Anda di halaman 1dari 3

Focus on Fire Protection

By Matthew Roy

Designing Combined Standpipe and


Sprinkler Systems
In the past, automatic sprinkler systems were installed of Healthcare Organizations (JACHO) standards for health
only to protect extra and special hazard occupancies. A care facilities. Finally, this article assumes that hydraulic cal-
separate set of piping, the standpipe system (a water distri- culations are not required to be provided on a project and
bution system within a property servicing hose cabinets and that the pipe schedule method of design can be applied in a
fire department hose valves or hydrants), was installed to particular jurisdiction.
provide adequate water flow for hose streams used to extin-
The NFPA 13 Approach
guish fire. Due to the relatively high demands required by
Chapter 11 of NFPA 13 defines the design approaches for
extra and special hazard occupancies, the sprinkler piping
sprinkler systems. It is noteworthy that Section 11.1.1 allows
and the standpipe piping were kept separate.
three design approaches for any sprinkler system.
Today, however, virtually every multi-occupant residential
1. Occupancy Hazard Approach. For light and ordinary
and commercial building is fitted with an automatic sprin-
hazard occupancies, hydraulic calculations are not
kler system in addition to the traditional standpipe system
required. In these applications, the hazard approach can
as a result of such tragedies as the Seton Hall University fire
be used for design.
in January of 2000, which claimed three lives and resulted in
the hospitalization of dozens of building occupants. Boland 2. Storage Design Approach. Storage facilities must be
Hall, the freshman dormitory in which the fire occurred, was hydraulically calculated and must follow the require-
built in 1952 and was not equipped with a sprinkler system. ments of Chapter 12.
Due to the lower fire flow demands of light or ordinary 3. Special Design Approach. Special hazard applications
hazard occupancies, both NFPA 13: Standard for the Instal- are required to be hydraulically calculated and must
lation of Sprinkler Systems and NFPA 14: Standard for the follow the requirements of Chapter 13.
Installation of Standpipe and Hose Systems allow the stand- Combined systems for light and ordinary hazard occupan-
pipe and sprinkler piping to be shared. The shared piping, cies can be designed using the occupancy hazard approach.
known as a combined system, dramatically reduces installa- Using this method, NFPA 13 Table 11.2.2.1 requires light
tion costs, making automatic sprinkler systems economically hazard applications to be designed for capacities of 500-
feasible for more new and existing buildings. The shared dis- 750 gallons per minute for durations of 30-60 minutes (see
tribution piping does not compromise the reliability of the Table 1). Ordinary hazard applications should be designed
system, and it reduces system maintenance. for 850-1,500-gpm capacities for durations of 60-90 minutes.
With past versions of NFPA 13 and NFPA 14, applying both Table 1  Water Supply Requirements for Pipe Schedule Sprinkler Systems
standards to an installation resulted in system designs with
conflicts and inconsistencies. For the most part, these con- Acceptable Flow at Base
Minimum Residual of Riser, Including Hose
flicts and inconsistencies have been resolved. In particular, Occupancy Pressure Required Stream Allowance Duration
the standards work together quite well for residential and Classification (psi) (gpm) (minutes)
commercial buildings classified as light or ordinary hazard. Light hazard 15 500 - 750 30 - 60
Ordinary hazard 20 850 - 1,500 60 - 90
The most recent NFPA 13 (2002) and NFPA 14 (2003) Note: For SI units, 1 gpm = 3,785 L/min; 1 psi = 0.0689 bar
define requirements for combined sprinkler/standpipe sys- Source: NFPA 13 (2002) Table 11.2.2.1
tems. Which standard does one use as the driving force for a
particular design? The answer to this question is somewhat The capacities defined in this table cover both sprinkler and
muddy, but it becomes much clearer if you evaluate a build- hose stream demands.
ing using the two design approaches independently. The NFPA 14 Approach
This article will focus on some of the important consid- NFPA 14 requires a system to be designed based on the
erations in calculating water supply requirements (water number of standpipes and the type of hose valves (standpipe
flow, pressure, and duration) for a combined fire protection class). NFPA 101 no longer allows Class II standpipe systems
system for a light or ordinary hazard application. It is impor- (those with 1½-inch hose valves for most buildings), so I’ll
tant to note that sprinkler and standpipe requirements vary limit the discussion to combined sprinkler/standpipe sys-
by jurisdiction, so you should make sure you know which tems of the Class I and Class III types.
applicable international and local codes apply for a par- For Class I and Class III systems (any system with 2½-inch
ticular project. This article assumes use of NFPA 101: Life hose valves for fire department use), NFPA 14 Section 7.10.1.1
Safety Code. Many jurisdictions that have not adopted NFPA requires 500 gpm for the first standpipe plus 250 gpm for
101 use the International Building Code (IBC) as a driver each additional standpipe to a maximum of 1,000 gpm for
for overall fire protection design. Specialized installations fully sprinklered occupancies (1,250 gpm for partially sprin-
such as health care facilities may be subject to other code klered occupancies). An important consideration in Sec-
requirements such as Joint Commission on Accreditation tion 7.10.1.1.2 is that 750 gpm should be used for any single
18  Plumbing Systems & Design  JANUARY/FEBRUARY 2006 PSDMAGAZINE.ORG
&ORALLYOURFIXTURESUPPORTNEEDS USEWHATTHEEXPERTS
CHOOSE *AY23MITH-FG#OWATERCLOSETSUPPORTS
7EHAVEDEVELOPEDA
COMPLETELINEOFFIXTURE
SUPPORTSFORMOUNTINGALL
TYPESOFOFF THE FLOORAND
FLOORMOUNTEDBACKOUTLET
FIXTURES3UPPORTSHAVE
BEENDESIGNEDFORWATER
CLOSETS URINALSANDMANY
SPECIALPURPOSEHOSPITAL
INSTITUTIONALANDINDUS
TRIALPLUMBINGFIXTURES
7ALLMOUNTEDFIXTURES
HAVENOEXTERNALCONTACT
WITHTHEFINISHEDFLOOR
ANDARECLASSIFIEDASOFF
THE FLOORFIXTURES

"

!

#
`ÕÃÌ>Li œÀÊޜÕÀʘiÝÌÊ«ÀœiVÌ]ʏœœŽÊ̜Ê>ÞÊ,°Ê-“ˆÌ…
ˆÝÌÕÀi
-Õ««œÀÌ] v}°Ê
œ°Ê7iÊ«ÕÌʜÕÀʎ˜œÜi`}iʜvÊޜÕÀ ­°®Ê™äÊ i}ÀiiʘiÌÊ-Ì>VŽÊ
ˆ}ÕÀiÊäÓä™9‡x{ VÀ>vÌʈ˜ÌœÊi>V…Ê«Àœ`ÕVÌÊÜiʓ>˜Õv>VÌÕÀiÊ>˜`Ê ˆÌ̈˜}ʈ}ÕÀiÊä{{{9
Å>œÜÊÀœÕ}…‡ˆ˜ÊÌÞ«iÊ vœÀÊÕÃiÊ܅iÀiʜ˜iÊÃÌ>VŽÊ
܈̅Ê>Õ݈ˆ>ÀÞʈ˜iÌÊÌœÊ `ˆÃÌÀˆLÕÌi°ÊÀœ“Ê̅iÊ̈“iÊÜiÊÀiViˆÛiÊޜÕÀ vˆÌ̈˜}ÊÃiÀÛiÃÊÌܜ
«ˆVŽÊÕ«ÊÕÀˆ˜>Ê“œÕ˜Ìi`Ê ˆ˜Ã̈ÌṎœ˜>ÊvˆÝÌÕÀiÃ
L>VŽ‡Ìœ‡L>VŽÊ܈̅Ê
ÀiµÕiÃÌ]Ê̜Ê̅iÊ̈“iÊ̅iÊ«Àœ`ÕVÌʈÃʈ˜ÃÌ>i`]
­ °®Ê`ÕÃÌ>LiʈÝÌÕÀiÊ
Ü>ÌiÀÊVœÃiÌ° ÜiÊÃÌ>˜`ÊÀi>`ÞÊ̜ÊÃiÀÛiÊޜÕÊ܈̅Êi˜}ˆ˜iiÀˆ˜} -Õ««œÀÌ]
܏Ṏœ˜ÃÊ>˜`Ê«Àœ`ÕVÌʈ˜˜œÛ>̈œ˜Ã° ˆ}ÕÀiÊäÓ£ä 9‡x{Ê
Å>œÜÊÀœÕ}…‡ˆ˜ÊÌÞ«iÊvœÀÊ
È«…œ˜ÊiÌÊÜ>ÌiÀÊVœÃiÌÃ
MEMBER OF:

SMITH® JAY R. ­
°®Ê
œ“«>VÌʈÝÌÕÀiÊ
SMITH MFG. CO. -Õ««œÀÌ]Ê
DIVISION OF SMITH INDUSTRIES, INC.
.)4!29
3!

POST OFFICE BOX 3237 ˆ}ÕÀiÊä{{ä9Ê


MONTGOMERY, ALABAMA 36109-0237 (USA)
TEL: 334-277-8520 FAX: 334-272-7396 www.jrsmith.com
.
vœÀÊÈ«…œ˜ÊiÌ
%

'

') ).
E
0R

CUSTOMER
UR

VE
NTI . % % 2 A N #
E

ON 2
DRIVEN ATH E R 4 H

Ü>ÌiÀÊVœÃiÌÃ
œÀʓœÀiʈ˜vœÀ“>̈œ˜Êœ˜ÊœÕÀÊ«Àœ`ÕVÌÃÊ>˜`ÊÃiÀۈViÃʜÀÊ̜ÊVœ˜Ì>VÌÊޜÕÀʏœV>Ê>ÞÊ,°Ê
-“ˆÌ…Êv}°Ê
œ°ÊÀi«ÀiÃi˜Ì>̈Ûi]ÊۈÈÌÊ̅iÊ6ˆÀÌÕ>Ê9iœÜÊ*>}iÃÁÊ­69*®ÊÜiLÊÈÌiÊ>Ì\Ê
ÜÜÜ°Àӈ̅°Vœ“
Circle 19 on your reader response card for product information.
FOCUS on FIRE PROTECTION individual control valve and check valve of the same size as the
standpipe system in which individual branches off the standpipe connection.”
riser service three or more hose cabinets or fire department hose
valves. This section ensures that at least three hose streams are Example
available to fight fires in large buildings regardless of whether one Consider a 10-floor multi-usage residential and commercial
or more standpipes are used in the design. In terms of pressure, building with 50 dwelling units. The commercial space is offices
100-pounds-per-square-inch residual pressure is required at the and has no rack storage or combustibles stacked higher than 8 feet.
most hydraulically remote standpipe outlet. It is important to note The building height is 110 feet from the municipal water supply
that some jurisdictions, primarily those where the fire department entrance to the topmost fire department hose valve outlet. The
uses straight-bore nozzles, still allow 65-psi residual pressure for floor plan is 250 feet by 60 feet and is effectively rectangular. Stair-
standpipe systems. wells are located at opposite ends of the building, and the building
Adding the sprinkler system to the picture, Section 7.10.1.3 is completely protected by an automatic sprinkler system.
defines what additional flows are required. For fully sprinklered In this arrangement, NFPA 101 would require one standpipe
buildings, no additional flow needs to be added for the sprinkler in each exit stairwell with 2½-inch valves located on the land-
demand. For partially sprinklered buildings, 150 gpm and 500 ings between floors. NFPA 14 would require a design flow for the
gpm are to be added to the standpipe demand for light and ordi- standpipe system of 750 gpm (500 gpm for the first standpipe plus
nary hazard occupancies respectively. 250 gpm for the second standpipe). Being a combined system, the
risers would have to be sized a minimum of 6 inches. No additional
The Combined Approach flow would be required for the sprinkler system because the entire
Having looked at the NFPA 13 and NFPA 14 design approaches building is sprinklered. Note that NFPA 13 Table 11.2.2.1 requires
for combined systems, you can see that the two codes very closely 500-750 gpm for this system including sprinkler system demand
agree regarding calculations. Note that NFPA 14 Section 7.6.2 and hose stream allowance. Thus, the two standards agree.
further requires the normal 4-inch minimum standpipe sizing to If a water supply tank is required for this building, it would need
be increased to 6 inches for combined systems. In answering the to be sized for 750 gpm for a duration of 30 minutes at a minimum.
question of which approach to use, the answer is clearly both. The tank would need a minimum volume of 22,500 gallons and
The following procedure is a simple approach to designing a would be required to be installed in accordance with NFPA 22.
combined system. Regarding pressure, you would be required to flow 500 gpm at
1. Using NFPA 101, determine the location and number of risers the two topmost outlets of the standpipe while maintaining a 100-
for the system. The risers and all supply piping should be sized psi residual pressure at the acceptance test. Using the Hazen-Wil-
6 inches minimum. liams Formula for riser pipe losses, 500 gpm would induce a 7-psi
2. Use NFPA 14 to locate hose connections and valves, being loss in the 6-inch riser. Elevation would account for another 48 psi,
careful to ensure each pressure-regulating device has a 2½- resulting in a pressure requirement at the base of the riser of 155
inch test connection to a 3-inch drain riser. psi.
3. Use NFPA 14 to determine both capacity and residual pres- For losses entering the building, you would need to count the
sure requirements for the standpipe system. Pressure drops valves and fittings and calculate pressure losses based on equiva-
through the distribution system should be calculated using lent lengths of pipe. As a final note, ensure that the appropriate
the Hazen-Williams Formula (also defined in NFPA 14). losses for the reduced-pressure principle backflow preventer are
4. Add the sprinkler allowance for partially sprinklered build- considered in the calculations.
ings. Though buildings should be fully sprinklered, this step Upon further study of the combined system, it becomes clear
applies to jurisdictions where complete sprinkler coverage is that NFPA 13 and NFPA 14 offer a relatively simple and elegant
not required. approach to design. Though occasional loopholes or inconsis-
tencies occur between standards, the NFPA requirements for the
5. Locate sprinklers and size distribution piping per NFPA 13.
entire water-based fire protection system mesh completely and
6. If a water supply tank is required to meet the capacity require- beautifully for light and ordinary hazard applications.
ments of the system, use NFPA 13 Table 11.2.2.1 to size the
tank for the appropriate duration. Refer to NFPA 22: Standard
for Water Tanks for Private Fire Protection for installation
requirements.
7. If the water supply is a city main, use NFPA 24: Standard for
the Installation of Private Fire Service Mains and Their Appur- Matthew Roy is Marketing Manager for the Fire
tenances to design the water supply piping. Determine the & Plumbing Product Groups for Armstrong Pumps.
For more information or to comment on this article,
available static and residual supply pressures at the main from e-mail articles@psdmagazine.org.
a hydrant test (defined by NFPA 291: Recommended Practice
for Fire Flow Testing and Marking of Hydrants).
8. Size the fire pump to meet the pressure and flow requirements
and design the pump room to comply with NFPA 20: Standard
for the Installation of Stationary Pumps for Fire Protection.
As a final note on combined systems, keep in mind that NFPA
14 Section 6.2.5.1 requires “each connection from a standpipe that
is part of a combined system to a sprinkler system shall have an

20  Plumbing Systems & Design  JANUARY/FEBRUARY 2006 PSDMAGAZINE.ORG

Anda mungkin juga menyukai