Section 21 10 00: Water- main fire sprinkler controls shall Based Fire Suppression have label, “FIRE SPRINKLER CONTROLS’ in red one inch Systems high letters on white background. 1. PROTECTION REQUIREMENTS F. If at all possible, locate sprinkler A. The entire sprinkler system to be riser in a mechanical room with designed to meet the direct outside access. Ensure that requirements of the university’s room is heated by a permanent insurance underwriter. fixed means or electrical heat source. Electrical heating tapes B. All spaces in the building must shall not be considered as an be fully protected by fire acceptable alternative means for sprinklers in accordance with freezer protection. NFPA-13, 13R, or 13D, whichever is applicable. This G. Indicate the location of all requirement includes all spaces standpipe, tamper switches and below suspended ceilings and flow switches. Provide a riser above suspended ceilings where diagram showing major combustible materials are or are components. intended to be located. Plastic H. All valve controlling water piping, telephone cabling, and supplies for sprinkler systems of plastic ductwork are examples of portions thereof, including floor combustibles. All equipment control valves, shall be located must be UL listed and in the for convenient access and latest edition of the university’s operable from the floor level or insurance underwriter's Approval another location approved by the Guide. Fire Marshal. All sprinkler C. In addition to the requirements valves and controls shall be of NFPA-13, the rulings and labeled: FIRE SPRINKLER interpretations of the local Fire CONTROLS". Signage with red Marshal and the requirements of one inch letters and white OSU must be incorporated into background is preferred. the design. I. Sprinkler FDC shall be located D. Dry Sprinkler Systems must be forty (40) feet from structure resettable externally by a when possible and location pre- plunger. For sensing Waterflow approved by the Corvallis Fire and Low Air, must use Potter Department. Connection shall PS10-2A for Waterflow and be labeled as to what the Potter PS40-2A for Low Air. If connection actually serves, I.e. an accelerator is needed, "Wet sprinklers and wet Reliable Accelerator B1 must be standpipe". used. J. Locate Backflow Preventers inside building. Otherwise in an exterior vault. K. Do not use riser mounted air compressors. Use the largest air compressor allowed by code. Air compressor shall be hardwired with a protected circuit, or if plugged in, install a system that secures the plug into the outlet. L. The use of self-luminous exit signs containing radioactive material is prohibited unless specifically approved by Environmental Health & Safety (EH & S). M. All Exit signs and Egress lighting must be on a dedicated Generator or UPS circuit or approved by the Alarm Shop. N. Install an exterior water flow bell in a location that is in direct line of sight of the fire department connection and shall have a “IF BELL RINGS, CALL 9-1-1” sign attached. 2. REFERENCES
A. Uniform Fire Code – Latest edition.
B. NFPA13-Installation of sprinkler systems. 2. IDENTIFICATION