COMSAB II
Computerized Control System
for refrigerating compressors

Version 1.06

0178-444--ENG 1
Preface

The present instruction manual, that covers COMSAB II vers. 1.06 additionally gives the
the COMSAB II gateway, describes how to user access to read and write data in the Sa-
install the unit and how to use the SABROE broe Chiller Control Unit.
protocol 0178-400. The COMSAB II functions as a gateway, con-
verting from the proprietary HDLC/RS485
COMSAB II gives the user access to read
protocol, which is used between the com-
and write data in the following SABROE com-
pressor control units, to a very simple ascii/
pressor control units: PROSAB II,
RS232 protocol (0178-400) which is de-
UNISAB S/R/RT/RTH and UNISAB II.
scribed in this manual.
This manual refers to COMSAB software
version 1.06.

YORK Refrigeration
P.O. Box 1810, DK--8270 Hoejbjerg Phone: +45 87 36 70 00
Chr. X’s Vej 201, Aarhus, Denmark Fax: +45 87 36 77 05

2 0178-444--ENG
Contents

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Port 1 -- RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Port 2 - RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Diodes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Message format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Reply from the COMSAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Possible error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 0178-402 - Points to READ for UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
COP - valves Points to READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 0178-402 - Points to WRITE for UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Capacity Control (communication) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
COMPRESSOR CONTROL MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
COMPRESSOR MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
CONTROL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
MULTISAB STATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table of alarms/warnings for UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
List of Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

0178-444--ENG 3
Installation:

COMSAB II is installed as shown in the figure -- a 2 wire screened RS485 communication


below. cable
You would need:
(See the instruction book, Installing a data
-- a 2 wire power cable
communications cable for the right commu-
-- a 3 wire RS232 cable nication cable type).

RS232 cable
PLC/PC

J6 J7 J2
CPU51 Interface Code
Diodes
COMSAB II Port 3
J5
Power Port 1 Port 2
J1 J3 J4
4 1 9 1 9 1
Power cable
24 VAC/VDC RS485 cable
RS485 BUSS

UNISAB/PROSAB II
1 2 Max 14

There are no jumpers or switches on COM- Protective ground potential should best be
SAB II which have to be set before operation. the same for UNISAB and COMSAB as well
as for any PCs or PLCs connected to it. A
Place the COMSAB II, the RS232 cable and eavy gauge wire (6 mm2) running along with
the RS485 communication cable in a dis- the communications tables from one protec-
tance of minimum 30 cm from contactors, tive ground to the next, may prevent a lot of
high power cables or any other unit radiating trouble. Please observe local safety regula-
electromagnetic noise. tions which may not allow this.

4 0178-444--ENG
Dimensions:
237 mm

J6 J7 J2
Code
110 mm

Diodes
UNISAB
J5
J1 J3 J4
4 1 9 1 9 1

Depht = 68 mm incl. coverplate

Power: Pin #1: Chassis (Ground connection)

COMSAB II has to be supplied with either Pin #2: AC / DC +


15-28 VAC or 18-40 VDC on plug J1:
Pin #3: AC / DC --

Pin #4: Not connected

Power Consumption 12 VA.


J1
Port 1 -- RS485:
1 2 3 4
Ground The plug (J3) connections are:

Pin #1: Gnd Signal ground.


+ --
24 VAC or DC Pin #2 + 8: Tx/Rx + Transmit/Receive Data.

Pin #4 + 6: Tx/Rx -- Transmit/Receive Data.

Port 1

J3

TX+Term. TX-Term. RX-Term. RX+Term.

Gnd TX+Data TX--Data RX--Data RX+Data


1 2 3 4 5 6 7 8 9

Cable screen

+ --

0178-444--ENG 5
*In order to terminate the communication, nected to the RS485 network. The setting in
pins 2 + 3 and pins 4 + 5 must be connected UNISAB II must be 1200 and 9600 baud.
together -- as shown.
Port 2 - RS232:
The data transmission to PLC/PC is based
The baud rate between COMSAB II and Dan- on the RS232C async serial standard.
buss is set up automaltically to be the same No handshake signals are being used, so the
as configured in the UNISAB/PROSAB con- plug (J4) connections are very simple:

Port 2

J4

Gnd TxD RxD


1 2 3 4 5 6 7 8 9

Signal ground Transmitted Data Received Data

Pin #1: Gnd Signal ground. until COMSAB II responds. (COMSAB II ini-
tialize at 19.200 baud at power on).
Pin #2: TxD Transmitted Data.
Diodes:
Pin #8: RxD Received Data.
There are 4 diodes on COMSAB II, with the
following function:
The data format is: 8 data bit, 1 stop bit and
even parity.
Yellow ª (Idle)
-- Light when net activity on port 1 (RS485).
Note that the COMSAB II is functioning as a
DTE (Data Terminal Equipment). Green ª (Frame err.)
-- Light when COMSAB II has synchronized
The baud rate between COMSAB II and itself to the baud rate on the net (RS485).
PLC/PC is set up automatically, the baud rate
setting in the PLC/PC must be 9.600 or Red ª (Overfl.)
19.200 baud. -- Light when COMSAB II is master.

Communication is initiated by the PLC/PC Yellow ª= (Power)


issuing a number of READ messages (1-3) -- Light when power is on.

6 0178-444--ENG
Protocol:

SABROE protocol 0178-400 describes the Index Indicates the dialing # of the
data communication between a central com- UNISAB/PROSAB which must
puter (PLC or PC), and a COMSAB II receive this telegram (1 character).
module. The value must be 20H [¬]
= UNISAB/PROSAB # 1.
This protocol allows any type of computer
(when above hardware is available) to re- The value must be 21H [!]
trieve data from a UNISAB or a PROSAB = UNISAB/PROSAB # 2.
control panel, through the COMSAB II mod-
The value must be 2EH [.]
ule. The protocol always waits to get polled = UNISAB/PROSAB # 14.
by the central computer. It never starts a
communication by it self. Point Indicates the address of the variable
which should be read or changed
The communication is based on the central (1 character).
computer sending a telegram (a message) to
The value must be 20H-FFH
the COMSAB II module. The telegram should
according to the table 0178-402.
always consist of a total of 11 (ascii) charac-
ters, that is 9 message characters plus 2 Data field
control characters STX (Start of TeXt) and The Data field contains always
ETX (End of TeXt). 6 characters.

The Data field can contain any


(The corresponding ASCII character is
integer value from --990 to + 99999.
shown in sharp parenthesis, where [¬] The value must be right justified.
means an ASCII ’space’) Not used characters must be space
filled.
Message format: The value in the Data field may be
Stx - Code - Index - Point - Data--field - Etx multiplied by a factor of 10.
See Data format/Range in Read
Stx Starts the telegram (1 character). table and/or Write table.

Stx = 02H [ ^B] Etx Ends the telegram (1 character).

Code Indicates read/write telegram Etx= 03H [^C]


(1 character).
Reply from the COMSAB II:
The value should be 20H [¬] when
When writing data by a COMSAB II, the re-
reading data.
ply message is a copy of the message sent
The value should be 21H [!] when to the COMSAB II.
writing data.
Data written to UNISAB II is checked in the
The value should be 22H [”] when UNISAB II. If the value exceeds the limits
reading COP data from UNISAB II. that are built into UNISAB II (see UNISAB II

0178-444--ENG 7
instruction book for reference) then UNISAB If a parity error occurs, or the number of
II accepts and returns the lowest or highest characters received in a message by the
of the built-in limits, depending on which limit COMSAB II is different from 11, no reply will
is exceeded. be given to the central computer.

Data written to UNISAB I or PROSAB II is


Tables:
checked in the COMSAB II. If the value ex-
ceeds the limits that are build into COMSAB In the table 0178-402 /Read and Write, de-
II, then COMSAB II returns an error mes- tails about selecting the correct point, details
sage with code F____6. about translating the reply for compressor
control mode etc are given.
For reference -- see the limits table under
note (5), placed under notes following the Response time:
table Points to Write.
There is always a time delay from the mo-
When reading data by a COMSAB II, the re- ment a change in e.g. pressure on the com-
ply message is a copy of the message sent pressure unit is seen until it actually can be
to the COMSAB II, except from the Data field read by the COMSAB II module. The worst
which will be filled with the value asked for. case time delay can approximately be calcu-
lated with this equation:
Depending on the data type then the value
returned may be in 1/10 of the unit asked for, TimeDelay = 13 + ( 1,5 * N ) seconds at
i.e. +/-- xx.x BAR, +/-- xxx.x ’C, xxx.x % etc, 1200 Baud.
se Data format/Range for the specific point TimeDelay = 7 + ( 0,8 * N ) seconds at
asked for. 2400 Baud.

TimeDelay = 1 + ( 0,1 * N ) seconds at


Possible error messages: 19200 Baud.
This protocol gives an error message if the
N is the number of compressors connected
communication fails. The error message is
to this COMSAB II module.
given in the Data field:
Another delay occurs in the communication
Data field: _____ No error ( 6 spaces ).
between the COMSAB II and the central
Data field: F___3 Code does not exist. computer. This delay depends on the se-
Data field: F___4 Index does not exist. quence of communications from the central
Data field: F___5 Point does not exist. computer to the COMSAB II. (As worst case).
Data field: F___6 Read/write not At worst, this time delay must be added to
possible. the time delay calculated above.
Data field: F___7 UNISAB/PROSAB
does not exist. Examples:
Data field: F___8 No such control In the following some message examples are
system. given. The message codes are shown both
Data field: F___9 Syntax error in as HEX values and as ASCII characters
message received. [in sharp parenthesis].

8 0178-444--ENG
Example 1: Telegram from the central computer to the
Read the oil temperature in compressor #5: COMSAB II:

Telegram from the central computer to the Stx - Code - Index - Point - Data--field - Etx
COMSAB II: 02H 21H 20H 30H _ _ -- 2 5 0 03H
[^B!!0¬¬--250^C]
Stx - Code - Index - Point - Data--field - Etx
02H 20H 24H 22H _ _ _ _ _ _ 03H Reply from the COMSAB II to the central
[^B¬$”¬¬¬¬¬¬^C] computer:

Stx - Code - Index - Point - Data--field - Etx


Reply from the COMSAB II to the central
02H 21H 20H 30H _ _ -- 2 5 0 03H
computer:
[^B!!0¬¬--250^C]
Stx - Code - Index - Point - Data--field - Etx
Set point 2 for suction pressure control has
02H 20H 24H 22H _ _ _ 5 3 1 03H
now been changed to the value --25,0 ’C/R.
[^B¬$”¬¬¬531^C]
Example 4:
This means that the oil temperature is Start compressor #3.
53,1 ’C.
Telegram from the central computer to the
Example 2: COMSAB II:
Read the control mode of compressor #2:
Stx - Code - Index - Point - Data--field - Etx
Telegram from the central computer to the 02H 21H 22H 35H _ _ _ _ _1 03H
COMSAB II: [^B!”5¬¬¬¬¬1^C]

Stx - Code - Index - Point - Data--field - Etx Reply from the COMSAB II to the central
02H 20H 21H 3FH _ _ _ _ _ _ 03H computer:
[^B¬!?¬¬¬¬¬¬^C]
Stx - Code - Index - Point - Data--field - Etx
Reply from the COMSAB II to the central 02H 21H 22H 35H _ _ _ _ _1 03H
computer: [^B!”5¬¬¬¬¬1^C]

Stx - Code - Index - Point - Data--field - Etx Compressor #3 will now start.
02H 20H 21H 3FH _ _ _ _ 3 0 03H Example 5:
[^B¬!?¬¬¬¬30^C] Start compressor #3 -- error message.
According to the table Control modes this Telegram from the central computer to the
means the compressor is in remote control. COMSAB II:

Example 3: Stx - Code - Index - Point - Data--field - Etx


Write a new set point 2 for suction pressure 02H 21H 22H 35H _ _ _ _ _1 03H
control, on compressor #1: [^B!”5¬¬¬¬¬1^C]

0178-444--ENG 9
Reply from the COMSAB II to the central Stx - Code - Index - Point - Data--field - Etx
computer: 02H 20H 22H 34H _ _ _ _ _ _ 03H
[^B¬”4¬¬¬¬¬¬^C]
Stx - Code - Index - Point - Data--field - Etx
read first alarm in the queue
02H 21H 22H 35H F _ _ _ _ 6 03H Reply from the COMSAB II to the central
[^B!”5F¬¬¬¬6^C] computer:
Compressor #3 will not start. Perhaps be- Stx - Code - Index - Point - Data--field - Etx
cause compressor #3 does not exist (in the 02H 20H 22H 34H _ _ _ _ _ 0 03H
communications system), maybe the com- [^B¬”40¬¬¬¬¬^C]
pressor is not in remote control or the com- no alarm in the queue
pressor cannot start because of an alarm in
OR:
the control system.
Reply from the COMSAB II to the central
Example 6: computer:
Read alarms from compressor #3.
Stx - Code - Index - Point - Data--field - Etx
In the UNISAB II all alarms, i.e. an alarm 02H 20H 22H 34H _ _ _ _ 4 2 03H
number, are stored in an alarm-queue, con- [^B¬”4¬¬¬¬42^C]
taining max. 5 alarms. first alarm is ”High oil temperature”
The first (oldest) alarm is stored in ”alarm 1” Telegram from the central computer to the
(read point 52), the next alarm in ”alarm 2” COMSAB II:
(read point 53) and the last (newest) alarm is
Stx - Code - Index - Point - Data--field - Etx
stored in ”alarm 5” (read point 56) -- see read
02H 20H 22H 35H _ _ _ _ _ _ 03H
table.
[^B¬”5¬¬¬¬¬¬^C]
To read the UNISAB II alarm-queue you will read second alarm in the queue
have to do the following: Reply from the COMSAB II to the central
Send a read message -- reading point 52. computer:
Stx - Code - Index - Point - Data--field - Etx
If there isn’t any alarm in the UNISAB II then
02H 20H 22H 35H _ _ _ _ _ 0 03H
the reply will be a 0 (zero).
[^B¬”5¬¬¬¬¬0^C]
If there is one (or more) alarms in the no more alarms in the queue
UNISAB II then the reply will be the number OR:
of the oldest alarm, i.e. a alarm number from
Reply from the COMSAB II to the central
31 to 76 -- see the table of alarm/warnings.
computer:
To see if there is more than one alarm in the
Stx - Code - Index - Point - Data--field - Etx
queue, send a read message reading point
02H 20H 22H 34H _ _ _ _ 4 7 03H
53, then point 54, 55 and 56 until the reply
[^B¬”5¬¬¬¬47^C]
from the COMSAB II is a 0 (zero).
second alarm is ”Compressor motor error”
Telegram from the central computer to the
COMSAB II: and so on...

10 0178-444--ENG
Example 7: Reply from the COMSAB II to the central
Read warnings from compressor #3. computer:

In the UNISAB II all warnings, i.e. a warning Stx - Code - Index - Point - Data--field - Etx
number, are stored in an warning-queue, 02H 20H 22H 39H _ _ _ _ _ 0 03H
containing max. 5 warnings. [^B¬”9¬¬¬¬¬0^C]
no warnings in the queue
The first (oldest) warning are stored in ”warn-
ing 1” (read point 57), the next warning in OR:
”warning 2” (read point 58) and the last (new- Reply from the COMSAB II to the central
est) warning are stored in ”warning 5” (read computer:
point 61) -- see read table.
Stx - Code - Index - Point - Data--field - Etx
The procedure for reading the warning-queue 02H 20H 22H 39H _ _ _ _ 4 2 03H
is the same as for reading the alarm-queue, [^B¬”9¬¬¬¬42^C]
see example 6. first warning is ”High oil temperature”

To read the UNISAB II warning-queue you Telegram from the central computer to the
will have to do the following: COMSAB II:

Send a read message -- reading point 57. Stx - Code - Index - Point - Data--field - Etx
02H 20H 22H 3AH _ _ _ _ _ _ 03H
If there isn’t any warning in the UNISAB II [^B¬”:¬¬¬¬¬¬^C]
then the reply will be a 0 (zero). read second warning in the queue
If there is one (or more) warnings in the Reply from the COMSAB II to the central
UNISAB II then the reply will be the number computer:
of the oldest warning, i.e. a warning number
from 31 to 76 -- see the table of alarm/warn- Stx - Code - Index - Point - Data--field - Etx
ings. 02H 20H 22H 3AH _ _ _ _ _ 0 03H
[^B¬”:¬¬¬¬¬0^C]
To see if there is more than one warning in no more warnings in the queue
the queue, then send a read message read-
ing point 58, then point 59, 60 and 61, until OR:
the reply from the COMSAB II is a 0 (zero). Reply from the COMSAB II to the central
computer:
Telegram from the central computer, to the
COMSAB II: Stx - Code - Index - Point - Data--field - Etx
02H 20H 22H 3AH _ _ _ _ 3 2 03H
Stx - Code - Index - Point - Data--field - Etx
[^B¬”:¬¬¬¬32^C]
02H 20H 22H 39H _ _ _ _ _ _ 03H
second warning is ”High suction pressure”
[^B¬”9¬¬¬¬¬¬^C]
read first warning in the queue and so on...

0178-444--ENG 11
Table 0178-402 - Points to READ for UNISAB II:

Name of value: COMSAB Available on: Data format


II
POINT PII/UI U-II Range UNIT
Suction gas temp. 32 X X I*0,1 °C
Disch. gas temp. 33 X X I*0,1 °C
Oil temp 34 X X I*0,1 °C
Suct.pressure 35 X X I*0,1 BAR
Disch.pressure 36 X X I*0,1 BAR
Suct.pressure 37 X X I*0,1 ’C/R
Disch.pressure 38 X X I*0,1 ’C/R
Capacity position 39 X X I*0,1 %
Volume slide position 40 X(7) X I*0,1 %
Motor current 41 X X I*0,1 Amps
Universal regulator 42 X I*0,1 %
Oil filter diff.pressure (s) / 43 X(8) X I*0,1 BAR
intermediate pressure (r)
Suct. gas superheat 44 X X I*0,1 °C
Brine /intermediate temperature 45 X(9) X I*0,1 °C
Running hours 46 X(10) X(10) UI Hours
Setp.1, suct.press. 47 X X I*0,1 °C/R
Setp.2, suct.press. 48 X X I*0,1 °C/R
N.zone, suct.press 49 X X I*0,1 °C/R
Set point actual, brine temp 50 X X I*0,1 °C
N.zone, brine temp 51 X X I*0,1 °C
Alarm 1 52 X X B (4)
Alarm 2 53 X X B (4)
Alarm 3 54 X X B (4)
Alarm 4 55 X X B (4)
Alarm 5 56 X X B (4)
Warning 1 57 X X B (4)
Warning 2 58 X X B (4)
Warning 3 59 X X B (4)
Warning 4 60 X X B (4)
Warning 5 61 X X B (4)

12 0178-444--ENG
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
Compressor mode 62 X X B (3)
Control mode 63 X X B (2)
Startsequence no. 64 X X B 0-14
Suct.system 1 regulator 65 X B 1-14
Suct.system 2 regulator 66 X B 1-14
Suct.system 3 regulator 67 X B 1-14
Suct.system 4 regulator 68 X B 1-14
Suct.system 5 regulator 69 X B 1-14
Suct.system 6 regulator 70 X B 1-14
Suct.system 7 regulator 71 X B 1-14
Suct.system 8 regulator 72 X B 1-14
Suct.system 9 regulator 73 X B 1-14
Suct.system 10 regulator 74 X B 1-14
Suct.system 11 regulator 75 X B 1-14
Suct.system 12 regulator 76 X B 1-14
Suct.system 13 regulator 77 X B 1-14
Suct.system 14 regulator 78 X B 1-14
System for this unit 79 X X B 1-14
Which control system 80 X X B (5)
Oil pressure 81 X X I*0,1 BAR
MultiSab state 82 (X) (X) B (6)
Preceding compr 83 (X) (X) B 1-14
Next compr. 84 (X) (X) B 1-14
Cmp to follow the next 85 (X) (X) B 1-14
Selected sysregulator 86 X X B 1-14
Communication errors 87 X X I %
Not used 88
Disch.gas superheat 89 X I*0,1 °C
Switch reg. SP1/SP2 90 X B 0-1
Set point actual, suct. press. 91 X I*0,1 °C/R
P.band, suct. press. 92 X I*0,1 °C/R
Set point 1, brine temp. 93 X I*0,1 °C

0178-444--ENG 13
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
Set point 2, brine temp. 94 X I*0,1 °C
P. band, brine temp. 95 X I*0,1 °C
Set point actual, discharge 96 X I*0,1 °C/R
Set point 1, discharge 97 X I*0,1 °C/R
Set point 2, discharge 98 X I*0,1 °C/R
N. zone, discharge 99 X I*0,1 °C/R
P. band, discharge 100 X I*0,1 °C/R
Set point actual, external 101 X I*0,1 %
Set point 1, external 102 X I*0,1 %
Set point 2, external 103 X I*0,1 %
N. zone, external 104 X I*0,1 %
P. band, external 105 X I*0,1 %
Set point 1, oil pressure 106 X I*0,1 BAR
Set point 2, oil pressure 107 X I*0,1 BAR
Switch motor SP1/SP2 108 X B 0-1
Set point 1, motor curr. 109 X I Amps
Set point 2, motor curr. 110 X I Amps
Ext. starting permission - normal 111 X B 0-1
Ext. starting permission - instant 112 X B 0-1
Start request OK (PMS) 113 X B 0-1
Set point 1, oil temp. -- cooling 114 X I*0,1 °C
Set point 2, oil temp. -- heating 115 X I*0,1 °C
N. zone, oil temp. 116 X I*0,1 °C
P. band, oil temp. 117 X I*0,1 °C
Set point 1, suct. gas superheat 118 X I*0,1 °C
Set point 1, disch. gas temp. 119 X I*0,1 °C
Set point 1, volume slide 120 X I*0,1 %
Run time since last start 121 X(11) UI Sek
Setpoint 1, capacity 122 X I*0,1 %
N. zone capacity 123 X I*0,1 %
P. band capacity 124 X I*0,1 %
Cap. mode 125 X(13) B 0-1
Software version 127 X I
Start-start delay 130 X I Sek
Stop-start delay 131 X I --

14 0178-444--ENG
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
Delay before start 132 X I --
Delay before stop 133 X I --
Suct. press. ramp function 134 X I --
Slide max. down time (s)/ 135 X I --
Delay up (r)
Prelubrication (s)/ 136 X I --
Delay down (r)
Oil flow switch active (s)/ 137 X I --
Take over max. time (r)
Oil flow switch delay (s)/ 138 X I --
Take over delay (r)
Oil flow max. drop out (s)/ 139 X I --
M-press. (r)
Lubrication time after start (s)/ 140 X I --
not used (r)
Difference pressure OK (s)/ 141 X I --
not used (r)
Oil pressure low -- delay 142 X I --
Oil filter diff. press. high (s)/ 143 X I --
oil pressure high (r)
Oil temperature low 144 X I --
Oil temperature high 145 X I --
Superheat low 146 X I --
Superheat high 147 X I --
Discharge press. overload 148 X I --
Motor current overload 149 X I --
Compr. motor starting time 150 X I --
PMS feed back 151 X I --
Full flow pump starting time (s)/ 152 X I --
not used (r)
Oil pump starting time (s)/ 153 X I --
not used (r)
Oil rectifier start 154 X I --
Oil rectifier delay 155 X I --
Oil rectifier suppress 156 X I --

0178-444--ENG 15
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
Start High press. 157 X I --
Communication delay 158 X I --
Cap. negative 159 x I --
P.band factor, start delay 160 X B 1-10
P.band factor, stop delay 161 X B 1-10
P.band factor, delay up (r) 162 X B 1-10
P.band factor, delay down (r) 163 X B 1-10
Transfer factor, delay down (r) 164 X B 1-10
Transfer zone, delay down (r) 165 X I %
Take over factor, delay up (r) 166 X B 1-10
Take over factor, start delay (r) 167 X B 1-10
Take over zone, delay up (r) 168 X I %
Compressor type 170 X I 1-50
Refrigerant type 171 X B 1-9
Regulation mode 172 X B 0-5
VI-control mode 173 X B 0-1
Automatic start 174 X B 0-1
Automatic stop 175 X B 0-1
Prelubrication 176 X B 0-1
Full flow pump 177 X B 0-1
Booster 178 X B 0-1
Compressor no. 179 X B 0-14
Regulation master choice 180 X B 0-1
Economizer 181 X B 0-1
Economizer min. capacity 182 X I*0,1 %
Economizer max. suct. press. 183 X I*0,1 °C/R
Common condenser 184 X B 0-3
HP compr. on two stage 185 X B 0-1
Discharge cooling 186 X B 0-1
Oil cooling type 187 X B 0-4
Motor current range 188 X I Amps
Swept volume 189 X I m3/h
Cold store control 190 X B 0-1

16 0178-444--ENG
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
Out door temp. compensation 191 X B 0-1
Total unload 192 X B 0-1
Baud rate 193 X I baud
Oil rectifier 194 X B 0-1
Eur./US-units 195 X B 0-1
Factory reset 196 X B 0-1
Language 197 X B 1-15
Contrast 198 X I %
Aux. analog input function 199 X B 0-6
Aux. digital output function 200 X B 0-5
Cap. lim. low 201 X I*0,1 %
Cap. lim. high 202 X I*0,1 %
Manual zero 203 X I*0,1 %
Suct. pressure limits -- high alarm 204 X I*0,1 BAR
-- -- -- high warning 205 X I*0,1 BAR
-- -- -- low warning 206 X I*0,1 BAR
-- -- -- low alarm 207 X I*0,1 BAR
Disch.pressure limits -- high alarm 208 X I*0,1 BAR
-- -- -- high warning 209 X I*0,1 BAR
-- -- -- low warning 210 X I*0,1 BAR
-- -- -- low alarm 211 X I*0,1 BAR
Oil pressure limits -- high alarm 212 X I*0,1 BAR
-- -- -- high warning 213 X I*0,1 BAR
-- -- -- low warning 214 X I*0,1 BAR
-- -- -- low alarm 215 X I*0,1 BAR
Oil filter diff. press. limits (s) / 216 X I*0,1 BAR
Interm.press.limits(r) -- high alarm
-- -- -- high warning 217 X I*0,1 BAR
-- -- -- low warning 218 X I*0,1 BAR
-- -- -- low alarm 219 X I*0,1 BAR
Disch.temp. limits -- high alarm 224 X I*0,1 °C
-- -- -- high warning 225 X I*0,1 °C

0178-444--ENG 17
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
-- -- -- low warning 226 X I*0,1 °C
-- -- -- low alarm 227 X I*0,1 °C
Oil temp. limits -- high alarm 228 X I*0,1 °C
-- -- -- high warning 229 X I*0,1 °C
-- -- -- low warning 230 X I*0,1 °C
-- -- -- low alarm 231 X I*0,1 °C
Brine temperature (a) limits / 232 X I*0,1 °C
intermediate temp. (b) limits
-- high alarm
-- -- -- high warning 233 X I*0,1 °C
-- -- -- low warning 234 X I*0,1 °C
-- -- -- low alarm 235 X I*0,1 °C
Suct.gas superheat -- high alarm 236 X I*0,1 °C
-- -- -- high warning 237 X I*0,1 °C
-- -- -- low warning 238 X I*0,1 °C
-- -- -- low alarm 239 X I*0,1 °C
Disch.gas superheat -- high alarm 240 X I*0,1 °C
-- -- -- high warning 241 X I*0,1 °C
-- -- -- low warning 242 X I*0,1 °C
-- -- -- low alarm 243 X I*0,1 °C
External input limits -- high alarm 244 X I*0,1 %
-- -- -- high warning 245 X I*0,1 %
-- -- -- low warning 246 X I*0,1 %
-- -- -- low alarm 247 X I*0,1 %
Suct. pressure limits -- high alarm 248 X I*0,1 °C/R
-- -- -- high warning 249 X I*0,1 °C/R
-- -- -- low warning 250 X I*0,1 °C/R
-- -- -- low alarm 251 X I*0,1 °C/R
Disch.pressure limits -- high alarm 252 X I*0,1 °C/R
-- -- -- high warning 253 X I*0,1 °C/R
-- -- -- low warning 254 X I*0,1 °C/R
-- -- -- low alarm 255 X I*0,1 °C/R

18 0178-444--ENG
COP - valves Points to READ:

Name of value: COMSAB Available on: Data format


II
POINT PII/UI U-II Range UNIT
COP 32 X I*0.1
COP Carnot 33 X I*0.1
COP Mechanical 34 X I*0.1
Cooling Power 35 X I Kw
Mass Flow 36 X I kg/h
Shaft Power 37 X I Kw
Motor COP 38 X I*0.1 --
Volume Flow 39 X I m3/h
Superheated Spec. Volume 40 X I*0.1 l/kg
Saturated Spec. Volume 41 X I*0,1 l/kg
Enthalpy H1 42 X I kJ/kg
Enthalpy H4 43 X I kJ/kg
Enthalpy H2 44 X I kJ/kg

Please note that the command for reading these points has code 22H.

0178-444--ENG 19
Note the following: Read point 52. If there isn’t any
alarm in the UNISAB II then the
X: Valid for this control system:
reply will be a 0 (zero). If there is
PII/UI = PROSAB II and UNISAB S/ one (or more) alarms in the
R/ RT/ RTH. UNISAB II then reply will be the
number of the oldest alarm, i.e. a
UII = UNISAB II. alarm number from 31 to 76 - see
the table of alarm/warnings.
(X): Not used for normal control purpose.
Too see if there are more than one
Range: I = Integer, ie. data range alarm in the queue, then send a
-- 32268 -- + 32267 read message reading point 53, then
point 54, 55 and 56, until the reply
UI= Unsigned integer, ie.data from the COMSAB II is a 0 (zero).
range 0 -- 65535
The same procedure is used when
I*0,1 = Integer value in 1/10 of the reading the warnings-que.
unit for this point. I.e. for point 32
(5): See ”TABLE OF CONTROL
”suction gas temp.” this means that
SYSTEMS”.
a read value of 325 is 32,5°C.
(6): See ”TABLE OF MULTISAB
B = Byte, ie. data range
STATES”.
-- 128 -- + 127 or 0 -- 255.
(7): Only PROSAB II and UNISAB S.
(1): Only when hardware option
available. For UNISAB S this is a
calculated value.
(2): See ”TABLE OF COMPRESSOR Not a measured value.
CONTROL MODES”.
(8): Only PROSAB II, UNISAB S and
(3): See ”TABLE OF COMPRESSOR UNISAB R.
MODES”.
(9): Not UNISAB R.
(4): See ”TABLE OF ALARM/
WARNINGS”. (10): Running hours are read as
In the UNISAB II all alarms, i.e. a hours x 1.
alarm number, are stored in an
(11): Run time since last start are read in
alarm-queue, containing max. 5
sec.
alarms. The first (oldest) alarm are
stored in ”alarm1” (read point 52), (12): Not implemented.
the next alarm in ”alarm 2” (read
point 53) and the last (newest) alarm (13): Only UNISAB II. See notes for
are stored in ”alarm 5” capacity control
(read point 56) - see read table.
(s): Only screw compressors.
To read the UNISAB II alarm-queue
you will have to do the following: (r): Only reciprocating compressors.

20 0178-444--ENG
Table 0178-402 - Points to WRITE for UNISAB II:
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
Start sequence no. 32 X X B 0-14
Suct.system 1 regulator 33 X B 1-14
Suct.system 2 regulator 34 X B 1-14
Suct.system 3 regulator 35 X B 1-14
Suct.system 4 regulator 36 X B 1-14
Suct.system 5 regulator 37 X B 1-14
Suct.system 6 regulator 38 X B 1-14
Suct.system 7 regulator 39 X B 1-14
Suct.system 8 regulator 40 X B 1-14
Suct.system 9 regulator 41 X B 1-14
Suct.system 10 regulator 42 X B 1-14
Suct.system 11 regulator 43 X B 1-14
Suct.system 12 regulator 44 X B 1-14
Suct.system 13 regulator 45 X B 1-14
Suct.system 14 regulator 46 X B 1-14
Setp.1, suct.press. 47 X X I*0,1 °C/R
Setp.2, suct.press. 48 X X I*0,1 °C/R
N.zone, suct.press 49 X X I*0,1 °C/R
Setpoint 1, brine temp 50 X X I*0,1 °C
N.zone, brine temp 51 X X I*0,1 °C
Setpoint for capacity 52 X (1) X (1) I*0,1 %
Start compressor 53 X (3) X (3) B 1
Stop compressor 54 X (4) X (4) B 0
Select suction system 55 X X B 1-14
Setpoint 2, brine temp 56 X X I*0,1 °C
Control mode 63 X (2) B 0-3
P.band, suct. press. 92 X I*0,1 °C/R
P. band, brine temp. 95 X I*0,1 °C
Set point 1, discharge 97 X I*0,1 °C/R
Set point 2, discharge 98 X I*0,1 °C/R
N. zone, discharge 99 X I*0,1 °C/R

0178-444--ENG 21
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
P. band, discharge 100 X I*0,1 °C/R
101
Set point 1, external 102 X I*0,1 %
Set point 2, external 103 X I*0,1 %
N. zone, external 104 X I*0,1 %
P. band, external 105 X I*0,1 %
Set point 1, oil pressure 106 X I*0,1 BAR
Set point 2, oil pressure 107 X I*0,1 BAR
Set point 1, motor curr. 109 X I Amps
Set point 2, motor curr. 110 X I Amps
Set point 1, oil temp. -- cooling 114 X I*0,1 °C
Set point 2, oil temp. -- heating 115 X I*0,1 °C
N. zone, oil temp. 116 X I*0,1 °C
P. band, oil temp. 117 X I*0,1 °C
Set point 1, suct. gas superh. 118 X I*0,1 °C
Set point 1, disch. gas temp. 119 X I*0,1 °C
N. zone, capacity 123 X I*0,1 °C
P. band, capacity 124 X I*0,1 °C
Start-start delay 130 X I Sek
Stop-start delay 131 X I --
Delay before start 132 X I --
Delay before stop 133 X I --
Suct. press. ramp function 134 X I --
Slide max. down time (s)/ Delay up (r) 135 X I --
Prelubrication (s)/ Delay down (r) 136 X I --
PMS feed back 151 X I --
Oil rectifier start 154 X I --
Oil rectifier delay 155 X I --
Oil rectifier suppress 156 X I --
Start High press. 157 X I --
P.band factor, start delay 160 X B 1-10
P.band factor, stop delay 161 X B 1-10
P.band factor, delay up (r) 162 X B 1-10

22 0178-444--ENG
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
P.band factor, delay down (r) 163 X B 1-10
Transfer factor, delay down (r) 164 X B 1-10
Transfer zone, delay down (r) 165 X I %
Take over factor, delay up (r) 166 X B 1-10
Take over factor, start delay (r) 167 X B 1-10
Take over zone, delay up (r) 168 X I %
Regulation mode 172 X B 0-5
Automatic start 174 X B 0-1
Automatic stop 175 X B 0-1
Regulation master choice 180 X B 0-1
Economizer 181 X B 0-1
Economizer min. capacity 182 X I*0,1 %
Economizer max. suct. press. 183 X I*0,1 °C/R
Cold store control 190 X B 0-1
Suct. pressure limits -- high alarm 204 X I*0,1 BAR
-- -- -- high warning 205 X I*0,1 BAR
-- -- -- low warning 206 X I*0,1 BAR
-- -- -- low alarm 207 X I*0,1 BAR
Disch.pressure limits -- high alarm 208 X I*0,1 BAR
-- -- -- high warning 209 X I*0,1 BAR
-- -- -- low warning 210 X I*0,1 BAR
-- -- -- low alarm 211 X I*0,1 BAR
Oil pressure limits -- high alarm 212 X I*0,1 BAR
-- -- -- high warning 213 X I*0,1 BAR
-- -- -- low warning 214 X I*0,1 BAR
-- -- -- low alarm 215 X I*0,1 BAR
Oil filter diff. press. limits (s) / 216 X I*0,1 BAR
Intermed. press. limits (r)-- high alarm
-- -- -- high warning 217 X I*0,1 BAR
-- -- -- low warning 218 X I*0,1 BAR
-- -- -- low alarm 219 X I*0,1 BAR
Disch.temp. limits -- high alarm 224 X I*0,1 °C

0178-444--ENG 23
Name of value: COMSAB Available on: Data format
II
POINT PII/UI U-II Range UNIT
-- -- -- high warning 225 X I*0,1 °C
-- -- -- low warning 226 X I*0,1 °C
-- -- -- low alarm 227 X I*0,1 °C
Oil temp. limits -- high alarm 228 X I*0,1 °C
-- -- -- high warning 229 X I*0,1 °C
-- -- -- low warning 230 X I*0,1 °C
-- -- -- low alarm 231 X I*0,1 °C
Brine temperature (a) limits / 232 X I*0,1 °C
intermediate temp. (b) limits
-- high alarm
-- -- -- high warning 233 X I*0,1 °C
-- -- -- low warning 234 X I*0,1 °C
-- -- -- low alarm 235 X I*0,1 °C
Suct.gas superheat -- high alarm 236 X I*0,1 °C
-- -- -- high warning 237 X I*0,1 °C
-- -- -- low warning 238 X I*0,1 °C
-- -- -- low alarm 239 X I*0,1 °C
Disch.gas superheat -- high alarm 240 X I*0,1 °C
-- -- -- high warning 241 X I*0,1 °C
-- -- -- low warning 242 X I*0,1 °C
-- -- -- low alarm 243 X I*0,1 °C
External input limits -- high alarm 244 X I*0,1 %
-- -- -- high warning 245 X I*0,1 %
-- -- -- low warning 246 X I*0,1 %
-- -- -- low alarm 247 X I*0,1 %
Suct. pressure limits -- high alarm 248 X I*0,1 °C/R
-- -- -- high warning 249 X I*0,1 °C/R
-- -- -- low warning 250 X I*0,1 °C/R
-- -- -- low alarm 251 X I*0,1 °C/R
Disch.pressure limits -- high alarm 252 X I*0,1 °C/R
-- -- -- high warning 253 X I*0,1 °C/R
-- -- -- low warning 254 X I*0,1 °C/R
-- -- -- low alarm 255 X I*0,1 °C/R

24 0178-444--ENG
Note the following: Start conditions are:
X : Valid for this control system. -- Control mode = Remote +
PII/UI= PROSAB II and UNISAB S/ Config/Auto Start = YES or NO
R/ RT/ RTH
-- Compressor mode = Ready
UII= UNISAB II
(4) ”STOP COMPRESSOR”,
Range: I = Integer, ie. data range point = 54, must have datafield = 0
-- 32268 -- + 32267
Stop conditions are:
UI= Unsigned integer, ie.data
range 0 -- 65535 -- Control mode = Remote +
Config/Auto Stop = YES or NO
I*0,1 = Integer value in 1/10 of the
unit for this point. I.e. for point 32 -- Compressor mode = Running
”suction gas temp.” this means that (-- overload/suct.lim./disch.lim.) etc.
a read value of 325 is 32,5°C.
(5) Min/max limits for values written to
B = Byte, ie. data range PROSAB II or UNISAB I.
-- 128 -- + 127 or 0 -- 255
Point No. Min-limit Max-limit Unit
(1) Only PROSAB II, UNISAB S and
UNISAB II. 32 0 14 --
Se notes for Capacity Control. 33 -- 46 + 55 1 14 --
(2): See ”TABLE OF COMPRESSOR 47 + 48 --200 100 °C/R
CONTROL MODES”. 50 + 56 -- 70 210 °C
It is only possible to change to and 49 + 51 0 100 °C
from mode 0, 2 and 3. 52 0 100 %

(3) ”START COMPRESSOR”, 53 1 1 --


poin =53, must have datafield = 1 54 0 0 --

0178-444--ENG 25
Capacity Control (communication) The timers DELAY UP and DELAY DOWN
will be in function if the UNISAB II program
It is possible directly to control the capacity of
version is 1.08 or later.
the compressor by sending a capacity set-
point by communication. Notice, however, that the various limiting
functions may reduce the compressor capa-
For UNISAB II it is possible to control the ca- city.
pacity on both screw compressors and recip-
rocating compressors. When a capacity setpoint is sent to UNISAB
II, UNISAB S or PROSAB II it will enter the
For PROSAB II and UNISAB S it is only pos- capacity regulation mode, this can be seen
sible to control the capacity on screw com- by the fact that the start number is set to zero
pressors. (the ”old” start number is remembered,
UNISAB II stores the number itself and for
UNISAB II must be set to REMOTE in picture
UNISAB S/ PROSAB II the number is stored
CONTROL.
in PCCOMSAB II) .
PROSAB II and UNISAB must be set to RE- UNISAB II, UNISAB S or PROSAB are taken
MOTE mode by using the SET button. out of capacity regulation mode by sending a
new setpoint 1 or 2, neutral zone (NZ) or pro-
Screw compressors (when running) will di-
portional band (PB) value to one of the other
rectly follow the capacity value (0--100%)
regulators, e.g. suction regulator, brine regu-
whitch is specified in ”Setpoint for capacity”,
lator etc. When UNISAB / PROSAB II are
point 52 (remember the setpoint is in 1/10 of
taken out of capacity regulation mode the old
percent).
start number is reinserted.
Notice, however, that the various limiting It is possible to take UNISAB II out of capac-
functions may reduce the compressor capa- ity regulation mode by changing START NO
city. back to the old start number on the UNISAB
II display. In that case you must reset COM-
Reciprocating compressors will shift one ca-
SAB II. This is done by making a power off/
pacity stage up or down, depending on
on.
whether the value specified in ”Setpoint for
capacity”, point 52, is above or below the Read point 125 ”Cap. mode” will be ”1” if
percentage value that correspondes to the UNISAB II is in capacity regulation mode,
capacity stage in question. else ”Cap mode” will be ”0”.

26 0178-444--ENG
Start: Stop:

The compressor can be started in two ways The compressor can be stopped in two ways
(situation 2 is only possible for UNISAB II) (situation 2 is only possible for UNISAB II)

1. By sending the stop command ”STOP


1. By sending the start command ”START COMPRESSOR”, point 54
COMPRESSOR”, point 53.
2. When the capacity setpoint sent is below
2. When the capacity setpoint sent is above 5 % and AUTO STOP = YES has been
5 % and AUTO START = YES has been configured, the timer STOP DELAY begins
configured, the timer START DELAY be- to count down in case of screw compres-
gins to count down in case of screw com- sors.
pressors.
For reciprocating compressors the timer
STOP DELAY starts once the signal is be-
For reciprocating compressors the timer
low the lowest capacity stage, ie below
START DELAY starts once the signal is
25%, 33% or 50% depending on type,
above the lowest capacity stage, i.e.
however, for reciprocating compressors
above 25%, 33% or 50%, depending on
with total unloading, the timer STOP
type.
DELAY starts counting down, once the
signal is below 0%.
When the timer START DELAY has
counted down, the compressor starts and When the timer STOP DELAY has
will now follow the setpoint up/down. counted down, the compressor will stop.

0178-444--ENG 27
COMPRESSOR CONTROL MODES: Type = 1 = ”PROSAB II”
Control mode = 0 = ”STOPPED” Type = 2 = ”UNISAB, recip. compr.”
Control mode = 1 = ”MANUAL CONTROL” Type = 3 = ”UNISAB, screw compr.”

Control mode = 2 = ”AUTOMATIC CON- Type = 4 = ”UNISAB II”


TROL”

Control mode = 3 = ”REMOTE CONTROL” MULTISAB STATE:


Mode = 0 = ”NO PERMISSION TO START”
COMPRESSOR MODES: Mode = 1 = ”DO NOT START” (1)
Mode = 0 = NO UNIT CONNECTED
Mode = 2 = ”MAY START” (1)
Mode = 1 = ”READY”
Mode = 3 = ”RUNS AT 100 % CAPACITY”
Mode = 2 = ”RUNNNING”
Mode = 4 = ”LEAD COMPRESSOR”
Mode = 3 = ”STARTING”
Mode = 5 = ”LAG COMPRESSOR”
Mode = 4 = ”SHUTDOWN”
Mode = 6 = ”STOPPING”
Mode = 5 = ”PAUSE” Mode = 7 = ”RUNS, BUT WITHOUT
Mode = 6 = ”PRELUB” LEAD--LAG CONTROL”

Mode = 7 = ”CAPACITY SLIDE DOWN” Mode = 8 = ”STOPPING --


RAMPS CAPACITY UP”
Mode = 8 = ”RUNNING -- OVERLOAD”
Mode = 9 = ”STOPPING --
Mode = 9 = ”RUNNING DISCH. PRESSURE RAMPS CAPACITY DOWN”
LIMITATION”
Mode = 10 = ”ROTATUNE MASTER”
Mode = 10 = ”RUNNING SUCT. PRESSURE
Mode = 11 = ”ROTATUNE SLAVE”
LIMITATION”

Mode = 11 = ”STOPPED”

Note:
CONTROL SYSTEMS: (1) MULTISAB STATE mode 1 and 2 are
Type = 0 = NO SYSTEM reversed in PROSAB II.

28 0178-444--ENG
Table of alarms/warnings for UNISAB II

Id Alarm/warning text Alarm Warning

#31 Low suction pressure X X


#32 High suction pressure X (7)
#33 Low suction superheat X X
#34 High suction superheat X (8) X (8)
#35 Low discharge pressure X
#36 High discharge pressure X X
#37 High discharge temperature X X
#38 Low oil pressure X X
#39 Low brine-/interm. temperature X X
#40 Low discharge temperature X (8)
#41 Low oil temperature X X
#42 High oil temperature X X
#43 High oil filter diff. press. 2) X X
#44 Oil system error 2) X
#45 Capacity error 2)+4) X
#46 Compressor motor overload X
#47 Compressor motor error X
#48 Oil pump error 2)+3)+9) X (7)
#49 High motor temperature X
#51 Prom error X (5)
#52 Ram error X (5)
#53 Cpu error X (5)
#54 Sensor error X (5)
#55 PMS error X (6)
#56 No start permision X (6)
#57 High differential pressure 1) X (6) X (6)
#58 High brine-/interm. temperature X (6) X (6)
#59 High oil pressure 1) X (6) X (6)
#60 High intermediate pressure 1) X (6) X (6)
#61 Low intermediate pressure 1) X (6) X (6)

0178-444--ENG 29
Id Alarm/warning text Alarm Warning

#62 Full-flow pump error 2)+3) X (6)


#64 Oil rectifier error 2) X (6)
#65 Wrong start no. in sequence X (6)
#66 Diagnose EEPROM error X (6)
#67 Low external input signal X (6) X (6)
#68 High external input signal X (6) X (6)
#69 Low discharge superheat X (6) X (6)
#70 Discharge pressure overload X (6)
#73 Limiting suction pressure X (6)
#74 Limiting discharge pressure X (6)
#75 Limiting brine temp. X (6)
#76 Limiting hot water X (6)
#77 Evolution, warning from PLC X (6)
#78 Limiter, discharge temperature X (6)
#79 Watch the oil pressure X (2) (6)
#80 Common alarm from Chiller X (6)
#81 Chiller, no communication to Chiller X (6) X (6)
#82 Cooling fan error X (2) (6)
#83 Vi position error X (2) (6)
#84 Lube press X (2) (6) X (2) (6)

Note the following:


(1): Reciprocating Compressors only (5): Alarm/warning #51 -- #54
only for PROSAB II.
(2): Screw Compressors only
(6): Alarm/warning #55 -- #84
(3): The alarm will function as a warning only for UNISAB II.
when the compressor is running, i.e.
(7): Not UNISAB R/RT/RTH/S.
after prelubrication.
(8): Not PROSAB II
(4): The alarm will only stop the
compressor in mode remote/ (9): The alarm LOW OIL PUMP PRES-
multisab, in mode manual or auto SURE DURING OPERATION ap-
the compressor will not be stopped, plies to SAB 80. The alarm is only
i.e. the alarm will function as a activated at a discharge pressure
warning. level below 16 Bar.

30 0178-444--ENG
Chiller
The following tables are valid for UNISAB Chiller only.
Codes for read and write dommando are the same as for UNISAB II. The index= Chiller no. will
make the difference between UNISAB II (1--14) and UNISAB Chiller (16--31).

Points to READ for Chiller:


Parameter Name UNISAB Decimals Unit
Point No
BRINE LINE PRESS IN 32 I*0.1 BAR
BRINE LINE PRESS OUT 33 I*0.1 BAR
COOLING WATER LINE PRESS IN 34 I*0.1 BAR
COOLING WATER LINE PRESS OUT 35 I*0.1 BAR
BRINE LINE TEMP IN 36 I*0.1 _C
BRINE LINE TEMP OUT 37 I*0.1 _C
COOLING WATER LINE TEMP IN 38 I*0.1 _C
COOLING WATER TEMP OUT 39 I*0.1 _C
SUCTION SUPERHEAT AT EVAPORATOR 40 I*0.1 _C
MODE 41 I
STATE 42 I
CAPACITY (of expansion valve) 43 I*0.1 %
BRINE TEMP – SUCT PRESS . value 44 I*0.1 _C
BRINE TEMP – SUCT PRESS . actual sp 45 I*0.1 _C
“Hostdata_1 to _5 has changed” -- I
ALARM CODE (Word 0) 70 I
ALARM CODE (Word 1) 71 I
ALARM CODE (Word 2) 72 I
WARNING CODE (Word 3) 73 I
WARNING CODE (Word 4) 74 I
WARNING CODE (Word 5) 75 I

80
81
BRINE TEMP – SUCT PRESS . setpoint 1 82 I*0.1 _C
BRINE TEMP – SUCT PRESS . setpoint 2 ------ I*0.1 _C
BRINE TEMP – SUCT PRESS . neutral zone ------ I*0.1 _C
BRINE TEMP – SUCT PRESS . gain 85 I0.01
BRINE TEMP – SUCT PRESS . t sample 86 I*0.1 Sec
BRINE TEMP – SUCT PRESS . t integrating 87 I*0.1 Sec
BRINE TEMP – SUCT PRESS . t diff 88 I*0.1 Sec
BRINE TEMP – SUCT PRESS . P part 89 I*0.1 %
BRINE TEMP – SUCT PRESS . I part 90 I*0.1 %
BRINE TEMP – SUCT PRESS . D part 91 I*0.1 %
BRINE TEMP – SUCT PRESS . min pulse ------ I*0.1 Sec
BRINE TEMP – SUCT PRESS .actuator time ------ I*0.1 Sec
BRINE TEMP – SUCT PRESS . reg output 94 I*0.1 %
SUCTION SUPERHEAT . value 95 I*0.1 _C
SUCTION SUPERHEAT . actual setpoint 96 I*0.1 _C
SUCTION SUPERHEAT . setpoint 1 97 I*0.1 _C
SUCTION SUPERHEAT . setpoint 2 98 I*0.1 _C
SUCTION SUPERHEAT . neutral zone -------- I*0.1 _C
SUCTION SUPERHEAT . gain -------- I0.01

0178-444--ENG 31
SUCTION SUPERHEAT . t sample -------- I*0.1 Sec
SUCTION SUPERHEAT . t integrating -------- I*0.1 Sec
SUCTION SUPERHEAT . t differentiating -------- I*0.1 Sec
SUCTION SUPERHEAT . P part of output -------- I*0.1 %
SUCTION SUPERHEAT . I part of output -------- I*0.1 %
SUCTION SUPERHEAT . D part of output -------- I*0.1 %
SUCTION SUPERHEAT . min pulse -------- I*0.1 Sec
SUCTION SUPERHEAT . actuatortime -------- I*0.1 Sec
SUCTION SUPERHEAT . regulator output -------- I*0.1 %
No Valid Data ---------- I*0.1
No Valid Data ---------- I*0.1
No Valid Data ---------- I*0.1
No Valid Data ---------- I*0.1
Soft ware version 127 I0.01

PUMPS PRE RUN 130 I Sec


COMPR START 131 I Sec
START PUMP DOWN 132 I Sec
PUMP DOWN 133 I Sec
BRINE PUMP POST RUN 134 I Sec
WATER PUMP POST RUN 135 I Sec
BRINE FLOW START 136 I Sec
NO BRINE FLOW 137 I Sec
WATER FLOW START 138 I Sec
NO WATER FLOW 139 I Sec
OIL RETURN PUMP PERIOD 140 I Sec
OIL RETURN PUMP PULSE 141 I Sec
BRINE PUMP 1 MOTOR START 142 I Sec
BRINE PUMP 2 MOTOR START 143 I Sec
WATER PUMP 1 MOTOR START 144 I Sec
WATER PUMP 2 MOTOR START 145 I Sec
OFFSET DELAY 146 I Sec
NO COMMUNICATION 147 I Sec

BAUD RATE 170 I


NODE NUMBER 171 I
PRESSURE UNIT 172 I
COMPRESSOR NUMBER 173 I
BRINE PUMP MODE 174 I
WATER PUMP MODE 175 I
P1+ 176 I*0.1 %
P1-- 177 I*0.1 %
P2+ 178 I*0.1 %
P2-- 179 I*0.1 %
P3+ 180 I*0.1 %
P3-- 181 I*0.1 %
C+ 182 I*0.1
C-- 183 I*0.1
C cap 184 I*0.1 _C
START PUMP DOWN 185 I*0.1 _C
OIL RETURN PUMPING FUNCTION 186 I
TWO AKV VALVES 187 I

32 0178-444--ENG
DOUBLE EVAPORATOR 188 I
MANUAL STEP SIZE 189 I*0.1
FACTORY RESET 190 I 0--1
BRINE LINE PRESS IN High Alarm Limit 200 I*0.1 BAR
BRINE LINE PRESS IN High Warning Limit 201 I*0.1 BAR
BRINE LINE PRESS IN Low Warning Limit 202 I*0.1 BAR
BRINE LINE PRESS IN Low Alarm Limit 203 I*0.1 BAR
BRINE LINE PRESS OUT High Alarm Limit 204 I*0.1 BAR
BRINE LINE PRESS OUT High Warning Limit 205 I*0.1 BAR
BRINE LINE PRESS OUT Low Warning Limit 206 I*0.1 BAR
BRINE LINE PRESS OUT Low Alarm Limit 207 I*0.1 BAR
COOLING WATER LINE PRESS IN High Alarm Limit 208 I*0.1 BAR
COOLING WATER LINE PRESS IN High Warning Limit 209 I*0.1 BAR
COOLING WATER LINE PRESS IN Low Warning Limit 210 I*0.1 BAR
COOLING WATER LINE PRESS IN Low Alarm Limit 211 I*0.1 BAR
COOLING WATER LINE PRESS OUT High Alarm Limit 212 I*0.1 BAR
COOLING WATER LINE PRESS OUT High Warning Limit 213 I*0.1 BAR
COOLING WATER LINE PRESS OUT Low Warning Limit 214 I*0.1 BAR
COOLING WATER LINE PRESS OUT Low Alarm Limit 215 I*0.1 BAR
BRINE TEMP IN High Alarm Limit 216 I*0.1 _C
BRINE TEMP IN High Warning Limit 217 I*0.1 _C
BRINE TEMP IN Low Warning Limit 218 I*0.1 _C
BRINE TEMP IN Low Alarm Limit 219 I*0.1 _C
BRINE TEMP OUT High Alarm Limit 220 I*0.1 _C
BRINE TEMP OUT High Warning Limit 221 I*0.1 _C
BRINE TEMP OUT Low Warning Limit 222 I*0.1 _C
BRINE TEMP OUT Low Alarm Limit 223 I*0.1 _C
COOLING WATER TEMP IN High Alarm Limit 224 I*0.1 _C
COOLING WATER TEMP IN High Warning Limit 225 I*0.1 _C
COOLING WATER TEMP IN Low Warning Limit 226 I*0.1 _C
COOLING WATER TEMP IN Low Alarm Limit 227 I*0.1 _C
COOLING WATER TEMP OUT High Alarm Limit 228 I*0.1 _C
COOLING WATER TEMP OUT High Warning Limit 229 I*0.1 _C
COOLING WATER TEMP OUT Low Warning Limit 230 I*0.1 _C
COOLING WATER TEMP OUT Low Alarm Limit 231 I*0.1 _C
SUCT.SUPERHT. High Alarm Limit 232 I*0.1 _C
SUCT.SUPERHT. High Warning Limit 233 I*0.1 _C
SUCT.SUPERHT. Low Warning Limit 234 I*0.1 _C
SUCT.SUPERHT. Low Alarm Limit 235 I*0.1 _C
BRINE SUCTION DIFFERENCE High Alarm Limit 236 I*0.1 _C
BRINE SUCTION DIFFERENCE High Warning Limit 237 I*0.1 _C
BRINE SUCTION DIFFERENCE Low Warning Limit 238 I*0.1 _C
BRINE SUCTION DIFFERENCE Low Alarm Limit 239 I*0.1 _C

DIGITAL INPUTS Please see digital input packing description 253 I


DIGITAL OUTPUTS Please see digital output packing description 254 I
DIGITAL OUTPUTS Please see digital output packing description 255 I

0178-444--ENG 33
MODE description Point No 41 2 = READY
3 = PUMP START
0 = STOPPED 4 = START PUMP--DOWN
1 = MANUAL 5 = RUNNING
2 = AUTO 6 = PUMP--DOWN
7 = PUMP POST RUN
STATE description Point No 42
ALARM packing description
0 = STOPPED
1 = SHUTDOWN WORD 0 – Point No 70:

Alarm code 45 COOLING WATER DIFF PRESS LOW bit no 15


Alarm code 44 COOLING WATER DIFF PRESS HIGH bit no 14
Alarm code 43 COOLING WATER TEMP OUTLET LOW bit no 13
Alarm code 42 COOLING WATER TEMP OUTLET HIGH bit no 12
Alarm code 41 COOLING WATER TEMP INLET LOW bit no 11
Alarm code 40 COOLING WATER TEMP INLET HIGH bit no 10
Alarm code 39 BRINE LINE PRESS OUT LOW bit no 9
alarm code 38 BRINE LINE PRESS OUT HIGH bit no 8
alarm code 37 BRINE LINE PRESS IN LOW bit no 7
alarm code 36 BRINE LINE PRESS IN HIGH bit no 6
alarm code 35 BRINE DIFF PRESS LOW bit no 5
alarm code 34 BRINE DIFF PRESS HIGH bit no 4
alarm code 33 BRINE TEMP OUT LOW bit no 3
alarm code 32 BRINE TEMP OUT HIGH bit no 2
alarm code 31 BRINE TEMP IN LOW bit no 1
alarm code 30 BRINE TEMP IN HIGH bit no 0

WORD 1 – Point No 71:

No Valid Data No Valid Data bit no 15


No Valid Data No Valid Data bit no 14
No Valid Data No Valid Data bit no 13
No Valid Data No Valid Data bit no 12
alarm code 73 SUCT.SUPERHT. LOW bit no 11
alarm code 72 SUCT.SUPERHT. HIGH bit no 10
alarm code 71 BRINE OUTLET TEMP – SUCT.PRESS LOW bit no 9
alarm code 70 BRINE OUTLET TEMP – SUCT.PRESS HIGH bit no 8
alarm code 61 SUCTION SUPERHEAT 2 LOW bit no 7
alarm code 60 SUCTION SUPERHEAT 2 HIGH bit no 6
alarm code 59 SUCTION SUPERHEAT LOW bit no 5
alarm code 58 SUCTION SUPERHEAT HIGH bit no 4
alarm code 49 COOLING WATER LINE PRESS OUTLET LOW bit no 3
alarm code 48 COOLING WATER LINE PRESS OUTLET HIGH bit no 2
alarm code 47 COOLING WATER LINE PRESS INLET LOW bit no 1
alarm code 46 COOLING WATER LINE PRESS INLET HIGH bit no 0

34 0178-444--ENG
WORD 2 – Point No 72:

alarm code NO COMMUNICATION WITH UNISAB bit no 15


alarm code BRINE PUMP 1 MOTOR ALARM bit no 14
alarm code BRINE PUMP 2 MOTOR ALARM bit no 13
alarm code NO BRINE FLOW bit no 12
alarm code WATER PUMP 1 MOTOR ALARM bit no 11
alarm code WATER PUMP 2 MOTOR ALARM bit no 10
alarm code NO WATER FLOW bit no 9
alarm code BOTH BRINE PUMPS UNAVAILABLE bit no 8
alarm code BOTH WATER PUMPS UNAVAILABLE bit no 7
alarm code STARTING PUMP OUT TIMER EXPIRED bit no 6
No Valid Data No Valid Data bit no 5
No Valid Data No Valid Data bit no 4
No Valid Data No Valid Data bit no 3
No Valid Data No Valid Data bit no 2
No Valid Data No Valid Data bit no 1
No Valid Data No Valid Data bit no 0

WARNING packing description

WORD 3 – Point No 73:

warning code 45 COOLING WATER DIFF PRESS LOW bit no 15


warning code 44 COOLING WATER DIFF PRESS HIGH bit no 14
warning code 43 COOLING WATER TEMP OUTLET LOW bit no 13
warning code 42 COOLING WATER TEMP OUTLET HIGH bit no 12
warning code 41 COOLING WATER TEMP INLET LOW bit no 11
warning code 40 COOLING WATER TEMP INLET HIGH bit no 10
warning code 39 BRINE LINE PRESS OUT LOW bit no 9
warning code 38 BRINE LINE PRESS OUT HIGH bit no 8
warning code 37 BRINE LINE PRESS IN LOW bit no 7
warning code 36 BRINE LINE PRESS IN HIGH bit no 6
warning code 35 BRINE DIFF PRESS LOW bit no 5
warning code 34 BRINE DIFF PRESS HIGH bit no 4
warning code 33 BRINE TEMP OUT LOW bit no 3
warning code 32 BRINE TEMP OUT HIGH bit no 2
warning code 31 BRINE TEMP IN LOW bit no 1
warning code 30 BRINE TEMP IN HIGH bit no 0

0178-444--ENG 35
WORD 4 – Point No 74:

No Valid Data No Valid Data bit no 15


No Valid Data No Valid Data bit no 14
No Valid Data No Valid Data bit no 13
No Valid Data No Valid Data bit no 12
warning code 73 SUCT.SUPERHT. LOW bit no 11
warning code 72 SUCT.SUPERHT. HIGH bit no 10
warning code 71 BRINE OUTLET TEMP – SUCT.PRESS LOW bit no 9
warning code 70 BRINE OUTLET TEMP – SUCT.PRESS HIGH bit no 8
warning code 61 SUCTION SUPERHEAT 2 LOW bit no 7
warning code 60 SUCTION SUPERHEAT 2 HIGH bit no 6
warning code 59 SUCTION SUPERHEAT LOW bit no 5
warning code 58 SUCTION SUPERHEAT HIGH bit no 4
warning code 49 COOLING WATER LINE PRESS OUTLET LOW bit no 3
warning code 48 COOLING WATER LINE PRESS OUTLET HIGH bit no 2
warning code 47 COOLING WATER LINE PRESS INLET LOW bit no 1
warning code 46 COOLING WATER LINE PRESS INLET HIGH bit no 0

WORD 5 – Point No 75:

No Valid Data No Valid Data bit no 15


No Valid Data No Valid Data bit no 14
No Valid Data No Valid Data bit no 13
No Valid Data No Valid Data bit no 12
No Valid Data No Valid Data bit no 11
No Valid Data No Valid Data bit no 10
No Valid Data No Valid Data bit no 9
No Valid Data No Valid Data bit no 8
No Valid Data No Valid Data bit no 7
No Valid Data No Valid Data bit no 6
No Valid Data No Valid Data bit no 5
BRINE PUMP 1 NOT AVAILABLE bit no 4
BRINE PUMP 2 NOT AVAILABLE bit no 3
WATER PUMP 1 NOT AVAILABLE bit no 2
WATER PUMP 2 NOT AVAILABLE bit no 1
COMPR START TIMER EXPIRED bit no 0

36 0178-444--ENG
Digital input packing description Point No 253 Digital Output packing description
(INTEGER 02) Point No 255
No Valid Data bit no 15
No Valid Data bit no 14 No Valid Data bit no 15
No Valid Data bit no 13 No Valid Data bit no 14
No Valid Data bit no 12 No Valid Data bit no 13
No Valid Data bit no 11 No Valid Data bit no 12
Digital Input No 10 bit no 10 No Valid Data bit no 11
Digital Input No 09 bit no 09 No Valid Data bit no 10
Digital Input No 08 bit no 08 No Valid Data bit no 09
Digital Input No 07 bit no 07 No Valid Data bit no 08
Digital Input No 06 bit no 06 No Valid Data bit no 07
Digital Input No 05 bit no 05 No Valid Data bit no 06
Digital Input No 04 bit no 04 No Valid Data bit no 05
Digital Input No 03 bit no 03 No Valid Data bit no 04
Digital Input No 02 bit no 02 No Valid Data bit no 03
Digital Input No 01 bit no 01 No Valid Data bit no 02
Digital Input No 00 bit no 00 Digital Output No 17 bit no 01
Digital Output No 16 bit no 00

Digital Output packing description Digital Output packing description


(INTEGER 01) Point No 254 (INTEGER 02) Point No 255

Digital Output No 15 bit no 15 No Valid Data bit no 15


Digital Output No 14 bit no 14 No Valid Data bit no 14
Digital Output No 13 bit no 13 No Valid Data bit no 13
Digital Output No 12 bit no 12 No Valid Data bit no 12
Digital Output No 11 bit no 11 No Valid Data bit no 11
Digital Output No 10 bit no 10 No Valid Data bit no 10
Digital Output No 09 bit no 09 No Valid Data bit no 09
Digital Output No 08 bit no 08 No Valid Data bit no 08
Digital Output No 07 bit no 07 No Valid Data bit no 07
Digital Output No 06 bit no 06 No Valid Data bit no 06
Digital Output No 05 bit no 05 No Valid Data bit no 05
Digital Output No 04 bit no 04 No Valid Data bit no 04
Digital Output No 03 bit no 03 No Valid Data bit no 03
Digital Output No 02 bit no 02 No Valid Data bit no 02
Digital Output No 01 bit no 01 Digital Output No 17 bit no 01
Digital Output No 00 bit no 00 Digital Output No 16 bit no 00

0178-444--ENG 37
Points to WRITE for Chiller:
Parameter Name COMSAB Decimals Unit
POINT NO
BRINE TEMP -- SUCT PRESS . gain 85 I0.01
BRINE TEMP -- SUCT PRESS . t sample 86 I*0.1 Sec
BRINE TEMP -- SUCT PRESS . t integrating 87 I*0.1 Sec
BRINE TEMP -- SUCT PRESS . t diff 88 I*0.1 Sec
SUCTION SUPERHEAT . setpoint 1 97 I*0.1 _C
SUCTION SUPERHEAT . setpoint 2 98 I*0.1 _C

PUMPS PRE RUN 130 I Sec


COMPR SRART 131 I Sec
START PUMP DIWN 132 I Sec
PUMP DOWN 133 I Sec
BRINE PUMP POST RUN 134 I Sec
WATER PUMP POST RUN 135 I Sec
BRINE FLOW START 136 I Sec
NO BRAINE FLOW 137 I Sec
WATER FLOW START 138 I Sec
NO WATER FLOW 139 I Sec
OIL RETURN PUMP PERIOD 140 I Sec
OIL RETURN PUMP PULSE 141 I Sec
BRINE PUMP 1 MOTOR START 142 I Sec
BRINE PUMP 2 MOTOR START 143 I Sec
WATER PUMP 1 MOTOR START 144 I Sec
WATER PUMP 2 MOTOR START 145 I Sec
OFFSET DELAY 146 I Sec
NO COMMUNICATION 147 I Sec

BAUD RATE 170 I


NODE NUMBER 171 I
PRESSURE UNIT 172 I
COMPRESSOR NUMBER 173 I
BRINE PUMP MODE 174 I
WATER PUMP MODE 175 I
P1+ 176 I*0.1 %
P1-- 177 I*0.1 %
P2+ 178 I*0.1 %
P2-- 179 I*0.1 %
P3+ 180 I*0.1 %
P3-- 181 I*0.1 %
C+ 182 I*0.1
C-- 183 I*0.1
C cap 184 I*0.1 _C
START PUMP DOWN 185 I*0.1 _C
OIL RETURN PUMPING FUNCTION 186 I
TWO AKV VALVES 187 I
DOUBLE EVAPORATOR 188 I
MANUAL STEP SIZE 189 I*0.1
FACTORY RESET 190 I 0--1

38 0178-444--ENG
BRINE LINE PRESS IN High Alarm Limit 200 I*0.1 BAR
BRINE LINE PRESS IN High Warning Limit 201 I*0.1 BAR
BRINE LINE PRESS IN Low Warning Limit 202 I*0.1 BAR
BRINE LINE PRESS IN Low Alarm Limit 203 I*0.1 BAR
BRINE LINE PRESS OUT High Alarm Limit 204 I*0.1 BAR
BRINE LINE PRESS OUT High Warning Limit 205 I*0.1 BAR
BRINE LINE PRESS OUT Low Warning Limit 206 I*0.1 BAR
BRINE LINE PRESS OUT Low Alarm Limit 207 I*0.1 BAR
COOLING WATER LINE PRESS IN High Alarm Limit 208 I*0.1 BAR
COOLING WATER LINE PRESS IN High Warning Limit 209 I*0.1 BAR
COOLING WATER LINE PRESS IN Low Warning Limit 210 I*0.1 BAR
COOLING WATER LINE PRESS IN Low Alarm Limit 211 I*0.1 BAR
COOLING WATER LINE PRESS OUT High Alarm Limit 212 I*0.1 BAR
COOLING WATER LINE PRESS OUT High Warning Limit 213 I*0.1 BAR
COOLING WATER LINE PRESS OUT Low Warning Limit 214 I*0.1 BAR
COOLING WATER LINE PRESS OUT Low Alarm Limit 215 I*0.1 BAR
BRINE TEMP IN High Alarm Limit 216 I*0.1 _C
BRINE TEMP IN High Warning Limit 217 I*0.1 _C
BRINE TEMP IN Low Warning Limit 218 I*0.1 _C
BRINE TEMP IN Low Alarm Limit 219 I*0.1 _C
BRINE TEMP OUT High Alarm Limit 220 I*0.1 _C
BRINE TEMP OUT High Warning Limit 221 I*0.1 _C
BRINE TEMP OUT Low Warning Limit 222 I*0.1 _C
BRINE TEMP OUT Low Alarm Limit 223 I*0.1 _C
COOLING WATER TEMP IN High Alarm Limit 224 I*0.1 _C
COOLING WATER TEMP IN High Warning Limit 225 I*0.1 _C
COOLING WATER TEMP IN Low Warning Limit 226 I*0.1 _C
COOLING WATER TEMP IN Low Alarm Limit 227 I*0.1 _C
COOLING WATER TEMP OUT High Alarm Limit 228 I*0.1 _C
COOLING WATER TEMP OUT High Warning Limit 229 I*0.1 _C
COOLING WATER TEMP OUT Low Warning Limit 230 I*0.1 _C
COOLING WATER TEMP OUT Low Alarm Limit 231 I*0.1 _C
SUCT.SUPERHT. High Alarm Limit 232 I*0.1 _C
SUCT.SUPERHT. High Warning Limit 233 I*0.1 _C
SUCT.SUPERHT. Low Warning Limit 234 I*0.1 _C
SUCT.SUPERHT. Low Alarm Limit 235 I*0.1 _C
BRINE SUCTION DIFFERENCE High Alarm Limit 236 I*0.1 _C
BRINE SUCTION DIFFERENCE High Warning Limit 237 I*0.1 _C
BRINE SUCTION DIFFERENCE Low Warning Limit 238 I*0.1 _C
BRINE SUCTION DIFFERENCE Low Alarm Limit 239 I*0.1 _C

0178-444--ENG 39
Table of alarms and warnings for UNISAB II Chiller:

Id Alarm / warning text Alarm Warning


#1 No communication with UNISAB X
#2 Brine pump 1 motor starter error X
#3 Brine pump 2 motor starter error X
#4 Brine flow error X
#5 Water pump1 motor starter error X
#6 Water pump2 motor starter error X
#7 Water flow error X
#8 Both brine pumps unavaliable X
#9 Both water pumps unavaliable X
# 10 Starting pump down timer expired X
# 11 Not used
# 12 Not used
# 13 Not used
# 14 Not used
# 15 Not used
# 16 Not used
# 17 Not used
# 18 Not used
# 19 Not used
# 20 Not used
# 21 Not used
# 22 Not used
# 23 Not used
# 24 Not used
# 25 Not used
# 26 Not used
# 27 Not used
# 28 Not used
# 29 Not used
# 30 Brine temp in high X X
# 31 Brine temp in low X X
# 32 Brine temp out high X X
# 33 Brine temp out low X X
# 34 Brine diff press high X X
# 35 Brine diff press low X X
# 36 Brine line press in high X X
# 37 Brine line press in low X X
# 38 Brine line press out high X X
# 39 Brine line press out low X X
# 40 Cooling water temp at inlet high X X
# 41 Cooling water temp at inlet low X X
# 42 Cooling water temp at outlet high X X
# 43 Cooling water temp at outlet low X X
# 44 Cooling water diff press high X X
# 45 Cooling water diff press low X X
# 46 Cooling water line press at inlet high X X
# 47 Cooling water line press at inlet low X X
# 48 Cooling water line press at outlet high X X
# 49 Cooling water line press at outlet low X X

40 0178-444--ENG
# 50 Suction temp low X X
# 51 Suction temp low X X
# 52 Suction temp2 high X X
# 53 Suction temp2 low X X
# 54 Suction press high (Temp. saturated) X X
# 55 Suction press low (Temp. saturated) X X
# 56 Suction press high X X
# 57 Suction press low X X
# 58 Suction superheat high X X
# 59 Suction superheat low X X
# 60 Suction superheat2 high X X
# 61 Suction superheat2 low X X
# 62 Disch temp high X X
# 63 Disch temp low X X
# 64 Disch press high (Temp. saturated) X X
# 65 Disch press low (Temp. saturated) X X
# 66 Disch press high X X
# 67 Disch press low X X
# 68 Disch superheat high X X
# 69 Disch superheat low X X
# 70 Brine outlet temp – suct.press high X X
# 71 Brine outlet temp – suct.press low X X

0178-444--ENG 41
List of Versions

Version 1.00
Error when reading motor current and hour counter from Unisab I and Prosab II. Limiting values
for external input extended.

Version 1.03
Error when reading SP1 and SP2 for brine temperature when ClimateControl has been chosen
in Unisab II and when the brine temperature is being regulated.

Version 1.04
No errors.
Must be upgraded to include COP and chiller data.

Version 1.05
We have corrected an error which made the Unisab II change start number to # 0 and at the
same time change the control mode to auto. The change was automatically carried out by Uni-
sab II, whenever the direct 4-20 mA capacity signal was connected or disconnected.

Version 1.06
The Comsab II now recognizes a Unisab II configurated as a Rotatune controller.
In earlier versions it was not possible to see any of the values in the Unisab II if the answer to
the parameter Rotatune=(YES/NO) in the Unisab II menu was YES:
Main picture > main menu > setup > config > Motor > Rotatune
In spite of this problem, the Comsab II was still able to read the values from the other Unisab II
in the system (with Rotatune=NO).

In the manual the table of alarms/warnings for Unisab II has been updated to comply with the
eprom version 2.03.1.
Also the list of multisab states has been updated to comply with the eprom version 2.03.1.

42 0178-444--ENG