Anda di halaman 1dari 20

Instruction Manual

for
Coupling Capacitor Voltage Transformers
and
Coupling Capacitors

Bulletin 20 95 05

Rev. 02 11/2004
Contents Illustration
Page Page
Introduction .....................................................................2 Fig. 1 Sectioned Perspective View of a Typical
Construction and Types ..................................................3 Capacitor Voltage Transformer ...................... 4
• Capacitor Voltage Transformers .................3 Fig. 2 Capacitor units assembly and connection...... 4
• Coupling Capacitors ....................................3 Fig. 3 Low Voltage Terminal Box for CVT ................ 5
• Heaters ........................................................3 Fig. 4 Schematic Diagram of a typical CVT.............. 8
Inspection ........................................................................3 Fig. 5 Capacitance and Dissipation Factor
• Shielding Ring .............................................3 Temperature Correction Curves for Paper-
Storage & Transportation ................................................3 Film/PXE Capacitor ........................................ 9
Installation .......................................................................3 Fig. 6 Capacitor Voltage Transformer with One
• Erection........................................................3 Capacitor Section (Test 1 to 2)..................... 10
• Capacitor Assembly Instructions .................3 Fig. 7 Capacitor Voltage Transformer with Two
Connections ....................................................................5 Capacitor Sections (Test 1 to 3)................... 11
Commissioning and Routine Maintenance .....................5 Fig. 8 Capacitor Voltage Transformer with Three
Capacitor Sections (Test 1 to 4)................... 12
• Electrical Tests ............................................6
Fig. 9 Capacitor Voltage Transformer with Four
Capacitance Bridge Testing............................................6
Capacitor Sections (Test 1 to 5)................... 14
Capacitance and Dissipation Factor Measurements ......6
Precautions for High Voltage Testing .............................7
Connection of a Non-Linear (Magnetic) Burden .............7
CVT Principle of Operation .............................................7 Tables
• Main Components .......................................7 Page
• Auxiliary Components..................................9 Table I Troubleshooting ......................................... 17
For after sales assistance .............................................20 Table II Types: TECF, TECP, TEVF, TEMF, TEVP,
TERP, TEMP & TETP .................................. 18
Table III Types: TEICF, TEIRF and TEIMF ................ 18
Table IV Types: TEICF, TEHCF, TEHCP, TEIRF,
TEIMF, TEHMF, and TEHMP....................... 19
Table V Electrical Performance ................................. 19

Introduction
Trench Limited manufactures a comprehensive range of capacitor voltage transformers (CVT’s) and coupling capacitors
(CC’s). All basebox types utilize the same design principles and manufacturing techniques, the information detailed in this
manual is applicable in general, except where noted.
The circuit diagrams drawings and other data in this manual may vary in minor details, from the equipment supplied. In all
cases the diagrams supplied by the factory and identified with the equipment will be correct in all details.
The contents of this manual are designed to cover most situations, which may occur in practice. If any additional
information is required, please contact Trench Limited.

2 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Construction and Types Storage & Transportation
Fig. 1 show detailed cross sectional views of a typical Units may be safely stored upright only on level ground,
capacitor voltage transformer. All Trench Instrument outdoors for reasonable period of time. Multiple
Transformer Products contain oil, which has less than 2- capacitor units are shipped with the upper capacitor(s)
PPM PCB considered as non-detectable amount. units removed and bolted to the skid alongside the
basebox. The top ends of the capacitors exposed by the
Capacitor Voltage Transformers removal of the upper units are protected from the
Types TEVF, TEMF, TEVP, TEMP, TETP, TERP, weather by temporary plastic bag covers, which should
TEIRF, TEIMF, TEHMF and TEHMP are capacitor be examined when equipment is placed in storage, and
voltage transformers for use with PLC coupling adjusted if found to be damaged or loosened.
schemes, protective relaying and metering applications.
Units must be only transported in the upright position
They comprise an assembly of one or more capacitor
preferably with their original packaging.
units mounted on oil filled aluminum basebox or
electromagnetic unit (EMU), which contains the
intermediate transformer, series reactor and auxiliary Installation
components. Erection
A low voltage terminal box houses the secondary CC’s or CVT’s with more than one capacitor unit are
terminals and auxiliary components. shipped with the units dismantled. They are crated in
sets with all components required to assemble one or
Coupling Capacitors more complete units in one crate. Capacitor units must
Types TECF, TECP, TEICF, TEHCF and TEHCP are not be interchanged between different CVT’s.
coupling capacitors (CC’s) for use in power line carrier Assembly can be performed with a lifting crane. The use
(PLC) coupling schemes. They consist of an assembly of rope slings with a choker-type hitch arranged to bear
of one or more capacitor units of a flat base design with on the upper metal flange is an effective way of lifting the
no carrier accessories or mounted on an air filled capacitor units.
aluminum basebox complete with carrier accessories.
Assembly can be carried out as follows:
The film/paper/PXE fluid insulation system represents a Mount the basebox and bottom capacitor assembly on
premium system of a low dielectric loss design and its prepared foundation and assemble subsequent
outstanding stability performance. capacitor units on top in accordance with the instructions
detailed below.
Heaters
Note that Trench oil filled EMU do not require heaters. In Capacitor Assembly Instructions
the low voltage terminal box, heaters may be installed to Bolting the connection lead of the top end plate of the
prevent condensation during long storage periods in lower capacitor to the lower end plate of the upper
very humid environments. Power rating of heaters could capacitor makes the electrical connection between
be up to 15 watts and dual voltages 120/240V or capacitor units. The capacitors are secured by axial
240/480V. Once the CVT is in service it is not bolts around the joining ring that must be tightened to 20
recommended to keep the heater on especially when ft. lb. (27 Nm). For the sake of appearance, the
ambient temperature exceeds 40oC. individual nameplates should be aligned with each other
during assembly. Fig.2 shows details of the assembly
and connection procedure.
Inspection
For high seismic areas, the use of damping pads may be
All shipments should be inspected upon arrival for
required. Please refer to the contract drawings supplied
chipped or damaged porcelains, metallic parts and oil
with the equipment.
leaks. The LV terminal box should be opened and
examined for loose components or broken wiring. If
transit damage has been found, file a claim with the Caution:
Transit Company and notify Trench limited immediately. It is essential that the capacitor unit serial numbers
shown on the main nameplate match the actual
Shielding Ring serial numbers of the capacitor units installed on the
When a shielding ring is supplied, refer to the outline device.
drawing regarding the way the shielding ring should be
mounted on the unit. Check the shielding ring for any
Accuracy performance may be severely affected if
scratches or points, which may have been caused
capacitor units are interchanged between CVT’s.
during transit and file smooth before installation.

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 3
Fig. 1 Sectioned Perspective View of a Typical Capacitor Voltage Transformer

Fig. 2 Capacitor units assembly and connection

4 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Connections
The basebox should be solidly grounded by means Caution (refer to Fig. 3)
of a grounding cable connected to the aluminum • The ground connection for the surge protective
ground pad located on the side of the base box. (See device must never be removed during normal
Fig. 1). service conditions. This provides the ground for
the magnetic unit.
All low voltage and carrier terminals are in the air filled
low voltage terminal box located on the side of the • The carrier terminal must always be connected
basebox for CVT’s (See Fig. 3). to ground, either directly, if no carrier is
required, or via the drain coil.
Low voltage terminal blocks are provided for secondary
connections. Secondary wiring entrance to the low
voltage box is by 4” x 5” (102 x 127 mm) gland plate with
provision for 1¼” (32 mm) knock out conduit entry by
bosses. Carrier entrance to the low voltage box is by Fig. 3 Low Voltage Terminal Box for CVT
5/8” (16mm) internal diameter entrance bushing, with
customer connection directly on the carrier terminal stud.

DANGER
CAR P1
P2

HAZARD AND BODILY INJURY OR


EQUIPMENT DAMAGE

• Only qualified maintenance personnel should


operate, service, or maintain this equipment. This
document should not be viewed as sufficient for
those who are not otherwise qualified to operate,
service, or maintain the equipment discussed. This
bulletin is intended to provide accurate and
authoritative information only. Trench Limited
assumes no responsibility for any consequences
arising out of the use of this bulletin.
• The successful operation of this equipment depends Commissioning and Routine
upon proper handling and installation. Neglecting
fundamental installation requirements can lead to
Maintenance
personal injury as well as damage to electrical During a regular maintenance program perform a regular
equipment or other property. visual inspection of the following:
• Before servicing equipment, disconnect all sources • Chipped porcelain
of electrical power. Assume that all circuits are live • Abnormal pollution accumulation
until they have been completely de-energized, • Oil leaks
tested, grounded, and tagged. Pay particular • Check oil level of the basebox by means of the oil
attention to the design of the power system. gauge.
Consider all sources of power, including the
possibility of backfeeding. It is recommended to check the protective gap annually.
The life of this device depends on the frequency and
• Carefully inspect the area around the transformer for duration of system switching. Unless specified otherwise
tools and objects left near the unit. in the connection diagram of the CVT, the protective
device across P1 and P2 is a Siemens gas-filled surge
• For safety, at least two qualified individuals must be
protector type SI-A 350 with a.c. sparkover voltage of
present during installation.
250 volts rms and a tolerance of +/-20%. If the sparkover
voltage of the device is outside this range, it needs a
Failure to observe these precautions may result in replacement. When this protective device is installed, it
equipment damage, severe personal injury, or death! is important to make sure the metallic ends make good
contact in the holder.

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 5
If a preventive maintenance program calls for regular Compare to C2 value marked on main nameplate or
electrical tests, the following procedures may serve as a previous data.
guide for tests on a routine basis as governed by your
usual practice. If it is the practice of your utility to • Measure “C total”, from HV terminal to “CAR”
conduct a check at the time of commissioning, then terminal with ground switch open and grounding
these same procedures may be followed at this time. links removed from “P2” and “CAR” terminals.
Depending on the type of bridge used, there may be
Event if the CVT is utilized for PLC only, the potential difficulties in obtaining a balance for DF as leakage
ground switch must remain in the open position. currents through the insulation of the transformer
windings will cause apparent DF readings below the
true value or even to be negative, although
Electrical Tests
capacitance value obtained will be correct a change
See precautions for HV testing on page 7 before doing
of measurement “C” total from one routine test to
the tests.
another would be an indicator that additional
Measure capacitance and dissipation factor of each investigations are required.
capacitor unit.
Note that, on the bottom capacitor unit, the lower end
It is important to use equipment with a capacitance plate is isolated from the capacitor electrodes and
measurement error of 0.5% or less in order to detect a cannot be used as a connection point.
capacitor element failure. This can be achieved by the
use of Low Voltage Capacitance Bridge. All
measurements taken should be corrected to 20°C using
Fig. 5. Capacitance and Dissipation Factor
As there will always be differences between the Measurements
calibration of various capacitance measurement The procedures outlined below are operating
equipment, the initial capacitance readings on instructions for the use with Doble M4000 equipment.
installation should be recorded and used as a basis for
comparison with subsequent measurements made with The power factor reading from the capacitance and
the same test equipment. dissipation factor test corresponds to the DF shown on
the nameplate of each capacitor unit. The DF reading
• Measure the transformation ratio of the unit (CVT’s depends upon good solid test connections being
only). The use of Doble Test equipment as a power established and care must therefore be taken to obtain
supply to the HV terminal and measurement of valid test results. The capacitance data obtained at
secondary voltage is a convenient method of commissioning stage may differ from the nameplate
achieving this. values therefore the capacitance measurement done at
commission should be used as a reference for future
comparison. A capacitor element failure will result
Capacitance Bridge Testing normally in an increase in the total capacitance in
proportion to the original number of elements and those
It is possible, but not likely, for a damaged capacitor remaining in operating condition. Generally an increase
element to recover somewhat after de-energisation and of 1% in capacitance from the reference data obtained
the unit capacitance appear to be normal when during commissioning would be significant. The
measured at a low voltage, as by a low voltage bridge capacitance of the capacitor unit should be preferably
measurement. Factory measurements are made at measured with same equipment and compared to the
normal operating voltage. commissioning data to ensure good working condition of
Measure upper units by attaching the test leads directly the assembly.
to the joining ring bolts. Capacitance and dissipation factor test can be carried
For CVT’s, the presence of the intermediate transformer out on all ratings of Trench Limited coupling capacitors
connected to the tapping point on the bottom unit and capacitor voltage transformers.
requires special consideration. Referring to the For coupling capacitors, the carrier bushing is
connection diagram and low voltage terminal box, the accessible and tests can be done by energizing either
procedure detailed below should be followed: top or bottom end of the capacitor, as required by
• Close voltage tap ground switch and measure “C1”, circumstances.
(HV terminal to basebox with ground switch closed). For capacitor voltage transformers the HV terminal must
Compare to value marked on main nameplate or be disconnected from the HV bus for accurate
data taken in previous tests. measurements.
• With ground switch still closed, measure “C2”. If solidly bolted bus connections are to be used; it is
Remove ground connection at “CAR” terminal and recommended that suitable insulating supports be
measure between this terminal and basebox.
6 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
installed to isolate the CVT for the test purposes.
Shorting links normally used across these insulating WARNING
supports may then be easily removed for the tests and HAZARD OF ELECTRIC SHOCK.
replaced afterwards.
During storage, ensure that all capacitor porcelain
The test methods for assemblies, which have 1, 2, 3 or 4 assemblies are shorted.
capacitor units are detailed below and from page 10 to
16. Failure to observe these precautions can result in
personal injury or product damage.
• Remove carrier ground connection for the duration
of the capacitance and dissipation factor test
• Ground the basebox solidly to the test set
Connection of a Non-Linear
• Close the voltage tap ground switch (Magnetic) Burden
• IMPORTANT: Replace carrier connection Caution must be used when applying non-linear (or
immediately after test, before energizing. magnetic) burdens with CVT’s. The effect of a non-linear
burden on the CVT is to cause harmonics in the output
voltage and current, which, in turn, may cause variation
NOTE: in ratio and phase angle errors as well as increasing the
It is not unusual for dissipation factor (DF) voltage across the protective gaps. During momentary
measurements mode at 10kV or below to exceed overvoltage conditions, these effects of a non-linear
factory values, which are measured at operating burden may cause gap flashover and, thereby, interfere
voltage. If DF exceeds 0.35 please consult Trench with the operation of the relaying systems.
Limited
Most relays, synchroscopes, voltmeters and other
generally used instruments are essentially linear
burdens up to twice normal voltage. Burdens with closed
Precautions for High Voltage Testing magnetic circuits such as auxiliary potential transformers
If HV testing methods are employed on complete CVT’s, may not have linear characteristics over the entire
the following precautions should be taken: voltage range.
• Do not energize the HV terminal above the normal If such devices are used in the secondary circuits, these
rated line-to-ground voltage of the unit. The should be selected so that the iron core is operating at
terminals “P2” and “P1 “ are connected to the tapping not more than one-half the flux density required to reach
point between “C1” and “C2“ through the intermediate the knee of the magnetization curve. For example, it is
circuit, and the voltage of the tapping point will desirable to use a 230-230 volt auxiliary potential
appear at them when the ground link is removed transformer in the 115-volt circuit instead of one having
from “P2” unless the voltage grounding switch (refer a 115-115 volt rating. The same precaution should be
to Fig. 4) is closed. taken for relay coils.
• The normal operating voltage of the tapping point is
approximately 5 kV (TEVF), 11 kV (TEMF, TEMP
and TEHMF). It is recommended that capacitance CVT Principle of Operation
measurements be taken at voltages below the
Main Components
normal rated voltage of the unit, so that the voltage
The main components are the capacitor divider, the
appearing on “P1 “ and “P2” terminals during the
intermediate step-down transformer and the series
measurement will be proportionately reduced.
reactor, as shown in Fig. 4.
• Extreme care must be taken to ensure that
connections to the “CAR” terminal are completely The step-down transformer and series reactors are
away from the “P1 “ and P2” terminals, because of connected to the intermediate voltage tap between C1 &
the high voltage which will appear there. C2. The series reactor is manufactured so its impedance
cancels the impedance of the capacitor; therefore, the
• Qualified personnel only, who fully understand the full intermediate voltage is delivered to the terminals of
circuit involved, should make measurements. the step-down transformer, in phase with the primary
• Maximum test voltage to “P1 “ and “P2” and “CAR” line voltage. Series reactor and primary winding of the
terminals with respect to grounds should not exceed step-down transformer are manufactured with taps to
2 kV. enable ratio and phase angle adjustment. These are
factory preset and do not require alteration after delivery
unless a capacitor unit is changed.

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 7
Fig. 4 Schematic Diagram of a typical CVT
Base box type

UNIVERSAL BOX LOW PROFILE BOX


Without carrier accessories
With carrier accessories

Legend: c Series Reactors g Secondary Terminal Board k Drain Coil, Gap & Carrier Ground
d Intermediate Voltage Transformer h Faraday Field Switch Assembly
e Harmonic Suppression Filter i Potential Ground Switch
f Sealed Protective Gap j Choke Coil & Gap Assembly

Note: connection between internal terminals L1…L8 and A, D…O are made at the factory as required for each unit.

8 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Example for use of Fig. 5 The protective gap (item 4 Fig. 4) is a voltage sensitive
device wired in series with a loading resistor on a
1. Make measurement at field temperature. E.g.:
secondary winding of the series reactor. The protective
Temperature = -10°C
gap is normally open circuit, but goes in short circuit
Capacitance = 10280 pF
mode when the intermediate voltage exceeds 190% of
Dissipation Factor = 0.065%
rated value, or when the secondary current causes the
2. Find our factory values from test report. E.g.: thermal burden rating shown in Table V to be exceeded.
Capacitance = 10 000 pF This has the effect of de-tuning the CVT and limiting the
Dissipation Factor = 0.055% secondary current available during overvoltage and
external short circuit conditions. The protective gap also
3. Calculate predicted values at field temperature. E.g.:
serves to further limit ferroresonance oscillations. If the
Capacitance at -10°C = 100.25% of factory
fault condition persists for more than about thirty
value
seconds, the protective gap will not reset from the short
= 10250 pF
circuit mode and must be replaced. Its location inside
4. Dissipation Factor at -10°C = 113% of factory value the low voltage terminal box facilitates replacement.
= 0.062%
The drain coil, gap and carrier ground switch are
supplied if the CVT is to function as a coupling capacitor
Compare values from 1 and 4.
for power line carrier.

Fig. 5 Capacitance and Dissipation Factor Temperature CAUTION on operation of potential ground switch:
Correction Curves for Paper-Film/PXE Capacitor
The potential ground switch position (see Fig. 4,
item 7) is provided for maintenance purposes only. It
is not meant to be closed on permanent bases, due
to increased stress of C1 capacitor elements.
Closing the potential ground switch for more than 8
hours is not recommended.

Note: Measurement is done at normal operating voltage.


Significant error on dissipation factor may result if
measurement performed at low voltage (1-10kV).

Auxiliary Components
All items referred to are identified on the connection
diagram.
The choke coil assembly prevents the grounding of the
carrier signal when the voltage tap ground switch is
closed.
The harmonic suppression filter prevents sustained
ferroresonance oscillations. It consists of a resistor in
series with a saturable reactor and a parallel resistor.
The reactor is designed to saturate above the highest
over-voltage rating to form a loading circuit, which will
dampen sub-harmonic ferroresonant oscillations.

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 9
Fig. 6 Capacitor Voltage Transformer with One Capacitor Section (Test 1 to 2)
ƒ Test 1 - one capacitor section

Test Procedures

Measure: C1
Test Voltage: 10kV
Circ. Desc.: GND-RB
HV Lead: A
LV Lead: -
F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

ƒ Test 2 - one capacitor section

Test Procedures

Measure: C2
Test Voltage: 2kV
Circ. Desc. GND-RB
HV Lead: F
LV Lead: -
F: Disconnected
(carrier lead)
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

10 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Fig. 7 Capacitor Voltage Transformer with Two Capacitor Sections (Test 1 to 3)
ƒ Test 1 - two capacitor sections

Test Procedures

Measure: C1-1
Test Voltage: 10kV
Circ. Desc.: GAR-R
HV Lead: B
LV Lead: A
F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

ƒ Test 2 - two capacitor sections

Test Procedures

Measure: C1-2
Test Voltage: 10kV
Circ. Desc. UST-R
HV Lead: B
LV Lead: A
F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 11
ƒ Test 3 - two capacitor sections

Test Procedures

Measure: C2
Test Voltage: 2kV
Circ. Desc.: GND-RB
HV Lead: F
LV Lead: -
F: Disconnected
(carrier lead)
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

Fig. 8 Capacitor Voltage Transformer with Three Capacitor Sections (Test 1 to 4)


ƒ Test 1 - three capacitor sections

Test Procedures

Measure: C1-1
Test Voltage: 10kV
Circ. Desc.: GAR-R
HV Lead: C
LV Lead: B
A, F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

12 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
ƒ Test 2 - three capacitor sections

Test Procedures

Measure: C1-2
Test Voltage: 10kV
Circ. Desc.: UST-R
HV Lead: B
LV Lead: C
A, F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

ƒ Test 3 - three capacitor sections

Test Procedures

Measure: C1-3
Test Voltage: 10kV
Circ. Desc.: GAR-R
HV Lead: B
LV Lead: C
A, F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 13
ƒ Test 4 - three capacitor sections

Test Procedures

Measure: C2
Test Voltage: 2kV
Circ. Desc.: GND-RB
HV Lead: F
LV Lead: -
A: Grounded
F: Disconnected
(carrier lead)
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

Fig. 9 Capacitor Voltage Transformer with Four Capacitor Sections (Test 1 to 5)


ƒ Test 1 – four capacitor sections

Test Procedures

Measure: C1-1
Test Voltage: 10kV
Circ. Desc.: GAR-R
HV Lead: D
LV Lead: C
A, F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

14 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
ƒ Test 2 – four capacitor sections

Test Procedures

Measure: C1-2
Test Voltage: 10kV
Circ. Desc.: UST-R
HV Lead: C
LV Lead: D
A, F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

ƒ Test 3 – four capacitor sections

Test Procedures

Measure: C1-3
Test Voltage: 10kV
Circ. Desc.: UST-R
HV Lead: B
LV Lead: C
A, F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 15
ƒ Test 4 – four capacitor sections

Test Procedures

Measure: C1-4
Test Voltage: 10kV
Circ. Desc.: GAR-R
HV Lead: B
LV Lead: C
A, F: Grounded
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

ƒ Test 5 – four capacitor sections

Test Procedures

Measure: C2
Test Voltage: 2kV
Circ. Desc.: GND-RB
HV Lead: F
LV Lead: -
A: Grounded
F: Disconnected
(carrier lead)
S1 Switch: Grounded
S2 Switch: Grounded

Note:
S1: Carrier ground switch
S2: Voltage tap ground switch
L1: Drain coil
L2: Choke coil

16 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors

please contact Trench Limited.


The following is a list of possible problems and their solutions. If difficulty is encountered at any stage,
Table I Troubleshooting
Problem Possible Cause Procedures

Zero Secondary Output 1.1 Volt tap ground switch closed Open volt tap ground switch (up position)
1.2 Short circuit on secondary connections Remove external wiring and measure output voltage at terminals. If there is still no
voltage, then proceed as follows:
1. Megger X and Y windings to tank should read 50 meg ohms or more.
2. Remove P2 ground link.
3. Open ground switch.
4. Megger P2 to tank should read 50 meg ohms or more.
1.3 Open circuit on intermediate transformer Remove P2 connection.
Close volt tap ground switch.
1. Measure resistance from P2 connection to tank, should read less than 1000 ohms.
Remove carrier ground connection and close volt tap ground switch.
2. Measure capacitance between CAR connection and basebox. This gives C2 value.
3. Measure capacitance from top of capacitor to basebox. This gives C1 value. Either
of above tests will confirm integrity of tap lead from lower capacitor unit.
4. Measure P1 - P2, should read less than 75 ohms
1.4 No connection between units Confirm as per test 1.3 b) and c).
1.5 Broken connection inside capacitor unit As per test 1.3 b) and c). If no continuity confirm that connections between capacitor
units are made. If still no continuity change capacitor unit.
Low Secondary Output 2.1 Poor secondary connection Check all connections.
2.2 Failure of a C2 capacitor element Check C2 value as per test 1.3 b).
2.3 Extreme load on secondary Remove external wiring to substation and re-check secondary output at terminals.
High Secondary Output 3 Failure of one or more C1 capacitor elements Remove unit from service immediately for evaluation. Check C1 per 1.3 c)
Replace capacitor unit if capacitance is more than 1% high.
Fluctuating Secondary 4 Loose intermediate or secondary connections Check all connections.
Output
High Dissipation Factor in 5 Oil contamination due to capacitor element Remove unit from service immediately. Replace capacitor unit.
Capacitor Unit(s) arcing/failure
High Capacitance Values 6 Capacitor element failure As above (5.1).
Low Capacitance Values 7 Possible measurement error Check measurement equipment.
8.1 Malfunction of harmonic suppression filter Check harmonic suppression filter wiring and components, replace as necessary.
Waveform Distortion
8.2 Use of non linear (saturable) burden See further section “Connection of saturable (non-linear) burden”.
Low Secondary Output 9.1 P1 - P2 surge protector shorted Replace surge protector.
and Phase Angle Error 9.2 Faulty harmonic suppression filter As above (8.1).
10.1 Extremely high ambient temperature In no case should oil be more than 10 mm (3/8”) above mark.
High Oil Level in Basebox 10.2 Oil leak in lower capacitor unit tap or carrier Check expansion chamber on top of lower capacitor unit. Consult factory immediately.
bushing
11.1 Extremely low ambient temperature In no case should oil level be more than 10 mm (3/8”) below mark. Top up if necessary.
Low Oil Level in Basebox
11.2 Basebox leaking oil Check for leaks around tank and report to factory if necessary.
12.1 Oil leak of expansion chamber Replace expansion chamber.
17

Sign of Oil on Porcelains 12.2 Capacitor failure causing expansion chamber Inspect expansion chamber. If punctured, remove unit from service immediately. Consult
to puncture factory.

CAUTION: BEFORE PERFORMING ANY TESTS ENSURE THAT UNIT HAS BEEN COMPLETELY DE-ENERGIZED
Table II Types: TECF, TECP, TEVF, TEMF, TEVP, TERP, TEMP & TETP
Standard Technical Data

PARAMETER UNIT 69 115 138 161 230 287 345 400 500

Maximum System Voltage kV 72.5 121 145 169 242 300 362 420 550
*Rated Secondary Voltage 115 115 115 115 115 115 115 (1) 115 & 69
(1) V & & & & & & &
67.08 69 67.08 65.7 69 69 69 63.9 (1) 115 & 63.9
*Transformation ratio (2) 350- 600- 700- 800- 1,200- 2,500:1 1,800- 2,000- (1) 2,700-4,500:1
600:1 1,000:1 1,200:1 1,400:1 2,000:1 3,000:1 3,600:1 (1) 2,500-4,500:1
Total capacitance
pF 10,000 6,000 5,000 4,300 3,000 2,500 2,150 1,650 1,430
TECF, TEVF, TEMF
TECP, TEVP, TEMP, TETP pF 20,800 12,500 10,400 8,300 6,200 5,200 4,100 3,500 2,800
Power frequency withstand
(Hipot) - dry 1 min. kV 165 265 320 370 525 640 785 785 900
- wet 10 sec. 140 230 275 325 460 570 680 680 780
Full wave withstand (BIL)
kV 350 550 650 750 1,050 1,300 1,550 1,550 1,800
1.2 x 50 microsecond
Number of capacitor units 1 1 1 1 2 2 2 3 3
Overall Height in. 55.25 69.25 78 86.25 116.25 133.5 150.25 189 214
mm 1,403 1,750 1,981 2,191 2,953 3,391 3,816 4,801 5,435
Total Section Height in. 35.75 49.75 58.50 66.75 96.75 114 130.75 169.50 194.75
mm 908 1,264 1,486 1,695 2,457 2,896 3,321 4,305 4,947
Creepage Distance in. 63 102 130 149 205 260 297 390 446
mm 1,590 2,600 3,300 3,775 5,200 6,600 7,550 9,900 11,325
Strike Distance in. 23 37 46 54 74 92 108 138 162
mm 580 940 1,160 1,370 1,880 2,320 2,740 3,480 4,110
*Weight lb. 575 650 675 725 875 900 1,000 1,125 1,300
(add 40 kg/88lbs. for TEMP) kg 261 295 306 329 397 408 454 510 590
Max. Horizontal terminal pull
in 80 mph (130 km/h) wind lb. 3,500 2,550 2,175 1,900 1,300 1,075 925 675 550
referring to capacitor kN 15.57 11.34 9.68 8.45 5.78 4.78 4.11 3.06 2.45
porcelain strength
Shielding ring No No No No Yes Yes Yes(2) Yes Yes

1. Upper value is CSA C13.1 ratio, lower value is C93.1 ANSI * Not applicable to TECF, TECP
2. 345 kV, 1300 kV BIL designs available without shielding rings

Table III Types: TEICF, TEIRF and TEIMF


Standard Technical Data

PARAMETER UNIT 115 138 161 230 345 400 500 765

in. 71.75 80.25 90.75 121.5 159.5 197 228.50 297


Height mm 1,822 2,038 2,305 3,086 4,051 5,004 5,798 7,544

in. 112 139 173 224 345 419 518 691


Creepage Distance mm 2,845 3,545 4,385 5,690 8,770 10,636 13,155 17,540

in. 37 46 56 74 112 138 168 224


Strike Distance mm 940 1,170 1,420 1,880 2,840 3,500 4,270 5,690

lb. 975 1,025 1,100 1,350 1,600 1,875 2,100 2,600


Weight kg 442 465 499 612 725 850 953 1,179

Max. Horizontal terminal pull in 80


lb. 4,750 4,250 3,475 2,750 1,900 1,600 1,200 800
mph (130 km/h) wind referring to
kN 21.13 18.9 15.45 12.23 8,45 7.12 5.33 3,56
capacitor porcelain strength

18 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Table IV Types: TEICF, TEHCF, TEHCP, TEIRF, TEIMF, TEHMF, and TEHMP
Standard Technical Data

PARAMETER UNIT 115 138 161 230 345 400 500 765

Maximum System Voltage kV 121 145 169 242 362 420 550 800
115 & 115 & 115 & 115 & 69 115 & 69 115 & (1) 115 & 69 115 & 69
*Rated Secondary Voltage (1) V
69 67.08 65.7 63.9 (1) 115 & 63.9
600- 700- 800- 1,200- 1,800- 2,000- (1) 2,700-4,500:1 3,750-6,250:1
*Transformation ratio (2)
1,000:1 1,200:1 1,400:1 2,000:1 3,000:1 3,600:1 (1) 2,500-4,500:1
Total capacitance
TEHMF, TEIMF pF 20,000 16,500 15,000 10,000 7,500 5,500 5,000 4,000
TEICF, TEHCF, TEIRF
TEHMP, TEHCP pF 47,500 38,100 30,500 22,800 15,200 12,700 10,100 6,.200
Power frequency withstand kV
(Hipot) - dry 1 min. 265 320 370 525 785 785 900 1,200
- wet 10 sec. 230 275 325 460 680 680 780 1,050
Full wave withstand (BIL)
kV 550 650 750 1,050 1,550 1,550 1,800 2,425
1.2 x 50 microsecond
Number of capacitor units 1 1 1 2 2 3 3 4
in. 71.25 79.75 88.25 121.75 155.50 197.75 223 290.50
**Overall Height
mm 1,810 2,026 2,242 3,092 3,950 5,023 5,664 7,379
in. 53 61.50 70 103.50 137.25 179.25 204.50 271.75
**Total Section Height
mm 1,346 1,562 1,778 2629 3,486 4,553 5,194 6,902
in. 112 139 166 224 332 417 498 665
**Creepage Distance
mm 2,850 3,530 4,220 5,700 8,440 10,590 12,660 16,880
in. 37 46 54 74 108 138 162 216
Strike Distance
mm 940 1,170 1,370 1,880 2,740 3,500 4,110 5,480
lb. 1,100 1,175 1,300 1,650 1,975 2,350 2,700 3,425
**Weight
kg 499 533 590 748 896 1,066 1,225 1,554
Max. Horizontal terminal pull lb. 4,750 4,250 3,850 2,750 2,100 1,600 1,375 900
in 80 mph (130 km/h) wind kN 21.13 18.9 17.12 12.23 9.34 7.12 6.12 4.00
referring to capacitor
porcelain strength
Shielding ring No No No No Yes(2) No No No
1. Upper value is CSA C13.1 ratio, lower value is C93.1 ANSI * Not applicable to TEHCP, TEICF, TEHCF
2. 345 kV, 1300 kV BIL designs available without shielding rings ** Not applicable TEICF, TEIRF and TEIMF

Table V Electrical Performance


CHARACTERISTICS TEVF / TEVP TEMF TETP TEIRF TEMP TEHMF, TEHMP, TEIMF
400VA(0.3class) 400VA(0.3class),400VA (0.15)
Accuracyclass(1)ANSI 200VA(0.6class) 200VA(0.3class) 200VA(0.6class) 200VA(0.3class)
200VA(0.15class) 200VA(0.15class)
Each main winding (2) 0.6 MWXYZ 0.3 MWXYZ 0.6 MWXYZ 0.3 MWXYZ 0.3 MWXYZ, ZZ, 0.3 MWXYZ, ZZ
1.2Z, ZZ 0.15MWXYZ 0.15 MWXYZ
0.15 MWXYZ and ZZ (3)
Auxiliary Winding 1.2Y 1.2Y 1.2Y 1.2Y 1.2Y 1.2Y

IEC(2)
Each main winding
cl 0.1, 50 Hz 100 VA 100 VA
cl 0.2, 50 Hz 225 VA 250 VA
cl 0.2, 60 Hz 250 VA 300 VA
cl 0.5, 50 Hz 150VA 250 VA 150 VA 350 VA 500 VA 600 VA
cl 0.5, 60 Hz 200 VA 300 VA 200 VA 400 VA 550 VA 700 VA
cl 1.0, 50 Hz 300 VA 500 VA 300 VA 600 VA 700 VA 1000 VA
cl 1.0, 60 Hz 400 VA 600 VA 400 VA 700 VA 700 VA 1000 VA
Auxiliary winding Class 3P, 50 VA Class 3P, 50 VA Class 3P, 50 VA Class 3P, 50 VA Class 3P, 50 VA Class 3P, 50 VA
Less than % (of crest) residual voltage in 1 cycle @ burden:
Transient response ZT(200 VA) ZT(200 VA) ZT(200 VA) ZT(200 VA) ZZT(400 VA) ZZT(400 VA)
10% 10% 6% 5% 10% 5%
Ferroresonance suppression Less than 10 % (of crest) in 200 milliseconds at 120% of rated voltage
Thermal rating 1000 VA 1000 VA 1000 VA 1500 VA 1000 VA 1500 VA
Notes: (1) Two main windings are supplied as standard, with a third auxiliary winding available as an optional extra.
(2) The accuracy class for total simultaneous loading is equal to the values given for each main winding.
(3) On special demand

Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors 19
TRENCH Facilities

‰ TRENCH Austria GmbH ‰ TRENCH Limited


Paschinger Strasse 49, PLC Division
A-4060 Linz-Leonding 815 Middlefield Road Unit 7
Tel: +43.732.6793-0 Scarborough, Ontario
Fax: +43.732.6713.41 Canada M1V 2P9
Tel: (416) 291.8544
‰ TRENCH Brazil Ltda. Fax: (416) 292.0684
Via Expressa de Contagem, 2685
Contagem, MG ‰ TRENCH France S.A.
Brazil 16, rue du Général Cassagnou
BP 70
‰ TRENCH China Limited F-68302 Saint Louis
427 Jumen Road France
Shanghai 200023 Tel: +33 (0)3.89.70.23.23
P.R. China Fax: +33 (0)3.89.67.26.63

‰ TRENCH Limited ‰ TRENCH Germany GmbH


Coil Division Nürnberger Strasse 199
71 Maybrook Drive D-96050 Bamberg
Scarborough, Ontario Germany
Canada M1V 4B6 Tel: +49 (0)951 1803
Tel: (416) 298.8108 Fax: +49 (0)951.1313.45
Fax: (416) 298.2209
‰ TRENCH Switzerland
‰ TRENCH Limited Lehenmattstrasse 353
Instrument Transformer Division PO box
390 Midwest Road, Ch-4028 Basel
Scarborough, Ontario Switzerland
Canada M1P 3B5 Tel: +41 61.315.5100
Tel: (416) 751.8570 Fax: +41.61.315.5916
Fax: (416) 751.6952
‰ TRENCH U.K. Limited
‰ TRENCH Limited Tyne & Wear
Bushings Division N31 1UW
432 Monarch Avenue England
Ajax, Ontario
Canada L1S 2G7
Tel: (905) 426.2665
Fax: (905) 426.2671

For after sales assistance


Please contact Trench Limited and provide the following information for the unit in question:
• Type of unit
• Serial number
• Trench shop order number

Note all this information is available from the main nameplate. Please supply the information regarding the
problems or questions you may have.

www.trenchgroup.com
20 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors

Anda mungkin juga menyukai