Anda di halaman 1dari 7

Produced on 09-Jan-18 with Xpress Selection V8.2.0 - database DIL 12.5.

Project name KIRIN BEER


Project address MYANMAR
Viet Nam
Reference VAN DIEP
Client name KIRIN
Revision 0

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXQ16TAYM 1 Cooling only VRV IV STANDARD
RXQ18TAYM 2 Cooling only VRV IV STANDARD
FXFQ125LUV1 10 VRV FLU - Ceiling Mounted Cassette(Round Flow)
KHRP26A33T 2 Refnet branch piping kit
KHRP26A72T 5 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E62 10 Wired Remote Controller (Navigation Remote
Controller)
BYCP125K-W1 10 Decoration panel
BHFP22P151 1 Outdoor unit multi connection piping kit

2. Indoor Unit Details


2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / RH)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
WxHxD WidthxHeightxDepth
Wght Weight of the device

2.2. Out 1 - RXQ52TANYM


Capacity data at conditions and connection ratio (96%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflo
°C BTU/h BTU/h BTU/h BTU/h °C °C BTU/h BTU/h l/s
Ind 1 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 2 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 3 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 4 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 5 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 6 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 7 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 8 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 9 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5
Ind 10 FXFQ125LUV1 26.0 / 60% 47770 48595 n/a 29617 Auto n/a n/a n/a 5

Required cooling capacity towards the outdoor unit: 477700BTU/h.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Ind 1 34-44 230V 1ph 1.5 840×288×840 25
Ind 2 34-44 230V 1ph 1.5 840×288×840 25
Ind 3 34-44 230V 1ph 1.5 840×288×840 25
Ind 4 34-44 230V 1ph 1.5 840×288×840 25
Ind 5 34-44 230V 1ph 1.5 840×288×840 25
Ind 6 34-44 230V 1ph 1.5 840×288×840 25
Ind 7 34-44 230V 1ph 1.5 840×288×840 25
Ind 8 34-44 230V 1ph 1.5 840×288×840 25
Ind 9 34-44 230V 1ph 1.5 840×288×840 25
Ind 10 34-44 230V 1ph 1.5 840×288×840 25

Outdoor unit placed 6.0m below the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C BTU/h BTU/h °C BTU/h BTU/h
Out 1 RXQ52TANYM 96 35.0 477988 477700

Name Model Piping Refrigerant


m Type
Bse Refr Ex Refr
kg kg
Out 1 RXQ52TANYM 30.0 R410A 31.4 n/a

Name Model PS MCA WxHxD Wght


A mm kg
Out 1 RXQ52TANYM 380V 3ph
* RXQ18TAYM 31 1240×1657×765 285
* RXQ18TAYM 31 1240×1657×765 285
* RXQ16TAYM 31 1240×1657×765 285

Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping Out 1


Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring Out 1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P151 Outdoor unit multi connection piping kit Out 1 [RXQ52TANYM]

6.2. Indoor Unit Options


Model Description Used by
BYCP125K-W1 Decoration panel Ind 1 [FXFQ125LUV1] Ind 2 [FXFQ125LUV1] Ind 3 [FXFQ125LUV1]
Ind 4 [FXFQ125LUV1] Ind 5 [FXFQ125LUV1] Ind 6 [FXFQ125LUV1]
Ind 7 [FXFQ125LUV1] Ind 8 [FXFQ125LUV1] Ind 9 [FXFQ125LUV1]
Ind 10 [FXFQ125LUV1]

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7