555

DEEP SEA ELECTRONICS AMF AND


INSTRUMENTATION
MODULE
Issue 6
FEATURES DESCRIPTION VH 18/03/03

Ø ‘Basic’ module provides a number of The Model 555 is an Automatic Mains


control and monitoring features with Failure Control Module, with
expansion capability to meet comprehensive instrumentation and load
demanding specifications. The ideal control option. The module is used to
choice where a remote monitor a mains supply and automatically
communications control system is
specified (when used with one of the start and stop the engine. It indicates the
comms output options below). operational status and fault conditions,
automatically shutting down the engine and
Ø ‘Enhanced power measurement’ indicating engine failure by means of an
module provides all the functions of LCD display, and flashing LED on the front
the ‘Basic’ unit but also includes full panel.
power monitoring instrumentation
(detailed right) and powerful auto-sync Selected operational sequences, timers
functions as standard. The inclusion
and alarms can be altered by the
of auto-sync now allows the OEM to
offer the choice of clean break or customer. Alterations to the system are
‘Bumpless’ no break transfers to and made using the 810 interface and a PC.
from the gen-set. No need for This interface also provides real time
complex sync panels etc. Simply use diagnostic facilities. OPTIONAL FEATURES on Power
the 555 Power measurement module
and interface to the engine governor Measurement version only:
It is also possible to monitor the operation
and AVR.(No break transfer using the of the system either locally or remotely
555 module requires connecting to a (Optional: Remote Communications output • Generator kVA L1,L2,L3, Total
suitable electronic governor and AVR.)
version only). Access to the module is • Generator kW L1,L2,L3, Total
Ø Load control versions can be used to restricted by PIN number. • Generator pf L1,L2,L3,Average
export a fixed amount of power to the • Generator kVAr L1,L2,L3, Total
Operation of the module is via pushbutton
load while in parallel with the mains, • Generator KWh
controls (with security locking facility)
with soft transfer to and from the gen- • Generator KVAh
set. mounted on the front panel with
STOP/RESET, AUTO, TEST, MANUAL • Generator KVArh
• Generator Phase Sequence
Ø Optional RS232 port allows and START functions. The first four
comprehensive remote control and pushbuttons feature LED ‘selected’ • Synchroscope Display
monitoring. RS232 provides modem indications. Further pushbuttons provide
link to PC via PSTN line or GSM MUTE/LAMP TEST, LCD PAGE and The instrumentation displays are
network (with suitable modem). DISPLAY SCROLL functions. supplemented further by LCD
Uniquely, the module supplies DC display pages covering operating
power to the modem ensuring The module features 32-Bit Microprocessor status and alarms. The selected
integrity of link during loss of mains control and a comprehensive list of timers page is displayed along with an
and engine starting. The module can and pre-configured sequences. User LED tell-tale:
also signal Engineers via the cell
configurable expansion facilities are also
phone network using the GSM SMS
messaging system to advise of provided. • Status Page
system alarms. • Alarm Page
The 555 module provides metering and • Engine Instruments Page
alarm facilities via the LCD display with • Generator Instruments Page
Ø Optional RS485 ‘Modbus’ output.
the following instrumentation displays, • Mains Instruments Page
Using industry standard
communication protocol allows full accessed via the LCD PAGE and • Event Log Page
system integration into new and DISPLAY SCROLL push-buttons:
existing building management and • Generator Volts L1-N, L2-N, L3-N LED indication is provided for
control schemes. • Generator Volts L1-L2, L2-L3, L3-L1 Alarm present.
• Generator Amps L1,L2,L3
• Generator Frequency Hz Four uncommitted LED’s allow the
The 500 series modules have • Mains Volts L1-N, L2-N, L3-N user to configure the module to
been designed for front panel • Mains Volts L1-L2, L2-L3, L3-L1 provide other status indications
mounting. The module is fitted from either internal states or from
• Mains Frequency Hz
into the cut-out with the fixing external digital inputs.
• Engine Speed RPM
clips removed. These are then • Engine Oil Pressure
fitted from the rear. Connection is • Engine Temperature
via locking plug and socket
• Plant battery Volts
connectors. • Engine Hours Run
• Number of Start Attempts
• Remaining Time until Maintenance Description continues overleaf...

Deep Sea Electronics reserve the right to change


specification without prior notice.
DESCRIPTION TIMERS AND INPUT
CONTINUED FUNCTIONS
• Generator Phase rotation error (‘PM’’ • Start delay timer
The module accepts the following digital Version only)
inputs: • Generator Short Circuit Protection
(‘PM’’ Version only) • Stop delay timer
• Emergency Stop Input - A N/C DC • Loss of speed sensing signal
• Mains out of limits • Crank/Crank Rest timers
positive input
• Mains Phase rotation error
• 9 fully configurable warning or • Fail to Synchronise • Engage Attempt and Manual
shutdown inputs • MPU Open circuit failure along with any Crank Limit timers
configurable input alarms as selected.
With the exception of the Emergency Alarms are indicated by an LCD • Safety On delay timer
Stop Input, these are configurable to be Message, LED illumination and Audible
either N/C or N/O contacts connected to Alarm.
• Warm-up timer
the -Ve DC. The nine fully configurable
auxiliary inputs can be selected to be
indication, warning or shutdown inputs, SPECIFICATION • Cooling timer
either immediate or held off during start
up, to allow for use as protection DC Supply: • Energise to Stop hold timer
expansion inputs. Alternatively they may 8 to 35 V Continuous.
be configured to control extra functions Cranking Dropouts: • Pre-heat timer / Pre-heat bypass
such as manual load switching, Lamp Able to survive 0 V for 50 mS, providing timer
Test or Remote Start input, Generator supply was at least 10 V before dropout
Start signal and many others. and supply recovers to 5V. This is • Smoke Limiting control timers
achieved without the need for internal
Engine analogue inputs are provided batteries. • Fail to Come to Rest timer
for Oil Pressure and Engine Max. Operating Current:
Temperature. These connect to 513mA at 12 V. 263 mA at 24 V. • Over-speed Overshoot timer
conventional engine-mounted resistive Max. Standby Current:
sender units (such as VDO or Datcom 370 mA at 12 V. 210 mA at 24 V. • Breaker Pulse control timers
Type) to provide accurate monitoring and Alternator Input Range:
protection facilities. Alternatively they 15 V(ph-N) to 277 V(ph-N) AC (+20%) • DC Battery alarm delay timers
can be configured to interface with digital Alternator Input Frequency:
switch-type inputs for Low Oil Pressure 50 - 60 Hz at rated engine speed
and High Engine Temperature (Minimum: 15V AC Ph-N) TELEMETRY
shutdowns. Magnetic Pick-up Voltage Input
Range: The 555 module provides the user with
Relay outputs are provided for Fuel
+/- 0.5 V to 70 V Peak the option of full telemetry facilities via
Solenoid, Start and four configurable
Magnetic Input Frequency: 10,000 Hz the optional communications software.
outputs. The configurable relay functions
(max) The module can be either connected to
can be selected from a range of 100+
Mains Sensing Input Range: the PC using the 810 interface or via a
different functions, conditions or alarms.
15V(ph-N) to 277V(ph-N) AC (+20%) suitable modem (Optional: Remote
The relays supply positive plant supply
Mains Sensing Input Frequency: Communications output version only).
out. Additional output relays can be
added by means of up to two 157 Relay 50 - 60 Hz at rated engine speed The PC software is MS-Windows TM
Expansion Modules. A total of 20 (Minimum: 15V AC Ph-N) based and allows the operator to
outputs are available with full expansion Start Relay Output: control the module from a remote
of the 555 Module. This allows the 16 Amp DC at supply voltage. location.
module system to be incorporated into Fuel Relay Output:
existing telemetry or Building 16 Amp DC at supply voltage. The remote operator can also view the
Management Schemes via volt-free Auxiliary Relay Outputs: instrumentation, Alarm and Data log
5 Amp DC at supply voltage. details, and the relay and input status.
contacts.
Generator loading Relay Output:
All access is password controlled so
Refer to appropriate manuals for details. 8 Amp AC 250V.
unauthorised operators cannot log
Mains loading Relay Output:
onto the system.
Multiple alarm channels are provided to 8 Amp AC 250V
monitor the following: Charge Fail / Excitation Range: Additionally in the event of the module
0 V to 35 V detecting an alarm condition, it will
• Under/Over Generator Volts Operating Temperature Range: initiate a modem dial out to the host PC
• Over-current -30 to +70°C to inform the remote operator of the
• Under/Over Generator Frequency Dimensions: problem, giving identification of the
• Under/Overspeed 192mm x 144mm x 138mm module followed by the alarm event
• Charge Fail 7.6’’ x 5.7’’ x 5.5’’ and the time and date of occurrence.
• Emergency Stop (Optional: Remote Communications
• Low Oil Pressure output version only).
• High Engine Temperature
• Fail to Start
NOTE If using a GSM modem, the module is
• Low/High DC Battery Volts
also able to send text messages to a
• Fail to come to rest
An Automatic Start version of the 555 GSM cell phone to indicate gen-set,
• Reverse Power (‘Power Measurement’
Version only) is also available (Model 550). site and alarm condition.
Please refer to Deep Sea Electronics
for details
ENVIRONMENTAL
EVENT CAPTURE
TESTING STANDARDS
The standard module features event • Adjustable crank cycle/attempts Electromagnetic Compatibility
capture facilities, this records the last • Maintenance Due Alarm facility BS EN 50081-2 EMC Emission
25 shutdown alarms allowing the • External remote start input (On Standard for the Industrial Environment
operator to view the recent operating load/Off load)
history of the module to assist in fault • Built-in exercise scheduler function BS EN 50082-2 EMC Immunity
finding, etc. • Magnetic Pick-up or Alternator Standard for the Industrial Environment
speed monitoring
• Synchroscope with Auto-sync Vibration
Event Log: output (Option) BS EN 60068-2-6 Ten sweeps (up and
• Full Remote Control and Telemetry back down) at 1 octave/minute in each
19 Apr2000 14:34:14 (Option) of the three major axes.
• Engine Instrumentation 5Hz to 8 Hz @ +/-7.5mm constant
LOW OIL PRESSURE • Alternator Output Instrumentation displacement.
• 9 Digital inputs - Fully user 8Hz to 500 Hz @ 2gn constant
configurable acceleration
• 4 Configurable relay outputs (100+
CONFIGURATION Control functions) Temperature
Cold:
• LCD Back-lighting for low light level
operation BS EN 60068-2-1-to -300 C
PC based configuration software allows
Hot:
for fast, simple and secure configuration • Security via PIN Number restricted
BS EN 60068-2-2 to 700 C
of module parameters. Utilising the P810 access
interface to provide a safe isolated link to • SMS messaging capability with
Humidity
the PC, changes can easily be made to suitable GSM Modem
BS EN 2011 part 2.1 93% RH @ 400 C
the system by authorised personnel. • Load switching control push-button for 48 hours
Access is PIN number protected. inputs
• Mains Under/Over Volts detection Shock
Complex configurations can be saved
and loaded from disk or output to a • Mains Under/Over Frequency BS EN 60068-2-27 Three half sine
printer for reference. Diagnostic facilities detection shocks in each of the three major axes
allow for fault finding and monitoring • Change-over contactor control 15gn amplitude. 11mS duration.
during test and installation. • Limited configuration from front
panel - including user language Electrical Safety
selection BS EN 60950 Low Voltage
BUILT-IN FUNCTIONS • Graphic LCD Display for true Multi- Directive/Safety of information
lingual use technology equipment, including
• Alternator Under/Over Volts • Multi-lingual capability - 4 default electrical business equipment.
Warning/Shutdown languages.
• Alternator Under/Over Freq.
Warning/Shutdown
• Under/Over Speed
SYNCHRONISING
Warning/Shutdown AND LOAD CONTROL
• Low Oil Pressure Warning/Shutdown OPTIONS
• High Engine Temp
Warning/Shutdown Ø Sync check
• High/Low Battery Volts Warning Ø Governor/engine speed control
• Over-current Warning/Electrical Ø AVR/voltage control
Trip/Shutdown Ø Dead bus sensing
• Reverse Power Electrical Ø Synchroscope
Trip/Shutdown (Option)
• Phase Sequence Electrical Ø No break change-over
Trip/Shutdown (Option) Ø Parallel running with the mains
• Earth Fault Shutdown (Option) Ø KW/kVAr load control with mains
• Short Circuit Fault Electrical
Ø P120 analogue governor
Trip/Shutdown
interface
Ø P121 analogue AVR interface
Ø P122 Digital resistance interface

Hz +0.9 V +0.2
CASE DIMENSIONS

144.0mm
137mm
5.7 ‘’
5.4 ‘’

155.0mm 185.0mm 7.3 ‘’


110mm
4.3 ‘’ 192.0mm 7.6 ‘’

7.5mm Panel Cut-out:138mmx185mm


0.3 ‘’ 5.5 ‘’ x 7.3’’

TYPICAL CONNECTIONS

LOAD
L1 L2 L3 N
Refer to Operators Manuals for further information

Current
Transformers

ALTERNATOR MAINS

Generator Mains
F F F G Contactor Contactor M F F F

Electrical Interlock

Optional 157 Relay


Expansion Board
25 26 27 29 34 33 32 31 36 35 40 39 38 42 43 44 45 (Maximum 2 off)
Generator Loading Mains Loading FCC68 - 4 Way
Relay Relay

Internal Emergency Stop

FCC68 - 8 Way 810


1 2 8 20 21 22 24 23 9 10 11 12 13 14 15 16 17 6
Configuration
3 5 4 7 18 19 30
4 Safety Earth Connection
Must be connected to
the Safety Earth

Oil Temp
F F Sender Sender
MPU NOTE:-
When connected to a
completed Panel / Gen-set
5 Real-time diagnostic display
These Ground connections must be is available
on the engine block and must
be a sound electrical connection 6
to the sender bodies.
The wire to Terminal 24 must not 7
be used to provide a ground 8
connection to any other device
9

Configurable inputs

Deep Sea Electronics Plc. Deep Sea Electronics inc.


Highfield House, Hunmanby Industrial Estate, 5301 E. State St. – Suite 202
North Yorkshire. YO14 0PH. ENGLAND Rockford, Illinois 61108 U.S.A.
Tel +44 (0)1723 890099. Phone +1 (815) 316-8706
Fax +44 (0)1723 893303. Fax +1 (815) 316-8708
Email - sales@deepseaplc.com Email – dsesales@deepseausa.com
Web - www.deepseaplc.com Web – www.deepseausa.com

Anda mungkin juga menyukai