Anda di halaman 1dari 10

Computers and Structures 122 (2013) 135–144

Contents lists available at SciVerse ScienceDirect

Computers and Structures


journal homepage: www.elsevier.com/locate/compstruc

Dynamic analysis of an overhead transmission line subject to gusty wind


loading predicted by wind–conductor interaction
Hooman Keyhan a,⇑, Ghyslaine McClure a, Wagdi G. Habashi b
a
McGill University, Department of Civil Engineering and Applied Mechanics, Montreal, QC, Canada
b
McGill University, Computational Fluid Dynamics Laboratory, Department of Mechanical Engineering, Montreal, QC, Canada

a r t i c l e i n f o a b s t r a c t

Article history: The authors present a new method to determine wind loading on transmission line conductors based on
Received 16 June 2012 fluid–structure interaction (FSI) analysis. FSI results yield a more accurate representation of pressure
Accepted 27 December 2012 loads acting on moving conductors than provided by the pseudo-static pressure calculation based on Ber-
Available online 26 January 2013
noulli’s equation, which is the current approach used in design. The results based on the proposed
method are compared to those obtained using the Bernoulli load model using four natural wind records
Keywords: to perform a nonlinear dynamic analysis of a three-span transmission line section. The quasi-static
Computational fluid dynamics
approach significantly overestimates the conductor motion and the cable tensions.
Fluid–structure interaction
Overhead line conductors
Ó 2013 Elsevier Ltd. All rights reserved.
Wind loads

1. Introduction Where, Cxc is the drag coefficient of the conductor (considered in the
un-iced condition), Gc is the combined wind factor for the conduc-
Transmission line structures are designed to withstand several tors, which depends on height above ground and terrain roughness
different load cases they may experience during their service life. categories, and GL is the span factor. Other standards such as IEC
Among these load cases, those involving extreme wind and 60826, Design criteria of overhead transmission lines issued by
combined wind and icing in cold climates are typically governing International Electrotechnical Commission [3] and ASCE Manual
the design for lateral loads. In design practice wind loading on No. 74 [4] use similar approaches.
transmission line conductors is applied following simplified static Among the different mechanical components of transmission
procedures that are meant to be conservative. Such procedures, lines, conductors have the largest area exposed to wind, especially
described in national and international codes and standards or in in high and ultra high voltage lines where bundles of four or more
utility guidelines, are very similar and essentially based on conductors are used. Line conductors are particularly sensitive to
Bernoulli equation. Referring to Eq. (1) provided by Canadian wind effects as they are long and relatively flexible compared to
standards CSA-C22.3 No. 60826-10, Design criteria of overhead their supports. Because of their flexibility, conductors may experi-
transmission lines [1], the wind pressure on towers and conduc- ence large motions under wind loading: depending on wind speed,
tors, q, is obtained by multiplying the reference dynamic wind line parameters and span length, horizontal (swinging) displace-
pressure, qo – actually the equivalent pseudo-static pressure pre- ments at the mid span may reach 10–20 m in high voltage lines.
dicted by Bernoulli equation, by a gust effect factor proposed by In cold climates, atmospheric ice accretions of various types, from
Davenport in the late 1970s [2] to account for tower resonant re- light rime to dense glaze, further increase the effects of wind loads
sponse and wind gustiness. The incident wind speed nominally on lines and give rise to the most severe design loading conditions.
specified at 10 m elevation is also modified to account for terrain Although simplified static methods are expected to be conservative
roughness and height according to the classical boundary layer for design, economy brings other incentives to better understand
wind model. Finally, a span coefficient is used to consider the and quantify the effects of wind loads on line conductors, espe-
random unevenness of wind gust speed along the span. cially in the context of older line assessment where overly conser-
vative load estimates may lead to costly retrofit measures that are
q ¼ q0 C xc Gc GL ð1Þ
not necessary. It is clear that in extreme wind conditions conduc-
tors experience large displacements and interact with the wind
⇑ Corresponding author. Address: McGill University, Department of Civil Engi- flow: is this interaction contributing to increasing or decreasing
neering and Applied Mechanics, Room 475F, 817 Sherbrooke Street West, Montréal,
the net pressures on the conductor span and consequently the
Québec, Canada, H3A 0C3. Tel.: +1 604 782 3053; fax: +1 (514) 398 7361.
E-mail addresses: hooman.keyhan@mail.mcgill.ca (H. Keyhan), ghyslaine.
loads transferred to their supporting towers? This is the main
mcclure@mcgill.com (G. McClure), wagdi.habashi@mcgill.com (W.G. Habashi). question that motivated this research. A refined computational

0045-7949/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.compstruc.2012.12.022
136 H. Keyhan et al. / Computers and Structures 122 (2013) 135–144

model of the conductor cross section on flexible supports in sur- equilibrium iterations are carried using the Full Newton method
rounding moving air is used to investigate the dynamic interaction for stiffness updates. In the following equation u is the cable dis-
between wind and conductor motion. The net wind load resulting placement vector; K, M and C are stiffness, mass and damping
from fluid–structure interaction (FSI) analysis is then applied to matrices respectively, and Ft+Dt represents the fluid force applied
detailed three-dimensional models of a line section to determine on the conductor nodes at time t + Dt.
the loads transferred to line supports.
M Du €  C u_  Ku
€ þ C Du_ þ K Du ¼ F tþdt  M u ð2Þ
2. Fluid–structure interaction analysis
For computational fluid dynamics, the modeling parameters that
were found to have the most influence on accuracy are the fluid do-
Considering the conductor motion in the wind flow, an accurate
main dimensions and the mesh fineness. Thereafter, these were
computational evaluation of wind pressure on overhead conduc-
iteratively adjusted with several numerical experiments until the
tors requires FSI analysis. In this analysis, a two-dimensional mod-
computational domain was found adequate to minimize blockage
el of the conductor cross section is coupled to its surrounding air
and boundary effects on cable response while keeping the compu-
flow (fluid) domain, as illustrated in Fig. 1. In the solid domain,
tational cost reasonable. The fluid domain is discretized with quad-
only the outer cable boundary is modeled with 450 2-node Hermi-
rilateral FCBI-C elements [6], using a structured ‘‘O’’ shape mesh
tian beam elements with constant cross-sectional properties. A
(see Fig. 1). To capture the fluid response with reasonable accuracy
very high flexural stiffness (high Young’s modulus) is prescribed
450 elements are used at the fluid–solid interface. The fluid ele-
to prevent deformation of the conductor cross section. It is as-
ments’ thickness is reduced when approaching the interface and a
sumed that large displacements/rotations can occur, but only small
refined mesh is used in a ring zone of about 1  D thickness around
strains. The stiffness matrix and internal force vector of this ele-
the cable surface of diameter D to keep at least 5 layers of elements
ment are evaluated in closed form [7]. The mass of the conductor
with Y+ under 1.00. An extensive mesh study has been conducted in
is attributed to individual elements of its contour while the sup-
the initial stage of modeling to determine the appropriate size and
port stiffness is distributed along the contour with spring elements
shape of the mesh that would yield good convergence and accuracy
assigned in two orthogonal directions. In other words, the cross
while keeping the numerical effort manageable: finer meshes were
section is assumed mounted on elastic springs with equivalent ver-
tested and improved to the pressure calculations by less than 5%.
tical and horizontal linearized stiffnesses that can be adjusted for
The CFD analysis is based on the direct time-step integration of
various line parameters. In the application presented here, these
the unsteady Reynolds-averaged Navier–Stokes equations (Eq. (3))
equivalent stiffness properties were determined for a mid-span
using the Euler a-method of first order, and a constant time-step
cross section using a detailed large kinematics nonlinear static
size of 0.1 ms was found optimal for the problem at hand.
analysis of a level 355-m span suspended in still air, with a hori-
zontal tension of 19.2 kN in the bare condition (cable self-weight h   i
14.9 N/m). A viscous damping constant equivalent to 2% of critical
qu j @ u i =@xj ¼ qf i þ @=@xi pdij þ l @ u i =@xj þ @ u j =@xi  qu0i u0j
is also assigned at the support in each orthogonal direction to ð3Þ
approximate internal material damping in the conductor. Interface
boundary conditions are assigned to the solid and fluid elements to  i and u0j are the mean and fluctuating
In Eq. (3), q is the air density, u
ensure that in each iteration the fluid domain displacements on the components of i-th component of the fluid velocity, p  is the mean
contour are updated to correspond to the beam element displace- static pressure, l is the air viscosity and f i is a vector representing
ments. The corresponding fluid pressures determined by CFD anal- the mean external forces applied on the control fluid domain. The
ysis in the fluid domain are also transferred to the beam elements iterative solver for the linearized incremental equations is the Alge-
of the solid domain as external nodal point loads. These two- braic Multi-Grid method (AMG). Airflow turbulence is modeled
dimensional models provide a tool to evaluate the effects of several with the Spalart–Allmaras one-equation approach and vortex-shed-
parameters such as the magnitude of incident wind speeds, con- ding effects are introduced with the Detached Eddy Simulation
ductor shape, surface roughness and ice accretion on resultant (DES) algorithm. In FSI analysis, the Arbitrary-Lagrangian–Eulerian
wind loading of overhead line conductors.[5] (ALE) formulation is used to allow for compatible mesh deforma-
In the solid domain, direct time-step integration is used to solve tions and displacements for the air surrounding the cable in motion
the incremental form of the nonlinear equations of motion (Eq. (2)) in each solution step. Note that these features are available in com-
of the cable cross section on spring supports and dashpots, and the mercial software ADINA which was used in the study. [7]

Fig. 1. Two-dimensional model of stranded conductor cross section coupled to its surrounding air flow.
H. Keyhan et al. / Computers and Structures 122 (2013) 135–144 137

The evaluation of the wind pressure field on the conductor pro- The catenary equation of an inextensible cable is employed to
ceeds by CFD analysis of the fluid domain in each time step, and position the conductor nodes in the initial condition and a geomet-
the resultant load on the air-cable interface is obtained by integra- rically nonlinear static analysis under self weight provides a realis-
tion of the pressure field on the cable contour. This net wind load is tic equilibrium configuration. Dynamic wind loading analyses are
calculated at each time step and acts as an external load on the restarted from the line at rest. To avoid singularities in the initial
conductor in the solid domain. Based on this calculated load, the stiffness matrix of the cable elements in the initial run, a
solid domain is solved and the cable displacement is determined pre-stressing value corresponding to the initial tension is assigned
which updates the position of the fluid boundary subsequently in to each element. The conductors are attached to suspension towers
each time step. This two-dimensional FSI analysis serves to con- by 1.4-m long insulator strings, which are modeled with a two-
struct wind loading time histories to be used in nonlinear dynamic node isoparametric truss element of high axial rigidity [8,9].
analysis of three-dimensional line section models assumed in still In the numerical model of the line, damping is introduced with
air conditions (i.e. solid models only). To illustrate the process, the discrete viscous dashpots defined between the two end nodes of
results obtained from FSI analysis for four different wind velocity each cable element. For the gusty wind loading condition where
time histories are presented in section III where the conductor is the conductor experiences several meters of sway displacement
assumed in the bare (non iced) condition, i.e. its surface shows in the mid span region, damping has two main sources: internal
the corrugations of a stranded construction. and aerodynamic. Internal damping is mainly caused by friction
between the strands in contact and friction induced by bending
of the wires. The values suggested for internal damping ratio of
3. Transmission line model non iced aluminum–steel conductors can vary from about 0.5–2%
of equivalent critical viscous values depending on size, number
A three-dimensional computational model of a 120 kV double- and profile of strands and the type of conductor (aluminum, steel
circuit line section owned and operated by Hydro-Québec is built reinforced, composite or trapezoidal). Based on previous computa-
in ADINA (see Fig. 2) to illustrate the application of the proposed tional studies [9,11] and considering that structural damping (in
wind load model on conductors and its effects on the forces trans- the form of friction between the strands) will tend to increase with
ferred to supporting towers. A detailed finite element model com- increasing tension and lateral displacement, a value of 2% of
prising five spans and four intermediate lattice supports was equivalent critical damping is used. Our study shows that conduc-
available from a previous structural dynamics study presented in tor response to wind load is not sensitive to small variations in
Ref. [8] and following a methodology described in Ref. [9]. In the structural damping introduced in the model. It is emphasized that
present study, the model was truncated to three spans and two aerodynamic damping was found to be higher than the prescribed
suspension towers for simplicity; the wind load is applied only structural damping and the conductor is not in free vibration: this
to the central span of 355 m. The boundary conditions provided can explain the low sensitivity of the predicted response to varia-
by the suspension insulator strings at the both ends of the loaded tion in structural damping. Conductor instabilities like galloping
span are quite realistic in allowing conductor motions under wind. and Aeolian vibrations are very sensitive to structural damping
The far ends of the conductors in the adjacent spans are assumed variation but this is not the case for stable response to gusty winds
perfectly fixed to represent a strain tower condition where conduc- in this study. Aerodynamic damping is evaluated from FSI analysis;
tors are directly anchored to the structure instead of being sus- the results obtained indicate 3–5% of critical damping depending
pended. Although the strain towers experience some deflection on the incident wind velocity. Considering both sources of
under load and the conductors’ attachment points and are not per- damping, a total damping ratio equivalent to 5% and 7% of critical
fectly rigid, this flexibility has negligible effects in this study dom- damping is modeled with the viscous dashpot elements for wind
inated by transverse conductor displacements in swinging mode. records 1,2 and 3,4 respectively. Introducing damping is also
Detailed properties of the stranded 54/7 CONDOR ACSR conductor beneficial to filter out the spurious high frequency response of
used in this example are available in [10]. Each conductor span is the finite element model that is not representative of the behavior
discretized with 30 two-node isoparametric truss elements with of the physical system [10].
three translational degrees of freedom at each node. To account The geometrically nonlinear dynamic analysis of the line sec-
for the cable’s slackening in the dynamic analysis; tension-only tion model subjected to wind is conducted by direct time integra-
linear elastic material is modeled for the conductor with the tion of the incremental equations of motion (Eq. (2)). Newmark’s
equivalent composite modulus of elasticity, which accounts for classical trapezoidal rule is employed for integration and equilib-
compatibility of cable strand deformations and layering effects. rium iterations are performed in each time step until convergence
is reached according to set threshold residual errors. The conver-
gence criteria are selected based on displacement and energy error
norms [12].

4. Wind load model

In this section the proposed new method for transmission line


wind loading is described. It proceeds in five main steps illustrated
in Fig. 3. The first step is to evaluate the horizontal transverse
stiffness of the conductor under horizontal load at different posi-
tions along the span, using nonlinear static analysis. As expected,
the analysis results show that the stiffness varies with higher rate
near the end support points of the span while a few meters away
from suspension point the horizontal stiffness is only slightly
larger than at the mid span. In the example selected as a case
study, nine sections of conductor are selected to be representative
Fig. 2. Computational model of double circuit overhead transmission line section of the whole span and their lateral and vertical stiffness values are
on steel lattice supports. used in the FSI model.
138 H. Keyhan et al. / Computers and Structures 122 (2013) 135–144

Fig. 3. Wind load modeling and dynamic analysis procedure.

Fig. 4. Conductor lateral stiffness from near support to mid span.

In Step 2, FSI analysis is performed with the different cable sup- The results from FSI analysis on all selected sections along the
port stiffness values determined in Step 1. The resultant wind load span for each wind case are transferred to the 3-D line model
history on each cable section is computed and the results from this (see Fig. 9) and nonlinear dynamic analysis is performed in Step
analysis are applied as input to the 3-D line model in Step 3 for 4 to predict the response of the transmission line components.
nonlinear dynamic analysis. Results of the dynamic analysis of Step 4 for the four wind load
Because this loading differs from the static loading used in Step cases are discussed next.
1 to evaluate the lateral stiffness of the cable, the conductor will In Figs. 5–8, the results from FSI analysis performed in Step 2, at
experience slightly different displacements which in turn provide three different cross sections along the span are compared against
different values of conductor lateral stiffness. So the FSI analysis the wind pressure predicted by Bernoulli’s equation (neglecting
of Step 2 is repeated with the new stiffness values and after a wind–conductor interaction) for all four incident wind load cases
few iterations a very good estimate of lateral stiffness of the con- used in this study. The results confirm that the wind load predicted
ductor is obtained. Fig. 4 presents an example of the variation in by FSI analysis at different sections of the span differs from the
lateral stiffness of the conductor obtained from this procedure. prediction made using Bernoulli’s equation. As expected, the
H. Keyhan et al. / Computers and Structures 122 (2013) 135–144 139

Fig. 5. Calculated wind load on conductor at three different positions along the span (wind record 1).

Fig. 6. Calculated wind load on conductor at three different positions along the span (wind record 2).

Fig. 7. Calculated wind load on conductor at three different positions along the span (wind record 3).

equivalent quasi-static pressure predicted by Bernoulli’s equation Another observation is the oscillatory character (high fre-
shows better general agreement with the computed dynamic wind quency, low amplitude) of the wind load from FSI analysis which
pressure applied on cable sections closer to end supports: these makes the plots appear as thick lines: this is caused by the
sections undergo smaller cable displacements, and subsequently oscillation in drag force due to vortex shedding. Such an oscillation
lower wind–structure interaction when compared to conductor in wind load (of rather small amplitude) will not significantly
cross sections further away from the supports. affect the lateral displacement of the conductor, which is the main
140 H. Keyhan et al. / Computers and Structures 122 (2013) 135–144

Fig. 8. Calculated wind load on conductor at three different positions along the span (wind record 4).

Fig. 9. 3-D transmission line model with wind load determined from FSI analysis.

parameter that will influence FSI analysis results. Comparing Fig. 5 displacements and tension are first examined, followed by internal
and 6, fluctuations in the loads determined along the span by FSI forces such as the horizontal shear and axial force in one of the
analysis (i.e. at cross sections of varying support stiffness) are more tower legs. For the sake of brevity, conductor tensions and
important when incident wind has higher turbulence intensity. horizontal displacements for wind record 4 are displayed in Figs. 12
Fig. 8 displays similar results but for the wind record with higher and 11 while the numerical results for all four wind records are
speed and turbulence intensity: differences between FSI-based summarized in Table 1.
wind loads and the wind load values predicted by Bernoulli’s equa- Table 1 summarizes the conductor response results. It is seen
tion are much larger in this case because of the higher degree of that for lower wind speeds (records 1 and 2) the FSI-based loading
cable wind interaction. yields significantly smaller displacements (by 26% and 23%, respec-
tively) than Bernoulli’s approach although the conductor tensions
5. Dynamic analysis of wind-loaded line section are comparable with differences less than 2%. For the two stronger
wind records (3 and 4), the displacements obtained with FSI-based
To illustrate the proposed methodology and assess the effects of loading are still smaller but the differences are less important (4%
this new wind load model on the line response calculation, the line and 9% respectively). However, the differences in conductor ten-
section model is studied under the four wind load models derived sions are very significant, with 13% and 37%, respectively. In the
by FSI analysis (see Fig. 9). load cases with lower wind velocity (records 1 and 2) the insulator
Fig. 10 displays the four wind speed records used in the study, position is close to vertical and changes in wind pressure on the
which are based on natural wind measurements in Quebec. The conductor will have more effect on the insulator swing (hence on
sampling rate of the available wind records is 1/s. The power the conductor lateral displacement) than higher wind velocity. It
spectral density functions of these wind records are displayed in is seen in response to wind records 3 and 4 that insulator suspen-
the bottom right insert of the graph. sion strings experience large swing (they become almost horizon-
Results from nonlinear dynamic analysis of the short line sec- tal), so any further increase in the wind pressure cannot increase
tion subject to wind loading obtained from both the proposed the conductor displacement (available slack has been removed)
method and using Bernoulli’s equation are compared next. Among and will rather cause an increase in conductor tension. Accord-
the many response indicators computed by nonlinear dynamic ingly, the difference between FSI and Bernoulli’s method is mainly
analysis, a selection was made to highlight the salient features of reflected in conductor displacement for records 1 and 2, but in
the results and illustrate the differences predicted by the conductor tension for records 3 and 4. In general, these results sug-
(FSI-based and Bernoulli wind loading methods). The conductor gest that Bernoulli’s method is overly conservative in predicting
H. Keyhan et al. / Computers and Structures 122 (2013) 135–144 141

Fig. 10. Four incident wind velocity time histories used in this study.

Table 1 by increasing required clearances as well as the right of way, which


Conductor response to different wind loadings. can have significant environmental impacts. It is seen from Fig. 11
Wind Average Turbulence Conductor Conductor
and Table 1 that the benefits of wind–conductor interaction
record time wind intensity maximum horizontal analysis become more important in higher wind speed with high
history speed (%) horizontal tension (kN) turbulence intensity.
(m/s) displacement at In Fig. 12 the horizontal tension in the conductor predicted with
mid span (m)
the two load models is compared for wind record 4. Conductor
FSI Bernoulli FSI Bernoulli tension is the most important factors in determining the structural
1 16.8 8.7 6.0 8.1 20.0 20.4 loading of towers. Overestimating it can greatly penalize tower de-
2 17.1 37.2 7.8 10.1 21.1 21.5 sign, especially in angle suspension towers and in strain towers.
3 36.5 19.3 20.5 21.4 38.3 44.1 Results in Table 1 indicate that conductor tension is overestimated
4 39.8 23.2 22.1 24.5 45.0 71.0
when wind–conductor interaction is neglected, and this overesti-
mation will increase with conductor motion: For FSI-based wind
record 1, the overestimation is of approximately 2% only while it
increases to 55% for wind record 4. Comparing the effects of wind
line response to high wind speeds and high turbulence intensities turbulence intensity and average wind speed of the wind records
that characterize wind storm events. shows that the peak tension is more affected by wind speed than
Horizontal displacement of conductors is an important param- turbulence intensity.
eter in transmission line design and in selecting tower top geome- As mentioned previously, the difference in the wind pressure
try: underestimating it can result in clearance violations while evaluation not only affects the conductor tension and mid span
overestimating it can make the line construction very expensive displacement predictions but it also greatly affects the loads

Fig. 11. Conductor horizontal displacement at the mid span subject to wind record 4.
142 H. Keyhan et al. / Computers and Structures 122 (2013) 135–144

Fig. 12. Conductor horizontal tension in the span subject to wind record 4.

Fig. 13. Insulator swing angle in suspension tower supporting the loaded span subject to wind record 2.

Fig. 14. Transverse shear force in tower leg supporting the loaded span subject to wind record 2.

transferred to the tower attachment points, which affect the conductor tension (by approximately 2% only), the magnitudes of
internal forces in all the tower members and line components. To the swing angle of the suspension insulating strings predicted by
illustrate these effects on the tower internal forces, time histories the two wind load models are considerably different as shown in
of the transverse shear force and axial force in one of the tower legs Fig. 13. This explains why the Bernoulli load model overestimates
obtained from dynamic analysis are compared in Figs. 14 and 15 the shear force and axial force in the tower leg by as much as 21%
for wind record 2. Despite the small difference in the predicted and 19% respectively.
H. Keyhan et al. / Computers and Structures 122 (2013) 135–144 143

Fig. 15. Axial force in tower leg supporting the loaded span subject to wind record 2.

6. Validation of FSI analysis results

A new wind loading approach to evaluate line response to


turbulent wind is demonstrated in this research. Although a valida-
tion of the proposed procedure was done at various steps, it was
impossible to find in the literature a complete experiment (or
theoretical treatment) that could allow global accuracy checks.
Because of the scale of the overhead transmission line model,
problems in dynamic scaling, and the number of variables affecting
line response to wind, no direct comparison could be made
between computational results and physical experiments. Indeed
wind tunnel experiments or overhead line monitoring cannot
provide specific measurements of pressure fields around the con-
ductor (this is actually a great advantage of computational studies).
The proposed wind load modeling approach can be divided into
two steps. In the first step the wind pressure is evaluated using Fig. 17. Vortex shedding frequency, versus wind velocity; Angles of attack, (h) are:
FSI analysis and then the stress resultants on the solid perimeter j (0°), D (45°), s (90°), d (180°). Adapted from [15] (Results in red are obtained
from FSI analysis).
are used as external loading for the three-dimensional nonlinear
dynamic analysis of the line section. This nonlinear dynamic
analysis of overhead line sections is not a new subject and results
Steel Reinforced (ACSR 26/7) with two outer layers of aluminum
have already been validated in previous work [13,14]. However,
strands and 6 steel strands in the core. The aluminum strands
computational modeling of wind–conductor interaction is new
are 4.8 mm in diameter and the total diameter of the conductor
and results need validation. The following example was found for
is 30.5 mm. A light elliptical shape with smooth surface is added
a stranded conductor partly covered with ice and tested in a wind
to the bottom of the conductor to simulate an iced conductor
tunnel (see Figs. 16 and 17) [15]. The cable is Aluminum Conductor
condition (Fig. 17). The results reported in this experimental study
were the vortex shedding frequency and Strouhal number for
different wind velocities and angles of attack.
Results from our computational study (shown in red on
Fig. 17) were obtained for wind velocities of 10, 20 and 30 m/s
with angle of attack of 0°, 45°, 90° and 180°. The slight differences
obtained for vortex shedding frequencies can be attributed to end
effects of the tested conductor and a wind tunnel blockage ratio
of 4.5% in the experimental study while we have 2.5% in the
computational model. The agreement between calculated and
measured values is very good and the validation is deemed
successful.

7. Conclusions

In this paper a new method is proposed to determine wind


loading of transmission lines with a view to obtain a more accurate
representation of pressure loads acting on moving line conductors
than provided by the pseudo-static pressure calculation based on
Bernoulli’s equation which neglects any fluid–structure interac-
Fig. 16. Computational model of iced ACSR conductor (solid domain) with 45° tion. It combines two-dimensional CFD and FSI analyses on
angle of attack. conductor sections moving in their surrounding wind flow, which
144 H. Keyhan et al. / Computers and Structures 122 (2013) 135–144

yield the resultant wind load on the conductor. The wind load time Acknowledgements
histories are then used as input in a three-dimensional finite
element model of a line section for nonlinear dynamic analysis. A research team grant from the Fonds québécois de la recherche
Four different natural wind records are used to generate the sur la nature et les technologies (FQRNT) is gratefully acknowledged.
conductor load cases using the proposed FSI-based method and
the Bernoulli’s equation method prescribed in most overhead line References
design standards [1,3,4]. For the sake of brevity, only a few line re-
sponse parameters are presented which show that the current [1] Canadian Standards Association. CSA-C22.3 No. 60826-10, Design criteria of
overhead transmission lines. Canadian Standards Association; 2010. p. 350.
method neglecting wind–conductor interaction overestimates the [2] Davenport AG. Gust response factors for transmission line loading. In: Fifth
wind pressure on the conductor within the span where it experi- international conference on wind engineering. Colorado State University,
ences large displacements. Owing to conductor flexibility, a large Pergamon Press; 1979. p. 899–909.
[3] International Electrotechnical Commission. Design criteria of overhead
portion of the span experiences sizeable horizontal displacements transmission lines. International standard. 3rd ed. Geneva: International
especially in the suspension spans where the conductor is attached Electrotechnical Commission; 2003. p. 252.
to suspension insulator strings. Thereafter in the gusty wind condi- [4] ASCE. Guidelines for electrical transmission line structural loading. 3rd ed.
ASCE; 2010.
tion, where conductors experience large displacements, the Ber-
[5] Keyhan H, McClure G, Habashi WG. Computational study of surface roughness
noulli method overestimates the total wind load on the line and and ice accumulation effects on wind loading of overhead line conductors. Int
the conductor tensions, which results in higher internal forces in Rev Civil Eng 2011;2:207–14.
tower members. These results clearly show that wind–conductor [6] Bathe K-J, Zhang H. A flow-condition-based interpolation finite element
procedure for incompressible fluid flows. Comput Struct 2002;80:1267–77.
interaction should be considered in wind pressure evaluation on [7] ADINA R&D Inc. Automatic dynamic incremental nonlinear analysis (ADINA).
conductors, especially in gusty conditions where conductors expe- Theory and modeling guide, 2000. Report ARD 00-7, Watertown, MA; 2009.
rience notable displacements. [8] Lapointe M. Dynamic analysis of a power line subjected to longitudinal
loads. Montréal, Canada: McGill University; 2003.
It is understood that the procedure is meant to assess the de- [9] McClure G, Lapointe M. Modeling the structural dynamic response of overhead
gree of conservatism of current simplified wind load models based transmission lines. Comput Struct 2003;81:825–34.
on static methods, and is not recommended for direct design appli- [10] Keyhan H, McClure G, Habashi WG. A fluid structure interaction-based wind
load model for dynamic analysis of overhead transmission lines. In: 9th
cations as it requires specialized expertise to guarantee good re- International symposium on cable dynamics, Shanghai, China; 2011. pp. 86–94.
sults and their correct interpretation. This study is pioneering the [11] Roshan Fekr M, McClure G. Numerical modelling of the dynamic response of
field of computational mechanics analysis of overhead power lines: ice-shedding on electrical transmission lines. Atmos Res 1998;46:1–11.
[12] Bathe Kj. Finite element procedures. Prentice Hall: Pearson Education Inc.;
The proposed procedure is of general applicability for conductor 2006.
types, line geometry, and input wind and icing conditions, which [13] Jamaleddine A, McClure G, Rousselet J, Beauchemin R. Simulation of ice-
announces great potential to study the response of overhead lines shedding on electrical transmission lines using ADINA. Comput Struct
1993;47(4/5):523–36.
to realistic climatic loading scenarios. Subsequent computational
[14] Vincent P, Huet C, Charbonneau M, Guilbault P, Lapointe M, McClure G. Testing
studies are planned to help improve the accuracy range of the and numerical simulation of overhead transmission lines dynamics under
simplified methods currently in used: a direct application is the component failure conditions. In: 40th General session of CIGRÉ, Paris, France;
assessment of the effect of approximations on the assumed 2004. Paper No. B2–308. p. 8.
[15] Zdero R, Turan OF. The effect of surface strands, angle of attack, and ice
conductor drag coefficient for various wind and ice loading accretion on the flow field around electrical power cables. J Wind Eng Ind
conditions. Aerodyn 2010;98:672–8.

Anda mungkin juga menyukai