Calculation for Fire Pump Room Ventilation

Ventilation Fans will work at same ACH in case of fire & normal mode
with constant 10 ACH

Area = 30 m²
Hight = 4.00 m²
Volume = 30 x 4 = 120 m ³

One Air Change ≈ = 70 CFM

Ventilation Rate Required: 70 x 10 = 700 CFM

Y:\Sameh Helal - Typing\Al Madaen\378000479.xls Page 1 of 3


Calculation for Domestic Pump Room Ventilation

Ventilation Fans will work at same ACH in case of fire & normal mode
with constant 10 ACH

Area = 15 m²
Hight = 4.00 m²
Volume = 15 x 4 = 60 m ³

One Air Change ≈ = 35 CFM

Ventilation Rate Required: 35 x 10 = 350 CFM

Y:\Sameh Helal - Typing\Al Madaen\378000479.xls Page 2 of 3


Calculation for Generator Room Ventilation

In Case of Generator Work

Our Generator Capacity 1500 KVA.


From Generator Suppliers Generator Requirement as

Fresh Air = 40000


Exhaust Air = 36000
Exhaust Gases = 5800

Fresh Air Supplied By Fresh Air Louver


Maximum Speed of Air On Louver Face 500 FPM
Area of Fresh Air Louver = CFM * 144 / V
40000 * 144 / 500 = 13,440 in2

Louver Size = 3.50 m X 2.20 m = 7.4 m2

Area of Exhaust Air Louver = CFM * 144 / V


36000* 144 / 500 = 12,000 in2 = 6.6 m2

Louver Size = 3.00 m X 2.20 m