1 SPF-01 STAIRCASE PRESSURISATION FAN STAIRCASE-01 12157.32 15275
SPECIFIED
NOT
2 SPF-02 STAIRCASE PRESSURISATION FAN STAIRCASE-02 12157.32 15314
SPECIFIED
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL W
FAN - SPF-1
I
a)
b)
c)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL W
FAN - SPF-1
d)
e)
II
a)
b)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL W
FAN - SPF-1
c)
d)
e)
f)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL W
FAN - SPF-1
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL WADEE
FAN - SPF-1
DESCRIPTION
Total no.of floors
Total no.of doors
Total Stairwell wall area (Refer wall area calculation attached)
Total Exterior Building Wall Area
Total Windows Perimeter
Total Lift Well Wall Area
Total Lift Landing Doors Area
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
FAN - SPF-1
Total leakage rate via other areas containing machanical extraction system (Q t)
Total air flow needed through open door to prevent smoke infiltration into stairwell
(Qdo)
The total no of doors considered open
(Fire Affected Floor, Above Floor and Door on Ground Floor)
Velocity of air through open Stairwell door to prevent smoke infiltration into Stairwell
{ = 1 x 6.6 }
FAN - SPF-1
Leakage area for Single Leaf opening into a pressurised space
Leakage area for all Single Leaf opening into a pressurised space (12 Nos)
Total Leakage through Closed Door Gaps (Q dc) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.12 x sqrt (12.5)}
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
Since Qsdo is Greater than Qs, Qsdo is selected for Fan Selection
{ = 7.21 x 1000 }
{ = 7212 x 2.118 }
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL WADEE
FAN - SPF-1
Calculation Unit
14 Nos
15 Nos
779.37 sq m
13.75 sq m
0.00 m
0.00 sq m
0.00 sq m
0.01 sq m
0.15 sq m
0.88 cu.m/s
0.0000 sq m
0.00 cu.m/s
0 sq m
1 - AL WADEEMA
0 sq m
sq m
14 sq m
779 sq m
sq m
0.0886 sq m
0.52 cu.m/s
1.40 cu.m/s
2.101 cu.m/s
3 Nos
1.00 m/s
6.60 sq.m
6.60 cu.m/s
1 - AL WADEEMA
0.01 sq m
0.12 sq m
0.35 cu.m/s
0.0000 sq m
0.00 cu.m/s
0 sq m
0 sq m
sq m
14 sq m
779 sq m
0 sq m
0.0886 sq m
0.26 cu.m/s
7.21 cu.m/s
7.21 cu.m/s
7212 LPS
15275 CFM
1 - AL WADEEMA
15275
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL W
FAN - SPF-2
I
a)
b)
c)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL W
FAN - SPF-2
d)
e)
II
a)
b)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL W
FAN - SPF-2
c)
d)
e)
f)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL W
FAN - SPF-2
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL WADEE
FAN - SPF-2
DESCRIPTION
Total no.of floors
Total no.of doors
Total Stairwell wall area (Refer wall area calculation attached)
Total Exterior Building Wall Area
Total Windows Perimeter
Total Lift Well Wall Area
Total Lift Landing Doors Area
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
FAN - SPF-2
Total leakage rate via other areas containing machanical extraction system (Q t)
Total air flow needed through open door to prevent smoke infiltration into stairwell
(Qdo)
The total no of doors considered open
(Fire Affected Floor, Above Floor and Door on Ground Floor)
Velocity of air through open Stairwell door to prevent smoke infiltration into Stairwell
{ = 1 x 6.6 }
FAN - SPF-2
Leakage area for Single Leaf opening into a pressurised space
Leakage area for all Single Leaf opening into a pressurised space (13 Nos)
Total Leakage through Closed Door Gaps (Q dc) = 0.839 x A x sqrt (delta P)
{= 0.839 x 0.13 x sqrt (12.5)}
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
Since Qsdo is Greater than Qs, Qsdo is selected for Fan Selection
{ = 7.23 x 1000 }
{ = 7231x 2.118 }
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL WADEE
FAN - SPF-2
Calculation Unit
14 Nos
16 Nos
746.63 sq m
13.00 sq m
0.00 m
0.00 sq m
0.00 sq m
0.01 sq m
0.16 sq m
0.94 cu.m/s
0.0000 sq m
0.00 cu.m/s
0 sq m
2 - AL WADEEMA
0 sq m
sq m
13 sq m
747 sq m
sq m
0.0849 sq m
0.50 cu.m/s
1.44 cu.m/s
2.156 cu.m/s
3 Nos
1.00 m/s
6.60 sq.m
6.60 cu.m/s
2 - AL WADEEMA
0.01 sq m
0.13 sq m
0.38 cu.m/s
0.0000 sq m
0.00 cu.m/s
0 sq m
0 sq m
sq m
13 sq m
747 sq m
0 sq m
0.0849 sq m
0.25 cu.m/s
7.23 cu.m/s
7.23 cu.m/s
7231 LPS
15314 CFM
2 - AL WADEEMA
15314
WADEEMA - STAIRCASE INNER WALL AREA
STAIRWALL AREA
Fdc is the force required to open the door without a pressure differential applied
across the door. E.g. The door closer mechanism etc (in N)
W is the width of the door (in M)
A is the area of cross section of the door (in m
d is the distance from the door knob to the knob side of the door (in m)
If at design stage, the force required to overcome the door closer is unknown, a maximum pressure differential of
60 Pa may be utilised for design purpose.
I STAIRCASE -01
ΔP (Q/(0.839 X A))2
1297.79
P - 1297.79
Fdc - Unknown
W - 1
A - 2.2
d - 0.1
Fo = (P x A x W)
2 x (W-d)
(1298 x 2.2 x 1)
=
2 x (1 - 0.1)
1586
A 0.904
II STAIRCASE -02
ΔP (Q/(0.839 X A))2
1238.74
P - 1238.74
Fdc - Unknown
W - 1
A - 2.2
d - 0.1
Fo = (P x A x W)
2 x (W-d)
(1239 x 2.2 x 1)
=
2 x (1 - 0.1)
1514
A 0.901
ATION - DOOR OPENING FORCE & VENT AREA
QUIREMENT (WADEEMA)
pressure differential across a door opening into a pressurised space is
:
m3/s
m2
Pa
Pa
m
m2
m
m3/s
m3/s
Sqmt
m3/s
m2
Pa
Pa
m
m2
m
m3/s
m3/s
Sqmt