Cable Analysis Report

P1

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P1 Name:

Connection From: MSWB To: GAC MCC


Load Main cable to Switchboard Design Current Ib (A): 398.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 120

Qty. & Size (mm²): Phase = 1 x 240 [a] Neutral = 1 x 240 [a]
CPC Size (mm²): Separate 95

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 240 [a]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 398.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 500 A In >= Ib

Ir = N/A --

Iz = 500.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 546.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 0.175 0.125 120 1.00 1.00 546.0 A 398.0 /0.84 398.0 / 0.84 398.0 / 0.84 0.0

Total m : 21 15 Correction Factor (Ct) = 0.9121


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 61.9 L1 L2 L3

Cable Energy Loss (W): At Design Current = 5114.3 Fully Loaded = 5762.3 5.57 / 2.42 5.57 / 2.42 5.57 / 2.42

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 1 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P1 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 500

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 500

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 500 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 398.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 25.000 Load End = 10.467 Source End Earth Fault Current (kA): 25.00

Line Conductor Max. disconnection time (s) = (k²S²/I²): 33.47 Minimum Load End Fault Current Ifmin (kA) = 5.932
Adiabatic Check
Actual disconnection time (s) = 0.71

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 500

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.00924 0.01490 0.03308 0.05686 0.06510


Separate 143 (k2) 95 Actual x (k2/k1) = 95.00

Total = 95.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 2.92 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 4.06 I²t =48.15 x 106 A²s Min. S (mm²) = 48.53

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 2 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P10

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P10 Name:

Connection From: To: LCS-P1101


Load Junction Box Design Current Ib (A): 105.4 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80

Qty. & Size (mm²): Phase = 1 x 35 [f]


CPC Size (mm²): Separate 16

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 35 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 105.4 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 162.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.15 0.135 80 1.00 1.00 162.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0

Total m : 92 11 Correction Factor (Ct) = 0.8918


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 55.4 L1 L2 L3

Cable Energy Loss (W): At Design Current = 1524.4 Fully Loaded = 1769.3 4.43 / 1.93 4.43 / 1.93 4.43 / 1.93

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 3 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P10 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 160

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 160 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): N/A Design Current Ib (A): 105.4 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 3.766 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.085
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 25.05 x 10 Phase Conductor Section S (mm²) = 35

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 160

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.05348 0.11509 0.21913 0.28048


Separate 143 (k2) 16 Actual x (k2/k1) = 16.00

Total = 16.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 1.92 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.05 I²t =2.13 x 106 A²s Min. S (mm²) = 10.21

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 4 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P10-A

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P10-A Name:

Connection From: LCS-P1101 To: P1101


Load Motor, Soft Start, three phase Design Current Ib (A): 105.4 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 10

Qty. & Size (mm²): Phase = 1 x 25 [a]


CPC Size (mm²): Integral 25

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 25 [a]

Installation Method: 33 - Spaced from a wall Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 105.4 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 123.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.6 0.15 10 1.00 1.00 123.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0

Total m : 16 2 Correction Factor (Ct) = 0.9535


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 85 Actual = 70.4 L1 L2 L3

Cable Energy Loss (W): At Design Current = 289.7 Fully Loaded = 307.7 0.81 / 0.35 0.81 / 0.35 0.81 / 0.35

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 5 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P10-A Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 160

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 160 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): 160 A Design Current Ib (A): 105.4 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 3.766 Load End = 3.371 Source End Earth Fault Current (kA): 1.05

Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.750
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 11.22 x 10 Phase Conductor Section S (mm²) = 25

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 160

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 134 (k1) Actual Equivalent

0.21913 0.00928 0.00928 0.23764 0.28048


Integral 134 (k2) 25 Actual x (k2/k1) = 25.00

Total = 25.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 2.62 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =2.47 x 106 A²s Min. S (mm²) = 11.73

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 6 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P11

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P11 Name:

Connection From: To: LCS-P1102


Load Junction Box Design Current Ib (A): 105.4 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80

Qty. & Size (mm²): Phase = 1 x 35 [f]


CPC Size (mm²): Separate 16

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 35 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 105.4 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 162.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.15 0.135 80 1.00 1.00 162.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0

Total m : 92 11 Correction Factor (Ct) = 0.8918


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 55.4 L1 L2 L3

Cable Energy Loss (W): At Design Current = 1524.4 Fully Loaded = 1769.3 4.43 / 1.93 4.43 / 1.93 4.43 / 1.93

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 7 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P11 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 160

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 160 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): N/A Design Current Ib (A): 105.4 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 3.766 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.085
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 25.05 x 10 Phase Conductor Section S (mm²) = 35

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 160

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.05348 0.11509 0.21913 0.28048


Separate 143 (k2) 16 Actual x (k2/k1) = 16.00

Total = 16.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 1.92 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.05 I²t =2.13 x 106 A²s Min. S (mm²) = 10.21

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 8 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P11-A

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P11-A Name:

Connection From: LCS-P1102 To: P1102


Load Motor, Soft Start, three phase Design Current Ib (A): 105.4 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 10

Qty. & Size (mm²): Phase = 1 x 25 [a]


CPC Size (mm²): Integral 25

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 25 [a]

Installation Method: 33 - Spaced from a wall Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 105.4 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 123.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.6 0.15 10 1.00 1.00 123.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0

Total m : 16 2 Correction Factor (Ct) = 0.9535


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 85 Actual = 70.4 L1 L2 L3

Cable Energy Loss (W): At Design Current = 289.7 Fully Loaded = 307.7 0.81 / 0.35 0.81 / 0.35 0.81 / 0.35

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 9 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P11-A Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 160

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 160 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): 160 A Design Current Ib (A): 105.4 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 3.766 Load End = 3.371 Source End Earth Fault Current (kA): 1.05

Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.750
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 11.22 x 10 Phase Conductor Section S (mm²) = 25

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 160

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 134 (k1) Actual Equivalent

0.21913 0.00928 0.00928 0.23764 0.28048


Integral 134 (k2) 25 Actual x (k2/k1) = 25.00

Total = 25.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 2.62 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =2.47 x 106 A²s Min. S (mm²) = 11.73

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 10 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P12

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P12 Name:

Connection From: To: LCS-P1103


Load Junction Box Design Current Ib (A): 105.4 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80

Qty. & Size (mm²): Phase = 1 x 25 [a]


CPC Size (mm²): Separate 16

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 25 [a]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 105.4 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 131.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.6 0.14 80 1.00 1.00 131.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0

Total m : 128 11 Correction Factor (Ct) = 0.9338


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 68.8 L1 L2 L3

Cable Energy Loss (W): At Design Current = 2253.2 Fully Loaded = 2461.7 6.29 / 2.73 6.29 / 2.73 6.29 / 2.73

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 11 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P12 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 160

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 160 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): N/A Design Current Ib (A): 105.4 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 3.007 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.431
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 12.78 x 10 Phase Conductor Section S (mm²) = 25

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 160

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.07418 0.11509 0.23968 0.28048


Separate 143 (k2) 16 Actual x (k2/k1) = 16.00

Total = 16.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 2.70 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.96 I²t =2.51 x 106 A²s Min. S (mm²) = 11.08

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 12 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P12-A

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P12-A Name:

Connection From: LCS-P1103 To: P1103


Load Motor, Soft Start, three phase Design Current Ib (A): 105.4 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 10

Qty. & Size (mm²): Phase = 1 x 35 [f]


CPC Size (mm²): Integral 35

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 35 [f]

Installation Method: 33 - Spaced from a wall Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 105.4 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 151.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.15 0.15 10 1.00 1.00 151.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0

Total m : 12 2 Correction Factor (Ct) = 0.9104


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 85 Actual = 56.8 L1 L2 L3

Cable Energy Loss (W): At Design Current = 196.2 Fully Loaded = 221.2 0.57 / 0.25 0.57 / 0.25 0.57 / 0.25

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 13 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P12-A Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 160

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 160 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): 160 A Design Current Ib (A): 105.4 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 3.007 Load End = 2.813 Source End Earth Fault Current (kA): 0.96

Line Conductor Max. disconnection time (s) = (k²S²/I²): 4.26 Minimum Load End Fault Current Ifmin (kA) = 2.271
Adiabatic Check
Actual disconnection time (s) = 0.12

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 160

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 134 (k1) Actual Equivalent

0.23968 0.00670 0.00670 0.25307 0.28048


Integral 134 (k2) 35 Actual x (k2/k1) = 35.00

Total = 35.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 3.32 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.91 I²t =2.77 x 106 A²s Min. S (mm²) = 12.42

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 14 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P13

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P13 Name:

Connection From: To: LCS-P1201


Load Junction Box Design Current Ib (A): 73.1 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 50

Qty. & Size (mm²): Phase = 1 x 10 [a] Neutral = 1 x 10 [a]


CPC Size (mm²): Armour 43

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 10 [a]

Installation Method: 34 - On a ladder Ref. Method = E Arrangement: Horizontal Touching

Cables in Parallel: No

Grouping Details: Subject to simultaneous overload = No No. of ladders = 1

Total Number of Grouped Circuits = 2 Derating for 2 circuits/cables No. of circuits per ladder = 2

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 0.87 4C4 In = 100 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 63.1 A BS 7671, App. 4.5, Equations 3/4 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 78.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 4 0 50 1.00 0.87 78.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0

Total m : 200 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 99.7 L1 L2 L3

Cable Energy Loss (W): At Design Current = 1925.6 Fully Loaded = 1853.6 6.59 / 2.86 6.59 / 2.86 6.59 / 2.86

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 15 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P13 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 100

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 100 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): N/A Design Current Ib (A): 73.1 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 3.670 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 1.559
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 2.04 x 10 Phase Conductor Section S (mm²) = 10

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 100

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.05774 0.23495 0.34184 0.44231 Armour 46 (k2) 43 Actual x (k2/k1) = 13.83

Total = 13.83
Earth Fault Disconnection Time (s)

Actual from characteristic = 1.77 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.68 I²t =809.26 x 103 A²s Min. S (mm²) = 6.29

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 16 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P13-A

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P13-A Name:

Connection From: LCS-P1201 To: P1201


Load Motor, Star delta started, three phase and neutralat GAC MCC Design Current Ib (A): 73.1 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 5

Qty. & Size (mm²): Phase = 1 x 35 [f] Neutral = 1 x 35 [a]


CPC Size (mm²): Separate 10

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 35 [f]

Installation Method: 33 - Spaced from a wall Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 100 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 60.8 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 151.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.15 0.15 5 1.00 1.00 151.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0

Total m : 6 1 Correction Factor (Ct) = 0.8664


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 85 Actual = 42.9 L1 L2 L3

Cable Energy Loss (W): At Design Current = 44.3 Fully Loaded = 53.3 0.18 / 0.08 0.18 / 0.08 0.18 / 0.08

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 17 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P13-A Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 100

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 100 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): 100 A Design Current Ib (A): 73.1 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 3.670 Load End = 3.594 Source End Earth Fault Current (kA): 0.68

Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 1.525
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 22.00 x 10 Phase Conductor Section S (mm²) = 35

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 100

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 134 (k1) Actual Equivalent

0.34184 0.00167 0.01100 0.35447 0.44231


Separate 115 (k2) 10 Actual x (k2/k1) = 8.58

Total = 8.58
Earth Fault Disconnection Time (s)

Actual from characteristic = 2.02 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.65 I²t =859.32 x 103 A²s Min. S (mm²) = 6.92

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 18 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P14

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P14 Name:

Connection From: To: LCS-P1202


Load Junction Box Design Current Ib (A): 73.1 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 50

Qty. & Size (mm²): Phase = 1 x 35 [f] Neutral = 1 x 35 [f]


CPC Size (mm²): Armour 80

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 35 [f]

Installation Method: 34 - On a ladder Ref. Method = E Arrangement: Horizontal Touching

Cables in Parallel: No

Grouping Details: Subject to simultaneous overload = No No. of ladders = 1

Total Number of Grouped Circuits = 2 Derating for 2 circuits/cables No. of circuits per ladder = 2

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 0.87 4C4 In = 100 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 63.1 A BS 7671, App. 4.5, Equations 3/4 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 162.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 1.15 0.135 50 1.00 0.87 162.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0

Total m : 58 7 Correction Factor (Ct) = 0.8963


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 46.2 L1 L2 L3

Cable Energy Loss (W): At Design Current = 439.5 Fully Loaded = 532.9 1.88 / 0.82 1.88 / 0.82 1.88 / 0.82

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 19 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P14 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 100

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 100 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): N/A Design Current Ib (A): 73.1 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 6.865 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.313
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 25.05 x 10 Phase Conductor Section S (mm²) = 35

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 100

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.01671 0.12700 0.19415 0.44231 Armour 46 (k2) 80 Actual x (k2/k1) = 25.73

Total = 25.73
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.19 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.19 I²t =274.66 x 103 A²s Min. S (mm²) = 3.66

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 20 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P14-A

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P14-A Name:

Connection From: LCS-P1202 To: P1202


Load Motor, Star delta started, three phase and neutralat GAC MCC Design Current Ib (A): 73.1 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting, armoured *RUN TO 70°C Cu Length (m): 5

Qty. & Size (mm²): Phase = 1 x 16 [a] Neutral = 1 x 16 [a]


CPC Size (mm²): Armour 49 + Integral 16

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting, armoured *RUN TO 70°C Cu Size (mm²): 16 [a]

Installation Method: 34 - On a ladder Ref. Method = E Arrangement: Horizontal Touching

Cables in Parallel: No

Grouping Details: Subject to simultaneous overload = No No. of ladders = 1

Total Number of Grouped Circuits = 2 Derating for 2 circuits/cables No. of circuits per ladder = 2

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 0.87 4C4 In = 100 A In >= Ib

Ir = 105.37 A Motor Overload: GN6, amendment 2, p16

Iz = 63.1 A BS 7671, App. 4.5, Equations 3/4 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 83.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 2.4 0 5 1.00 0.87 83.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0

Total m : 12 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 70 Actual = 71 L1 L2 L3

Cable Energy Loss (W): At Design Current = 111.7 Fully Loaded = 111.2 0.40 / 0.17 0.40 / 0.17 0.40 / 0.17

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 21 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P14-A Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 100

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 100 Motor Overload Setting Ir (A): 105.37 A

Motor Rating (A): 100 A Design Current Ib (A): 73.1 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 6.865 Load End = 6.388 Source End Earth Fault Current (kA): 1.19

Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.034
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 3.39 x 10 Phase Conductor Section S (mm²) = 16

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 100

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 115 (k1) Actual Equivalent

0.19415 0.00346 0.00293 0.20045 0.44231 Armour 115 (k2) 49 Actual x (k2/k1) = 49.00

Integral 115 (k2) 16 Actual x (k2/k1) = 16.00

Total = 65.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.22 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.15 I²t =293.49 x 103 A²s Min. S (mm²) = 4.71

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 22 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P2

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P2 Name:

Connection From: GAC MCC To: Site Lighting


Load Distribution Board Design Current Ib (A): 0.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 10

Qty. & Size (mm²): Phase = 1 x 10 [f] Neutral = 1 x 10 [f]


CPC Size (mm²): Armour 43

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 10 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 50 A In >= Ib

Ir = N/A --

Iz = 50.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 78.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 4 0 10 1.00 1.00 78.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0

Total m : 40 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 30 L1 L2 L3

Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 23 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P2 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 50

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 50

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 50 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 0.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 6.200 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 13.50 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.868
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 2.04 x 10 Phase Conductor Section S (mm²) = 10

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 50

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.02309 0.04699 0.12182 1.04544 Armour 46 (k2) 43 Actual x (k2/k1) = 13.83

Total = 13.83
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.90 I²t =13.50 x 10 3 A²s Min. S (mm²) = 0.81

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 24 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P3

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P3 Name:

Connection From: GAC MCC To: Potable Water Booster


Load Distribution Board Design Current Ib (A): 0.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 10

Qty. & Size (mm²): Phase = 1 x 6 [f] Neutral = 1 x 6 [f]


CPC Size (mm²): Armour 36

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 32 A In >= Ib

Ir = N/A --

Iz = 32.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 6.8 0 10 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0

Total m : 68 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 30 L1 L2 L3

Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 25 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P3 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 32

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 32

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 32 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 0.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 4.709 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 3,400.00 Minimum Load End Fault Current Ifmin (kA) = 2.065
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 32

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.03926 0.05461 0.14495 1.84027 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58

Total = 11.58
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.59 I²t =3,400.00 A²s Min. S (mm²) = 0.41

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 26 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P4

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P4 Name:

Connection From: GAC MCC To: Building Services


Load Distribution Board Design Current Ib (A): 0.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 20

Qty. & Size (mm²): Phase = 1 x 6 [f] Neutral = 1 x 6 [f]


CPC Size (mm²): Armour 36

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 40 A In >= Ib

Ir = N/A --

Iz = 40.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 6.8 0 20 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0

Total m : 136 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 30 L1 L2 L3

Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 27 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P4 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 40

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 40

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 40 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 0.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 2.932 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 8,500.00 Minimum Load End Fault Current Ifmin (kA) = 1.220
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 40

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.07852 0.10922 0.23751 1.35300 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58

Total = 11.58
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.06 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =8,500.00 A²s Min. S (mm²) = 0.64

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 28 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P5

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P5 Name:

Connection From: GAC MCC To: LCP1


Load Distribution Board Design Current Ib (A): 21.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 60

Qty. & Size (mm²): Phase = 1 x 6 [f] Neutral = 1 x 6 [f]


CPC Size (mm²): Armour 40

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 21.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 32 A In >= Ib

Ir = N/A --

Iz = 32.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 6.8 0 60 1.00 1.00 56.0 A 21.0 /1.00 21.0 / 1.00 21.0 / 1.00 0.0

Total m : 408 0 Correction Factor (Ct) = 0.8389


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 38.4 L1 L2 L3

Cable Energy Loss (W): At Design Current = 247.4 Fully Loaded = 311.6 4.15 / 1.80 4.15 / 1.80 4.15 / 1.80

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 29 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P5 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 32

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 32

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 32 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 21.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 1.152 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 3,400.00 Minimum Load End Fault Current Ifmin (kA) = 0.460
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 32

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.23556 0.32766 0.61176 1.84027 Armour 143 (k2) 40 Actual x (k2/k1) = 40.00

Total = 40.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.38 I²t =3,400.00 A²s Min. S (mm²) = 0.41

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 30 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P6

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P6 Name:

Connection From: GAC MCC To: LCP2


Load Distribution Board Design Current Ib (A): 29.1 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 60

Qty. & Size (mm²): Phase = 1 x 6 [f] Neutral = 1 x 6 [f]


CPC Size (mm²): Armour 40

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 29.1 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 32 A In >= Ib

Ir = N/A --

Iz = 32.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 6.8 0 60 1.00 1.00 56.0 A 29.1 /1.00 29.1 / 1.00 29.1 / 1.00 0.0

Total m : 408 0 Correction Factor (Ct) = 0.8630


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 46.1 L1 L2 L3

Cable Energy Loss (W): At Design Current = 491.8 Fully Loaded = 596.4 5.91 / 2.57 5.91 / 2.57 5.91 / 2.57

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 31 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P6 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 32

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 32

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 32 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 29.1 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 1.152 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 3,400.00 Minimum Load End Fault Current Ifmin (kA) = 0.460
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 32

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.23556 0.32766 0.61176 1.84027 Armour 143 (k2) 40 Actual x (k2/k1) = 40.00

Total = 40.00
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.38 I²t =3,400.00 A²s Min. S (mm²) = 0.41

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 32 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P7

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P7 Name:

Connection From: GAC MCC To: Plant Room Hoist


Load Distribution Board Design Current Ib (A): 0.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 20

Qty. & Size (mm²): Phase = 1 x 6 [f] Neutral = 1 x 6 [f]


CPC Size (mm²): Armour 36

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 10 A In >= Ib

Ir = N/A --

Iz = 10.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 6.8 0 20 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0

Total m : 136 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 30 L1 L2 L3

Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 33 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P7 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 10

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 10

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 10 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 0.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 2.932 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 280.00 Minimum Load End Fault Current Ifmin (kA) = 1.220
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 10

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.07852 0.10922 0.23751 7.18748 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58

Total = 11.58
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.04 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =280.00 A²s Min. S (mm²) = 0.12

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 34 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P8

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P8 Name:

Connection From: GAC MCC To: Relift PS Hoist


Load Distribution Board Design Current Ib (A): 0.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80

Qty. & Size (mm²): Phase = 1 x 6 [f] Neutral = 1 x 6 [f]


CPC Size (mm²): Armour 36

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 10 A In >= Ib

Ir = N/A --

Iz = 10.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 6.8 0 80 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0

Total m : 544 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 30 L1 L2 L3

Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 35 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P8 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 10

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 10

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 10 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 0.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 0.882 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 280.00 Minimum Load End Fault Current Ifmin (kA) = 0.350
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 10

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.31408 0.43688 0.79932 7.18748 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58

Total = 11.58
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.04 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.29 I²t =280.00 A²s Min. S (mm²) = 0.12

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 36 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
Cable Analysis Report
P9

Project Reference: Killyhevlin WTW-GAC Job Number:


Document No: Created On : 05/08/2014 Rev Date :
Created By : gabriel.cucu Modified By: Rev No:

CIRCUIT DETAILS

Cable Reference Id No.: P9 Name:

Connection From: GAC MCC To: Common Actuated VDB


Load Distribution Board Design Current Ib (A): 0.0 A

PROJECT SETTINGS

Source Id No.: MSWB

Name: Type: TN Public

Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)

Switching Scenario N/A

CABLES

Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 1

Qty. & Size (mm²): Phase = 1 x 6 [f] Neutral = 1 x 6 [f]


CPC Size (mm²): Armour 36

CABLE SIZING Calculations based on BS 7671:2008 (2011) Appendix 4

Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]

Installation Method: 34 - On a ladder Ref. Method = E

Cables in Parallel: No

Grouping Details:

Rating Factor Condition Table Parameter Rule

Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 2 A In >= Ib

Ir = N/A --

Iz = 2.0 A BS 7671, App. 4.5, Equations 1 [per parallel cable]

Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]

Ci = 1.00 Run Through Insulation = No 52.2

VOLTAGE DROP Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

Cable Data Design Current Ib (A/PF)

Impedance: r= x= Length (m) Ca Cg It L1 L2 L3 N

mV/A/m: 6.8 0 1 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0

Total m : 7 0 Correction Factor (Ct) = 1.0000


Voltage Drop (V/%)

Temperature (°C) : Max. Normal (tp) = 90 Actual = 30 L1 L2 L3

Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 37 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013
CIRCUIT DETAILS

Cable Reference Id No.: P9 Name:

PROTECTIVE DEVICES

Overcurrent Type: Generic BS 88-2 Fuse System E Rating In (A): 2

Settings: Phase fault discrimination check required

Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 2

Settings: N/A

OVERCURRENT PROTECTION Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

Protective Device Type: Generic BS 88-2 Fuse System E

Overload: Rating In (A): 2 Overload Setting Ir (A): N/A

Motor Rating (A): N/A Design Current Ib (A): 0.0 A

Breaking Capacity (kA): Icu = 80 Cascaded = No Ics = 80

Max. Fault Current (kA): Source End = 10.467 Load End = 9.476 Source End Earth Fault Current (kA): 4.06

Line Conductor CPD Energy Let-through (A²s): 6.00 Minimum Load End Fault Current Ifmin (kA) = 5.089
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6

EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

Protection: Generic BS 88-2 Fuse System E Rating (A): 2

Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details

Ze Z1 Z2 Zs Max Zs Conductor k Value Section (mm 2)

External Phase CPC Total Phase 143 (k1) Actual Equivalent

0.05686 0.00393 0.00546 0.06495 46.16567 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58

Total = 11.58
Earth Fault Disconnection Time (s)

Actual from characteristic = 0.03 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k

Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 3.56 I²t =6.00 A²s Min. S (mm²) = 0.05

ERRORS

Calculated in accordance with BS 7671

COMMENTS

KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 38 of 38

Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Printed on: 07/08/2014


Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013