STANDARD FEATURES
Casing Flatform
The casing is built on a framework of extruded Aluminum profiles assembled by
means of insertion joints sturdy nylon corner pieces. This makes assembly much

AIR HANDLING
easier and allows to place the air handling units in locations that could not be
considered before.
Slope design for drain pan with galvanized sheet to prevent standing water and
minimize microbial growth can meet challenging indoor air quality (IAQ), controls, and
acoustic (sound sensitive) projects.

Panels
3
25 mm double wall high density (45 kg/m ) panels manufactured by injecting
polyurethane foam between two metal sheet. Exterior wall shall be fabricated from
2,500 m3/hr ... 0.5 mm pre-painted galvanized sheet and factory applied protection film.
Panels assembled with mechanical fasteners such that each panel is individually
65,000 m3/hr removable. Access door are completed constructed with the same material as casing
panels shall permit a complete 180o swing at nylon reinforced door hinge.

Fans
All units equipped with High Performance double inlet centrifugal fans with scaling in
accordance to AMCA Standard for maximum performance.
The following fan types are available :
3 3
• Forward Curved blade Fans : Volume flow from 200 m /h to 140,000 m /h
Total pressure up to 1,000 Pa
• Backward Curved blade Fans : Volume flow from 200 m3/h to 110,000 m3/h
Total pressure up to 2,000 Pa

Electric Motor
Factory furnished and installed 3-phase Asynchronous Induction Motor fan motors
shall be mounted inside the unit. The Motors are totally enclosed fan cooled (TEFC)
type with 380Volts, 3 Phase, 50 Hz electrical supply, class F Insulation and IP 54
Degree of Protection. Other specification motors are available on Request.
Fan and Motor Base are made of painted heavy gauge galvanized steel to ensure
proper installation.

FE
Chilled Water or Direct Expansion
Coils
Designed, manufactured and tested by AICOOL. Chilled Water Coil are aluminum
finned copper tube that have galvanized steel casing end plate, copper tubes header
ADE IN
M with male threaded connections. Mechanically expanded copper tubes on aluminum
BEST fin construction with die-formed spacer collars for uniform spacing and leak tested to
PERFORMANCE
a minimum 450 psig air pressure under water. Completed with manual air vent plug
N
for all water coils.
I

DO I
NES
Evaporator (DX) coils and heating coils are an options.

Every Cooling Solution... We Have It AICOOL reserves the right to change in specifications without prior notice
SPECIFICATION DATA
AIR HANDLING UNIT
MODEL FE 01 FE 02 FE 03 FE 04 FE 05 FE 06 FE 07 FE 08 FE 09 FE 10
GUIDE SPECIFICATIONS
@2.0 m/s CMH 2,925 4,175 5,427 10,791 16,304 18,115 21,181 27,525 30,784 46,246 * Indoor mounted central station
(400 FPM) CFM 1,722 2,458 3,196 6,354 9,600 10,667 12,467 16,207 18,127 27,231 air handling unit designed to
3,291 4,697 6,106 12,140 18,341 20,379 23,829 30,965 34,632 52,027 provide air to a conditioned space
@2.3 m/s CMH as required to meet specified
(450 FPM) CFM 1,938 2,766 3,595 7,148 10,800 12,000 14,026 18,233 20,392 30,635 performance requirements for
@2.5 m/s CMH 3,656 5,219 6,784 13,489 20,379 22,644 26,477 34,406 38,480 57,807 ventilation, heating, cooling and
Airflow (500 FPM) CFM air distribution.
2,153 3,073 3,995 7,943 12,000 13,333 15,584 20,259 22,658 34,039
@2.8 m/s CMH 4,022 5,741 7,463 14,838 22,417 24,908 29,124 37,846 42,328 63,588 * Unit shall be assembled for
(550 FPM) CFM 2,368 3,380 4,394 8,737 13,200 14,667 17,142 22,285 24,924 37,443 draw thru application and shall
be arranged to discharge
kW 15 29 42 80 125 138 165 216 246 333 conditioned air horizontally.
4 Rows
MBtu/h 52 99 144 275 427 471 564 739 839 1,135
* Unit with a direct expansion
kW 23 36 51 98 143 160 187 246 270 384
5 Rows cooling coil shall have capability
Cooling Coil MBtu/h 77 123 172 335 489 546 640 840 920 1,311 to be used in a refrigerant circuit
Capacity* kW 27 41 57 108 165 184 209 271 307 467 in conjunction with a field supplied
6 Rows and matched condensing unit.
MBtu/h 90 141 194 369 565 629 712 925 1,048 1,594
kW 32 48 64 124 189 205 241 315 353 519
8 Rows
MBtu/h 109 163 219 422 644 700 824 1,075 1,205 1,771
Length mm 1,131 1,131 1,131 1,477 1,477 1,824 2,211 2,211 2,558 2,558
Basic Unit
Width mm 1,090 1,284 1,477 1,824 2,252 2,252 2,599 2,599 2,904 3,679
Dimension
Height mm 654 854 1,054 1,160 1,384 1,577 1,577 1,924 1,924 2,352
*) Nominal Cooling Capacity Conditions: Evaporator Air Inlet Temp. 26.7°C / 50%, Airflow @2.5 m/s velocity, Chilled Water Inlet Temp. 6 °C; Outlet Temp. 12 °C, Fin spacing 2mm (12FPI)
We improve our products continuously, therefore we reserve the right to make modifications without prior notice.

DUCT CONNECTION DATA


Unit FE 01 FE 02 FE 03 FE 04 FE 05 FE 06 FE 07 FE 08 FE 09 FE 10
H
Fan Type 225/250 280/315 355/400 450/500 500/560 630 710 800 900 1000
Supply Fan 1 288 x288 361 x361 453 x453 569 x569 638 x638 801 x801 898 x898 1007 x1007 1130 x1130 1267 x1267
Supply Fan 2 322 x322 404 x404 507 x507 638 x638 715 x715 - - - - -
Return 500 x1000 700 x1200 900 x1400 900 x1700 1200 x2100 1400 x2100 1400 x2500 1600 x2500 1600 x2800 2100 x3500

W L The FE series are designed with wide range option functions : Reheat Coil, Higher Class Filter, Integrated Heater, in simple modular form