Anda di halaman 1dari 22

Job

tnxTower Verificación Estructural


Page
1 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Tower Input Data

The main tower is a 3x free standing tower with an overall height of 42.00 m above the ground line.
The base of the tower is set at an elevation of 0.00 m above the ground line.
The face width of the tower is 1.75 m at the top and 3.50 m at the base.
This tower is designed using the TIA/EIA-222-F standard.
The following design criteria apply:
Basic wind speed of 121 kph.
Deflections calculated using a wind speed of 81 kph.
Weld together tower sections have flange connections..
Connections use galvanized A325 bolts, nuts and locking devices. Installation per TIA/EIA-222 and AISC Specifications..
Tower members are ''hot dipped'' galvanized in accordance with ASTM A123 and ASTM A153 Standards..
Welds are fabricated with ER-70S-6 electrodes..
Pressures are calculated at each section.
Stress ratio used in tower member design is 1.333.
Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered.

Options
Consider Moments - Legs Distribute Leg Loads As Uniform Use ASCE 10 X-Brace Ly Rules
Consider Moments - Horizontals Assume Legs Pinned Calculate Redundant Bracing Forces
Consider Moments - Diagonals √ Assume Rigid Index Plate Ignore Redundant Members in FEA
Use Moment Magnification √ Use Clear Spans For Wind Area SR Leg Bolts Resist Compression
√ Use Code Stress Ratios √ Use Clear Spans For KL/r All Leg Panels Have Same Allowable
Use Code Safety Factors - Guys Retension Guys To Initial Tension Offset Girt At Foundation
Escalate Ice Bypass Mast Stability Checks Consider Feed Line Torque
Always Use Max Kz √ Use Azimuth Dish Coefficients Include Angle Block Shear Check
Use Special Wind Profile √ Project Wind Area of Appurt. Use TIA-222-G Bracing Resist. Exemption
Include Bolts In Member Capacity Autocalc Torque Arm Areas Use TIA-222-G Tension Splice Exemption
√ Leg Bolts Are At Top Of Section Add IBC .6D+W Combination Poles
√ Secondary Horizontal Braces Leg √ Sort Capacity Reports By Component Include Shear-Torsion Interaction
Use Diamond Inner Bracing (4 Sided) √ Triangulate Diamond Inner Bracing Always Use Sub-Critical Flow
SR Members Have Cut Ends Treat Feed Line Bundles As Cylinder Use Top Mounted Sockets
SR Members Are Concentric
Job
tnxTower Verificación Estructural
Page
2 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Wind 180

Leg A

Wind 90

Fa
A

ce
ce
Fa

B
Leg C Z Leg B

Face C

Wind Normal

Triangular Tower

Tower Section Geometry


Tower Tower Assembly Description Section Number Section
Section Elevation Database Width of Length
Sections
m m m
T1 42.00-36.00 1.75 1 6.00
T2 36.00-30.00 1.75 1 6.00
T3 30.00-24.00 1.75 1 6.00
T4 24.00-18.00 1.75 1 6.00
T5 18.00-12.00 1.75 1 6.00
T6 12.00-6.00 2.30 1 6.00
T7 6.00-0.00 2.90 1 6.00

Tower Section Geometry (cont’d)


Tower Tower Diagonal Bracing Has Has Top Girt Bottom Girt
Section Elevation Spacing Type K Brace Horizontals Offset Offset
End
Job
tnxTower Verificación Estructural
Page
3 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

m m Panels mm mm
T1 42.00-36.00 1.50 X Brace No No 0 0
T2 36.00-30.00 1.50 X Brace No No 0 0
T3 30.00-24.00 1.50 X Brace No No 0 0
T4 24.00-18.00 1.50 X Brace No No 0 0
T5 18.00-12.00 2.00 X Brace No No 0 0
T6 12.00-6.00 2.00 X Brace No No 0 0
T7 6.00-0.00 2.00 X Brace No No 0 0

Tower Section Geometry (cont’d)


Tower Leg Leg Leg Diagonal Diagonal Diagonal
Elevation Type Size Grade Type Size Grade
m
T1 42.00-36.00 Pipe O 4''x6.02 A37-24ES Single Angle L40x40x4 A37-24ES
(235 MPa) (235 MPa)
T2 36.00-30.00 Pipe O 4''x6.02 A37-24ES Single Angle L40x40x5 A37-24ES
(235 MPa) (235 MPa)
T3 30.00-24.00 Pipe O 6''x7.11 A37-24ES Single Angle L50x50x4 A37-24ES
(235 MPa) (235 MPa)
T4 24.00-18.00 Pipe O 6''x7.11 A37-24ES Single Angle L50x50x5 A37-24ES
(235 MPa) (235 MPa)
T5 18.00-12.00 Pipe O 6''x10.97 A37-24ES Single Angle L60x60x4 A37-24ES
(235 MPa) (235 MPa)
T6 12.00-6.00 Pipe O 6''x10.97 A37-24ES Single Angle L60x60x6 A37-24ES
(235 MPa) (235 MPa)
T7 6.00-0.00 Pipe O 6''x10.97 A37-24ES Single Angle L60x60x6 A37-24ES
(235 MPa) (235 MPa)

Tower Section Geometry (cont’d)


Tower Top Girt Top Girt Top Girt Bottom Girt Bottom Girt Bottom Girt
Elevation Type Size Grade Type Size Grade
m
T1 42.00-36.00 Single Angle L40x40x4 A37-24ES Solid Round A37-24ES
(235 MPa) (235 MPa)

Tower Section Geometry (cont’d)


Tower Gusset Gusset Gusset Grade Adjust. Factor Adjust. Weight Mult. Double Angle Double Angle Double Angle
Elevation Area Thickness Af Factor Stitch Bolt Stitch Bolt Stitch Bolt
(per face) Ar Spacing Spacing Spacing
Diagonals Horizontals Redundants
m m2 mm mm mm mm
T1 42.00-36.00 0.00 0 A36 1 1 1 914 914 914
(248 MPa)
T2 36.00-30.00 0.00 0 A36 1 1 1 914 914 914
Job
tnxTower Verificación Estructural
Page
4 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

(248 MPa)
T3 30.00-24.00 0.00 0 A36 1 1 1 914 914 914
(248 MPa)
T4 24.00-18.00 0.00 0 A36 1 1 1 914 914 914
(248 MPa)
T5 18.00-12.00 0.00 0 A36 1 1 1 914 914 914
(248 MPa)
T6 12.00-6.00 0.00 0 A36 1 1 1 914 914 914
(248 MPa)
T7 6.00-0.00 0.00 0 A36 1 1 1 914 914 914
(248 MPa)

Tower Section Geometry (cont’d)


K Factors1
Tower Calc Calc Legs X K Single Girts Horiz. Sec. Inner
Elevation K K Brace Brace Diags Horiz. Brace
Single Solid Diags Diags
Angles Rounds X X X X X X X
m Y Y Y Y Y Y Y
T1 42.00- No No 1 1 1 1 1 1 1 1
36.00 1 1 1 1 1 1 1
T2 36.00- No No 1 1 1 1 1 1 1 1
30.00 1 1 1 1 1 1 1
T3 30.00- No No 1 1 1 1 1 1 1 1
24.00 1 1 1 1 1 1 1
T4 24.00- No No 1 1 1 1 1 1 1 1
18.00 1 1 1 1 1 1 1
T5 18.00- No No 1 1 1 1 1 1 1 1
12.00 1 1 1 1 1 1 1
T6 12.00-6.00 No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T7 6.00-0.00 No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
1
Note: K factors are applied to member segment lengths. K-braces without inner supporting members will have the K factor in the out-of-plane direction applied to
the overall length.

Tower Section Geometry (cont’d)


Tower Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal
Elevation
m
Net Width U Net Width U Net Width U Net U Net U Net U Net U
Deduct Deduct Deduct Width Width Width Width
mm mm mm Deduct Deduct Deduct Deduct
mm mm mm mm
T1 42.00-36.00 0 1 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75
T2 36.00-30.00 0 1 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75
T3 30.00-24.00 0 1 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75
T4 24.00-18.00 0 1 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75
T5 18.00-12.00 0 1 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75
T6 12.00-6.00 0 1 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75
Job
tnxTower Verificación Estructural
Page
5 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

T7 6.00-0.00 0 1 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75 0 0.75

Feed Line/Linear Appurtenances - Entered As Round Or Flat


Description Face Allow Component Placement Total Number Clear Width or Perimete Weight
or Shield Type Number Per Row Spacing Diameter r
Leg m mm mm kglm
mm
1'' A No Ar (CaAa) 2.10 - 42.00 6 2 60 25 1.00
1'' A No Ar (CaAa) 2.10 - 42.00 6 2 60 25 1.00
1'' A No Ar (CaAa) 2.10 - 42.00 6 2 60 25 1.00
3/8'' A No Ar (CaAa) 2.10 - 42.00 8 6 60 10 0.20
5/8'' A No Ar (CaAa) 2.10 - 42.00 3 2 60 16 0.60
1/4'' A No Ar (CaAa) 2.10 - 42.00 3 2 60 6 0.15
3/8'' A No Ar (CaAa) 2.10 - 42.00 2 1 60 10 0.20
1'' A No Ar (CaAa) 2.10 - 42.00 6 1 60 25 1.00
1'' A No Ar (CaAa) 2.10 - 38.00 6 1 60 25 1.00

Feed Line/Linear Appurtenances Section Areas


Tower Tower Face AR AF CAAA CAAA Weight
Section Elevation In Face Out Face
m m2 m2 m2 m2 kg
T1 42.00-36.00 A 0.000 0.000 5.957 0.000 181.50
B 0.000 0.000 0.000 0.000 0.00
C 0.000 0.000 0.000 0.000 0.00
T2 36.00-30.00 A 0.000 0.000 6.688 0.000 205.50
B 0.000 0.000 0.000 0.000 0.00
C 0.000 0.000 0.000 0.000 0.00
T3 30.00-24.00 A 0.000 0.000 6.688 0.000 205.50
B 0.000 0.000 0.000 0.000 0.00
C 0.000 0.000 0.000 0.000 0.00
T4 24.00-18.00 A 0.000 0.000 6.688 0.000 205.50
B 0.000 0.000 0.000 0.000 0.00
C 0.000 0.000 0.000 0.000 0.00
T5 18.00-12.00 A 0.000 0.000 6.688 0.000 205.50
B 0.000 0.000 0.000 0.000 0.00
C 0.000 0.000 0.000 0.000 0.00
T6 12.00-6.00 A 0.000 0.000 6.688 0.000 205.50
B 0.000 0.000 0.000 0.000 0.00
C 0.000 0.000 0.000 0.000 0.00
T7 6.00-0.00 A 0.000 0.000 4.347 0.000 133.57
B 0.000 0.000 0.000 0.000 0.00
C 0.000 0.000 0.000 0.000 0.00

Discrete Tower Loads


Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight
or Type Horz Adjustment Front Side
Job
tnxTower Verificación Estructural
Page
6 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Leg Lateral
Vert
m ° m m2 m2 kg
m
m
RF 1.94x0.27x0.13 A From Leg 0.60 20.000 42.00 No Ice 0.79 0.64 46.54
0.00
1.50
RF 1.94x0.27x0.13 B From Leg 0.60 30.000 42.00 No Ice 0.79 0.64 46.54
0.00
1.50
RF 1.94x0.27x0.13 C From Leg 0.60 50.000 42.00 No Ice 0.79 0.64 46.54
0.00
1.50
RF 2.03x0.28x0.08 A From Leg 0.60 60.000 42.00 No Ice 0.84 0.54 46.54
0.00
1.50
RF 2.03x0.28x0.08 B From Leg 0.60 10.000 42.00 No Ice 0.84 0.54 46.54
0.00
1.50
RF 2.03x0.28x0.08 C From Leg 0.60 50.000 42.00 No Ice 0.84 0.54 46.54
0.00
1.50
RF 1.3x0.14x0.05 A From Leg 0.60 30.000 42.00 No Ice 0.37 0.35 36.54
0.00
1.50
RF 1.3x0.14x0.05 B From Leg 0.60 30.000 42.00 No Ice 0.37 0.35 36.54
0.00
1.50
RF 1.3x0.14x0.05 C From Leg 0.60 50.000 42.00 No Ice 0.37 0.35 36.54
0.00
1.50
RRU 0.3x0.175x0.08 A From Leg 0.00 0.000 42.00 No Ice 0.07 0.03 20.00
0.00
1.00
RRU 0.3x0.175x0.08 B From Leg 0.00 0.000 42.00 No Ice 0.07 0.03 20.00
0.00
1.00
RRU 0.3x0.175x0.08 C From Leg 0.00 0.000 42.00 No Ice 0.07 0.03 20.00
0.00
1.00
RRU 0.3x0.175x0.08 C From Leg 0.00 0.000 42.00 No Ice 0.07 0.03 20.00
0.00
1.00
RRU 0.3x0.175x0.08 C From Leg 0.00 0.000 42.00 No Ice 0.07 0.03 20.00
0.00
1.00
RRU 0.3x0.175x0.08 C From Leg 0.00 0.000 42.00 No Ice 0.07 0.03 20.00
0.00
1.00
RRU 055x0.45x0.12 C From Leg 0.00 0.000 42.00 No Ice 0.35 0.09 30.00
0.00
1.00
RRU 055x0.45x0.12 C From Leg 0.00 0.000 42.00 No Ice 0.35 0.09 30.00
0.00
1.00
RRU 055x0.45x0.12 C From Leg 0.00 0.000 42.00 No Ice 0.35 0.09 30.00
0.00
1.00
Job
tnxTower Verificación Estructural
Page
7 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

RF 1.6x0.4x0.13 WOM A From Leg 0.60 0.000 38.00 No Ice 0.97 0.55 46.54
0.00
0.00
RF 1.6x0.4x0.13 WOM B From Leg 0.60 0.000 38.00 No Ice 0.97 0.55 46.54
0.00
0.00
RF 1.6x0.4x0.13 WOM C From Leg 0.60 0.000 38.00 No Ice 0.97 0.55 46.54
0.00
0.00
RRU 0.4x0.3x0.12 WOM A From Leg 0.00 0.000 38.00 No Ice 0.17 0.07 30.00
0.00
0.00
RRU 0.4x0.3x0.12 WOM B From Leg 0.00 0.000 38.00 No Ice 0.17 0.07 30.00
0.00
0.00
RRU 0.4x0.3x0.12 WOM C From Leg 0.00 0.000 38.00 No Ice 0.17 0.07 30.00
0.00
0.00
RF 2.68x0.3x0.08 CLARO A From Leg 0.60 0.000 42.00 No Ice 1.18 0.65 56.54
0.00
0.00
RF 2.68x0.3x0.08 CLARO B From Leg 0.60 0.000 42.00 No Ice 1.18 0.65 56.54
0.00
0.00
RF 2.68x0.3x0.08 CLARO C From Leg 0.60 0.000 42.00 No Ice 1.18 0.65 56.54
0.00
0.00
RRU 0.56x0.48x0.12 A From Leg 0.00 0.000 42.00 No Ice 0.38 0.09 30.00
CLARO 0.00
0.00
RRU 0.56x0.48x0.12 B From Leg 0.00 0.000 42.00 No Ice 0.38 0.09 30.00
CLARO 0.00
0.00
RRU 0.56x0.48x0.12 C From Leg 0.00 0.000 42.00 No Ice 0.38 0.09 30.00
CLARO 0.00
0.00

Dishes
Description Face Dish Offset Offsets: Azimuth 3 dB Elevation Outside Aperture Weight
or Type Type Horz Adjustment Beam Diameter Area
Leg Lateral Width
Vert
m ° ° m m m2 kg
MM.OO 0.6m B Paraboloid From 0.00 0.000 38.80 0.60 No Ice 0.28 30.00
w/Shroud (HP) Leg 0.00
0.00
MM.OO 1.2m B Paraboloid From 0.00 0.000 39.00 1.20 No Ice 1.13 80.00
w/Shroud (HP) Leg 0.00
0.00
MM.OO 1.2m A Paraboloid From 0.00 0.000 38.50 1.20 No Ice 1.13 80.00
w/Shroud (HP) Leg 0.00
0.00
Job
tnxTower Verificación Estructural
Page
8 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

MM.OO 0.6m B Paraboloid From 0.00 0.000 31.10 0.60 No Ice 0.28 30.00
w/Shroud (HP) Leg 0.00
0.00
MM.OO 0.9m A Paraboloid From 0.00 0.000 28.50 0.90 No Ice 0.64 50.00
w/Shroud (HP) Leg 0.00
0.00
MM.OO 0.6m B Paraboloid From 0.00 0.000 28.30 0.60 No Ice 0.28 30.00
w/Shroud (HP) Leg 0.00
0.00
MM.OO 0.6m A Paraboloid From 0.00 0.000 38.00 0.60 No Ice 0.28 30.00
w/Shroud (HP) Leg 0.00
0.00
MM.OO 0.9m A Paraboloid From 0.00 0.000 36.00 0.90 No Ice 0.64 50.00
w/Shroud (HP) Leg 0.00
0.00

Tower Pressures - No Ice


GH = 1.139

Section z KZ qz AG F AF AR Aleg Leg CAAA CAAA


Elevation a % In Out
c Face Face
m m kgsm m2 e m2 m2 m2 m2 m2
T1 42.00-36.00 39.00 1.473 104.0 11.186 A 0.755 1.372 1.372 64.50 5.957 0.000
6 B 0.755 1.372 64.50 0.000 0.000
C 0.755 1.372 64.50 0.000 0.000
T2 36.00-30.00 33.00 1.404 99.21 11.186 A 0.689 1.372 1.372 66.55 6.688 0.000
B 0.689 1.372 66.55 0.000 0.000
C 0.689 1.372 66.55 0.000 0.000
T3 30.00-24.00 27.00 1.326 93.69 11.510 A 0.837 2.020 2.020 70.70 6.688 0.000
B 0.837 2.020 70.70 0.000 0.000
C 0.837 2.020 70.70 0.000 0.000
T4 24.00-18.00 21.00 1.234 87.19 11.510 A 0.833 2.020 2.020 70.79 6.688 0.000
B 0.833 2.020 70.79 0.000 0.000
C 0.833 2.020 70.79 0.000 0.000
T5 18.00-12.00 15.00 1.121 79.20 13.161 A 0.940 2.022 2.022 68.27 6.688 0.000
B 0.940 2.022 68.27 0.000 0.000
C 0.940 2.022 68.27 0.000 0.000
T6 12.00-6.00 9.00 1 70.66 16.611 A 1.105 2.023 2.023 64.67 6.688 0.000
B 1.105 2.023 64.67 0.000 0.000
C 1.105 2.023 64.67 0.000 0.000
T7 6.00-0.00 3.00 1 70.66 20.211 A 1.287 2.023 2.023 61.11 4.347 0.000
B 1.287 2.023 61.11 0.000 0.000
C 1.287 2.023 61.11 0.000 0.000

Tower Pressure - Service


GH = 1.139

Section z KZ qz AG F AF AR Aleg Leg CAAA CAAA


Elevation a % In Out
Job
tnxTower Verificación Estructural
Page
9 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

c Face Face
m m kgsm m2 e m2 m2 m2 m2 m2
T1 42.00-36.00 39.00 1.473 46.63 11.186 A 0.755 1.372 1.372 64.50 5.957 0.000
B 0.755 1.372 64.50 0.000 0.000
C 0.755 1.372 64.50 0.000 0.000
T2 36.00-30.00 33.00 1.404 44.46 11.186 A 0.689 1.372 1.372 66.55 6.688 0.000
B 0.689 1.372 66.55 0.000 0.000
C 0.689 1.372 66.55 0.000 0.000
T3 30.00-24.00 27.00 1.326 41.98 11.510 A 0.837 2.020 2.020 70.70 6.688 0.000
B 0.837 2.020 70.70 0.000 0.000
C 0.837 2.020 70.70 0.000 0.000
T4 24.00-18.00 21.00 1.234 39.07 11.510 A 0.833 2.020 2.020 70.79 6.688 0.000
B 0.833 2.020 70.79 0.000 0.000
C 0.833 2.020 70.79 0.000 0.000
T5 18.00-12.00 15.00 1.121 35.49 13.161 A 0.940 2.022 2.022 68.27 6.688 0.000
B 0.940 2.022 68.27 0.000 0.000
C 0.940 2.022 68.27 0.000 0.000
T6 12.00-6.00 9.00 1 31.66 16.611 A 1.105 2.023 2.023 64.67 6.688 0.000
B 1.105 2.023 64.67 0.000 0.000
C 1.105 2.023 64.67 0.000 0.000
T7 6.00-0.00 3.00 1 31.66 20.211 A 1.287 2.023 2.023 61.11 4.347 0.000
B 1.287 2.023 61.11 0.000 0.000
C 1.287 2.023 61.11 0.000 0.000

Tower Forces - No Ice - Wind Normal To Face


Section Add Self F e CF RR DF DR AE F w Ctrl.
Elevation Weight Weight a Face
c
m kg kg e m2 kg kglm
T1 42.00- 181.50 433.84 A 0.19 2.629 0.588 1 1 1.562 1193.01 198.84 C
36.00 B 0.19 2.629 0.588 1 1 1.562
C 0.19 2.629 0.588 1 1 1.562
T2 36.00- 205.50 452.14 A 0.184 2.649 0.587 1 1 1.495 1203.57 200.60 C
30.00 B 0.184 2.649 0.587 1 1 1.495
C 0.184 2.649 0.587 1 1 1.495
T3 30.00- 205.50 675.41 A 0.248 2.443 0.601 1 1 2.051 1248.66 208.11 C
24.00 B 0.248 2.443 0.601 1 1 2.051
C 0.248 2.443 0.601 1 1 2.051
T4 24.00- 205.50 714.92 A 0.248 2.444 0.601 1 1 2.048 1161.44 193.57 C
18.00 B 0.248 2.444 0.601 1 1 2.048
C 0.248 2.444 0.601 1 1 2.048
T5 18.00- 205.50 953.86 A 0.225 2.514 0.596 1 1 2.145 1090.08 181.68 C
12.00 B 0.225 2.514 0.596 1 1 2.145
C 0.225 2.514 0.596 1 1 2.145
T6 12.00-6.00 205.50 1084.52 A 0.188 2.636 0.588 1 1 2.295 1025.11 170.85 C
B 0.188 2.636 0.588 1 1 2.295
C 0.188 2.636 0.588 1 1 2.295
T7 6.00-0.00 133.57 1132.14 A 0.164 2.721 0.584 1 1 2.468 890.57 148.43 C
B 0.164 2.721 0.584 1 1 2.468
C 0.164 2.721 0.584 1 1 2.468
Sum Weight: 1342.58 5446.84 OTM 172598.3 7812.45
kg-m
Job
tnxTower Verificación Estructural
Page
10 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Tower Forces - No Ice - Wind 60 To Face


Section Add Self F e CF RR DF DR AE F w Ctrl.
Elevation Weight Weight a Face
c
m kg kg e m2 kg kglm
T1 42.00- 181.50 433.84 A 0.19 2.629 0.588 0.8 1 1.411 1145.95 190.99 C
36.00 B 0.19 2.629 0.588 0.8 1 1.411
C 0.19 2.629 0.588 0.8 1 1.411
T2 36.00- 205.50 452.14 A 0.184 2.649 0.587 0.8 1 1.357 1162.29 193.71 C
30.00 B 0.184 2.649 0.587 0.8 1 1.357
C 0.184 2.649 0.587 0.8 1 1.357
T3 30.00- 205.50 675.41 A 0.248 2.443 0.601 0.8 1 1.884 1205.03 200.84 C
24.00 B 0.248 2.443 0.601 0.8 1 1.884
C 0.248 2.443 0.601 0.8 1 1.884
T4 24.00- 205.50 714.92 A 0.248 2.444 0.601 0.8 1 1.881 1120.98 186.83 C
18.00 B 0.248 2.444 0.601 0.8 1 1.881
C 0.248 2.444 0.601 0.8 1 1.881
T5 18.00- 205.50 953.86 A 0.225 2.514 0.596 0.8 1 1.957 1047.42 174.57 C
12.00 B 0.225 2.514 0.596 0.8 1 1.957
C 0.225 2.514 0.596 0.8 1 1.957
T6 12.00-6.00 205.50 1084.52 A 0.188 2.636 0.588 0.8 1 2.074 978.23 163.04 C
B 0.188 2.636 0.588 0.8 1 2.074
C 0.188 2.636 0.588 0.8 1 2.074
T7 6.00-0.00 133.57 1132.14 A 0.164 2.721 0.584 0.8 1 2.211 834.17 139.03 C
B 0.164 2.721 0.584 0.8 1 2.211
C 0.164 2.721 0.584 0.8 1 2.211
Sum Weight: 1342.58 5446.84 OTM 166141.9 7494.07
kg-m

Tower Forces - No Ice - Wind 90 To Face


Section Add Self F e CF RR DF DR AE F w Ctrl.
Elevation Weight Weight a Face
c
m kg kg e m2 kg kglm
T1 42.00- 181.50 433.84 A 0.19 2.629 0.588 0.85 1 1.449 1157.72 192.95 C
36.00 B 0.19 2.629 0.588 0.85 1 1.449
C 0.19 2.629 0.588 0.85 1 1.449
T2 36.00- 205.50 452.14 A 0.184 2.649 0.587 0.85 1 1.392 1172.61 195.43 C
30.00 B 0.184 2.649 0.587 0.85 1 1.392
C 0.184 2.649 0.587 0.85 1 1.392
T3 30.00- 205.50 675.41 A 0.248 2.443 0.601 0.85 1 1.926 1215.94 202.66 C
24.00 B 0.248 2.443 0.601 0.85 1 1.926
C 0.248 2.443 0.601 0.85 1 1.926
T4 24.00- 205.50 714.92 A 0.248 2.444 0.601 0.85 1 1.923 1131.09 188.52 C
18.00 B 0.248 2.444 0.601 0.85 1 1.923
C 0.248 2.444 0.601 0.85 1 1.923
T5 18.00- 205.50 953.86 A 0.225 2.514 0.596 0.85 1 2.004 1058.09 176.35 C
12.00 B 0.225 2.514 0.596 0.85 1 2.004
C 0.225 2.514 0.596 0.85 1 2.004
T6 12.00-6.00 205.50 1084.52 A 0.188 2.636 0.588 0.85 1 2.129 989.95 164.99 C
B 0.188 2.636 0.588 0.85 1 2.129
Job
tnxTower Verificación Estructural
Page
11 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

C 0.188 2.636 0.588 0.85 1 2.129


T7 6.00-0.00 133.57 1132.14 A 0.164 2.721 0.584 0.85 1 2.275 848.27 141.38 C
B 0.164 2.721 0.584 0.85 1 2.275
C 0.164 2.721 0.584 0.85 1 2.275
Sum Weight: 1342.58 5446.84 OTM 167756.0 7573.66
kg-m

Tower Forces - Service - Wind Normal To Face


Section Add Self F e CF RR DF DR AE F w Ctrl.
Elevation Weight Weight a Face
c
m kg kg e m2 kg kglm
T1 42.00- 181.50 433.84 A 0.19 2.629 0.588 1 1 1.562 534.62 89.10 C
36.00 B 0.19 2.629 0.588 1 1 1.562
C 0.19 2.629 0.588 1 1 1.562
T2 36.00- 205.50 452.14 A 0.184 2.649 0.587 1 1 1.495 539.35 89.89 C
30.00 B 0.184 2.649 0.587 1 1 1.495
C 0.184 2.649 0.587 1 1 1.495
T3 30.00- 205.50 675.41 A 0.248 2.443 0.601 1 1 2.051 559.56 93.26 C
24.00 B 0.248 2.443 0.601 1 1 2.051
C 0.248 2.443 0.601 1 1 2.051
T4 24.00- 205.50 714.92 A 0.248 2.444 0.601 1 1 2.048 520.47 86.74 C
18.00 B 0.248 2.444 0.601 1 1 2.048
C 0.248 2.444 0.601 1 1 2.048
T5 18.00- 205.50 953.86 A 0.225 2.514 0.596 1 1 2.145 488.49 81.42 C
12.00 B 0.225 2.514 0.596 1 1 2.145
C 0.225 2.514 0.596 1 1 2.145
T6 12.00-6.00 205.50 1084.52 A 0.188 2.636 0.588 1 1 2.295 459.38 76.56 C
B 0.188 2.636 0.588 1 1 2.295
C 0.188 2.636 0.588 1 1 2.295
T7 6.00-0.00 133.57 1132.14 A 0.164 2.721 0.584 1 1 2.468 399.09 66.51 C
B 0.164 2.721 0.584 1 1 2.468
C 0.164 2.721 0.584 1 1 2.468
Sum Weight: 1342.58 5446.84 OTM 77345.7 3500.95
kg-m

Tower Forces - Service - Wind 60 To Face


Section Add Self F e CF RR DF DR AE F w Ctrl.
Elevation Weight Weight a Face
c
m kg kg e m2 kg kglm
T1 42.00- 181.50 433.84 A 0.19 2.629 0.588 0.8 1 1.411 513.53 85.59 C
36.00 B 0.19 2.629 0.588 0.8 1 1.411
C 0.19 2.629 0.588 0.8 1 1.411
T2 36.00- 205.50 452.14 A 0.184 2.649 0.587 0.8 1 1.357 520.85 86.81 C
30.00 B 0.184 2.649 0.587 0.8 1 1.357
C 0.184 2.649 0.587 0.8 1 1.357
T3 30.00- 205.50 675.41 A 0.248 2.443 0.601 0.8 1 1.884 540.00 90.00 C
24.00 B 0.248 2.443 0.601 0.8 1 1.884
Job
tnxTower Verificación Estructural
Page
12 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

C 0.248 2.443 0.601 0.8 1 1.884


T4 24.00- 205.50 714.92 A 0.248 2.444 0.601 0.8 1 1.881 502.34 83.72 C
18.00 B 0.248 2.444 0.601 0.8 1 1.881
C 0.248 2.444 0.601 0.8 1 1.881
T5 18.00- 205.50 953.86 A 0.225 2.514 0.596 0.8 1 1.957 469.38 78.23 C
12.00 B 0.225 2.514 0.596 0.8 1 1.957
C 0.225 2.514 0.596 0.8 1 1.957
T6 12.00-6.00 205.50 1084.52 A 0.188 2.636 0.588 0.8 1 2.074 438.37 73.06 C
B 0.188 2.636 0.588 0.8 1 2.074
C 0.188 2.636 0.588 0.8 1 2.074
T7 6.00-0.00 133.57 1132.14 A 0.164 2.721 0.584 0.8 1 2.211 373.81 62.30 C
B 0.164 2.721 0.584 0.8 1 2.211
C 0.164 2.721 0.584 0.8 1 2.211
Sum Weight: 1342.58 5446.84 OTM 74452.3 3358.28
kg-m

Tower Forces - Service - Wind 90 To Face


Section Add Self F e CF RR DF DR AE F w Ctrl.
Elevation Weight Weight a Face
c
m kg kg e m2 kg kglm
T1 42.00- 181.50 433.84 A 0.19 2.629 0.588 0.85 1 1.449 518.80 86.47 C
36.00 B 0.19 2.629 0.588 0.85 1 1.449
C 0.19 2.629 0.588 0.85 1 1.449
T2 36.00- 205.50 452.14 A 0.184 2.649 0.587 0.85 1 1.392 525.47 87.58 C
30.00 B 0.184 2.649 0.587 0.85 1 1.392
C 0.184 2.649 0.587 0.85 1 1.392
T3 30.00- 205.50 675.41 A 0.248 2.443 0.601 0.85 1 1.926 544.89 90.82 C
24.00 B 0.248 2.443 0.601 0.85 1 1.926
C 0.248 2.443 0.601 0.85 1 1.926
T4 24.00- 205.50 714.92 A 0.248 2.444 0.601 0.85 1 1.923 506.87 84.48 C
18.00 B 0.248 2.444 0.601 0.85 1 1.923
C 0.248 2.444 0.601 0.85 1 1.923
T5 18.00- 205.50 953.86 A 0.225 2.514 0.596 0.85 1 2.004 474.16 79.03 C
12.00 B 0.225 2.514 0.596 0.85 1 2.004
C 0.225 2.514 0.596 0.85 1 2.004
T6 12.00-6.00 205.50 1084.52 A 0.188 2.636 0.588 0.85 1 2.129 443.62 73.94 C
B 0.188 2.636 0.588 0.85 1 2.129
C 0.188 2.636 0.588 0.85 1 2.129
T7 6.00-0.00 133.57 1132.14 A 0.164 2.721 0.584 0.85 1 2.275 380.13 63.36 C
B 0.164 2.721 0.584 0.85 1 2.275
C 0.164 2.721 0.584 0.85 1 2.275
Sum Weight: 1342.58 5446.84 OTM 75175.7 3393.95
kg-m

Force Totals
Load Vertical Sum of Sum of Sum of Sum of Sum of Torques
Case Forces Forces Forces Overturning Overturning
X Z Moments, Mx Moments, Mz
Job
tnxTower Verificación Estructural
Page
13 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

kg kg kg kg-m kg-m kg-m


Leg Weight 3897.79
Bracing Weight 1549.05
Total Member Self-Weight 5446.84 -50.5 -17.5
Total Weight 8257.51 -50.5 -17.5
Wind 0 deg - No Ice -121.18 -9754.31 -250990.2 4258.0 2.7
Wind 30 deg - No Ice 4726.56 -8231.39 -212889.5 -122467.8 34.6
Wind 60 deg - No Ice 8164.51 -4716.67 -122315.6 -212236.4 -64.0
Wind 90 deg - No Ice 9519.77 16.72 444.0 -247025.3 -147.0
Wind 120 deg - No Ice 8404.81 5017.73 130304.1 -216410.0 -50.6
Wind 150 deg - No Ice 4779.51 8319.10 215774.6 -124132.9 -29.4
Wind 180 deg - No Ice 66.77 9499.35 246679.6 -2308.2 -43.4
Wind 210 deg - No Ice -4701.43 8335.08 216502.5 121500.5 -51.4
Wind 240 deg - No Ice -8456.79 4907.81 126545.3 218415.7 47.9
Wind 270 deg - No Ice -9576.71 -101.94 -3594.7 249067.4 158.2
Wind 300 deg - No Ice -8199.58 -4814.02 -125615.7 213336.0 107.4
Wind 330 deg - No Ice -4804.90 -8281.01 -214554.4 125039.8 35.0
Total Weight 8257.51 -50.5 -17.5
Wind 0 deg - Service -54.30 -4371.15 -112502.9 1898.5 1.2
Wind 30 deg - Service 2118.09 -3688.69 -95429.0 -54890.6 15.5
Wind 60 deg - Service 3658.72 -2113.66 -54840.6 -95118.1 -28.7
Wind 90 deg - Service 4266.05 7.49 171.1 -110707.9 -65.9
Wind 120 deg - Service 3766.41 2248.57 58364.7 -96988.4 -22.7
Wind 150 deg - Service 2141.82 3728.00 96666.1 -55636.7 -13.2
Wind 180 deg - Service 29.92 4256.90 110515.4 -1044.0 -19.5
Wind 210 deg - Service -2106.83 3735.16 96992.3 54437.8 -23.0
Wind 240 deg - Service -3789.70 2199.31 56680.3 97867.9 21.5
Wind 270 deg - Service -4291.57 -45.68 -1638.7 111603.7 70.9
Wind 300 deg - Service -3674.44 -2157.28 -56319.4 95591.5 48.1
Wind 330 deg - Service -2153.20 -3710.93 -96175.1 56023.8 15.7

Load Combinations
Comb. Description
No.
1 Dead Only
2 Dead+Wind 0 deg - No Ice
3 Dead+Wind 30 deg - No Ice
4 Dead+Wind 60 deg - No Ice
5 Dead+Wind 90 deg - No Ice
6 Dead+Wind 120 deg - No Ice
7 Dead+Wind 150 deg - No Ice
8 Dead+Wind 180 deg - No Ice
9 Dead+Wind 210 deg - No Ice
10 Dead+Wind 240 deg - No Ice
11 Dead+Wind 270 deg - No Ice
12 Dead+Wind 300 deg - No Ice
13 Dead+Wind 330 deg - No Ice
14 Dead+Wind 0 deg - Service
15 Dead+Wind 30 deg - Service
16 Dead+Wind 60 deg - Service
17 Dead+Wind 90 deg - Service
18 Dead+Wind 120 deg - Service
19 Dead+Wind 150 deg - Service
20 Dead+Wind 180 deg - Service
Job
tnxTower Verificación Estructural
Page
14 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

21 Dead+Wind 210 deg - Service


22 Dead+Wind 240 deg - Service
23 Dead+Wind 270 deg - Service
24 Dead+Wind 300 deg - Service
25 Dead+Wind 330 deg - Service

Maximum Member Forces


Section Elevation Component Condition Gov. Force Major Axis Minor Axis
No. m Type Load Moment Moment
Comb. kg kg-m kg-m
T1 42 - 36 Leg Max Tension 12 6643.95 22.3 17.9
Max. Compression 10 -8012.15 19.3 -9.0
Max. Mx 11 -527.23 32.8 -0.2
Max. My 8 -2760.28 1.3 31.9
Max. Vy 5 -441.16 0.0 0.0
Max. Vx 2 424.66 0.0 0.0
Diagonal Max Tension 7 1248.42 0.0 0.0
Max. Compression 13 -1247.33 0.0 0.0
Max. Mx 10 1075.19 0.7 -0.0
Max. My 9 588.12 0.3 -0.1
Max. Vy 10 -1.62 0.7 -0.0
Max. Vx 9 -0.07 0.0 0.0
Top Girt Max Tension 10 218.62 0.0 0.0
Max. Compression 4 -217.36 0.0 0.0
Max. Mx 1 0.33 -0.9 0.0
Max. Vy 1 2.09 0.0 0.0
T2 36 - 30 Leg Max Tension 12 20084.78 27.1 15.5
Max. Compression 10 -22026.99 45.0 -24.8
Max. Mx 11 -19006.96 51.4 0.9
Max. My 2 -21529.51 2.2 50.4
Max. Vy 5 -61.52 -19.6 0.2
Max. Vx 8 -60.67 0.4 -18.8
Diagonal Max Tension 7 1783.35 0.0 0.0
Max. Compression 7 -1794.91 0.0 0.0
Max. Mx 10 1498.26 1.7 -0.0
Max. My 12 -1454.64 -0.6 -0.1
Max. Vy 10 -2.79 1.7 -0.0
Max. Vx 12 0.08 0.0 0.0
T3 30 - 24 Leg Max Tension 12 38343.65 100.5 58.6
Max. Compression 10 -41159.24 148.9 -86.2
Max. Mx 11 -35291.34 168.8 -0.7
Max. My 2 -40597.34 3.4 170.0
Max. Vy 11 -69.56 168.6 6.3
Max. Vx 2 -72.48 3.4 170.0
Diagonal Max Tension 7 2348.71 0.0 0.0
Max. Compression 7 -2352.22 0.0 0.0
Max. Mx 10 1995.16 2.7 0.0
Max. My 11 -1842.88 -0.8 -0.1
Max. Vy 10 -3.66 2.7 0.0
Max. Vx 11 0.13 0.0 0.0
T4 24 - 18 Leg Max Tension 12 61068.58 104.3 63.0
Max. Compression 10 -64814.03 371.0 -214.7
Max. Mx 10 -64814.03 371.0 -214.7
Max. My 2 -64164.26 2.9 424.3
Max. Vy 6 215.02 -369.4 -217.1
Job
tnxTower Verificación Estructural
Page
15 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Max. Vx 2 -245.28 2.9 424.3


Diagonal Max Tension 7 2809.78 0.0 0.0
Max. Compression 7 -2863.41 0.0 0.0
Max. Mx 6 2107.15 5.4 0.5
Max. My 11 2728.53 4.4 -0.7
Max. Vy 6 -6.28 5.4 0.5
Max. Vx 11 0.59 0.0 0.0
T5 18 - 12 Leg Max Tension 12 69225.74 -200.2 -1.3
Max. Compression 6 -73989.87 211.6 4.1
Max. Mx 10 -69140.43 428.6 -0.5
Max. My 11 -2851.96 -5.4 -305.0
Max. Vy 10 196.37 428.6 -0.5
Max. Vx 7 121.52 -7.1 -303.7
Diagonal Max Tension 12 983.49 0.0 0.0
Max. Compression 6 -1045.58 0.0 0.0
Max. Mx 12 876.48 5.5 0.5
Max. My 13 -839.30 -3.6 -0.9
Max. Vy 6 -5.73 5.4 0.3
Max. Vx 13 0.78 0.0 0.0
T6 12 - 6 Leg Max Tension 12 73743.19 -164.2 -1.3
Max. Compression 6 -79614.75 142.7 3.1
Max. Mx 6 -75863.49 211.6 4.1
Max. My 11 -3109.28 3.0 -184.3
Max. Vy 8 -63.34 -206.9 2.3
Max. Vx 7 -53.49 -2.2 -183.3
Diagonal Max Tension 7 827.71 0.0 0.0
Max. Compression 7 -834.84 0.0 0.0
Max. Mx 6 541.40 6.3 0.1
Max. My 12 -589.94 -1.4 -0.4
Max. Vy 6 -7.32 6.3 0.1
Max. Vx 12 0.35 0.0 0.0
T7 6-0 Leg Max Tension 12 78068.61 -139.0 -2.2
Max. Compression 6 -85006.16 0.0 -0.0
Max. Mx 6 -83326.99 163.1 1.5
Max. My 11 -3781.68 -5.1 -262.0
Max. Vy 12 -100.13 -139.0 -2.2
Max. Vx 11 -159.84 -5.1 -262.0
Diagonal Max Tension 12 1107.65 0.0 0.0
Max. Compression 10 -1188.50 0.0 0.0
Max. Mx 6 707.41 6.0 0.7
Max. My 11 988.12 5.0 -0.8
Max. Vy 6 -7.55 6.0 0.7
Max. Vx 11 0.58 0.0 0.0

Maximum Reactions
Location Condition Gov. Vertical Horizontal, X Horizontal, Z
Load kg kg kg
Comb.
Leg C Max. Vert 10 86031.56 5755.12 -3333.30
Max. Hx 10 86031.56 5755.12 -3333.30
Max. Hz 4 -78063.34 -5205.70 3019.51
Min. Vert 4 -78063.34 -5205.70 3019.51
Min. Hx 4 -78063.34 -5205.70 3019.51
Min. Hz 10 86031.56 5755.12 -3333.30
Job
tnxTower Verificación Estructural
Page
16 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Leg B Max. Vert 6 86078.54 -5763.04 -3331.30


Max. Hx 12 -78921.86 5251.86 3050.79
Max. Hz 12 -78921.86 5251.86 3050.79
Min. Vert 12 -78921.86 5251.86 3050.79
Min. Hx 6 86078.54 -5763.04 -3331.30
Min. Hz 6 86078.54 -5763.04 -3331.30
Leg A Max. Vert 2 85557.81 -5.69 6630.15
Max. Hx 11 3938.43 87.06 279.48
Max. Hz 2 85557.81 -5.69 6630.15
Min. Vert 8 -78630.67 -4.01 -6063.82
Min. Hx 5 2606.02 -88.36 195.17
Min. Hz 8 -78630.67 -4.01 -6063.82

Tower Mast Reaction Summary


Load Vertical Shearx Shearz Overturning Overturning Torque
Combination Moment, Mx Moment, Mz
kg kg kg kg-m kg-m kg-m
Dead Only 8257.51 0.00 -0.00 -50.5 -17.5 0.0
Dead+Wind 0 deg - No Ice 8257.51 -121.18 -9754.32 -250990.2 4258.0 2.7
Dead+Wind 30 deg - No Ice 8257.51 4726.56 -8231.40 -212889.6 -122467.9 34.6
Dead+Wind 60 deg - No Ice 8257.51 8164.51 -4716.67 -122315.7 -212236.5 -64.0
Dead+Wind 90 deg - No Ice 8257.51 9519.78 16.72 444.0 -247025.4 -147.0
Dead+Wind 120 deg - No Ice 8257.51 8404.81 5017.73 130304.1 -216410.0 -50.6
Dead+Wind 150 deg - No Ice 8257.51 4779.51 8319.10 215774.6 -124132.9 -29.4
Dead+Wind 180 deg - No Ice 8257.51 66.77 9499.35 246679.6 -2308.2 -43.4
Dead+Wind 210 deg - No Ice 8257.51 -4701.43 8335.08 216502.6 121500.5 -51.4
Dead+Wind 240 deg - No Ice 8257.51 -8456.79 4907.81 126545.4 218415.7 47.9
Dead+Wind 270 deg - No Ice 8257.51 -9576.72 -101.94 -3594.7 249067.5 158.2
Dead+Wind 300 deg - No Ice 8257.51 -8199.58 -4814.02 -125615.7 213336.0 107.4
Dead+Wind 330 deg - No Ice 8257.51 -4804.90 -8281.01 -214554.4 125039.9 35.0
Dead+Wind 0 deg - Service 8257.51 -54.30 -4371.15 -112502.9 1898.5 1.2
Dead+Wind 30 deg - Service 8257.51 2118.09 -3688.70 -95429.0 -54890.6 15.5
Dead+Wind 60 deg - Service 8257.51 3658.72 -2113.66 -54840.6 -95118.1 -28.7
Dead+Wind 90 deg - Service 8257.51 4266.05 7.49 171.1 -110708.0 -65.9
Dead+Wind 120 deg - Service 8257.51 3766.41 2248.57 58364.7 -96988.4 -22.7
Dead+Wind 150 deg - Service 8257.51 2141.82 3728.00 96666.2 -55636.7 -13.2
Dead+Wind 180 deg - Service 8257.51 29.92 4256.90 110515.5 -1044.0 -19.5
Dead+Wind 210 deg - Service 8257.51 -2106.83 3735.16 96992.4 54437.8 -23.0
Dead+Wind 240 deg - Service 8257.51 -3789.70 2199.31 56680.3 97867.9 21.5
Dead+Wind 270 deg - Service 8257.51 -4291.57 -45.68 -1638.7 111603.7 70.9
Dead+Wind 300 deg - Service 8257.51 -3674.44 -2157.28 -56319.4 95591.6 48.1
Dead+Wind 330 deg - Service 8257.51 -2153.20 -3710.93 -96175.1 56023.8 15.7

Solution Summary
Sum of Applied Forces Sum of Reactions
Load PX PY PZ PX PY PZ % Error
Comb. kg kg kg kg kg kg
1 0.00 -8257.51 0.00 -0.00 8257.51 0.00 0.000%
2 -121.18 -8257.51 -9754.31 121.18 8257.51 9754.32 0.000%
3 4726.56 -8257.51 -8231.39 -4726.56 8257.51 8231.40 0.000%
Job
tnxTower Verificación Estructural
Page
17 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

4 8164.51 -8257.51 -4716.67 -8164.51 8257.51 4716.67 0.000%


5 9519.77 -8257.51 16.72 -9519.78 8257.51 -16.72 0.000%
6 8404.81 -8257.51 5017.73 -8404.81 8257.51 -5017.73 0.000%
7 4779.51 -8257.51 8319.10 -4779.51 8257.51 -8319.10 0.000%
8 66.77 -8257.51 9499.35 -66.77 8257.51 -9499.35 0.000%
9 -4701.43 -8257.51 8335.08 4701.43 8257.51 -8335.08 0.000%
10 -8456.79 -8257.51 4907.81 8456.79 8257.51 -4907.81 0.000%
11 -9576.71 -8257.51 -101.94 9576.72 8257.51 101.94 0.000%
12 -8199.58 -8257.51 -4814.02 8199.58 8257.51 4814.02 0.000%
13 -4804.90 -8257.51 -8281.01 4804.90 8257.51 8281.01 0.000%
14 -54.30 -8257.51 -4371.15 54.30 8257.51 4371.15 0.000%
15 2118.09 -8257.51 -3688.69 -2118.09 8257.51 3688.70 0.000%
16 3658.72 -8257.51 -2113.66 -3658.72 8257.51 2113.66 0.000%
17 4266.05 -8257.51 7.49 -4266.05 8257.51 -7.49 0.000%
18 3766.41 -8257.51 2248.57 -3766.41 8257.51 -2248.57 0.000%
19 2141.82 -8257.51 3728.00 -2141.82 8257.51 -3728.00 0.000%
20 29.92 -8257.51 4256.90 -29.92 8257.51 -4256.90 0.000%
21 -2106.83 -8257.51 3735.16 2106.83 8257.51 -3735.16 0.000%
22 -3789.70 -8257.51 2199.31 3789.70 8257.51 -2199.31 0.000%
23 -4291.57 -8257.51 -45.68 4291.57 8257.51 45.68 0.000%
24 -3674.44 -8257.51 -2157.28 3674.44 8257.51 2157.28 0.000%
25 -2153.20 -8257.51 -3710.93 2153.20 8257.51 3710.93 0.000%

Maximum Tower Deflections - Service Wind


Section Elevation Horz. Gov. Tilt Twist
No. Deflection Load
m mm Comb. ° °
T1 42 - 36 190.75 22 0.453 0.019
T2 36 - 30 143.13 18 0.438 0.019
T3 30 - 24 98.70 18 0.382 0.015
T4 24 - 18 60.31 18 0.317 0.010
T5 18 - 12 31.04 18 0.207 0.006
T6 12 - 6 13.21 18 0.127 0.002
T7 6-0 3.33 18 0.059 0.001

Critical Deflections and Radius of Curvature - Service Wind


Elevation Appurtenance Gov. Deflection Tilt Twist Radius of
Load Curvature
m Comb. mm ° ° m
42.00 RF 1.94x0.27x0.13 22 190.75 0.453 0.019 22266
39.00 MM.OO 1.2m 22 166.73 0.449 0.019 22266
38.80 MM.OO 0.6m 22 165.14 0.449 0.019 20875
38.50 MM.OO 1.2m 22 162.76 0.448 0.019 19087
38.00 MM.OO 0.6m 22 158.80 0.447 0.019 16708
36.00 MM.OO 0.9m 18 143.13 0.438 0.019 11230
31.10 MM.OO 0.6m 18 106.48 0.393 0.016 6435
28.50 MM.OO 0.9m 18 88.43 0.368 0.014 5298
28.30 MM.OO 0.6m 18 87.09 0.366 0.013 5228
Job
tnxTower Verificación Estructural
Page
18 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Maximum Tower Deflections - Design Wind


Section Elevation Horz. Gov. Tilt Twist
No. Deflection Load
m mm Comb. ° °
T1 42 - 36 425.79 10 1.010 0.043
T2 36 - 30 319.49 10 0.977 0.042
T3 30 - 24 220.28 6 0.853 0.033
T4 24 - 18 134.60 6 0.707 0.022
T5 18 - 12 69.26 6 0.462 0.013
T6 12 - 6 29.48 6 0.283 0.005
T7 6-0 7.42 6 0.131 0.002

Critical Deflections and Radius of Curvature - Design Wind


Elevation Appurtenance Gov. Deflection Tilt Twist Radius of
Load Curvature
m Comb. mm ° ° m
42.00 RF 1.94x0.27x0.13 10 425.79 1.010 0.043 10047
39.00 MM.OO 1.2m 10 372.20 1.003 0.043 10047
38.80 MM.OO 0.6m 10 368.65 1.002 0.043 9419
38.50 MM.OO 1.2m 10 363.33 1.000 0.043 8612
38.00 MM.OO 0.6m 10 354.49 0.997 0.043 7538
36.00 MM.OO 0.9m 10 319.49 0.977 0.042 5062
31.10 MM.OO 0.6m 6 237.64 0.878 0.035 2887
28.50 MM.OO 0.9m 6 197.35 0.821 0.030 2373
28.30 MM.OO 0.6m 6 194.36 0.817 0.030 2342

Compression Checks

Leg Design Data (Compression)


Section Elevation Size L Lu Kl/r Fa A Actual Allow. Ratio
No. P Pa P
m m m MPa mm2 kg kg Pa
T1 42 - 36 O 4''x6.02 6.00 1.50 39.1 126.4 2048 -8012.17 26403.03 0.303
K=1.00
T2 36 - 30 O 4''x6.02 6.00 1.50 39.1 126.4 2048 -22027.00 26403.03 0.834
K=1.00
T3 30 - 24 O 6''x7.11 6.00 1.50 26.3 132.3 3600 -41159.26 48588.37 0.847
K=1.00
T4 24 - 18 O 6''x7.11 6.00 1.50 26.3 132.3 3600 -64813.83 48588.37 1.334
K=1.00
H1-3 (1.33 CR) - 85
Job
tnxTower Verificación Estructural
Page
19 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

T5 18 - 12 O 6''x10.97 6.01 2.00 35.9 128.0 5422 -73990.01 70771.77 1.045


K=1.00
T6 12 - 6 O 6''x10.97 6.01 2.00 35.9 128.0 5422 -79614.56 70769.05 1.125
K=1.00
T7 6-0 O 6''x10.97 6.01 2.00 35.9 128.0 5422 -85005.96 70769.05 1.201
K=1.00

Diagonal Design Data (Compression)


Section Elevation Size L Lu Kl/r Fa A Actual Allow. Ratio
No. P Pa P
m m m MPa mm2 kg kg Pa
T1 42 - 36 L40x40x4 2.30 1.08 137.0 54.9 304 -1247.33 1700.84 0.733
K=1.00
T2 36 - 30 L40x40x5 2.30 1.08 137.7 54.3 375 -1794.91 2076.46 0.864
K=1.00
T3 30 - 24 L50x50x4 2.30 1.04 105.4 82.6 384 -2352.22 3236.27 0.727
K=1.00
T4 24 - 18 L50x50x5 2.30 1.04 106.0 82.2 475 -2863.41 3980.44 0.719
K=1.00
T5 18 - 12 L60x60x4 2.72 1.31 110.3 78.6 464 -1045.59 3717.02 0.281
K=1.00
T6 12 - 6 L60x60x6 3.44 1.68 142.3 50.8 684 -834.84 3545.08 0.235
K=1.00
T7 6-0 L60x60x6 3.95 1.93 163.9 38.3 684 -1188.50 2674.10 0.444
K=1.00

Top Girt Design Data (Compression)


Section Elevation Size L Lu Kl/r Fa A Actual Allow. Ratio
No. P Pa P
m m m MPa mm2 kg kg Pa
T1 42 - 36 L40x40x4 1.75 1.64 208.0 23.8 304 -217.36 737.61 0.295
K=1.00
KL/R > 200 (C) - 5

Tension Checks

Leg Design Data (Tension)


Section Elevation Size L Lu Kl/r Fa A Actual Allow. Ratio
No. P Pa P
Job
tnxTower Verificación Estructural
Page
20 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

m m m MPa mm2 kg kg Pa
T1 42 - 36 O 4''x6.02 6.00 1.50 39.1 141.2 2048 6643.95 29488.87 0.225

T2 36 - 30 O 4''x6.02 6.00 1.50 39.1 141.2 2048 20084.76 29488.87 0.681

T3 30 - 24 O 6''x7.11 6.00 1.50 26.3 141.2 3600 38343.67 51846.53 0.740

T4 24 - 18 O 6''x7.11 6.00 1.50 26.3 141.2 3600 61068.52 51846.53 1.178

H1-3 (1.33 CR) - 86


T5 18 - 12 O 6''x10.97 6.01 2.00 35.9 141.2 5422 69225.93 78078.69 0.887

T6 12 - 6 O 6''x10.97 6.01 2.00 35.9 141.2 5422 73743.25 78078.69 0.944

T7 6-0 O 6''x10.97 6.01 2.00 35.9 141.2 5422 78068.71 78078.69 1.000

Diagonal Design Data (Tension)


Section Elevation Size L Lu Kl/r Fa A Actual Allow. Ratio
No. P Pa P
m m m MPa mm2 kg kg Pa
T1 42 - 36 L40x40x4 2.30 1.08 87.5 181.4 228 1248.42 4218.00 0.296

T2 36 - 30 L40x40x5 2.30 1.08 88.5 181.4 281 1783.35 5203.11 0.343

T3 30 - 24 L50x50x4 2.30 1.04 67.1 181.4 288 2348.71 5327.99 0.441

T4 24 - 18 L50x50x5 2.30 1.04 67.7 181.4 356 2809.78 6590.61 0.426

T5 18 - 12 L60x60x4 2.72 1.31 70.1 181.4 348 983.49 6438.02 0.153

T6 12 - 6 L60x60x6 3.44 1.68 90.9 181.4 513 827.72 9490.52 0.087

T7 6-0 L60x60x6 3.95 1.93 104.7 181.4 513 1107.65 9490.52 0.117

Top Girt Design Data (Tension)


Section Elevation Size L Lu Kl/r Fa A Actual Allow. Ratio
No. P Pa P
m m m MPa mm2 kg kg Pa
T1 42 - 36 L40x40x4 1.75 1.64 132.9 181.4 228 218.62 4218.00 0.052
Job
tnxTower Verificación Estructural
Page
21 of 22
Project Date
MIC SpA
Talavera de la Reina 963
AB 1083 Trapen 13:51:47 02/02/18

Santiago Client Designed by


Phone: 222112349 WOM Julio-Saldias B
FAX:

Section Capacity Table


Section Elevation Component Size Critical P SF*Pallow % Pass
No. m Type Element kg kg Capacity Fail
T1 42 - 36 Leg O 4''x6.02 1 -8012.17 35195.24 22.8 Pass
T2 36 - 30 Leg O 4''x6.02 31 -22027.00 35195.24 62.6 Pass
T3 30 - 24 Leg O 6''x7.11 58 -41159.26 64768.30 63.5 Pass
T4 24 - 18 Leg O 6''x7.11 85 -64813.83 64768.30 100.1 Fail
T5 18 - 12 Leg O 6''x10.97 113 -73990.01 94338.76 78.4 Pass
T6 12 - 6 Leg O 6''x10.97 134 -79614.56 94335.14 84.4 Pass
T7 6-0 Leg O 6''x10.97 155 -85005.96 94335.14 90.1 Pass
T1 42 - 36 Diagonal L40x40x4 10 -1247.33 2267.21 55.0 Pass
T2 36 - 30 Diagonal L40x40x5 36 -1794.91 2767.92 64.8 Pass
T3 30 - 24 Diagonal L50x50x4 63 -2352.22 4313.95 54.5 Pass
T4 24 - 18 Diagonal L50x50x5 90 -2863.41 5305.93 54.0 Pass
T5 18 - 12 Diagonal L60x60x4 129 -1045.59 4954.79 21.1 Pass
T6 12 - 6 Diagonal L60x60x6 138 -834.84 4725.60 17.7 Pass
T7 6-0 Diagonal L60x60x6 162 -1188.50 3564.58 33.3 Pass
T1 42 - 36 Top Girt L40x40x4 5 -217.36 983.23 22.1 Pass
Summary
Leg (T4) 100.1 Fail
Diagonal 64.8 Pass
(T2)
Top Girt 22.1 Pass
(T1)
RATING = 100.1 Fail