P1
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 120
Qty. & Size (mm²): Phase = 1 x 240 [a] Neutral = 1 x 240 [a]
CPC Size (mm²): Separate 95
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 240 [a]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 398.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 500 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 546.0 A It >= Iz [per parallel cable]
mV/A/m: 0.175 0.125 120 1.00 1.00 546.0 A 398.0 /0.84 398.0 / 0.84 398.0 / 0.84 0.0
Cable Energy Loss (W): At Design Current = 5114.3 Fully Loaded = 5762.3 5.57 / 2.42 5.57 / 2.42 5.57 / 2.42
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 1 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 500
Settings: N/A
Max. Fault Current (kA): Source End = 25.000 Load End = 10.467 Source End Earth Fault Current (kA): 25.00
Line Conductor Max. disconnection time (s) = (k²S²/I²): 33.47 Minimum Load End Fault Current Ifmin (kA) = 5.932
Adiabatic Check
Actual disconnection time (s) = 0.71
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 95.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 2.92 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 4.06 I²t =48.15 x 106 A²s Min. S (mm²) = 48.53
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 2 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 35 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 162.0 A It >= Iz [per parallel cable]
mV/A/m: 1.15 0.135 80 1.00 1.00 162.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0
Cable Energy Loss (W): At Design Current = 1524.4 Fully Loaded = 1769.3 4.43 / 1.93 4.43 / 1.93 4.43 / 1.93
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 3 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 3.766 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.085
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 25.05 x 10 Phase Conductor Section S (mm²) = 35
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 16.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 1.92 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.05 I²t =2.13 x 106 A²s Min. S (mm²) = 10.21
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 4 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 10
Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 25 [a]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 123.0 A It >= Iz [per parallel cable]
mV/A/m: 1.6 0.15 10 1.00 1.00 123.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0
Cable Energy Loss (W): At Design Current = 289.7 Fully Loaded = 307.7 0.81 / 0.35 0.81 / 0.35 0.81 / 0.35
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 5 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160
Settings: N/A
Max. Fault Current (kA): Source End = 3.766 Load End = 3.371 Source End Earth Fault Current (kA): 1.05
Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.750
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 11.22 x 10 Phase Conductor Section S (mm²) = 25
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 25.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 2.62 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =2.47 x 106 A²s Min. S (mm²) = 11.73
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 6 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 35 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 162.0 A It >= Iz [per parallel cable]
mV/A/m: 1.15 0.135 80 1.00 1.00 162.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0
Cable Energy Loss (W): At Design Current = 1524.4 Fully Loaded = 1769.3 4.43 / 1.93 4.43 / 1.93 4.43 / 1.93
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 7 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 3.766 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.085
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 25.05 x 10 Phase Conductor Section S (mm²) = 35
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 16.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 1.92 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.05 I²t =2.13 x 106 A²s Min. S (mm²) = 10.21
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 8 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 10
Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 25 [a]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 123.0 A It >= Iz [per parallel cable]
mV/A/m: 1.6 0.15 10 1.00 1.00 123.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0
Cable Energy Loss (W): At Design Current = 289.7 Fully Loaded = 307.7 0.81 / 0.35 0.81 / 0.35 0.81 / 0.35
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 9 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160
Settings: N/A
Max. Fault Current (kA): Source End = 3.766 Load End = 3.371 Source End Earth Fault Current (kA): 1.05
Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.750
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 11.22 x 10 Phase Conductor Section S (mm²) = 25
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 25.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 2.62 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =2.47 x 106 A²s Min. S (mm²) = 11.73
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 10 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 25 [a]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 131.0 A It >= Iz [per parallel cable]
mV/A/m: 1.6 0.14 80 1.00 1.00 131.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0
Cable Energy Loss (W): At Design Current = 2253.2 Fully Loaded = 2461.7 6.29 / 2.73 6.29 / 2.73 6.29 / 2.73
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 11 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 3.007 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 160.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.431
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 12.78 x 10 Phase Conductor Section S (mm²) = 25
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 16.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 2.70 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.96 I²t =2.51 x 106 A²s Min. S (mm²) = 11.08
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 12 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 10
Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 35 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 105.4 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 160 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 151.0 A It >= Iz [per parallel cable]
mV/A/m: 1.15 0.15 10 1.00 1.00 151.0 A 105.4 /0.81 105.4 / 0.81 105.4 / 0.81 0.0
Cable Energy Loss (W): At Design Current = 196.2 Fully Loaded = 221.2 0.57 / 0.25 0.57 / 0.25 0.57 / 0.25
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 13 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 160
Settings: N/A
Max. Fault Current (kA): Source End = 3.007 Load End = 2.813 Source End Earth Fault Current (kA): 0.96
Line Conductor Max. disconnection time (s) = (k²S²/I²): 4.26 Minimum Load End Fault Current Ifmin (kA) = 2.271
Adiabatic Check
Actual disconnection time (s) = 0.12
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 35.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 3.32 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.91 I²t =2.77 x 106 A²s Min. S (mm²) = 12.42
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 14 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 50
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 10 [a]
Cables in Parallel: No
Total Number of Grouped Circuits = 2 Derating for 2 circuits/cables No. of circuits per ladder = 2
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 0.87 4C4 In = 100 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 78.0 A It >= Iz [per parallel cable]
mV/A/m: 4 0 50 1.00 0.87 78.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0
Cable Energy Loss (W): At Design Current = 1925.6 Fully Loaded = 1853.6 6.59 / 2.86 6.59 / 2.86 6.59 / 2.86
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 15 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 3.670 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 1.559
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 2.04 x 10 Phase Conductor Section S (mm²) = 10
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.05774 0.23495 0.34184 0.44231 Armour 46 (k2) 43 Actual x (k2/k1) = 13.83
Total = 13.83
Earth Fault Disconnection Time (s)
Actual from characteristic = 1.77 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.68 I²t =809.26 x 103 A²s Min. S (mm²) = 6.29
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 16 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multi Core 85°C rubber insulated Cu Length (m): 5
Cable Type: Multi Core 85°C rubber insulated Cu Size (mm²): 35 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 100 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 151.0 A It >= Iz [per parallel cable]
mV/A/m: 1.15 0.15 5 1.00 1.00 151.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0
Cable Energy Loss (W): At Design Current = 44.3 Fully Loaded = 53.3 0.18 / 0.08 0.18 / 0.08 0.18 / 0.08
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 17 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100
Settings: N/A
Max. Fault Current (kA): Source End = 3.670 Load End = 3.594 Source End Earth Fault Current (kA): 0.68
Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 1.525
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 22.00 x 10 Phase Conductor Section S (mm²) = 35
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
Total = 8.58
Earth Fault Disconnection Time (s)
Actual from characteristic = 2.02 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.65 I²t =859.32 x 103 A²s Min. S (mm²) = 6.92
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 18 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 50
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 35 [f]
Cables in Parallel: No
Total Number of Grouped Circuits = 2 Derating for 2 circuits/cables No. of circuits per ladder = 2
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 0.87 4C4 In = 100 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 162.0 A It >= Iz [per parallel cable]
mV/A/m: 1.15 0.135 50 1.00 0.87 162.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0
Cable Energy Loss (W): At Design Current = 439.5 Fully Loaded = 532.9 1.88 / 0.82 1.88 / 0.82 1.88 / 0.82
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 19 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 6.865 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.313
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 25.05 x 10 Phase Conductor Section S (mm²) = 35
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.01671 0.12700 0.19415 0.44231 Armour 46 (k2) 80 Actual x (k2/k1) = 25.73
Total = 25.73
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.19 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.19 I²t =274.66 x 103 A²s Min. S (mm²) = 3.66
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 20 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting, armoured *RUN TO 70°C Cu Length (m): 5
Cable Type: Multicore, 90°C thermosetting, armoured *RUN TO 70°C Cu Size (mm²): 16 [a]
Cables in Parallel: No
Total Number of Grouped Circuits = 2 Derating for 2 circuits/cables No. of circuits per ladder = 2
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 73.1 A Diversified load current in highest loaded phase
Cg = 0.87 4C4 In = 100 A In >= Ib
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 83.0 A It >= Iz [per parallel cable]
mV/A/m: 2.4 0 5 1.00 0.87 83.0 A 73.1 /0.78 73.1 / 0.78 73.1 / 0.78 0.0
Cable Energy Loss (W): At Design Current = 111.7 Fully Loaded = 111.2 0.40 / 0.17 0.40 / 0.17 0.40 / 0.17
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 21 of 38
PROTECTIVE DEVICES
Earth Fault Type: Generic BS 88-2 Fuse System E Rating (A): 100
Settings: N/A
Max. Fault Current (kA): Source End = 6.865 Load End = 6.388 Source End Earth Fault Current (kA): 1.19
Line Conductor CPD Energy Let-through (A²s): 60.00 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 3.034
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 3.39 x 10 Phase Conductor Section S (mm²) = 16
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.19415 0.00346 0.00293 0.20045 0.44231 Armour 115 (k2) 49 Actual x (k2/k1) = 49.00
Total = 65.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.22 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.15 I²t =293.49 x 103 A²s Min. S (mm²) = 4.71
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 22 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 10
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 10 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 50 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 78.0 A It >= Iz [per parallel cable]
mV/A/m: 4 0 10 1.00 1.00 78.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0
Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 23 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 6.200 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 13.50 x 10 3 Minimum Load End Fault Current Ifmin (kA) = 2.868
Adiabatic Check 6
Adiabatic Limit k²S² (A²s): 2.04 x 10 Phase Conductor Section S (mm²) = 10
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.02309 0.04699 0.12182 1.04544 Armour 46 (k2) 43 Actual x (k2/k1) = 13.83
Total = 13.83
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.90 I²t =13.50 x 10 3 A²s Min. S (mm²) = 0.81
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 24 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 10
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 32 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]
mV/A/m: 6.8 0 10 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0
Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 25 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 4.709 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 3,400.00 Minimum Load End Fault Current Ifmin (kA) = 2.065
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.03926 0.05461 0.14495 1.84027 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58
Total = 11.58
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 1.59 I²t =3,400.00 A²s Min. S (mm²) = 0.41
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 26 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 20
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 40 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]
mV/A/m: 6.8 0 20 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0
Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 27 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 2.932 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 8,500.00 Minimum Load End Fault Current Ifmin (kA) = 1.220
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.07852 0.10922 0.23751 1.35300 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58
Total = 11.58
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.06 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =8,500.00 A²s Min. S (mm²) = 0.64
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 28 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 60
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 21.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 32 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]
mV/A/m: 6.8 0 60 1.00 1.00 56.0 A 21.0 /1.00 21.0 / 1.00 21.0 / 1.00 0.0
Cable Energy Loss (W): At Design Current = 247.4 Fully Loaded = 311.6 4.15 / 1.80 4.15 / 1.80 4.15 / 1.80
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 29 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 1.152 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 3,400.00 Minimum Load End Fault Current Ifmin (kA) = 0.460
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.23556 0.32766 0.61176 1.84027 Armour 143 (k2) 40 Actual x (k2/k1) = 40.00
Total = 40.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.38 I²t =3,400.00 A²s Min. S (mm²) = 0.41
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 30 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 60
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 29.1 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 32 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]
mV/A/m: 6.8 0 60 1.00 1.00 56.0 A 29.1 /1.00 29.1 / 1.00 29.1 / 1.00 0.0
Cable Energy Loss (W): At Design Current = 491.8 Fully Loaded = 596.4 5.91 / 2.57 5.91 / 2.57 5.91 / 2.57
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 31 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 1.152 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 3,400.00 Minimum Load End Fault Current Ifmin (kA) = 0.460
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.23556 0.32766 0.61176 1.84027 Armour 143 (k2) 40 Actual x (k2/k1) = 40.00
Total = 40.00
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.05 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.38 I²t =3,400.00 A²s Min. S (mm²) = 0.41
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 32 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 20
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 10 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]
mV/A/m: 6.8 0 20 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0
Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 33 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 2.932 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 280.00 Minimum Load End Fault Current Ifmin (kA) = 1.220
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.07852 0.10922 0.23751 7.18748 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58
Total = 11.58
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.04 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.97 I²t =280.00 A²s Min. S (mm²) = 0.12
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 34 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 80
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 10 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]
mV/A/m: 6.8 0 80 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0
Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 35 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 0.882 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 280.00 Minimum Load End Fault Current Ifmin (kA) = 0.350
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.31408 0.43688 0.79932 7.18748 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58
Total = 11.58
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.04 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 0.29 I²t =280.00 A²s Min. S (mm²) = 0.12
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 36 of 38
CIRCUIT DETAILS
PROJECT SETTINGS
Voltage Drop Limits (%) Lighting = 3.00 Other = 5.00 Setting: BS 7671:2008 (2011)
CABLES
Phase and Neutral Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Length (m): 1
Cable Type: Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Size (mm²): 6 [f]
Cables in Parallel: No
Grouping Details:
Ca = 1.00 Air Temperature (°C) = 30.0 4B1 Ib = 0.0 A Diversified load current in highest loaded phase
Cg = 1.00 4C4 In = 2 A In >= Ib
Ir = N/A --
Ch = 1.00 3rd Harmonic = 0.00 % 11A It = 56.0 A It >= Iz [per parallel cable]
mV/A/m: 6.8 0 1 1.00 1.00 56.0 A 0.0 /0.00 0.0 / 0.00 0.0 / 0.00 0.0
Cable Energy Loss (W): At Design Current = 0 Fully Loaded = 0 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 37 of 38
PROTECTIVE DEVICES
Settings: N/A
Max. Fault Current (kA): Source End = 10.467 Load End = 9.476 Source End Earth Fault Current (kA): 4.06
Line Conductor CPD Energy Let-through (A²s): 6.00 Minimum Load End Fault Current Ifmin (kA) = 5.089
Adiabatic Check 3
Adiabatic Limit k²S² (A²s): 736.16 x 10 Phase Conductor Section S (mm²) = 6
EARTH FAULT PROTECTION Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1
Earth Fault Loop Impedance (Ω) Circuit Protective Conductor (CPC) Details
0.05686 0.00393 0.00546 0.06495 46.16567 Armour 46 (k2) 36 Actual x (k2/k1) = 11.58
Total = 11.58
Earth Fault Disconnection Time (s)
Actual from characteristic = 0.03 Earth Fault Current (kA) Adiabatic Check: Minimum Section CPC S = (I²t)/k
Maximum for circuit type = 5.00 Uo/(Zs x 1000) = 3.56 I²t =6.00 A²s Min. S (mm²) = 0.05
ERRORS
COMMENTS
KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition Page 38 of 38