Anda di halaman 1dari 9

www.ietdl.

org
Published in IET Generation, Transmission & Distribution
Received on 7th October 2012
Revised on 11th February 2013
Accepted on 10th March 2013
doi: 10.1049/iet-gtd.2012.0579

ISSN 1751-8687

Enhancement of voltage stability margin in radial


distribution system with squirrel cage induction
generator based distributed generators
Pitchaimuthu Raja, Manickavasagam Parvathy Selvan, Natarajan Kumaresan
Electrical and Electronics Engineering, National Institute of Technology, Tiruchirappalli 620015, India
E-mail: selvanmp@nitt.edu; selvanmp@gmail.com

Abstract: This study investigates the effect of voltage profile and steady-state voltage stability margin when a wind-driven
squirrel cage induction generator (SCIG)-based distributed generator (DG) is integrated with radial distribution system (RDS).
The study has been carried out considering different configurations of SCIG. The node at which a DG has to be installed is
identified based on voltage collapse index (VCI), which is a measure of steady-state voltage stability margin. The
computational procedure for studying the voltage profile of RDS without and with DG has been developed. The developed
algorithm has been tested on the 33-bus RDS with 1 MW SCIG integrated at the identified node and results are furnished.
Finally, a configuration of SCIG having star and delta switching arrangements with permanently connected capacitor across
each phase winding of the stator is found to be superior in providing improved system performance over a wide range of
wind velocity. A switching criterion for this type of DG is proposed based on VCI for the improved performance of RDS.

1 Introduction technique using the genetic algorithm [4, 12] and [13].
Clustering method based on voltage or loss sensitivity
It is known that a distributed generator (DG) unit with index is used in [14] to address multiple DG placement
adequate generation capacity can be directly connected to a problems. In all the above investigations, number of nodes
bulk consumer or integrated to the distribution grid of the for integration of DG units are either assumed or preset to
utility at an appropriate location. Such integration of DG in compute their ratings using enumerative techniques or
the radial distribution system (RDS) provides benefits like optimisation methods. In order to overcome this, different
reduction in transmission and distribution loss, methods such as iterative genetic algorithm [15], fuzzy
improvement in voltage profile, power quality and system embedded genetic algorithm [16] and goal programming
reliability to both electricity consumers and utilities [1–3]. approach [17] have been proposed.
On the other hand, DG units may introduce few problems Moreover, DG placement for enhancement of voltage
to the existing protection systems because of their short stability of the nodes in a distribution system is attempted
circuit current contributions [4]. Hence, identification of in [18] using continuation power flow (CPF) method. In
appropriate locations for grid integration of DG units and case of RDS, the power flow Jacobian is usually
determination of their ratings are vital optimisation ill-conditioned. This is because of high R/X ratio of
problems for the distribution system planners. Several distribution system lines and lack of diagonal dominance of
researchers proposed different methodologies for solving the system Jacobian. In view of this, use of the Newton
this problem. Rau and Wan [5] has proposed the Lagrange Raphson method and its extension to form a continuation
function-based approach and meta-heuristics optimisation method may become numerically unstable. By exploiting
methods have been proposed in [4, 6–14]. In [7], the the radial nature of distribution systems, an equivalent
location of DG units and reactive power sources is method based on voltage collapse index (VCI) is proposed
determined based on clustering method and ratings of DG in [19] for identification of nodes that are susceptible to
units are computed using Tabu search algorithm for voltage collapse and requiring DG integration, which is fast
different load levels. Genetic Algorithm has been employed and computationally less intensive. In this work, a simple
in [8–12] for siting and sizing of DG units. The analysis is approach of forward and backward sweep algorithms [20] is
carried out in [8] with only single DG unit of fixed size. used. The voltage collapse margin of the nodes can be
However, placement of multiple DG units is practically substantially improved with local generation support, and
preferred by considering the technical and economical hence a node with low-voltage collapse margin can be
benefits. Multiple DG placement problems have been selected for DG placement.
solved using pareto-optimal set of solutions obtained either Since, wind turbine generator system (WTGS) is the most
by employing non-dominated sorting or ε-constrained popular DG technology in India and most part of the world,

898 IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906
& The Institution of Engineering and Technology 2013 doi: 10.1049/iet-gtd.2012.0579
www.ietdl.org
this paper investigates on the enhancement of voltage collapse integration point in the RDS. The placement of proposed
margin when a WTGS is connected as DG at the bus with low DG type at the suitable bus is discussed in Section
or minimum VCI as suggested in [19]. Various techniques by 3. Section 4 presents various case studies to validate the
which further improvement in VCI would be obtained with effectiveness of the proposed methodology using 33-bus
respect to induction generator operation are also explored in RDS. Section 5 provides the inference and conclusion
this paper. It is well known that the power output of arrived at from the present study on the determination of
squirrel cage induction generator (SCIG) not only depends grid integration point and modified operation of SCIG for
on the slip but also on the voltage of the node at which it is enhancement of voltage stability margin under varying
connected [21]. Moreover, it requires sufficient amount of wind velocity.
reactive power support from the grid. Kumaresan and
Subbiah [22, 23] have proposed a delta–star switching of
stator winding of the induction generator to decrease the 2 Voltage collapse index
reactive power drawn from grid, which in turn improves the
node voltage at which DG is installed. However, such Voltage stability concerns about acceptable voltage levels all
delta–star winding SCIG is not popular as it requires special over the system buses. Voltage instability has been classified
winding design and specific number of stator and rotor slots. into steady state and transient voltage instability according to
As a continuation to the technique proposed in [22, 23], the time spectrum of occurrence of the phenomena. A power
Raja et al., have investigated the possibility of improvement system is said to have entered a state of voltage instability
in the performance of SCIG with star and delta switching when a disturbance causes a progressive and uncontrollable
strategies by adding a permanent capacitor across each decline in voltage [25, 26]. Voltage stability analysis often
phase of three phase stator winding [24] as shown in Fig. 1. requires examination of lot of system states and
Whenever the machine’s stator winding is switched from contingency scenarios. For this reason, an approach based
delta to star or vice versa, the connected capacitors are also on steady-state analysis is more feasible and it can also
switched along with the stator winding. The capacitors have provide global insight of the reactive power problems [26].
been selected to maintain the power factor at the stator The voltage stability phenomenon has been well recognised
terminal close to unity. This mode of operation provides in distribution systems. A RDS with high resistance to
better performance than that of [23] in terms of reactive reactance ratio experiences high power loss and voltage
power consumption for the same rating of machine, and drop, and hence it may suffer from such voltage collapse.
thus improves the node voltage at the point of connection. DG placement for enhancement of voltage stability of the
In the present work, SCIG with stator winding configuration nodes in distribution system was attempted in the past [18].
proposed in [24] is considered as a DG to be connected at the When the penetration of DG is high, the generated power of
identified bus for the enhancement of voltage collapse margin DG units not only alters power flow in distribution system,
of the system. The variation in VCI value at the DG installed but also in transmission system. As a consequence, the
bus is observed with respect to change in wind velocity as connection of DG to the grid may influence the stability of
well as stator winding configuration. Consequently, a power system, that is angle, frequency and voltage stability
criterion for delta and star switching in the point of view of [27–31]. CPF method was utilised in [18] to identify the
improving the performance of the system is arrived at in grid integration point requiring placement of DG units. In
addition to the condition proposed in [24]. this method, each iteration of DG placement requires
This paper is organised as follows: the VCI described in execution of CPF program at all nodes, which is
Section 2, has been employed for identification of DG computationally intensive for a practical system with large
number of nodes. In this regard, to reduce the
computational burden, a VCI method was suggested in [19]
for identification of nodes that are susceptible to voltage
collapse and requiring DG integration. The computation of
VCI is discussed below.
Fig. 2 shows a typical 15-bus RDS, whose electrical
equivalent circuit is shown in Fig. 3.
From Fig. 3

Vn1 − Vn2
Ib = (1)
Rb + jXb

Fig. 1 Wind-driven SCIG using star–delta switching with


permanently connected capacitor
A1, A2, B1, B2, C1 and C2 are the stator phase winding terminals and S1–S5 are
anti-parallel thyristor units. Fig. 2 Typical RDS

IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906 899
doi: 10.1049/iet-gtd.2012.0579 & The Institution of Engineering and Technology 2013
www.ietdl.org
loading conditions of the two-bus equivalent of a test
system are shown in Fig. 4. It can be understood from the
PV curve that at any loading point, two values exist for
|Vn2|, out of which one value corresponds to stable operating
point and other corresponds to an unstable operating point
[18]. However, at one loading point, the solutions of (6)
become equal and that point is called as nose point of the
PV curve. Further, it can be observed from Fig. 4 that the
Fig. 3 Two bus equivalent of Fig. 2 nose point of the PV curve is the loading point at which
VCI = 0. Thus, the VCI computed from load flow results
gives equivalent information that of the CPF method with
∗ less computation and can be utilised for identification of
Pn2 − jQn2 = Vn2 Ib (2)
nodes requiring DG integration.
From (1) and (2)
3 Placement of DG based on VCI

 
Vn2 Vn1 − Vn2
= Pn2 − jQn2 (3) As the VCI is an indicative measure of proximity to voltage
Rb + jXb collapse point, it can be used to identify the node that needs
DG integration. At any steady-state operating point, VCI for
or all nodes in RDS can be evaluated from the results of load
 2   flow analysis. A node with minimum value of VCI can be

Vn1 Vn2 − Vn2  = Pn2 Rb + Qn2 Xb chosen as the candidate location for DG integration. In this
  method, as VCI is calculated from the results of load flow
+ j Pn2 Xb − Rb Qn2 (4)
analysis of RDS, the execution of CPF can be avoided.
Equating the real parts in (4) and rearranging, a quadratic
equation in |Vn2| is obtained 3.1 Modelling of DG
 2      Based on the basic principle of operation and integration with
V  −V  cos d − d V 
n2
 n1 n1
 n2 n2 grid, wind-driven induction generator based DGs are
+ Pn2 Rb + Qn2 Xb = 0 (5) categorised in [15, 16] as Type-I DGs, Type-II DGs and
Type-III DGs, as described below
The solution of the quadratic (5) is (see (6))
For a feasible solution to exist for Vn2  Type-I DGs: these are DGs that supply real power to the
network depending on the availability or demand.
 2 2    
V  cos d − d − 4 P R + Q X ≥ 0 (7) Type-II DGs: these are DGs that supply real power to the
n1 n1 n2 n2 b n2 b
network only when adequate reactive power support is
provided by the network.
Equation (7) is a condition that determines the voltage
Type-III DGs: these are Type-II DGs that are compensated
collapse margin of nodes in RDS. Therefore this condition
sufficiently with either static or dynamic local reactive
can be treated as an index termed as VCI, indicating the
power support.
proximity of voltage collapse point.
The power vs voltage (PV) curve acquired by employing
Type-I DGs are doubly fed induction generator (DFIG)
CPF method and VCI computed using (7) for various
based WTGS. Type-II and Type-III DGs are SCIG-based
WTGS without and with sufficient local reactive power
support. Usually the stator winding of SCIG is delta
connected. In order to differentiate the configuration of
SCIG proposed in [24], a new type of DG is introduced and
defined as follows:

Type-IV DGs: these are SCIGs with delta and star switching
of stator terminals along with permanently connected
capacitors as shown in Fig. 1. The performance of Type-IV
DG has been well analysed and explained in [24].

The SCIG based WTGSs (Type-II DGs) are low cost and
simple for grid connected operation. They are very popular
in wind turbines of medium rating that are usually
interconnected in RDS. Moreover, such DGs are prone to
voltage stability problem because of high reactive power
Fig. 4 PV curve and VCI of the two bus equivalent of a typical requirement from the grid at medium and high wind
RDS velocities. Hence, in this paper, the study on performance

    
2    
  Vn1  cos dn1 − dn2 + Vn1  cos2 dn1 − dn2 − 4 Pn2 Rb + Qn2 Xb
V  = (6)
n2
2

900 IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906
& The Institution of Engineering and Technology 2013 doi: 10.1049/iet-gtd.2012.0579
www.ietdl.org

Fig. 5 Computational procedure for VCI in all buses at a given wind velocity

of distribution network is limited only with the integration of 4.2 Effect of Type- II DG Integration on VCI
SCIG-based DG (i.e. Type-II, Type-III and Type-IV).
The steps involved in the performance analysis are shown With a DG based on SCIG installed at bus-17, VCI at all
as a flowchart in Fig. 5. The 33-bus distribution system [20] buses has been computed under different operating
has been considered for analysis of performance of the conditions like (i) with different wind velocity and (ii) with
system with Type-IV DG integration. The base voltage and star and delta setting of stator of SCIG. The comparison of
base MVA chosen for entire analysis are 11 kV and 100 nodal VCIs of the system without integration of DG and
MVA, respectively. Different case studies are carried out on with star and delta connected SCIG for low (6 m/s) and
33-bus system without and with a 3-phase, 1 MW, 690 V, high (15 m/s) wind speeds are given in Figs. 7 and 8,
50 Hz SCIG having following equivalent circuit parameters respectively. It is noted that the star setting of stator
[32]: R1 = 0.0071, R2 = 0.0063, X1 = 0.2155, X2 = 0.0882, winding cannot be used at high wind velocity as the stator
Rm = 24.5 and Xm = 3.3606 (all are in p.u.) and the results current will exceed its limit [24].
are discussed in the next section.

4 Case study 4.3 Effect of Type-III DG on VCI

4.1 DG placement based on VCI The effect of Type-III DG, where necessary reactive power is
supplied through shunt capacitor, on nodal VCI has been
Using the computed voltage magnitude at each bus by means studied with star connected DG at a wind speed of 6 m/s
of a simple load flow analysis, VCI at all buses are calculated and delta connected DG at a wind speed of 15 m/s. The
and indicated in Fig. 6. results are given in Figs. 9 and 10.
It has been noted that bus-17 has poor value of VCI As expected, VCI with shunt capacitor configuration
compared with other buses. Hence, as per the discussion in (Type-III DG) is better than Type-II DG for both low and
Section 3, it is decided that bus-17 would be a suitable high wind speed conditions. It can be clearly understood
place to locate a DG. from Fig. 11.

IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906 901
doi: 10.1049/iet-gtd.2012.0579 & The Institution of Engineering and Technology 2013
www.ietdl.org

Fig. 6 VCI at all buses without DG integration

Fig. 7 Variation of VCI without DG and with Type-II DG at 6 m/s wind speed

The voltage profiles of the system during low and high The value of VCI improves as the wind speed
wind velocity are indicated in Figs. 12 and 13, respectively. increases. However, after a particular wind velocity, the
Further, the performance analysis is repeated for various performance of delta setting is better than that of star
wind velocities ranging from 4 to 15 m/s. VCI with setting. It is very clear from Fig. 14 that this occurs at
different types of DG integrated at bus-17 is computed and 8 m/s wind velocity for Type-II DG. With Type-III DG,
plotted in Fig. 14 for better understanding. the performance of delta setting becomes better than

Fig. 8 Variation of VCI without DG and with Type-II DG at 15 m/s wind speed

902 IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906
& The Institution of Engineering and Technology 2013 doi: 10.1049/iet-gtd.2012.0579
www.ietdl.org

Fig. 9 Variation of VCI without and with DG of star setting at 6 m/s wind speed

Fig. 10 Variation of VCI without and with DG of delta setting at 15 m/s wind speed

Fig. 11 VCI profile at 15 m/s wind velocity

that of star setting beyond 7 m/s. Consequently, the 5 Switching criteria for Type-IV DG
preferable DG configuration for better performance integrated to RDS
during both low and high wind velocities is Type-III
DG with star and delta switching, which is the Type-IV The real power supplied and reactive power drawn by
DG shown in Fig. 1. induction generator vary with the wind speed. In order to

IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906 903
doi: 10.1049/iet-gtd.2012.0579 & The Institution of Engineering and Technology 2013
www.ietdl.org

Fig. 13 Node voltage profile with DG of delta setting at 15 m/s


Fig. 12 Node voltage profile with DG of star setting at 6 m/s wind wind velocity
velocity

obtain the maximum possible reactive power saving, stator This criterion ensures that the generator delivers increased
winding of induction generator is switched between star and real power to the grid and draws reduced reactive power from
delta along with permanently connected fixed capacitor. the grid. Also it ensures that at least 20% power margin is
The switching from star to delta configuration in SCIG made available, so that the generator will operate in a stable
should be made at appropriate wind speed to obtain the best region at times of passing larger wind speed, without
performance. The switching criterion suggested in [24] is as exceeding the 10% permitted load.
follows

Pmy = min Ph , PPF , Pc (8)

where
Pmy is the mechanical power determined for switching
from star to delta configuration;
Pη is the highest mechanical power input at which power
output will be higher in star configuration;
PPF is the highest mechanical power input at which power
factor will be higher in star configuration; and
Pc is the 0.8 times the mechanical input power that
corresponds to 110% rated current in star configuration. Fig. 14 VCI against wind velocity for different types of DGs

Fig. 15 VCI and per phase current against wind velocity for SCIG based DG

904 IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906
& The Institution of Engineering and Technology 2013 doi: 10.1049/iet-gtd.2012.0579
www.ietdl.org
The switching criterion discussed above is well suited for a 2 Fahrioglu, M., Yong, T., Lasseter, R.H., Alvarado, F.L.: ‘Integrating
SCIG connected to the stiff grid. On the other hand, when distributed generation technology into demand management schemes’,
www.pserc.wisc.edu, 2001
SCIG is connected to radial distribution network, the 3 Pipattanasomporn, M., Rahman, S.: ‘Intelligent distributed autonomous
switching criterion should also depend on the network power systems (IDAPS) and their impact on critical electrical loads’.
parameters while operating SCIG within stator rated current. IEEE Int. Workshop on Critical Infrastructure Protection, Darmstadt,
Since VCI is considered to be a measure of performance of Germany, November 2005, pp. 3–4
the network, it is proposed to have VCI of the bus at which 4 Ochoa, L.F., Padilha-Feltrin, A., Harrison, G.P.: ‘Time series based
maximization of distributed wind power generation integration’, IEEE
SCIG is connected as one of the switching criteria. Hence, Trans. Energy Convers., 2008, 23, (3), pp. 968–974
the criterion has been altered to be in terms of wind speed 5 Rau, N.S., Wan, Y.H.: ‘Optimum location of resources in distributed
rather than mechanical power input. planning’, IEEE Trans. Power Syst., 1994, 9, (4), pp. 2014–2020
The newly proposed switching criterion is 6 Nara, K., Hayashi, Y., Ikeda, K., Ashizawa, T.: ‘Application of Tabu
search to optimal placement of distributed generators’. IEEE PES
Winter Meeting, 2001, pp. 918–923
Usw = min UVCI , Uc (9) 7 Hemadani Golshan, M.E., Arefifar, S.A.: ‘Distributed generation,
reactive sources and network-configuration planning for power and
energy-loss reduction’, IEE Proc., Gener. Transm. Distrib., 2006, 153,
where (2), pp. 127–136
Usw is the wind speed determined for switching from star to 8 Singh, D., Singh, D., Verma, K.S.: ‘Multiobjective optimization for DG
delta configuration; planning with load models’, IEEE Trans. Power Syst., 2009, 24, (1), pp.
427–436
UVCI is the highest wind speed at which VCI of WTGS bus 9 Harrison, G.P., Piccolo, A., Siano, P., Robin Wallace, A.: ‘Distributed
is higher in star configuration as compared with VCI in delta generation capacity evaluation using combined genetic algorithm and
configuration; and OPF’, Int. J. Emerging Electr. Power Syst., 2007, 8, (2), pp. 1–13
Uc is the wind speed that corresponds to 95% of stator rated 10 Borges, C.L.T., Falcao, D.M.: ‘Optimal distributed generation allocation
current in star configuration. for reliability, losses, and voltage improvement’, Electr. Power Energy
Syst., 2006, 28, pp. 413–420.
It can be observed from Fig. 15 that the wind speed at 11 Grady, S.A., Hussaini, M.Y., Abdullah, M.M.: ‘Placement of wind
which star–delta switching has to be performed based on turbines using genetic algorithms’, Renew. Energy, 2005, 30, pp.
the criterion stated in (9) is Usw = min{7, 8.5} = 7 m/s. 259–270
Having VCI as a switching criterion enables better network 12 Celli, G., Ghiani, E., Mocci, S., Pilo, F.: ‘A multiobjective evolutionary
performance, as VCI is a measure of overall system algorithm for the sizing and siting of distributed generation’, IEEE
Trans. Power Syst., 2005, 20, (2), pp. 750–757.
performance, unlike power factor, which is a measure of the 13 Carpinelli, G., Celli, G., Mocci, S., Pilo, F., Russo, A.: ‘Optimisation of
performance of induction machine alone. embedded generation sizing and siting by using a double trade-off
method’, IEE Proc. Gener. Transm. Distrib., 2005, 152, (4), pp.
503–513
6 Conclusion 14 Popovic, D.H., Greatbanks, J.A., Begovic, M., Pregelj, A.: ‘Placement
of distributed generators and reclosers for distribution network
security and reliability’, Electr. Power Energy Syst., 2005, 27, pp.
In this paper, SCIG based DG has been integrated into RDS at 398–408.
the node with low VCI. The impact of integrating such DG on 15 Vinoth Kumar, K., Selvan, M.P.: ‘Capacity evaluation and identification
steady-state voltage stability of the network has been studied. of grid integration points of distributed generation in distribution
It has been shown that adding DG in RDS will improve the system’, Aust. J. Electr. Electron. Eng., 2011, 8, (2), pp. 137–153
voltage stability margin. Further, a substantial saving in 16 Vinothkumar, K., Selvan, M.P.: ‘Fuzzy embedded genetic algorithm
method for distributed generation planning’, Electr. Power Compon.
reactive power can be achieved by operating the SCIG in Syst., 2011, 39, (4), pp. 346–366.
delta and star settings at higher and lower wind speed, 17 Vinothkumar, K., Selvan, M.P.: ‘Distributed generation planning – a
respectively. Such reactive power savings in RDS lead to new approach based on goal programming’, Electr. Power Compon.
improvement in VCI and voltage profile. This has been Syst., 2012, 40, (5), pp. 497–512.
demonstrated using 33-bus RDS along with different 18 Hedayati, H., Nabaviniaki, S.A., Akbarimajd, A.: ‘A method for
placement of DG units in distribution networks’, IEEE Trans. Power
configurations of wind-driven SCIG. It is revealed from the Deliv., 2008, 23, (3), pp. 1620–1627.
case study that the delta and star switching of SCIG with a 19 Vinothkumar, K.: ‘Investigations on distributed generation planning
permanently connected capacitor across each phase, defined and certain grid interaction issues of wind turbine generation system’.
in this paper as Type-IV DG, gives enhanced performance PhD thesis, National Institute of Technology, Tiruchirappalli,
in the RDS. A new switching criterion for Type-IV DG has April 2011
20 Selvan, M.P., Shanti Swarup, K.: ‘Distribution system load flow using
been proposed based on VCI, considering social benefits object oriented methodology’. Int. Conf. Power System Technology,
such as better voltage profile, reduced system loss and (POWERCON 2004), Singapore, 21st–24th November 2004, pp.
reduced reactive power burden on the grid along with better 1168–1173
machine performance. The method described in this paper 21 Divya, K.C., Nagendra Rao, P.S.: ‘Models for wind turbine generating
for identification of the best candidate node to install a DG systems and their application in load flow studies’, Electr. Power Syst.
Res., 2006, 76, pp. 844–856
based on VCI can be applied to bigger systems without any 22 Kumaresan, N., Subbiah, M.: ‘Innovative reactive power saving in
further modifications. Moreover, with proper wind-driven grid-connected induction generators using a delta–star
communication between the system operator and the DG stator winding; part I’, Wind Eng., 2003, 27, (3), pp. 107–120
operators, the application of the proposed switching 23 Kumaresan, N., Subbiah, M.: ‘Innovative reactive power saving in
criterion for Type-IV DGs at multiple nodes of a bigger wind-driven grid-connected induction generators using a delta–star
stator winding; part II. Estimation of annual Wh and VARh of the
system can be practiced. delta–star generator and comparison with alternative schemes’, Wind
Eng., 2003, 27, (3), pp. 195–204
24 Raja, P., Kumaresan, N., Subbiah, M.: ‘Grid-connected induction
7 References generators using delta–star switching of the stator winding with a
permanently connected capacitor’, Wind Eng., 2012, 36, (2), pp.
1 Pipattanasomporn, M., Willingham, M., Rahman, S.: ‘Implications of 219–231
on-site distributed generation for commercial/industrial facilities’, 25 Kundur, P.: ‘Power system stability and control’, (EPRI, Power Systems
IEEE Trans. Power Syst., 2005, 20, (1), pp. 206–212 Engineering series, McGraw-hill, New York, 1994)

IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906 905
doi: 10.1049/iet-gtd.2012.0579 & The Institution of Engineering and Technology 2013
www.ietdl.org
26 Huang, G.M., Zhao, L. ‘Measurement based voltage stability monitoring transmission system stability’. IEEE PowerTech Conf., Bologna, Vol.
of power system’, (www.pserc.wisc.edu.) 2, 23–26 June 2003
27 Donnelly, M.K., Dagle, J.E., Trudnowski, D.J., Rogers, G.J.: ‘Impacts 30 CIGRE TF 38.01.10.: ‘Modeling new forms of generation and storage’,
of distributed utility on transmission system stability’, IEEE Trans. November 2000
Power Syst., 1996, 11, (2), pp. 741–746 31 Thong, V.V., Van Dommelen, D., Driesen, J., Belmans, R.: ‘Impact of
28 Guttromson, R.T.: ‘Modeling distributed energy resource dynamics on large scale distributed and unpredictable generation on voltage and angle
the transmission system’, IEEE Trans. Power Syst., 2002, 17, (4), pp. stability of transmission system’. 40th CIGRE Conf., article C6–205,
1148–1153 Paris, France, August 29–September 3, 2004
29 Reza, M., Slootweg, J.G., Schavemaker, P.H., Kling, W.L., Van der 32 Lubosny, Z.: ‘Wind turbine operation in electric power systems’,
Sluis, L.: ‘Investigating impacts of distributed generation on (Springer-Verlag, Berlin Heidelberg, New York, 2003, 1st edn.)

906 IET Gener. Transm. Distrib., 2013, Vol. 7, Iss. 8, pp. 898–906
& The Institution of Engineering and Technology 2013 doi: 10.1049/iet-gtd.2012.0579

Anda mungkin juga menyukai