IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 17, NO.

2, JUNE 2007 2355

Recent Progress of Power Application


of Superconductor in China
Liye Xiao and Liangzhen Lin

Abstract—The significant progresses in high Tc superconducting will briefly review the state-of-the-art of power applications of
wires or tapes have excited a great deal of research interests in superconductors in China.
power application. This paper will review the recent progresses
of power application of superconductor in China. An improved
bridge-type fault current limiter was tested and a 10.5 kV/1.5 kA II. HTS POWER CABLE
demonstrator has been operated at a substation in Hunan Province
in 2005. A 75 meter, 10.5 kV/1.5 kA three phase HTS cable has
Demand for electric power in China continues to grow dra-
been installed and operated at the Changtong Cable Headquarter matically year-over-year, power consumption in major urban
in the end of 2004, and a 30 meter, 35 kV/2 kA HTS power cable centers even grows at double digit rates. Therefore, China would
was installed at substation and has been operated since July 2004. rapidly need to find innovative ways of delivering huge amounts
A 10.5 kV/400 V/630 kVA HTS transformer has been installed and of electricity. HTS power cables, which is 3 to 5 times the elec-
operated at TBEA Electric Factory in 2005. A 500 kJ/150 kVA tric power capacity [4] as well as 50% reduction the transmis-
SMES unit was developed and tested. 1.0 MJ/0.5 MW SMES
will be installed in a power grid in 2006. Besides, a new kind
sion loss of copper cables, can support general load growth
equipment of fault-current-limiting SMES is being developed and without renewing the exist cable ducts.
a 100 kJ/25 kW prototype has been made and tested.
A. Changtong Power Cable Project
Index Terms—Superconducting fault current limiter, supercon-
ducting magnetic energy storage (SMES), superconducting power The Changtong cable project, which targeted to develop a
cable, superconducting power transformer. 3-phase, 75 meter long, 10.5 kV/1.5 kA HTS power cable with
warm-dielectric design, is sponsored by Institute of Electrical
Engineering (IEE), and supported by the “863” Program, CAS
I. INTRODUCTION
and Changtong Power Cable Company Ltd. The cable con-
ITH the commercialization of high Tc superconducting
W (HTS) tapes in the latest years of 1990’s, it had excited
worldwide research interests in the power application because
ductor and termination were designed and constructed by IEE;
the refrigeration system was made by Technical Institute of
Physics and Chemistry (TIPC); the cable insulation system was
superconductor is very helpful to increase the efficiency as well made by Baofeng Cable Group; and the joints for the cable’s
as to reduce volume and weight of the power equipments due cryogenic envelope were made by Shenzhen Woer Company.
to its performance of high engineering current-density and low The HTS tapes for the HTS cable are the stainless steel-rein-
power-loss [1]–[3]. Besides, superconductor is also promising forced multi-filamentary Bi-2223/Ag hermetic tapes manufac-
for the application in fault current limiter (FCL) and super- tured by American Superconductor (AMSC). The cable con-
conducting magnetic energy storages (SMES), which are very ductor (each conductor for each phase) consists of 36 Bi-2223
helpful to enhance the stability and reliability of the grid as tapes spirally reeled into 2 layers on the corrugated pipe, and the
well as to improve the power quality [1], [2]. Since the latest HTS tapes were soldered to the copper terminals using the low-
years of 1990’s, full-scale prototypes of FCL, power cables, mo- melting-point alloy solder. The cryogenic envelope for 75-m
tors, transformers made with superconductors especially with long power cable consists of two concentric corrugated stain-
Bi-2223 tapes have been tested and demonstrated in America, less steel tubes, and the insulation technique for the HTS cable
Europe and Japan [1]–[3]. is designed to be compatible with that of conventional copper
In China, since the year of 2000, the power application re- cable. The termination consists of a vacuum chamber, current
search of superconductor has been stressfully supported by the leads, liquid nitrogen transfer tube, and thermo-electrical insu-
State “863” Program (High Technology Research & Develop- lator. The main parameters of the HTS cable are given in Table I.
ment Program) and the Chinese Academy of Science (CAS), In order to fabricate long HTS power cable with length up
and the power equipment industries also paid much attention to kilometers in the future, the long-length envelope should be
to the R&D of this new technology. Within few years, super- made. In this project, the joints for the cryogenic envelope were
conducting power cables, FCL and transformers have been suc- also made. The cryogenic envelope for 75 m long power cable
cessfully made, tested and demonstrated in the live distribution made up of three sections connected in series, the length of each
gird, and SMES units have also been tested. In this paper, we envelope is 25 m. The inter-connecter for connecting the cryo-
genic envelopes was designed and fabricated.
Manuscript received September 2, 2006. In the installation, the power cable was bent to form a tri-U
The authors are with the Institute of Electrical Engineering, Chinese shape, simulating the practical laying situation. The overview
Academy of Sciences, Beijing 100080, China (e-mail: xiao@mail.iee.ac.cn).
Color versions of one or more of the figures in this paper are available online
of the cable is shown in Fig. 1. In preliminary tests, the crit-
at http://ieeexplore.ieee.org. ical current is up to 5 kA (DC), the cable’s rated voltage is up to
Digital Object Identifier 10.1109/TASC.2007.898160 10.5 kV, and it has conducted up to 1,600 Amperes (at 400 volts)
1051-8223/$25.00 © 2007 IEEE

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 19,2010 at 13:03:44 EDT from IEEE Xplore. Restrictions apply.
2356 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 17, NO. 2, JUNE 2007

TABLE I TABLE II
DESIGN PARAMETERS OF THE 75 meters LONG POWER CABLE DESIGN PARAMETERS OF THE 30 meters LONG POWER CABLE

Fig. 2. The 3-phase, 30 meters long HTS Cable.

After the cable was installed and tested, it was connected to


the Puji Substation near the Kunming city of Yunnan Province.
Fig. 2 shows the cable and its terminator.

Fig. 1. Overview of the 3-phase, 75 meters long HTS cable. III. FAULT CURRENT LIMITER
As the power capacity of China power grid increases quickly,
the short-circuit current also increases significantly, leading to
of alternating electrical current, limited only by the load avail- serious challenges to the stability of the grid as well as to the
able at the factories. After tests, the cable was then connected to safety of the power equipments. By reducing the fault current,
the distribution grid of Changtong Power Cable Company (6.6 the FCL can protect the power equipments from damages and
kV in rated voltage), serving for 5 factories at the company’s enhance the stability of the grid [5]. For live operation, it re-
headquarter. Since December 14, 2004, it has been operated for quires that FCL should be able to quickly react to the fault within
more than 7,000 hours without any breakdown. 1/4 cycles and recovery within 100–200 ms, and be low in the
operation loss and normal-state impedance, and be effective to
B. Innopower Cable Project limit both the peak fault current and steady-state fault current.
The cable project, targeted to develop a 3-phase, 30 meter Among all kinds of FCL, superconducting FCL is one of the
long, 35 k/2 kA HTS cable, was supported by “863” program, promising devices.
Beijing City Government and Yunnan Power Company. The
project is sponsored by Innopower Superconductor Cable A. 10 kV/1.5 kA Fault Current Limiter
Company, the terminator was made by the Institute of Plasma The HTS fault current limiter project, which was supported by
Physics, the cryogenic envelope and its insulation was made by “863” Program, CAS and Beijing City Government, was devel-
Nexsans, the Bi-2223 tapes were supplied by Innova Supercon- oped by IEE in collaboration with TIPC, Hunan Power Company,
ducting Technology. Northwest Institute for Non-Ferrous Metals (NIN) and Beijing
The cable is also in warm-dielectric design, the conductor for General Research Institute for Non-Ferrous Metals (GRINM).
each phase is made of 4 layers of Bi-2223 tapes, 21, 24, 24, 21 In order that the FCL can satisfy all the requirements of live
tapes for each layer respectively, in total, 90 tapes were used for operation, we suggested an improved bridge-type FCL which
each phase. The cable was cooled by G-M cryocooler, 7 Cry- employs the bridge-type FCL and IGCT switches as shown in
omech AL-300 refrigerators were used. The design parameters Fig. 3. At normal conditions, the line current can flow in ei-
are shown in Table II. ther direction through the bridge, and the IGCT switches are

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 19,2010 at 13:03:44 EDT from IEEE Xplore. Restrictions apply.
XIAO AND LIN: RECENT PROGRESS OF POWER APPLICATION OF SUPERCONDUCTOR IN CHINA 2357

Fig. 3. Schematic of the improved bridge-type FCL.

TABLE III
DESIGN PARAMETERS OF THE SUPERCONDUCTING COIL FOR THE FCL
Fig. 4. The overview of the FCL.

Fig. 5. Test results of 3-phase-to-ground short circuit.

switch-on, therefore, it performs just like the bridge-type FCL.


During fault condition, the first peak is limited by the HTS coil After August 14, 2005, the FCL has been operated in the live
which is against the rapid ramping of the current. When the cur- distribution grid for more than 7 months without breakdown. In
rent of the HTS coil reaches a set value, the IGCT switches are August 2006, the cryogenic system was checked, and the system
then switch off, and the resistors are plunged into the line, the will be operated for further time at the beginning of October,
fault current is then limited by both the coil and the resistors. 2006.
For this principle, the steady-state fault current can also be re-
stricted effectively. IV. POWER TRANSFORMER
Table III shows the design parameters of the HTS coil for
the FCL. The coils were structured in double pancakes. The HTS power transformer can serve as compact, environmen-
four double pancakes at each end of the coil were wound with tally friendly alternatives by reducing 50% both in loss, weight
two parallel Bi-2223 tapes supplied by AMSC, and the other and size. Besides, it can eliminate risk of environmentally haz-
six double pancakes in the coil were wound with single tapes, ardous oil leaks and fires due to the use of LN2 as the dielectric
leading to the homogenous current distribution among the tapes. and cooling fluid, and increase overload rating capability by 2
The cryostats for the HTS coil was made of epoxy material, times without insulation damage or degradation [6].
which are about 1100 mm in outer diameter and 1400 mm in
A. TBEA HTS Power Transformer Project
height. In order to compensate the loss of the cryostat, G-M
cryo-coolers were used for Phase-A as a demonstration. This project aims to develop a 3-phase HTS power trans-
The FCL was installed at Gaoxi Substation which is near to former with rated parameters of 10.5 kV/400 V/630 kVA, and is
Changcha, the capital city of Hunan Province. Fig. 4 shows the supported by the “863” Program and the Tebian Electric Com-
overview of the FCL. After routine tests, the FCL was then pany (TBEA), the largest transformer manufacturer in china.
connected the 10 kV substation, and a three-phase-to-ground The power transformer was developed by IEE in collaboration
short-circuit was done in the substation. In the test, a prospec- with TBEA.
tive fault current of 3.5 kA was limited to 635 A, the reduction The transformer windings were designed by using of the
ratio of short current reached up to 82%. The test result is shown HTS pancake coils made of the hermetic stainless steel-en-
in Fig. 5. forced multi-filamentary Bi2223/Ag supplied by AMSC, and

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 19,2010 at 13:03:44 EDT from IEEE Xplore. Restrictions apply.
2358 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 17, NO. 2, JUNE 2007

TABLE IV
DESIGN PARAMETERS OF THE TRANSFORMER

Fig. 6. Overview of 630 kVA three-phase transformer.

TABLE V
TEST RESULTS OF THE 630 kVA HTS TRANSFORMER

Fig. 7. The 300 kVA single phase transformer.


the core was designed by using of the amorphous alloys. Pri-
mary winding is a solenoid wound with 8 layers with cooling
channels in longitudinal, and secondary winding is made of in size. Tests show that the efficiency is up to 99.87% when the
23 double pancakes connected in parallel. All windings are cryogenic loss is excluded. The transformer is shown in Fig. 7.
wound with a strand consisted of two parallel transposed
multi-filamentary tapes in order to prevent unbalanced current V. SUPERCONDUCTING MAGNETIC ENERGY STORAGE
distribution. Specifications of the transformer are presented in A SMES unit can be regarded as quick-responding capacity
Table IV. of the power system, it can compensate the unbalances of the
The routine tests for the transformer were done according reactive power and real power quickly, so that SMES unit can
to the state standard. The test results are shown in Table V. be used to regulate the power quality and to increase transfer
After the tests, it was connected to the live distribution grid of capacity and protect utility grids from the destabilizing effects
TBEA headquarter in Changji City, Xinjiang Province. Since of short-term events such as voltage dips caused by lightning
November 2005, it was used for serving the new energy factory strikes and downed poles, sudden changes in customer demand
of TBEA for more than 2 months without breakdown. Fig. 6 levels and switching operations [7].
shows the appearance of the HTS power transformer. Now, the
cryogenic system is being checked and the transformer would A. Fault-Current-Limiting SMES
be put into operation again. This project is supported by National Science Foundation
and the “863” Program. Based on the principle of the improved-
B. Zhuzhou Locomotive Transformer Project bridge-type FCL, IEE proposed a new type SMES, namely
This project targeted to study the possibility to use HTS the Fault-Current-Limiting SMES. The principle schematic is
power transformer as an alternative in electric locomotive. The shown in Fig. 8. At normal state, the current regulator and con-
project is supported by “863” Program, and is sponsored by verter act as the bias voltage source of the bridge-type current
Zhouzhu Locomotive Company. limiter, and keep the current of the coil as much as 2 times of
In this project, a single phase HTS transformer with rated pa- the current of the transmission line. When there are voltage
rameters of 25 kV/6.6 kV/300 kVA was designed and fabricated. sags or power unbalance in the system, the power converter can
The transformer is 2278 kg in weight and output a compensating power, keeping the voltage level and the

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 19,2010 at 13:03:44 EDT from IEEE Xplore. Restrictions apply.
XIAO AND LIN: RECENT PROGRESS OF POWER APPLICATION OF SUPERCONDUCTOR IN CHINA 2359

Fig. 9. Overview of the prototype FCL-SMES.

Fig. 10. The current and voltage of the system at short-circuit state without
FCL-SMES.

Fig. 8. The topology of the FCL-SMES.

power factor. When there is short circuit fault, the converter


works as a virtual resistor, just like the resistors of the improved
bridge-type FCL, limiting the fault current to an acceptable
level.
In 2005, a prototype FCL-SMES of 100 kJ/20 kVA was made
by IEE, and it was tested at the laboratory. Fig. 9 shows the
overview of the prototype device and Figs. 10, 11 shows the test
results of the FCL-SMES. The test results show that this device
can successfully compensate the voltage sags and limit the fault
current.

B. 500 kJ/150 kVA SMES Unit


This project was supported by “863” Program and Tianwei Fig. 11. The current and voltage of the system at short-circuit state with the
Electric Group to develop a SMES unit for demonstration in FCL-SMES.
the Tsinghua University Information Center. The SMES unit
was made by Tsinghua University in collaboration with Tianwei
Electric Group. voltage of 230 V. This SMES unit is a current-source type, and
In December 2005, a 500 kJ/150 kVA SMES unit was suc- the magnet was made of NbTi wires. The design parameter of
cessfully made and tested at the Power System Laboratory with the magnet is shown in Table VI. The test shows that this unit

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 19,2010 at 13:03:44 EDT from IEEE Xplore. Restrictions apply.
2360 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 17, NO. 2, JUNE 2007

TABLE VI TABLE VII


DESIGN PARAMETER OF THE 500 kJ MAGNET DESIGN PARAMETERS OF THE 1 MJ HTS SMES COIL

sient power angle of the generator at fault condition. Further


study on the stability of power system is being done.

VI. SUMMARY
In last few years, there is a significant progress on the R&D
of HTS power application in China, demonstrators of cables,
FCL, transformers and SMES have been successfully made and
tested, and FCL, HTS Power Cable and Transformer have been
operated at live substations. Demonstrations show the prototype
apparatus are able to serve for the distribution grid successfully.
Fig. 12. Voltage compensation tests of the 500 kJ/150 kVA SMES unit. Top:
without the SMES, Bottom: with the compensation of the SMES.
Besides, a novel equipment of fault-current- limiting SMES has
been made and tested, and a 1 MJ/500 kVA HTS SMES will be
installed at a substation in Beijing.
In order to fabricate practical superconducting power equip-
can successfully compensate the voltage sags of the system, re- ments, the cost of the superconducting wires should be fur-
sults are shown in Fig. 12. This SMES would be used for the ther reduced, and the cryogenic system should be more cost-
Tsinghua University Information Center early next year. effective and more reliable and safer for long-term operation
without maintains.
C. Other Progress in SMES
Under the support of Chinese Academy of Science, a REFERENCES
1 MJ/500 kVA SMES is being developed by IEE. In order to [1] L. Z. Lin and L. Y. Xiao, “The recent progress of HTS power applica-
shift the Bi-2233 hermetic tapes (from AMSC) to YBCO tapes tion research worldwide and its prospective in the future,” Physics, vol.
in the near future, this SMES will employ a Bi-2223 coil as 35, pp. 491–496, June 2006.
the energy storage unit. The design parameter of the Bi-2223 [2] D. Larbalestier, Power Applications of Superconductivity in Germany
and Japan, WTEC Hyper-Librarian, September 1997 [Online]. Avail-
coil is shown in Table VII. The 500 kVA power converter able: http://www.wtec.org/loyola/scpa/
is voltage-source type consisted of 1 MVA DC-DC cascade [3] Y. Iwata, “High Tc superconducting power cables,” ISTEC Journal,
current regulator and DC-AC converter. vol. 11-1, pp. 60–65, January 1998.
[4] Application for HTS Wires [Online]. Available: http://www.amsuper.
This SMES will be installed at the Beijing Mentougou Sub- com/
station and serve for a high technology factory before the end [5] B. Hodges, J. Dvorak, and C. Braun, “Fault control system using solid
of 2006. state circuit breakers and high temperature superconducting fault cur-
rent limiters,” in Proceedings of the 1996 22nd International Power
Besides, a 35 kJ/7 kVA SMES system was developed by Modulator Symposium, June 1996, pp. 232–234.
Huazhong University of Science and Technology (HUST) [6] Y. S. Wang et al., “Development of a 45 kVA single-phase model HTS
in 2005. The coil made of Bi-2223 tapes is cooled by G-M transformer,” IEEE Trans. Applied Superconductivity, vol. 16, no. 2,
cryo-cooler and operated at 20 K. This system is now installed pp. 1477–1480, June 2006.
[7] C. H. Zhao, L. Y. Xiao, and L. Z. Lin, “The research and develop-
at the Power System Dynamic Simulation Laboratory of the ment of SMES-A review,” Power System Technology, vol. 28, no. 8,
university. Tests showed that the SMES can stabilize the tran- pp. 163–168, August 2004.