Anda di halaman 1dari 1

BSP-BOF: TOP5 - WATER


TOP conditions Pressure (kgf/cm2 g) Temperature C
Sl. No. Services Flow rate; m3/h Inlet water Outlet water Inlet water Outlet water TOP Location TOP valve in PT-IN scope Line No.

44 50 (max) F31 , BOP +5920 ,


1 Soft make-up water for BOF 6 - 35 - Yes 45-SOW-001-80
8 20 (avg.) DN80 (Ref. drg. C_3K20_AA_800-FPP45_RAZ101; R02 & RAZ113, R01)

246 (max) F31 , BOP +100 , +184


2 Fresh make-up water 6 7-9 - 35 - Yes 45-FW-001-150
142 (avg.) DN150 (Ref. drg. C_3K20_AA_800-FPP45_RAZ101; R02 & RAZ113, R01)

127 (max) SOS TOP5, BOP +1300,


3 Fresh make-up water 7-9 - 35 - Yes 42-FW-001-150
40 (avg.) DN150 (Ref. drg. C.3K20.AA.800-FPP42/RAZ101; R02)

251 (max) GH TOP5, BOP +9300,


4 Fresh make-up water 7-9 - 35 - Yes 43-FW-001-200
184 (avg.) DN200 (Ref. drg. C.3K20.AA.800-FPP13/RAZ101; R01)

840 804 (max) F31 , BOP +100 ,


5 Industrial cooling water supply for secondary cooling PHE of lance cooling circuit 6 - 35 - Yes 45-ICW-001-350
822 801 (avg. ) DN350 (Ref. drg. C_3K20_AA_800-FPP45_RAZ101; R02 & RAZ113, R01)
7-9

804 (max) F31 , BOP +5920 ,


6 Industrial cooling water return from secondary cooling PHE of lance cooling circuit - 5 - 45 Yes 45-ICW-006-350
801 (avg. ) DN350 (Ref. drg. C_3K20_AA_800-FPP45_RAZ101; R02 & RAZ113, R01)
55

SOS TOP5, BOP +870,


7 Industrial cooling water supply for miscellaneous at Switch Over Station (SOS) 30 7-9 - 35 - Yes 42-ICW-001-65
DN 65 (Ref. drg. C.3K20.AA.800-FPP42/RAZ101; R02)

SOS TOP5, BOP +645,


8 Industrial cooling water return from Switch Over Station (SOS) 30 - 4 - 55 Yes 42-ICW-002-65
DN 65 (Ref. drg. C.3K20.AA.800-FPP42/RAZ101; R02)

GH TOP5, BOP +9300,


9 Industrial cooling water supply for miscellaneous at Gas Holder (GH) 5 7-9 - 35 - Yes 43-ICW-001-25
DN25 (Ref. drg. C.3K20.AA.800-FPP13/RAZ101; R01)

GH TOP5, BOP +9300,


10 Industrial cooling water return from Gas Holder (GH) 5 - 4 - 55 Yes 43-ICW-002-25
DN25 (Ref. drg. C.3K20.AA.800-FPP13/RAZ101; R01)
TOP for 3 nos. DN400 shall be at convertors (F14B, F15B & F16B)
F31 , BOP +11846 ,
11 Cooling water supply for BOF GCP 1800 7 - 40 - Yes 46-DSC-001-500
DN500 (Ref. drg. C_3K20_AA_800-FPP45_RAZ101; R02 & RAZ113, R01)
4-6 at F30 column
G-24 (Through Launders)
1800 (max)
12 Return slurry water from BOF-GCP - 0 - 70 (Launders IL : + 13937) NA Launder
1650 ( avg.)
(Ref. drg. C_3K20_ET31_292B-M_ZSZ001, R01)

80 (max) SOS TOP5, BOP +400,


13 Dust collecting slurry water - 2.5 - 70 Yes 42-DSL-001-150
40 (avg.) DN 150 (Ref. drg. C.3K20.AA.800-FPP42/RAZ101; R02)

200 (max) GH TOP5, BOP +9300,


14 Dust collecting slurry water - 2.5 - 70 Yes 43-DSL-002-250
180 (avg.) DN250 (Ref. drg. C.3K20.AA.800-FPP13/RAZ101; R01)
This pipeline no has not been
indicated in said drawing.
227 (max) F31 , BOP +140 , +250
15 Condensate & Drain (Return Water) - 0 - 80 Yes 45-CS-001-200
33 (avg.) DN200 (Ref. drg. C_3K20_AA_800-FPP45_RAZ101; R02 & RAZ113, R01)

70 (max), 120 (max) F31 , BOP +140 , +250


16 Blow down water (Return Water) - 0 - Yes 45-BDW-001-200
0 (avg.) 70 (avg.) DN200 (Ref. drg. C_3K20_AA_800-FPP45_RAZ101; R02 & RAZ113, R01)

25 (max), B12, BOP +1500,


NEW Fresh make-up water 2 - 35 - Yes Lime Milk Spray
4 (avg.) DN 80

Please note that external water package has been finalised as per utility consumption list, rev-8. At this stage new TOP is not acceptable.