed on the board between engine cranking attempts
• Four failures of engine cranking attempts
• Unacceptable AC voltage for consecutive three seconds
- Possibility of using dry contact as a NO or NC
- Possibility to set the cooling time
- Possibility to set the loading time
- Possibility to set the delay of engine cranking after the absence of electricity
- Possibility to set the time between feeding on the protection board by DC voltage and the
engine cranking (this option is used for engines provided by electrical lift pump)
- Possibility to use or to cancel the oil protection
Page 1 of 3
PROGRAMMING

The PWR led of the DC supply should be lit to start programming

1- To enter the program mode, hold the


COOL + HEAT + START buttons in the same
time to hear the beeping sound and to
see the yellow flashing light in the TIME led.

2- To get alarm signal from the dry


contact, hold the COOL button for 2
seconds, and you’ll hear 2 beeping
sound.
Return line

3- To get load signal from the dry contact,


hold the HEAT button for 2 seconds, and
you’ll hear 2 beeping sound.

4- To set the starting motor, hold the START


button for 8 seconds, and you’ll hear 8
beeping sounds.

Page 2 of 3
5- To set the cool down of the engine,
hold the COOL button from 1 second to
20 minutes depending on your need,
each second of the time set you’ll hear
the beeping sound and see the TIME led
flashing.

6- To set the delay time of loading, hold


the HEAT button from 1 to 20 seconds
depending on your need, each second
of the time set you’ll hear the beeping
sound and see the TIME led flashing.

7- To set the delay of engine cranking


after the absence of electricity, hold the
COOL + HEAT buttons in the same time
from 1 to 20 seconds depending on your
need, each second of the time set you’ll
hear the beeping sound and see the
TIME led flashing. In order to cancel this
setting hold COOL + HEAT buttons for just
one long beeping.

8- To set the time between feeding on


the protection board by DC voltage
and the engine cranking, hold the HEAT
+ START buttons in the same time from 1
to 20 seconds depending on your need,
each second of the time set you’ll hear
the beeping sound and see the TIME led
flashing. In order to cancel this setting
hold HEAT + START buttons for just one
long beeping.

N.B.: While the programming, the maximum time between step 1 and 2, or 1 and 3 is
maximum 2 seconds.

SUMMARY:
- To set the AMF board on ALARM signal apply steps (1, 2, 4 and 5).
- To set the AMF board on LOAD signal apply steps (1, 3, 4, 5 and 6).
- 7 and 8 are options