DESIGN MANUAL
Table of Contents
Introduction ..................................................................................................................... 3
Design..................................................................................................................................................................... 3
Certification............................................................................................................................................................ 3
2
Introduction
Particleboard Flooring is a well established and well performed product in the Australian home building industry.
This wide use and acceptance has led to an increasing number of enquiries from engineers, architects and
designers about Particleboard Flooring for commercial and industrial applications.
Particleboard Flooring provides major cost savings through its economy and through lighter construction allowing
reduced foundation cost. Installation times are reduced since dry trades only are involved. Particleboard floors are
also more comfortable for people standing for long periods and offer better wearing characteristics than some
other flooring materials for wheeled traffic (especially small wheels) because of the dense surface layer.
Particleboard Flooring is also available with fungus resistance, termite resistance or fire retardancy (designated
"F", "H2" and "FR" respectively). These products are intended for use in applications where there is a risk of attack
from one or other of these wood destroying agents. Installation methods are the same for standard or treated
Particleboard Flooring.
This Design Manual applies specifically to the structural use of Particleboard Flooring installed over a system of
parallel joists. Particleboard Flooring can be installed over a concrete slab but such applications are outside the
scope of this Manual. (Refer to the EWPAA Particleboard Floating Floors Installation Manual).
This Manual is based on research partially funded by the Forest and Wood Products Australia.
Design
Safe Load Tables in this Manual cover a range of particleboard grades, thicknesses and spans. Safe loads were
calculated using a methodology developed specifically for flooring design because tests indicated that
modifications to conventional design methods were required to account for special effects not usually considered.
Particleboard Flooring designed according to the information given in this Manual meets the strength and stiffness
requirements of CSIRO Division of Forest Products Technological Paper No 34. Load deflection tests were used to
provide reasonable allowance for the effects of specified fixings.
Certification
The design information presented in this manual is based on bending calculations with modifications for a number
of effects arising from the installation specification. The information is consistent with the requirements of AS
1170 - 1989 (SAA Loading Code, Part 1 - Dead and Live Loads) and AS 1720 Part 1 -1988 (SAA Timber Structures
Code).
Design procedures and Safe Load Tables have been prepared in conjunction with Consulting Engineers, J A Taylor &
Associates of Melbourne who have certified to the correct application of test information and development of
design methods.
The information in this manual only applies to those particleboard flooring products that carry one of the following
EWPAA certification marks :
3
Notice to Purchaser
Flooring design data and methods in this Manual are based on sound engineering principles applied by an
experienced consultant and on appropriate Australian Standards and Building Codes. The Manual is intended to
assist engineers, designers, specifiers and experienced builders in designing and constructing particleboard floors
for a variety of industrial, commercial and institutional buildings.
The Manual does not cover all aspects of flooring in these types of buildings. Successful performance of
particleboard floors depends on many factors outside the control of the EWPAA. These include correct
determination of floor loads, selection of particleboard floor systems to support these loads, details of joists or
supporting framework, installation procedures, workmanship etc. EWPAA accepts no responsibility for, or in
conjunction with, the quality of the completed systems or their suitability for any purpose other than that which is
imposed by Australian State, Federal or Territory laws, and which is not capable of exclusion.
Particleboard suitable for use as structural flooring is manufactured by members of the Australian Wood Panels
Association and is identified by the EWPAA stamp on each sheet.
Particleboard flooring can provide an attractive hard and in institutional building such as the gym at
wearing floor in retail areas such as this timber products Tuggeranong College in Canberra.
store in Adelaide.
Design Parameters
Introduction
This section presents some information on design parameters in relation to the Safe Load Tables Section (click
here). These Tables cover joist spacings and sheet sizes most likely to apply in practice. The designer should review
carefully these parameters and ensure that they apply to the particular case under consideration.
Performance Criteria
Flooring performance must satisfy the two usual criteria relating to strength and deflection. Strength is straight
forward - design loads must not impose stresses in excess of allowable working stresses. The selection of
appropriate deflection limits requires some judgement.
CSIRO Division of Forest Products Technological Paper No 34 provides strength and stiffness requirements for
floors to guard against failure and to ensure human comfort. Particleboard floors covered by the Safe Load Tables
in this Manual meet these performance criteria of Technological Paper No 34 based on extensive testing and
experience of domestic use.
Safe Load Tables are provided for two deflection criteria - Span/200 and Span/300. These basic requirements lose
some relevance as floor spans become shorter. Therefore an additional absolute deflection limit was imposed, and
deflection criteria are as follows:
4
Span/200 or 3mm - whichever is greater.
Span/300 or 2mm - whichever is greater.
Calculations
Determination of safe loads was based on elastic theory which relates stresses and deflections to applied loads,
material properties and dimensions. The following considerations influenced these calculations.
Floor Loads
Design of particleboard flooring is usually controlled by concentrated loads rather than uniformly distributed loads.
Loads may be assessed by the designer or selected from the SAA Loading Code (AS/NZS 1170 Part 1). Loading Code
figures are based on extreme cases and may be much higher than will apply to most floors. Before designing a
floor a designer should consider several points.
1. The SAA Loading Code figures are based on a bearing area of 100 x 100mm (unless otherwise stated).
2. If the load is a safe or heavy cabinet the base area may be large enough to transfer the load directly to the
joist system, rather than through the floor sheeting (as in Figure 1).
3. High concentrated loads may be applied by construction or demolition equipment.
Figure 1
Economy may be served by distributing heavy loads directly to the joist system.
5
Sub-Floor Design
Particleboard Flooring can be installed over timber or metal joists. This Manual does not cover the design of joists
or other components of the sub-floor structure. Design of joists should be in accordance with the relevant
structural design code eg. the Timber Structures Code (AS 1720 Part 1 - 1988). Correct sub-floor design and
construction are essential for satisfactory floor performance.
Design property values used to calculate Safe Load Tables were determined from an
extensive research program carried out by the Timber & Wood Products Research
Centre, University of Central Queensland. This program involved sampling all
members' products, extensive property testing and the derivation of design values
from base data.
The above values were checked by an several research projects which was a joint
ventures with the Forest & Wood Products Research & Development Corporation. This
project was carried out by the Monash Timber Engineering Centre which involved
checking samples of a manufacturers' product which was considered to be typical of all
manufacturers products.
6
Safe Load Tables
7
Notes relating to Safe Load Tables
1. Linear interpolation is permitted.
2. Design data given in the Tables relates to performance under static bending. Experience shows that the
dynamic effects of walking are satisfactory for 19mm particleboard over joists at 450mm spacing and
22mm flooring on 600mm joist spacing. Caution should be exercised in selecting spans above 600mm
because of lack of knowledge about dynamic response.
3. Safe Loads in the Tables apply to Particleboard Flooring below 13 % moisture content. Moisture content
would be expected to exceed 13 % if the floor is subjected to climate conditions in excess of 85% relative
humidity for long periods of time.
4. The above requirement (3) precludes the use of particleboard flooring in commercial applications where it
will be exposed to the weather. The building must be enclosed before fixing particleboard flooring.
5. If concentrated loads act on areas less than 100x100mm (say 25x25mm) then allowable loads will be 10%
to 20% lower, based on bending calculations. However punching shear considerations (click here) may
require larger bearing areas.
Additional Requirements
The following additional requirements should be noted:
For concentrated loads higher than 3.0 kN or Uniformly Distributed Loads higher than 7 KPa, Close Fixing
should be used (see the Fastening Section and Figure 6 - click here); And
In Addition if Concentrated Loads are higher than 3.5 kN, fixing shall be by screws (plus adhesive) only.
When all edges must be supported it may be more economical to use the larger square edge sheets (3600 x
1800mm) than the usual T & G sheets.
8
Punching Shear
If concentrated loads act on a small bearing area, there may be a risk of punching the load point through the
particleboard sheet. This is termed Punching Shear.
Table 5 gives Safe Concentrated Loads assuming maximum spans for each board thickness. Support dimension is
diameter for circular supports or the side for square supports.
If design involves small support sizes and loads higher than those given in Table 5, pads should be placed under the
load point. A guide to pad size required can be obtained from Table 5.
Table 5
Safe Concentrated Loads for Punching Shear Maximum Load kN
Double Layers
Allowable Loads for double layers can be obtained by adding together the Allowable Loads for each individual layer
from Tables 1-4 as appropriate. This is a conservative approach, but installation procedures to achieve composite
action from the two layers are complex and difficult to verify and long term behaviour too is uncertain.
The additional fixing and support details of the Additional Requirements Section (click here) are required at
Concentrated Loads higher than 6 kN or Uniformly Distributed Loads higher than 20 kPa. In this case the bottom
sheet only requires screw fixing and full support on all edges.
Product Specification
Particleboard Flooring is manufactured in three
thicknesses - 19, 22 and 25mm and in various sheet
sizes. Sheets are factory machined to produce a
groove in the two long edges and a plastic tongue
or spline is inserted in one side. The plastic tongue
allows easier, more accurate installation and is
resistant to handling and transport damage. Square
edged sheets are available as specified or on
request.
9
Design Procedure
The following procedure relates to the design of particleboard floor sheeting. Design of timber or metal sub-floor
joists is not covered in this manual. Joists must be designed to meet the specific load/deflection criteria.
Design Examples
Example 1
Design a hotel floor with maximum Uniformly Distributed Load (UDL) of 5kPa and Concentrated Load (CL) of 3.6kN.
Refine the design. Check costs of possible solutions. Without going into detailed costs here,
it is likely that close joist spacings will represent the major cost. Therefore select 25mm
Step 3 Particleboard Flooring at 500mm joist spacing.
10
Check Punching Shear CL is 3.6 kN. Check Table 5 for maximum loads to resist punching
failure. Concentrated Load of 3.6 kN is safe for 25mm Particleboard if load point is 50mm
Step 4 (square or circular).
Ensure that Concentrated Loads are supported on 50mm bearing size or greater.
Installation should be in accordance with the Additional Requirements Section (click here).
Example 2
An office is to be constructed in an existing building. The floor is 22mm Particleboard on joists at 450mm centres.
Inspection shows that all timbers are sound, but the office floor loads are assessed at UDL = 5kPa. CL = 4.5kN.
Step 1 Loads and performance UDL = 5 kPa, CL = 4.5 kN, Deflection = Span/300
Preliminary design check capabilities of existing floor from Table 3, 22mm Particleboard @
450mm joist spacing can carry CL = 3.2 kN.
Step 2
From Table 4, floor can carry UDL = 10.8 kPa
Consider an extra layer of 19mm flooring. Load capacity of 19mm Particleboard Flooring on
joists at 450mm spacing is (From Table 3) CL = 2.1 kN.
Step 3
For one layer 22mm and one layer 19mm, add individual capabilities. Then CL = 3.2 + 2.1 =
5.3 kN which is satisfactory.
Check Punching Shear From Table 5. Punching Shear maximum load is 2.5 + 2.8 = 5.3 kN
Step 4
No minimum requirements necessary for bearing areas (although size of support should
never be less than 25mm).
Check adequacy of existing joist system. This example concentrated on the Particleboard
Step 5
Flooring but the joist system would also need to be checked against the new design loads.
11
Example 3
Single axle trolleys are being considered for use on an existing floor of 19mm particleboard on joists at 450mm
centres. Trolleys carry up to 400kg load. Can the floor carry these loads?
Step 2 From Table 1, 19mm particleboard at 450mm joist spacing can carry 2.5 kN live load.
Site Storage
Packs of Particleboard Flooring should be protected from the weather before installation. Particleboard Flooring is
resistant to moisture and there is often a tendency to leave packs unprotected on building sites. Water absorption
will cause expansion of the sheets and this will lead to gaps in the floor later when the particleboard sheets dry
out.
As shown in Figure 2, packs should be clear of the ground with supports about 600mm apart. Covering should
allow some air circulation during the storage period.
Figure 2
Good site storage is essential
12
Installation
Sub - Floor
Particleboard Flooring can be installed over timber or metal joists to form a load bearing floor system. Joists must
be installed such that their top surfaces are level. Timber joists must be kiln dried. Joists that are not seasoned at
the time of construction may shrink unevenly as they dry out, which may lead to localised high deflection and
squeaking of the finished floor. These problems can be extremely expensive to remedy some years after the
project has been finished.
Non-load bearing internal walls can be placed anywhere on the particleboard platform floor without any additional
support. However load bearing internal walls must be supported by a joist or trimmers under the bottom plate.
In cavity masonry walls, the openings required for ventilation must be provided in both leaves of the masonry,
with inner-leaf openings directly opposite outer-leaf openings.
2
One ventilation brick per metre of wall length provides about 7500 mm ventilation which is usually regarded as
the minimum requirement. Ventilation should be evenly spaced along the wall length with particular care being
taken to ventilate internal corners.
If internal walls are constructed in subfloor spaces, ventilation opening should be three times the figure above ie.
2
about 22,000 mm per metre.
The clearance between ground surface and the underside of the particleboard sheet should also comply with Local
Authority requirements; 350 mm is the minimum clearance recommended.
Sheet Layout
Particleboard Flooring sheets are laid with their long
side across floor joists and ends butted over a joist.
Sheet end joints should be staggered (as illustrated in
Figure 3) because any slight rounding of sheet corners
may present a hole in the floor if four corners come
together. Select a starting point for laying and set a
string line to ensure the first sheet is square with the
joists. Position the first sheet with its tongued edge to
the string line and note the printed information on
the sheets regarding top surface.
13
Expansion Joints
An expansion joint is a 20mm gap in flooring sheets located above a wide (50mm minimum) or double joist. Extra
joist area is necessary so that sheet ends can be properly fixed while still allowing the 20mm gap. The joint may be
covered by a metal or plastic moulding, screwed into the joist, or partitioning may be located over the joint. See
Figure 4.
It is difficult to provide general guidance about frequency of expansion joints. Particleboard Flooring would be
supplied from the factory with a moisture content in the range of 8-11%. Long term storage in regional
warehouses may raise or lower this figure but such "acclimatisation" should be of benefit in local applications.
Care must be taken to ensure that there is no likelihood of moisture build-up under the floor. Particleboard
Flooring will absorb moisture (and so expand slightly) in tropical areas. Even in air-conditioned buildings, any
concrete work may take a long time to dry out and cause a moist environment during this drying period.
Installation procedures are based on sheets being conditioned to the building environment.
Spacing of expansion joints should be between 10 and 20m with the final decision depending upon the following
assessment.
Fixing
Particleboard Flooring should be fixed with construction grade adhesive and mechanical fasteners.
A bead of adhesive is applied from the cartridge applicator to joists before positioning particleboard sheets. The
bead should be 5-6mm across and must not be laid too far ahead as it may cure quickly. The time available for
laying sheets before the adhesive bead becomes too hard and dry will depend on temperature and ventilation.
These conditions may restrict advance adhesive application to the amount required for one sheet only.
A bead of adhesive should also be applied along the tongue before sheets are pushed together, to ensure a
squeak-free floor. Sheets should be pushed firmly together by hand - mechanical cramping is unnecessary.
When sheets are cut on site, the cut edge should be sealed with adhesive.
Solvent based adhesives should be used on steel joists due to the possibility of traces of petroleum based
lubricants remaining on the steel.
14
Fastening
Fasteners (nails or screws) should be spaced according to the Standard Fixing or Close Fixing pattern as required in
the Additional Requirements Section (click here). Also refer to Figures 5 and 6 below. Fasteners should not be
placed closer than 25mm from tongued or grooved edges and 10mm from the short, butt jointed ends.
Nails may be driven by hand or by nailing gun. With gun nailing, care should be taken to adjust the air pressure for
softwood or hardwood joists, so that nails do not penetrate the surface by more than 1mm.
Table 7
Fasteners for Particleboard Flooring.
Nails may be Bullet, Jolt, Flat or Countersunk heads for hand driving or Tee or Finishing head for power driving.
Countersunk, self-drilling screws should be used for timber joists, while steel joists require countersunk, self-
drilling screws with self breaking cutter nibs. Twist shank hardened nails should be used for power driving into
steel joists.
Figure 5 Figure 6
Standard Fixing Close Fixing
15
Double Layers
Install the first layer as specified in this Section. The second layer should be laid so that the long joins are
staggered between the two layers and end joins meet on a different floor joist (see Figure 7). Run a bead of
adhesive on the first layer at joist positions and fasten through both layers into floor joists. Fastener length for
the second layer should provide at least 30mm penetration into joists.
Figure 7
Double Layer Layout
Platform Flooring
Methods described in this manual generally apply to Platform Construction. Although an exposure period of 3
months maximum is permitted, efforts should be made to protect Particleboard Flooring from excessive exposure.
Any ponded water should be swept off. Drain holes can be provided by drilling in places or skirtings. Roof cover
should be provided as soon as possible. Excessive and differential drying can be caused by the hot Australian sun.
This may result in cupping which could, in extreme cases, cause nail pull-out or pull-through of nail heads. In very
severe cases, shading may be needed, or alternatively, water should be sprayed onto the Particleboard Flooring
surface to recondition sheets back to uniform moisture content.
In general, attempts should be made to keep the exposure time to a minimum. Damage may also be caused by
other tradesmen and attention is needed to avoid:
16
Fitted Flooring
Fitted floors are those installed after internal walls are constructed and usually after the roof and wall claddings
are fixed. Fixing is basically as described. An expansion gap of 10 mm should be left around all walls. This gap will
later be covered by skirting boards
Finishing
Particleboard Flooring will usually need to be sanded prior to finishing or laying of floor coverings. However for
carpet installation sanding may not be needed if the surface layer is smooth and sound.
Before sanding, the floor should be dry and nail heads should be punched below the surface. Sanding should not
remove more than 1 mm of board generally or 2 mm at board edges.
If carpet is to be laid, a light sanding with 40-60 grit paper may be all that is necessary if building trades have not
left paint, plaster or cement on the floor. If a clear finish is to be applied, the 40-60 grit paper sanding should be
followed by fine sanding with 80-100 grit paper.
Clear Finishing
Particleboard Flooring can be clear finished with polyurethane to give a cork-like appearance. However some
colour variation between sheets is to be expected and construction activities and weather may contribute to
colour variation. Particular care is needed to avoid staining, discolouration, surface damage and distortion. For
these reasons a tint or stain may be an advantage in the clear finish.
After sanding fill all nail holes with appropriately coloured putty and apply the clear finish to manufacturers'
instructions. Three coats are recommend.
Particleboard Flooring can be used for resilient floor coverings without underlay. However it is not possible to give
a general recommendation on this matter. During exposure of platform floors to weather conditions, some
movement must occur in both the thickness and the plane of Particleboard sheets due to swelling and shrinkage.
This movement may lead to small gaps between sheets. It is thus not possible to guarantee that sheet edges and
nail holes will not show through soft, flexible floor coverings.
17
In general an underlayment is recommended. Special inspection is needed before an individual installation could
be approved for vinyl flooring laid directly onto the Particleboard.
Ceramic Tiles
Ceramic tiles should not be laid directly to Particleboard Flooring. An underlay of 6mm fibre-cement sheet should
be used, fixed according to manufacturers' instructions. Underlay sheets should be sealed before application of
adhesive or mortar.
Manufacturers' instructions should be followed for all details of ceramic tile installation.
Product Selection
Particleboard Flooring should only be used in wet area rooms if there is no risk of leaks allowing water to reach the
Particleboard. If it is considered that there is a risk of short-term dampness, Particleboard Flooring F should be
used. Please note that no Particleboard Flooring will perform satisfactorily if continually wet. Fungus resistance
provides protection until the cause of dampness can be found and fixed. Particleboard Flooring H2 is available for
areas with high termite activity and FR Flooring is available for areas where improved Indices of Early Fire Hazard
are specified.
To avoid the risk of water reaching the Particleboard the following construction features should be present:
1. Bearers and joists should be dried or stabilised. Shrinkage of green bearers and joists can lead to breakdown
of flashing and sealing.
2. A precast shower base or shower tray should be used. In-situ construction using rubber-type sheet or strip
flashing or sealing membranes do not provide the necessary assurance.
18
Sealing & Flashing
Room Perimeter
The perimeter of wet area rooms should be sealed with a rigid
PVC angle flashing 50 x 100 to 150 mm in size. The flashing must
be fixed before wall lining (plaster board or fibre cement sheet)
is applied, so that the flashing finishes behind lining sheets - see
Figure 8.
The angle flashing is glued to the floor (50mm side to the floor)
using Particleboard floor adhesive or a 2-part epoxy. Consult
Particleboard manufacturers' literature for approved adhesives.
PVC angle flashing should not be fixed to bottom plate or wall
studs, so that any subsequent movement of the timber frame
will not break it. However to ensure the flashing remains in Figure 8
place, a clout head or adhesive spot should be used at each stud Room Perimeter Detail
to provide a temporary restraint.
Board Joins
Shower Tray - preformed tray made from copper, stainless steel or fibreglass. These should be used when ceramic
tiles are to be fixed to form the finished shower floor.
Shower Base - precast ceramic or polyester (Polymarble) base intended to form the finished shower floor.
Trays and bases should usually be fixed before the wall sheeting which then runs down into the tray or onto the
base edge recess, according to manufacturers' instructions.
Shower trays and bases should be bonded to the floor surface with adhesive or mortar according to
manufacturers' instructions. Care should be taken to ensure that the tray is properly supported on the base and
sides, otherwise the weight of workmen or house occupants will cause distortion, movement and possibly fracture.
A properly installed, precast shower tray or shower base should provide the basis for a leak-free installation and
allow Particleboard Flooring to be used in wet area rooms.
19
Wall Corner
PVC, fibreglass or flexible strip flashing should be fixed to the shower
recess wall corner before wall sheeting is installed. Corner flashing
should run down into the shower tray. If a shower base is used, it will
run to the recessed edge - see Figures 9 and 10.
Site-made copper trays should be satisfactory but are at higher risk from
building movement than factory-made trays. Factory made trays should
use a folding process for corners, which are watertight but allow some
movement. Braised joints may fail from forces generated by wall and
floor movement.
Particleboard Flooring F should be used for wet area rooms if in-situ tray
construction is to be used.
Flexible membrane trays are made by gluing flexible membrane over the
shower recess floor and then bonding strip membrane material around
the shower recess perimeter. This material should be cut from metre-
wide sheets so that a one-piece installation results over the shower
recess floor. Details of corner strip and floor sheet bonding are shown in
Figures 9 and 10.
Figure 10
Flexible Membrane Shower Base
Figure 9
Corner Flashing for Showers
20
Hob Construction
A hob is the site construction (usually of bricks) to complete the fourth side of the shower recess. It provides the
entry, and is the base for a sliding screen door if such is being used.
With shower trays, bricks should be set inside the tray edge so as to retain water inside the shower recess. A
better system is split brick - bricks are cut in half with each half being laid on either side of the tray edge. However
tradesmen do not usually have equipment available for split brick construction.
With in-situ trays, care is needed to provide adequate sealing at the hob ends (ie. where it joins the wall) and along
the hob length. Rubber membrane trays should have the rubber turned up and bonded to the outside of the hob.
Alternatively a length of rigid PVC angle flashing can be glued in place and the hob laid inside this. Care must be
taken to avoid damage to the PVC angle between installation and laying the hob.
Careful attention to detail is needed generally because the shower recess screen or curtain will ensure a steady
stream of water down onto the hob and to its corners. The corners are common sources of leaks.
Floor Wastes
When holes are cut in Particleboard Flooring sheets for any service pipes, all edges of the hole should be sealed
with epoxy adhesive. A PVC flange should be used for the waste pipe and the flange should be bonded to the
Particleboard surface (or shower tray) with epoxy adhesive -see Figure 11.
Figure 11
Floor Waste Installation
Ceramic Tiles
Before laying a mortar bed for the fixing of ceramic tiles, the Particleboard surface must be sealed. An epoxy sealer
is recommended which must be tacky when the mortar bed is placed. It is unlikely that proper sealing of the
Particleboard, and a tacky surface for mortar bonding, will be achieved with one coat of epoxy. The first coat
should be brushed on and allowed to dry. Apply the second coat just before laying the mortar bed.
Prepare and lay the mortar bed (usually 3 parts sand to I part cement). Slope the mortar to floor drain where one
is required by local authority; typical slope is 1 in 80. Slope the mortar to shower recess drain, usually 1 in 60.
Follow Building Regulations regarding minimum mortar bed thickness, this may be as low as 12 mm in some states
but a thicker minimum, say 25 mm, is recommended.
It is common practice in some areas to seal shower recesses with a fibreglass system - liquid resin to seal corners,
drain and hob plus fibreglass mat for reinforcement. It can be difficult to obtain good bonding between the set
fibreglass and the mortar bed. A roughening or etching of surface is necessary to avoid later "drumminess".
21
Health & Safety Information
Refer to the Material Safety Data Sheet (MSDS) from the manufacturer. These are generally available from the
manufacturers web sites. Refer to the back page for a list of these web sites.
Revision History
Revision Changes Date Who
22
EWPAA Members
23