This document provides settings for fire pumps and jockey pumps according to NFPA-3 Chapter 4 standards. It specifies that the jockey pump will start at 165 PSI and stop at 175 PSI, while fire pump #1 will start at 160 PSI and can only be stopped manually, and fire pump #2 will start at 150 PSI and also only stop manually. The pressure relief valve is set to 175 PSI.
This document provides settings for fire pumps and jockey pumps according to NFPA-3 Chapter 4 standards. It specifies that the jockey pump will start at 165 PSI and stop at 175 PSI, while fire pump #1 will start at 160 PSI and can only be stopped manually, and fire pump #2 will start at 150 PSI and also only stop manually. The pressure relief valve is set to 175 PSI.
This document provides settings for fire pumps and jockey pumps according to NFPA-3 Chapter 4 standards. It specifies that the jockey pump will start at 165 PSI and stop at 175 PSI, while fire pump #1 will start at 160 PSI and can only be stopped manually, and fire pump #2 will start at 150 PSI and also only stop manually. The pressure relief valve is set to 175 PSI.
i. Jockey pump stop 175 12.1 ii. Jockey pump start 165 11.4 Fire pump #1 PSI BAR iii. Fire pump stop Manual iv. Fire pump start 160 11.0 Fire pump #2 PSI BAR v. Fire pump stop Manual vi. Fire pump start 150 10.3 Pressure Relieve Valve Setting is 175 12.1