Catalogue | 2014
LBSkit
MV Indoor switches
and disconnectors up to 36 kV
LBSkit Contents
Technical characteristics 4
Safety of people 7
By switchgear 7
By operating mechanism safety 8
Operating mechanisms 9
Auxiliaries 10
Interlocks 11
Installation Guides 12
AMTED306003EN.indd 1
LBSkit The experience of a world leader
The Schneider Electric group’s experience extends over 35 years in SF6 technology
for Medium Voltage switchgear.
This gives you the advantage of unique experience, that of a world leader,
with over 2,700,000 SF6 Medium Voltage units installed throughout the world.
Putting this experience at your service and remaining attentive to your requirements
is the spirit of active partnership that we want to develop in offering you the LBSkit.
LBSkit is a product to let you develop harmonized functions equipped with SF6
breaking technology switchgear.
These functions allow you to produce all your Medium Voltage substation
requirements up to 36 kV.
The result of in-depth analysis of your requirements, both now and in the future,
LBSkit means that you can take advantage of all the features of both a modern
and proven technology.
Commercial references
PE56350
Iran
Tabesh tablou, Teheran utility
Russia
MEL, Moscow utility
Canada
AVAD, Ontario
Sweden
KL Industry, Eon utility, Fortum
Turkey
CIMTAV, Istanbul
Elpa, Istanbul
ELTES, Ankara
AYSAN, Ankara
Aktif Energy, Ankara
EUROPOWER, Ankara
SETMAS, Ankara
ELKO, Ankara
ULUSOY, Ankara
UYAN, Izmir
Algeria
EDIEL, Algier
Thailand
ASEFA, Bangkok
India
Telawne Power Equipments, Bombay
China
Beijing Tongzhou Switchgear
East China Electrical
Guangzhou South Power Group Electrical
Brazil
Precisa Industrial, Rio de Janeiro
2 AMTED306003EN.indd
LBSkit The product’s advantages
Upgradability
LBSkit, a comprehensive product
bb A comprehensive product covering your present and future requirements
bb A design adapted to the extension of your units
bb A catalogue of components for all your applications
bb A product designed to be in compliance with standards constraints
bb Options to anticipate the control and monitoring of your units.
Compactness
LBSkit, an optimised product
bb Compact components, for reduced increment units
bb Rationalised space requirement for switchboard installation.
Maintenance
LBSkit, a product with reduced maintenance
bb The active parts (breaking and earthing) are integrated in an SF6-filled,
“sealed for life” unit
bb The control mechanisms, are intented to function with reduced maintenance
under normal operating conditions
bb Enhanced electrical endurance when breaking.
Ease of installation
LBSkit, a simple product to incorporate
bb Reduced dimensions and weights
bb A solution adapted to cable connection
bb Simplified switchboard busbar connection.
AMTED306003EN.indd 3
LBSkit Technical characteristics
16 630 A
12.5 630 A
Disconnector (kA/1 s) 25 630 - 1250 A 1250 A
20 630 - 1250 A
16 630 - 1250 A
12.5 630 - 1250 A
Maximum breaking capacity
Transformer off load (A) 16
Cables off load (A) 31.5 50
Switch and earthing switch 12-24 kV
Switch (A) 630
Fuse-switch ** (kA) 25 20
The making capacity is equal to 2.5 times the short-time withstand current.
(*) Equipped referring to installation guide, and setting up at an altitude below 1000 m.
(**) Depending on fuse characteristics, and on using of Schneider Electric Fusarc CF fuses.
Endurance
PE56373
Standards
LBSkit units meet all the following recommendations:
bb Switch:
IEC62271-103: High voltage switches - Part 1: switches for rated voltages above 1 kV
and less or equal to 52 kV.
bb Disconnector:
IEC 62271-102: High-voltage alternating current disconnectors and earthing
switches.
bb Switch /disconnector:
IEC 62271-200: A.C. metal-enclosed switchgear and controlgear for rated voltage
above 1 kV and up to including 52 kV.
bb VPIS:
IEC 62271-206: High-voltage prefabricated switchgear and controlgear assemblies-
Voltage presence indicating systems
4 AMTED306003EN.indd
LBSkit Dimensions and weights
for 12-24 kV
LBSkit 12-24 kV
630 A switch - 630 A disconnector Weight: 50 kg
840
DE57151
DE58867
220 200 200 350
213
417.5
190
72
202
940 365
840
DE57153
DE58868
213
417.5
190
72
191
940 365
AMTED306003EN.indd 5
LBSkit Dimensions and weights
for 36 kV
LBSkit 36 kV
630 A switch - 630 A disconnector (width 750 mm) Weight: 75 kg
1342.5 720
DE58831
DE58869
95 352.5 350 350 700
307.6
136
395.5
207
290
1250 A disconnector (width 750 mm) Weight: 76 kg
1342.5 720
DE58833
DE58870
307.6
136
395.5
207
279
1342.5 970
DE58871
136
395.5
207
290
1342.5 970
DE58872
136
395.5
207
279
6 AMTED306003EN.indd
LBSkit Safety of people
By switchgear
b Gas tightness
The three rotating contacts are placed in an enclosure filled with gas to a relative
pressure of 0.4 bar (400 hPa) for LBSkit 12-24 kV and 1 bar (1000 hPa) for LBSkit 36 kV.
It satisfies “sealed pressure system” requirements and seal tightness is always
factory checked.
vv the earthing switch placed in the SF6 has a short-circuit making capacity,
in compliance with standards.
vv any accidental over-pressures are eliminated by the opening of the safety
membrane, in which case the gas is directed toward the back of the unit,
away from the operator.
MT20184
Switch 36 kV
AMTED306003EN.indd 7
LBSkit Safety of people
By operating mechanism safety
8 AMTED306003EN.indd
LBSkit Operating mechanisms
b Switch function
Independent-operation opening or closing by lever or motor.
b Earthing-switch function
Independent-operation opening or closing by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
b Auxiliary contacts
v switch (2 O + 2 C) *
v switch (2 O + 3 C) and earthing switch (1 O + 1 C).
b Motor option
b Switch function
v independent-operation closing by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to close.
v independent-operation opening by push-button (O) or trip units.
b Earthing-switch function
Independent-operation closing and opening by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
b Auxiliary contacts
v switch (2 O + 2 C)
v switch (2 O + 3 C) and earthing switch (1 O + 1 C).
b Opening releases
v shunt trip.
b Switch function
v independent-operation closing in two steps:
1 - operating mechanism recharging by lever or motor
2 - stored energy released by push-button (I) or trip unit.
v independent-operation opening by push-button (O) or trip unit.
b Earthing-switch function
Independent-operation closing and opening by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
b Auxiliary contacts
v switch (2 O + 2 C) *
v switch (2 O + 3 C) and earthing switch (1 O + 1 C).
b Opening release shunt trip
b Closing release shunt trip
b Motor option
AMTED306003EN.indd 9
LBSkit Auxiliaries
Un DC AC (50/60 Hz)
Power supply (V) 24 48 110 220
Motor option
(W) 200
(VA) 200
Operating time for CIT (s) 1 to 2 1 to 2
and charging time for CI2 (s) 4 to 7 4 to 7
Opening releases
Shunt trip (W) 200 250 300
(VA) 750
Response time (ms) 35 35
Closing release
Shunt trip (W) 200 250 300
(VA) 750
Response time (ms) 55 55
10 AMTED306003EN.indd
LBSkit Interlocks
Functional interlocks
These comply with IEC recommendation 62271-200.
In addition to the functional interlocks, each disconnector and switch include
built-in padlocking capacities (padlocks not supplied).
Key-type interlocks
O X b To prevent the closing of an earthing switch if the switch of the other unit
has not been locked in the “open” position.
X O
O
MT20240EN
AMTED306003EN.indd 11
LBSkit Installation Guides
The Installation Guides have been written for “Panel Builders” who have to design,
realize, inspect and maintain own functions with LBSkit in compliance with
international standards of the International Electrotechnical Commission (IEC).
The Installation Guides are single documents covering the assembly of LBSkit and
related components and recommendations. They are intended for Panel Builders
who want to develop their own functions, then a range using LBSkit.
12 AMTED306003EN.indd
LBSkit Selection Guide for 12-24 kV
Switch function 1 to 24 kV, 630 A
Coil kits
Coil type: Without Without Without Opening Without Opening/closing Opening/closing
release release release
(included in
motorized switch)
3730304B 3730305B
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B 3730300B 3730307B 3730300B 3730307B
Included in Included in
7 AC : 2O-3C switch 3730300B motorized 3730300B 3730307B 3730300B 3730307B motorized
+ 1O-1C earthing switch + 3730301B switch + 3730301B + 3730308B + 3730301B + 3730308B switch
AMTED306003EN.indd 13
LBSkit Selection Guide for 12-24 kV
Fuse-switch function 1 to 24 kV, 630 A
Coil kits
Coil type: Without Opening release Without Opening/closing Opening/closing Without Without
release release
(included in motorized
switch)
3730304B 3730305B
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
Operating mechanism 1 piece out of 1 piece out of 1 piece out of 1 piece out of 1 piece out of 1 piece out of 1 piece out of
cover 51238920FC 51238920FC 51238920FF 51238920FF 51238920FF 51238920FG 51238920FG
Metal cover Metal cover Metal cover Metal cover Metal cover Metal cover Metal cover
manufactured manufactured manufactured manufactured manufactured manufactured manufactured
by customer * by customer * by customer * by customer * by customer * by customer * by customer *
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B 3730306B 3730300B 3730306B 3730300B
Included in Included in
7 AC : 2O-3C switch 3730300B 3730306B 3730300B 3730306B motorized 3730300B motorized
+ 1O-1C earthing switch + 3730301B + 3730308B + 3730301B + 3730308B switch + 3730301B switch
Capacitive dividers
3 pieces out of Included in earthing
51238495FA switch kit (3 pieces)
3730351B 3730351B
Interlocking type: A3 + 3731440 + 3731640
3730352B 3730352B
P1 + 3731440 3730350B + 3731640 3730350B
+ +
C4 BBV23780 BBV23781
+ 3731439 + 3731639
14 AMTED306003EN.indd
LBSkit Selection Guide for 12-24 kV
Disconnector function 1 to 24 kV
Operating mechanism CS
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B
Capacitive dividers
3 pieces out of 51238495FA
AMTED306003EN.indd 15
LBSkit Order form for 12-24 kV
Components
48 VDC+7AC 3730109AV 1
110 VDC+7AC 3730109AW 1
220 V 50 Hz+7AC 3730109AX 1
Motorized switch CI2 24 VDC+7AC+O/C coils 3730109AY 1
48 VDC+7AC+O/C coils 3730109AZ 1
110 VDC+7AC+O/C coils 3730109BA 1
220 V 50 Hz+7AC+O/C coils 3730109BB 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
16 AMTED306003EN.indd
LBSkit Order form for 12-24 kV
Components (continued)
For disconnector
For CS 4:2O-2C/Switch 3730300B 1
DE58843
Coil
For switch or fuse-switch without motor
Coil for CI1 24 VDC 3730304B + 3730332A 1+1
DE58844
AMTED306003EN.indd 17
LBSkit Order form for 12-24 kV
Components (continued)
DE58848
Fig. 2
Fig. 3
Cable connection for field distributor 3736435 75
DE58850
6 to 8.9 kV VPI62405 14
9 to 17.9 kV VPI62407 14
18 to 24 kV VPI62408 14
3 2 1G
UP
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
18 AMTED306003EN.indd
LBSkit Order form for 12-24 kV
Components (continued)
(complete with mimic 4 covers for switch unit with CI1 51238920FB 1
diagram and shutters) 4 covers for switch unit with CI2 51238920FE 1
4 covers for fuse-switch unit with CI1 51238920FC 1
4 covers for fuse-switch unit with CI2 51238920FF 1
4 covers for fuse-switch unit with CIT 51238920FG 1
4 covers for disconnector unit with CS 51238920FD 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
AMTED306003EN.indd 19
20 AMTED306003EN.indd
LBSkit Selection Guide for 36 kV
Switch function 36 kV, 630 A
Coil kits
Coil type: Without Without Without Opening Without Opening/closing Opening/closing
release release release
(included in
motorized
3730304B 3730305B switch)
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B 3730300B 3730307B 3730300B 3730307B
Included in Included in
7 AC : 2O-3C switch 3730300B motorized 3730300B 3730307B 3730300B 3730307B motorized
+ 1O-1C earthing switch + 3730301B switch + 3730301B + 3730308B + 3730301B + 3730308B switch
AMTED306003EN.indd 21
LBSkit Selection Guide for 36 kV
Fuse-switch function 36 kV, 630 A
48 VDC 51000162X
Coil kits
Coil type: Without Opening release Without Opening/closing release Opening/closing release
(included in motorized
switch)
3730304B 3730305B
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B 3730306B 3730300B 3730306B
Included in
7 AC : 2O-3C switch 3730300B 3730306B 3730300B 3730306B motorized
+ 1O-1C earthing switch + 3730301B + 3730308B + 3730301B + 3730308B switch
3730351B 3730351B
Interlocking type: A3 + 3731440 + 3731640
3730352B 3730352B
P1 + 3731440 3730350B + 3731640 3730350B
+ +
C4 BBV23780 BBV23781
+ 3731439 + 3731639
22 AMTED306003EN.indd
LBSkit Selection Guide for 36 kV
Disconnector function 36 kV, 630-1250 A
Operating mechanism CS
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B
AMTED306003EN.indd 23
LBSkit Order form for 36 kV
Components
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
24 AMTED306003EN.indd
LBSkit Order form for 36 kV
Components (continued)
For disconnector
For CS 4:2O-2C/Switch 3730300B 1
DE58843
Coil
For switch or fuse-switch without motor
Coil for CI1 24 VDC 3730304B + 3730332A 1+1
DE58844
AMTED306003EN.indd 25
LBSkit Order form for 36 kV
Components (continued)
DE58848
Fig. 2
Fig. 3
Cable connection for field distributor 3736435 75
DE58850
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
26 AMTED306003EN.indd
LBSkit Order form for 36 kV
Components (continued)
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
AMTED306003EN.indd 27
Notes
28 AMTED306003EN.indd
ART819791 © Schneider Electric Industries SAS - All rights reserved
AMTED306003EN 04-2014