Anda di halaman 1dari 3

INPUT PARAMETERS

LOADING/FORCE PARAMETERS
Nua  26.29kN Factored tensile force on group
of anchor
Vua  19.91kN Factored shear force on group
of anchor

GEOMETRICAL PARAMETERS
d a  16mm Outside diameter of anchor

futa  517MPa Tensile strength of anchor


2
AseN  146mm Crossectional area in tension
2
AseV  146mm Crossectional area in shear
2
Abrg  433mm Bearing area of head bolt

fc  43MPa Concrete cylindrical strength

ϕ  0.70 Concrete type factor


h ef  180mm Embedment depth

λa  1 Concrete modification factor

k c  10 Coefficient for simple breakout of


concrete
ca1  128mm Edge distance1
ca2  1258mm Edge distance 2
s1  510mm Spacing between anchors

h a  230mm Depth of slab

TENSION LOAD CHECK


CHECK FOR STEEL STRENGTH
ϕNsa  ϕ AseN futa  52.837 kN Factored strength of single bolt

Nua
SRT1   0.498 Capacity ratio
ϕNsa

CHECK FOR PULL-OUT STEEL STRENGTH


Np  8.Abrg fc  148.952  kN Pull-out strength in tension

ψcp  1.0 Pull-out strength modification factor

ϕNspn  ϕ ψcp Np  104.266  kN Factored strength of single bolt

Nua
SRT2   0.252 Capacity ratio
ϕNspn
CHECK FOR BREAK-OUT STRENGTH
fc hef  mm1.5 Basic concrete break-out strength
Nb  k c λa  MPa   158.359  kN
MPa mm


camin  min ca1 ca2  128  mm  Minimum edge distance

 
Anc  2  1.5 h ef  s1  camin  1.5h ef  417900 mm  2
Projected failure area

2 2
Anc0  9  h ef  291600 mm Projected failure area if not limited
by edge distance
en  70mm Eccentricity of load

 1   0.794
ψecN   Factor due to eccentricty
2  en
1  
 3  h ef 
 
 camin 
ψedN  0.7  0.3    0.842 Factor due to proximity of edges
1.5h ef
 
ψcpN  1 Factor due to supplimetary
reinforcements
 Anc 
ϕNcb  ϕ    ψedN ψecN ψcpN Nb  106.252  kN Concrete break-out strength
Anc0
 
Nua
SRT3   0.247 Capacity ratio
ϕNcb

SHEAR LOAD CHECK


CHECK FOR STEEL STRENGTH
ϕVsa  ϕ 0.6 2 AseV futa  63.405 kN Factored strength of single bolt

Vua Capacity ratio


SRV1   0.314
ϕVsa

CHECK FOR PRY-OUT STRENGTH


Basic concrete break-out strength
Nb  158.359  kN
camin  128  mm Minimum edge distance
2
Anc  417900 mm Projected failure area

2
Anc0  291600 mm Projected failure area if not limited
by edge distance
en  70 mm Eccentricity of load

ψecN  0.794 Factor due to eccentricty

ψedN  0.842 Factor due to proximity of edges

ψcpN  1

k cp  2 Factor due to supplimetary


reinforcements
 Anc 
ϕVcpg  ϕ k cp    ψedN ψecN ψcpN Nb  212.504  kN Bolt pryout strength
Anc0
 
Vua Capacity ratio
SRV2   0.094
ϕVcpg

CHECK FOR CONCRETE EDGE FAILURE

 
le  min 8  d a h ef  128  mm Load-bearing length of anchor

  l  .2  fc
 e  1.5
Vb  0.6    d a  λa  MPa  ca1  34.544 kN Basic concrete break-out strength
 da  MPa
   

 
Avc  2  1.5 ca1  s1  1.5 ca1  171648 mm
 
2
Projected failure area

2 2
Avc0  4.5 ca1  73728  mm Projected failure area if not limited
by edge distance
ev  70mm Eccentricity of load for shear

ψecV   1   0.733 Factor due to eccentricty


2  ev
1  
 3  ca1 
 
  ca2 
ψedV  min1 0.7  0.3    1 Factor due to proximity of edges
1.5ca1
  
ψcV  1 Factor due to cracks on concrete

 1.5ca1 
ψhV  max 1  1 Factor due to proximity of edges
 ha 

 Avc 
ϕVcbg  ϕ    ψecV ψedV ψcV ψhV Vb  41.256 kN Concrete edge strength
Avc0
 

Vua Capacity ratio


SRV3   0.483
ϕVcbg

COMBINED TENSION AND SHEAR LOADS

  
SRTV  max SRT1 SRT2 SRT3  max SRV1 SRV2 SRV3  0.98  < 1.2; Therefore OK!