Normal inverse ("inverse") IEC

Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
0.14 1000 3 1.12 1 0.12 1.14 0.2 0.23 0.14
T= x Tp
(I/Ip) 0.02
-1

Very inverse ("short in") IEC


Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
13.5 1000 3 333.33 1 332.33 0.04 0.2 0.01 13.5
T= x Tp
(I/Ip)1 - 1

Extremely inverse ("extr inv") IEC


Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
80 1000 3 ### 1 ### 0 0.2 0 80
T= x Tp
(I/Ip) - 1
2

Long time inverse ("long inv") IEC


Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
120 1000 3 333.33 1 332.33 0.36 0.2 0.07 120
T= x Tp
(I/Ip) - 1
1

RI-curve ("RI")

Ip (set Tp (set
pickup time
value) multiplier)
1 0.34 0.24 0.1 3 1000 0 0 3236.25 0.2 647.25

RD-curve ("RD")
Inverse ANSI/IEEE
Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
8.93 1000 3 191603.53 1 191602.53 0.000046628 0.18 0.18 0.2 0.04 8.93
( )
t= (I/Ip)2.0938 - 1 + 0.17966 x D
Short inverse ("short in") ANSI/IEEE
Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
0.27 1000 3 1870.34 1 1869.34 0.000142456 0.03 0.03 0.2 0.01 0.27
( )
t= (I/Ip)1.2969 - 1 + 0.03393 x D
Long inverse ("long inv") ANSI/IEEE
Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
5.61 1000 3 333.33 1 332.33 0.016893581 2.19 2.2 0.2 0.44 5.61
(
t= (I/Ip) - 1 )
+ 2.18592 x D

Moderately inverse ("mode inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
0.01 1000 3 1.12 1 0.12 0.083603053 0.02 0.11 0.2 0.02 0.01
(
t= (I/Ip)0.02 - 1 )
+ 0.0228 x D

Very inverse ("very inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
3.92 1000 3 111111.11 1 111110.11 0.000035298 0.1 0.1 0.2 0.02 3.92
(
t= (I/Ip)2 - 1 )
+ 0.0982 x D

Extremely inverse ("extr inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
5.64 1000 3 111111.11 1 111110.11 0.000050760 0.02 0.02 0.2 0 5.64
(
t= (I/Ip)2 - 1 )
+ 0.02434 x D

Definite inverse ("def inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
0.48 1000 3 8749.8 1 8748.8 0.000054830 0.21 0.21 0.2 0.04 0.48
( )
t= (I/Ip)1.5625 - 1 + 0.21359 x D
Squared inverse ("I-squared-t") ANSI/IEEE
Ip (set
I (fault pickup D (set time t (tripping
current) value) dialer) Time)
1000 3 111111.11 50.7 0.20 10.14 10.14 20.28 0 50.7 x D + 10.14
t=
(I/Ip)2