MECA 5A IEE
SOLAR POWER CALCULATION
Type of losses
SOLAR POWER CALCULATION
1.-Estimated losses due to
temperature and radiation: 9%
Photovoltaic efficiency is affected
by the temperature of the module,
in general efficiency decreases
with increasing temperature.
SOLAR POWER CALCULATION
2.-Estimated losses because not all
solar radiation reaches the sensitive
material of the panel and produces
electricity: 2.5%
SOLAR POWER CALCULATION
3.-Losses inside the electronic stage of
conversion to alternating current,
as are the losses caused by diodes, regulators
and inverters.
Plus the losses in the wiring necessary to reach
the precise place where you will consume the
electricity: 12%
SOLAR POWER CALCULATION
4.-Other losses: 1.5%
Total loss adopted: 25%
Loss factor = 1 - 0.25 = 0.75
SOLAR POWER CALCULATION
Applied to the previous calculation (*)
Photovoltaic energy resulting in AC per day
= Photovoltaic power installed in CC x
Solar Radiation per day x 0.75
For a 1kW (STC) installation consisting of
5 flat 200 watt photovoltaic panels:
It is 5 x 200 Watt = 1000 W = 1kW
Solar radiation accumulated during one day
of 2.9 kW / m² per day
SOLAR POWER CALCULATION
Queretaro, Ecologia 274, Tecnologico (Home): 17° N
Deorientation South: 0°
CHARGE REGULATOR:
OPEN SYSTEM TOTAL INTENSITY: 41.00 A
CLOSED SYSTEM TOTAL INTENSITY: 38.91 A
REGULATOR: 1 unit
A max: 45 A Voc: 48 V Eficiency: 89.6%
A. total 45 A
SOLAR POWER CALCULATION
BATTERIES: 12 UNITS
AUTONOMY: 3 DAYS
DISCHARGE: 60%
INVERSOR CHARGER
Efficiency 94
Units: 1
SOLAR POWER CALCULATION
www.lawebdelasenergiasrenovables.com
Promedio por meses (datos tomados por sátelites durante 22 años Julio 1983 - Junio 2005).
Radiación Solar Resultados: Coordenadas [ 21 / -100 ] cerca de Querétaro - Queretaro de Arteaga - Mexico