Stationary Louver
Drainable Blade
Application and Design
ESD-403 is a weather louver designed to protect air intake and
exhaust openings in building exterior walls. Design incorporates
a drainable head member and stationary horizontal blades to
channel water to the jambs which guides the water through vertical
downspouts for escape at the sill. The ESD-403 is an extremely
efficient louver with AMCA LICENSED PERFORMANCE DATA
enabling designers to select and apply with confidence.
Standard Construction
Frame ���������������Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.081 in. nominal wall thickness
Blades ���������������Drainable design, heavy gauge extruded
6063-T5 aluminum, 0.081 in. nominal wall
thickness, positioned at 37º and 45º angles on
approximately 4 in. centers
Construction �����Mechanically fastened
Birdscreen ���������3/4 in. x 0.051 in. flattened expanded aluminum in
removable frame, inside mount (rear)
Finish �����������������Mill
Minimum Size ���12 in. W x 12 in. H
Maximum Single
Section Size ������120 in. W or 120 in. H (limited to 70 ft. sq.)
108 3.98 6.56 9.14 11.72 14.30 16.88 19.46 21.42 24.00 26.58 29.16 31.74 34.32 36.90 39.48 41.33 43.91 46.49 49.07
114 4.17 6.88 9.58 12.29 14.99 17.70 20.40 22.46 25.16 27.87 30.57 33.28 35.98 38.69 41.39 43.33 46.04 48.74 51.45
120 4.37 7.21 10.05 12.88 15.72 18.56 21.39 23.54 26.38 29.22 32.05 34.89 37.73 40.57 43.43 45.43 48.27 51.11 53.94
Airflow Resistance (Standard Air - .075 lb/ft3) Water Penetration (Standard Air - .075 lb/ft3)
Pa in. wg Test size 48 in. x 48 in. Test duration of 15 min.
1 ml/m2 oz/ft2
0.9
200 Test Size 48 in. x 48 in. 0.30
0.8
3
0.7 Standard Air - .075 lb/ft Test Size 48 in. x 48 in.
0.6 Test Period 15 minutes
0.5
80 0.25 Standard Air - .075 lb/ft
3
100 0.4
Water Penetration per Unit Free Area
90
80 0.20
0.3
70 60
60
Static Pressure Drop
50 0.2
0.15
40
40
30 0.10
ke
Inta
0.1
0.09
20 0.08 20
t
0.05
aus
0.07
Exh
0.06
0.05
0 0.00
10 0.04
ft/min: 900 950 1000 1050 1100 1150 1200 1250 1300
9
8
0.03 m/s: 4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.2 6.3 6.4 6.5 6.6
7
Maximum single section size for model ESD-403 is 120 in. W x 84 in. H or 84 in. W x 120 in. H (70 sq. ft). Larger openings require
field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand
a 25 PSF wind-load (please consult Greenheck if the louvers must withstand higher wind-loads). Structural reinforcing members
may be required to adequately support and install multiple louver panels within a large opening. Structural reinforcing members
along with any associated installation hardware is not provided by Greenheck unless indicated otherwise by Greenheck. Additional
information on louver installation may be found in AMCA Publication #501, Louver Application Manual.
FINISHES
Standard Warranty
Finish Type Description/Application Color Selection
(Aluminum)
Standard Colors: Any of the 24
“Best.” The premier finish for extruded aluminum. Tough, 10 Years
2-coat 70% KYNAR 500®/HYLAR 5000® AAMA 2605 – standard colors shown can be
long-lasting coating has superior color retention and (Consult Greenheck for
Dry film thickness 1.2 mil. (AKA: Duranar®, Fluoropon®, furnished in 70% or 50% KYNAR
abrasive properties. Resists chalking, fading, chemical availability of extended
Trinar®, Flouropolymer, Polyvinylidene Fluoride, PVDF2) 500®/HYLAR 5000® or Baked Enamel.
abrasion and weathering. warranty)
2-Coat Mica:
“Better.” Tough, long-lasting coating has excellent color Greenheck offers 9 standard 2-
2-coat 50% KYNAR 500®/HYLAR 5000® AAMA 2604
retention and abrasive properties. Resists chalking, fading, coat Mica colors. Other colors are 5 Years
– Dry film thickness 1.2 mil. (AKA: Acroflur®, Acrynar®)
chemical abrasion and weathering. available. Consult Greenheck for
possible extra cost when selecting
Baked Enamel AAMA 2603 – Dry film thickness 0.8 mil. “Good.” Provides good adhesion and resistance to non-standard colors or special
1 Year
(AKA: Acrabond Plus®, Duracron®) weathering, corrosion and chemical stain. finishes.
“Two-step” anodizing is produced by following the normal Light, Medium or Dark Bronze;
Integral Color Anodize AA-M10C22A42 (>0.7 mil) 5 years
anodizing step with a second, colorfast process. Champagne; Black
Greenheck offers a number of industrial coatings such as Hi-Pro Polyester, Epoxy, and Permatector®.
Industrial coatings Consult Greenheck
Consult a Greenheck Product Specialist for complete color and application information.
Materials may be supplied in natural aluminum or galvanized steel finish when normal weathering is
Mill n/a
acceptable and there is no concern for color or color change.
Finishes meet or exceed AAMA 2605, AAMA 2604, and AAMA 2603 requirements. Please consult www.greenheck.com for complete information on standard and
extended paint warranties. Paint finish warranties are not applicable to steel products.
ESD-403
July 2007 Rev. 1
Copyright © 2007 Greenheck Fan Corporation